Atch 3 ACM Report.pdf

PDF 110 KB Posted

Attached to
Purchase and Install B1235 Carpet, FE Warren AFB, WY
Solicitation number
FA461324Q0031
Issued by

About this file

This document is an Asbestos Containing Materials (ACM) Report for Building 1235 at F.E. Warren Air Force Base in Cheyenne, Wyoming. The report details the findings of a non-destructive asbestos inspection performed on August 8, 2018, including the identification of asbestos-containing materials and sample locations. A total of 18 samples were collected and analyzed. The report also provides guidance on the handling of any suspect materials discovered during renovation or demolition activities.

This ACM Report is attached to a federal contract opportunity solicitation for the Purchase and Install B1235 Carpet at F.E. Warren AFB. The solicitation includes a Performance Work Statement, drawings, a Hazardous Materials Authorization Form, and salient characteristics. Key details include: Solicitation Number FA461324Q0031, a site visit request deadline of August 13, 2024, and a quote due date of August 22, 2024. The contract is being issued by the Department of the Air Force Global Strike Command.

View the file

Other files

File Type Posted
Atch 6 Post Site Visit Questions and Answers.pdf PDF
Atch 1 PWS 30 Jul 2024.pdf PDF
Atch 2 Drawings.pdf PDF
Atch 5 Salient Characteristics.xlsx XLSX spreadsheet
Solicitation - FA461324Q0031.pdf PDF
Atch 4 Hazmat Auth Form.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

August 8, 2018

F.E Warren Air Force Base Building 1235 Cheyenne, WY

Dear Customer, On August 8th, 2018 ATS performed an asbestos inspection of the above-mentioned project. The purpose of the survey is to identify asbestos containing material (ACM) using nondestructive sampling protocols.

Inspection, sampling and analytical procedures were performed in general accordance with the Environmental Protection Agency’s (EPA) interpretations, and guidelines of the Asbestos Hazardous Emergency Response Act (AHERA).

Asbestos containing materials as defined by the Occupational Safety and Health Administration (OSHA), the Environmental Protection Agency and the State of Wyoming are material with asbestos concentration greater than 1% (>1%) by volume.

However, OSHA governs asbestos exposures to employees above the Permissible Exposure Limit regardless of asbestos containing material concentration.

No inspection can eliminate the uncertainty regarding the presence of ACM. ATS’s level of diligence and investigative procedures are intended to reduce, but not eliminate potential uncertainty regarding the presence of ACM. The determinations in this report should not be constructed as a guarantee that all ACM present in the subject property has been included in this report.

The inspection was performed in a manner consistent with the level of care and expertise exercised by members of the asbestos inspection and assessment profession. Those entities and persons involved with the inspection and generation of this report do not imply or guarantee that all potential ACM on or in the building has been identified and sampled.

Historically, asbestos has been added as a component to over 3,000 materials and products produced in the United States.

The inspection was intended to identify those accessible materials that were reasonable suspect and that were most likely to contain asbestos in quantities subject to regulation, based on existing industry and regulatory standards.

If suspect material is discovered during renovation or demolition, work needs to be stopped and suspect material needs to be tested prior to proceeding.

Total samples taken: 18

Asbestos and Technical Services, Inc.

P.O. Box 2574 Cheyenne, WY 82003 307-214-0904 Asbestos Inspection Report

FIELD NOTES AND SAMPLE LOCATIONS

1235-1 Drywall- entry bay 5- E 121

1235-2 Drywall- entry bay 5- E 121

1235-3 Drywall- entry bay 5- E 121

1235-4 CMU- entry bay 5- E 121

1235-5 CMU- entry bay 5- E 121

1235-6 Base cove

1235-7 CMU- F 101

1235-8 Caulking- F 101

1235-9 Drywall- F 101

1235-10 Base cove- F 101

1235-11 Ceiling tile- F 101

1235-12 Ceiling tile- E 121

1235-13 CMU- H 110

1235-14 Base cove- H 110

1235-15 Drywall- H 110

1235-16 Ceiling tile- H 110

1235-17 Drywall- H 110

1235-18 Caulking- H 110

3M™ LeadCheck™ Swabs are EPA recognized when used by a certified renovator to determine if lead-based paint is present on wood and metal. When lead is detected, 3M™ LeadCheck™ Swabs and/or the surface being tested turns pink or red depending on the concentration of lead present. In the vast majority of test situations results are obtained in less than 30 seconds. When detecting low levels of lead, or lead chromate containing pigments, results may take longer to develop.

The results of swab testing are not quantitative.

Total samples taken: 4

FIELD NOTES AND SAMPLE LOCATIONS

Sample 1- E 121- NEGATIVE

Sample 2- F 101- NEGATIVE

Sample 3- H 110- NEGATIVE

Sample 4- H 110- door jam- NEGATIVE

Please feel free to contact me with any questions.

Sincerely, David Blackwell

Asbestos and Technical Services, Inc.

Owner

307-214-0904

Customer Project:

Reference #: Date: 8/10/2018

Analysis and Method

Discussion

Qualifications

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

Materials Characterization - Bulk Asbestos Analysis Laboratory Analysis Report - Polarized Light

Asbestos & Technical Services

P.O. Box 2574

Cheyenne, WY 82003 FE Warren Building 1235

CAL18085382AF

Summary of polarized light microscopy (PLM / Stereomicroscopy bulk asbestos analysis) using the methods described in 40CFR Part 763

Appendix E to Subpart E (Interim and EPA 600 / R-93 / 116 (Improved). The sample is first viewed with the aid of a stereomicroscope. Numerous liquid slide preparations are created for analysis under the polarized microscope where identifications and quantifications are preformed. Calibrated liquid refractive oils are used as liquid mouting medium. These oils are used for identification (dispersion staining). A calibrated visual estimation is reported, should any asbestiform mineral be present. Other techniques such as acid washing are used in conjugation with refractive oils for detection of smaller quantities of asbestos. All asbestos percentages are based on calibrated visual estimation traceable to NIST standards for regulated asbestos. Traceability to measurement and calibration is achieved by using known amounts and types of asbestos from standards where analyst and laboratory accuracy are measured. As little as 0.001% asbestos can be detected in favorable samples, while detection in unfavorable samples may approach the detection limit of 0.50% (well above the laboratory definition of trace).

Vermiculite containing samples may contain trace amounts of actinolite/tremolite. When not detected by PLM, these samples should be analyzed using TEM methods and / or water separation techniques. Suspected actinolite/vermiculite presence will be indicated through the sample comment section of this report.

Fibrous talc containing samples may contain a regulated asbestos fiber known as anthophyllite. Under certain conditions the same fiber may actually contain both talc and anthophyllite (a phenomenon called intergrowth). Again, TEM detection methods are recommended. CA Labs PLM report comments will denote suspected amounts of asbestiform anthophyllite with talc, where further analysis is recommended.

Some samples (floor tiles, surfacings, etc.) may contain fibers too small to be delectable by PLM analysis and should be analyzed by TEM bulk protocols.

AIHA LAP, LLC Laboratory #102929

A "trace asbestos" will be reported if the analyst observes far less than 1% asbestos. CA Labs defines "trace asbestos" as a few fibers detected by the analyst in several preparations and will indicate as such under these circumstances.

Since allowable variation in quantification of samples close to 1% is high, <1% may be reported. Such results are ideal for point counting, and the technique is mandatory for friable samples (NESHAP, Nov. 1990 and clarification letter 8 May 1991) under 1% percent asbestos or "trace asbestos".

In order to make all initial PLM reports issued from CA Labs NESHAP compliant, all <1% asbestos results (except floor tiles) will be point counted at no additional charge.

CA Labs is accredited by the National Voluntary Accreditation Program (NVLAP) for selected test methods for airborne fiber analysis (TEM), and for bulk asbestos fiber analysis (PLM). CA Labs is also accredited by AIHA LAP, LLC. in the PLM asbestos field of testing for Industrial Hygiene. All analysts have completed college courses or hold a degree in a natural science (geology, biology, or environmental science). Recognition by a state professional board in one these disciplines is preferred, but not required. Extensive in-house training programs are used to augment the educational background of the analyst. The Laboratory Director and Quality Manager have received supplemental McCrone Research training for asbestos identification. Analysis performed at Crisp Analytical Labs, LLC 1929 Old Denton Road Carrollton, TX 75006

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

Labs

A

C

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 1 of 7

Overview of Project Sample Material Containing Asbestos

Customer Project: FE Warren Building 1235 CA Labs Project #: CAL18085382AF

No Asbestos Detected.

Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

Sample # Layer

Analysts Physical Description of

Subsample

Asbestos type / calibrated visual estimate percent

List of Affected Building

Material Types

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)

This report relates to the items tested. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 2 of 7

Polarized Light Asbestiform Materials Characterization

Customer Info: Attn: Customer Project:

8/10/2018

8/9/18 10:30am

Phone # None Given

Fax #

Senior Analyst

Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Asbestos & Technical Services

FE Warren Building 1235

CAL18085382AF

P.O. Box 2574

Cheyenne, WY 82003 Date:

Turnaround Time: Samples Received:

307-214-0904 24 Hours Date Of Sampling:

Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

1235-1 1-1

Drywall/ white surfaced white compound n None Detected 100% qu,pe,bi,ca

1-2 white compound (beneath tape) y None Detected 100% qu,pe,ca

1-3 white drywall with paper n None Detected 10% ce 90% qu,gy

1235-2 2-1

Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca

2-2 white drywall with paper n None Detected 10% ce 90% qu,gy

1235-3 3-1

Drywall/ white surfaced white compound n None Detected 100% qu,mi,bi,ca

3-2 white drywall with paper n None Detected 10% ce 90% qu,gy

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.

Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.

ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:

Stanley Massett Technical Manager

Analyst Tanner Rasmussen

1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers

2. Fire Damage no significant fiber damages effecting fibrous percentages

3. Actinolite in association with Vermiculite

4. Layer not analyzed - attached to previous positive layer and contamination is suspected

5. Not enough sample to analyze

6. Anthophyllite in association with Fibrous Talc

7. Contamination suspected from other building materials

8. Favorable scenario for water separation on vermiculite for possible analysis by another method

9. < 1% Result point counted positive

10. TEM analysis suggested

Labs

A

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 3 of 7

8/10/2018

8/9/18 10:30am

Phone # None Given

Fax #

Senior Analyst

Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Asbestos & Technical Services

FE Warren Building 1235

CAL18085382AF

P.O. Box 2574

Cheyenne, WY 82003 Date:

Turnaround Time: Samples Received:

307-214-0904 24 Hours Date Of Sampling:

Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

1235-4 4-1

CMU/ white surfaced white finishing compound n None Detected 100% qu,mi,bi,ca

4-2 gray cement/mortar y None Detected 100% qu,ca

1235-5 5-1

CMU/ white surfaced white finishing compound n None Detected 100% qu,mi,bi,ca

5-2 gray cement/mortar y None Detected 100% qu,ca

1235-6 6-1 Base Cove/ gray baseboard y None Detected 100% qu,ma

6-2 tan mastic y None Detected 100% qu,bi

1235-7 7-1

CMU/ white surfaced white finishing compound n None Detected 100% qu,mi,bi,ca

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.

Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.

ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:

Stanley Massett Technical Manager

Analyst Tanner Rasmussen

1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers

2. Fire Damage no significant fiber damages effecting fibrous percentages

3. Actinolite in association with Vermiculite

4. Layer not analyzed - attached to previous positive layer and contamination is suspected

5. Not enough sample to analyze

6. Anthophyllite in association with Fibrous Talc

7. Contamination suspected from other building materials

8. Favorable scenario for water separation on vermiculite for possible analysis by another method

9. < 1% Result point counted positive

10. TEM analysis suggested

Labs

A

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 4 of 7

8/10/2018

8/9/18 10:30am

Phone # None Given

Fax #

Senior Analyst

Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Asbestos & Technical Services

FE Warren Building 1235

CAL18085382AF

P.O. Box 2574

Cheyenne, WY 82003 Date:

Turnaround Time: Samples Received:

307-214-0904 24 Hours Date Of Sampling:

Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

7-2 gray cement/mortar y None Detected 100% qu,ca

1235-8 8-1 Caulking/ gray sealant y None Detected 100% qu,ma,bi

1235-9 9-1

Drywall/ gray surfaced white compound n None Detected 100% qu,mi,bi,ca

1235-10 10-1 Base Cove/ gray baseboard y None Detected 100% qu,ma

10-2 tan mastic y None Detected 100% qu,bi

1235-11 11-1 Ceiling Tile/ white surfacing y None Detected 100% qu,bi

11-2 tan ceiling tile y None Detected

10% fg

40% ce 50% qu,pe,ma

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.

Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.

ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:

Stanley Massett Technical Manager

Analyst Tanner Rasmussen

1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers

2. Fire Damage no significant fiber damages effecting fibrous percentages

3. Actinolite in association with Vermiculite

4. Layer not analyzed - attached to previous positive layer and contamination is suspected

5. Not enough sample to analyze

6. Anthophyllite in association with Fibrous Talc

7. Contamination suspected from other building materials

8. Favorable scenario for water separation on vermiculite for possible analysis by another method

9. < 1% Result point counted positive

10. TEM analysis suggested

Labs

A

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 5 of 7

8/10/2018

8/9/18 10:30am

Phone # None Given

Fax #

Senior Analyst

Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Asbestos & Technical Services

FE Warren Building 1235

CAL18085382AF

P.O. Box 2574

Cheyenne, WY 82003 Date:

Turnaround Time: Samples Received:

307-214-0904 24 Hours Date Of Sampling:

Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

1235-12 12-1 Ceiling Tile/ white surfacing y None Detected 100% qu,bi

12-2 tan ceiling tile y None Detected

10% fg

40% ce 50% qu,pe,ma

1235-13 13-1

CMU/ white surfaced white finishing compound n None Detected 100% qu,mi,bi,ca

13-2 gray cement/mortar y None Detected 100% qu,ca

1235-14 14-1 Base Cove/ gray baseboard y None Detected 100% qu,ma

14-2 tan mastic y None Detected 100% qu,bi

1235-15 15-1 Drywall/ off-white compound y None Detected 100% qu,pe,ca

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.

Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.

ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:

Stanley Massett Technical Manager

Analyst Tanner Rasmussen

1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers

2. Fire Damage no significant fiber damages effecting fibrous percentages

3. Actinolite in association with Vermiculite

4. Layer not analyzed - attached to previous positive layer and contamination is suspected

5. Not enough sample to analyze

6. Anthophyllite in association with Fibrous Talc

7. Contamination suspected from other building materials

8. Favorable scenario for water separation on vermiculite for possible analysis by another method

9. < 1% Result point counted positive

10. TEM analysis suggested

Labs

A

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 6 of 7

8/10/2018

8/9/18 10:30am

Phone # None Given

Fax #

Senior Analyst

Julio Robles

CA Labs

Dedicated to Dedicated to Dedicated to Dedicated to

QualityQualityQualityQuality

Crisp Analytical, L.L.C.

1929 Old Denton Road

Carrollton, TX 75006

Phone 972-242-2754

Fax 972-242-2798

CA Labs, L.L.C.

12232 Industriplex, Suite 32

Baton Rouge, LA 70809

Phone 225-751-5632

Fax 225-751-5634

CA Labs Project #:

Asbestos & Technical Services

FE Warren Building 1235

CAL18085382AF

P.O. Box 2574

Cheyenne, WY 82003 Date:

Turnaround Time: Samples Received:

307-214-0904 24 Hours Date Of Sampling:

Purchase Order #:

Sample # Com ment

Layer

Analysts Physical Description of

Subsample

Homo-geneo us

(Y/N)

Asbestos type / calibrated visual estimate percent

Non-asbestos fiber type / percent

Non-fibrous type

/ percent

15-2 white compound (beneath tape) y None Detected 100% qu,pe,ca

15-3 white drywall with paper n None Detected 10% ce 90% qu,gy

1235-16 16-1 Ceiling Tile/ tan surfacing y None Detected 100% qu,bi

16-2 tan ceiling tile y None Detected

10% fg

40% ce 50% qu,pe,ma

1235-17 17-1 Drywall/ white compound y None Detected 100% qu,pe,ca

17-2 white drywall with paper n None Detected 10% ce 90% qu,gy

1235-18 18-1

Caulking/ white and gray sealant n None Detected 100% qu,ma,bi

Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235

AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.

Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.

ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot -other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:

Stanley Massett Technical Manager

Analyst Tanner Rasmussen

1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers

2. Fire Damage no significant fiber damages effecting fibrous percentages

3. Actinolite in association with Vermiculite

4. Layer not analyzed - attached to previous positive layer and contamination is suspected

5. Not enough sample to analyze

6. Anthophyllite in association with Fibrous Talc

7. Contamination suspected from other building materials

8. Favorable scenario for water separation on vermiculite for possible analysis by another method

9. < 1% Result point counted positive

10. TEM analysis suggested

Labs

A

/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 3 3/7/17) Page 7 of 7

3.1.4. Bldg. 1235 Asbestos Report FEWAFB #1235
ACM Report