Att 1_Aviation Mobile Power Converter Specs.pdf

PDF 45 KB Posted

Attached to
Aviation Power Converters
Solicitation number
W912LD26Q0005
Issued by

About this file

This document is a product specification sheet for an Aviation Mobile Power Converter (Power Cart) used for aircraft ground power application in hangars or on ramps during maintenance and inspection procedures.

The power converter must accept input of 208V, 3-phase, 50/60 Hz with a maximum full load input current of 114A, utilizing a 50-foot input cable with 3-Phase Hubble Connector and IEEE C62.41 Category B surge protection. The unit must provide output power ratings of 115V L-N / 200V L-L, 3-phase, 400 Hz at 130 amps through a 30-foot AC output cable with a Molded Blackhawk Connector and aircraft safety interlock. Required features include AC input and output ON/OFF connect/disconnect current sensing devices, automatic input line monitoring, built-in maintenance diagnostic system (BITE), event logging, USB communication ports, emergency power shut-off, 18-inch hazard area clearance, voltage/current/frequency monitoring, elapsed time meter, sleep mode, voltage adjustment capability, and summary fault indicators. The unit must be mobile with solid core casters for both indoor and outdoor use, include input and output cable racks, and be supplied with operator and maintenance manuals.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Aviation Mobile Power Converter (Power Cart)

Used for aircraft ground power application in hangar or on ramp to perform various maintenance or inspection procedures.

Power Converter must have the following specifications:

-Input-208 V, 3-phase, 50/60 Hz; maximum full load input current 114 A

-Input cable, 50 feet, single jacket 3-conductor with ground, pigtailed and plug ready, with 3 Phase Hubble Connector

-Input surge protection IAW IEEE C62.41, Category B

-AC input “ON/OFF” connect/disconnect current sensing device

-Automatic Input Line Monitoring

-Output power ratings: 115 V L-N / 200V L-L, 3 phase, 400 Hz, 130amps

-AC output cable, 30 feet, banded multiple conductor with aircraft plug and safety interlock Molded Blackhawk Connector

-AC output “ON/OFF” connect/disconnect current sensing device and aircraft safety interlock

-Indoor/Outdoor (Hangar/Ramp) Use (Rolling)

-solid core casters

-Event Log / Diagnostics

-Built-in maintenance diagnostic system (BITE)

-Internal Communication Ports - USB

-External Communication Port USB

-Emergency Power Shut-off

-18-Inch Hazard Area Clearance

-Voltage, Current, & Frequency Monitoring

-Elapsed Time Meter

-Sleep Mode

-Voltage Adjust

-Summary Fault Indicators

-Input & Output Cable Racks

-Operator and Maintenance Manual

File details come from the government source that posted it. Updated .