ATCH 02 Drawings-Repair Weather Towers at KSCC.pdf
PDF 7 MB Posted
- Solicitation number
- FA2521-21-B-0017
About this file
This is a solicitation for a firm-fixed-price construction contract to repair three weather stations located on NASA Kennedy Space Center property. The work includes providing labor, equipment, and materials to repair towers at various locations. The North American Industry Classification Systems Code is 237130 for power and communication line and related structures construction. The size standard is $39.5 million. The contract value is anticipated to be between $500,000 to $1 million. The period of performance is 150 calendar days including 25 non-access days. This solicitation is set aside for women-owned small businesses. The closing date for proposals is January 15, 2021, and all proposed costs must be valid until then. The soliciting agency is the Department of the Air Force Space Command.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation Amendment FA252121B00170001 SF 30.pdf | ||
| ATCH 07 Hazardous Waste Form.doc | DOC document | |
| Solicitation - FA252121B0017.pdf | ||
| ATCH 05 FL20210001-09Jul2021.pdf | ||
| ATCH 01 KSCC 18-1543 Repair Weather Towers-Specs.pdf | ||
| ATCH 04 Q and A Template.docx | DOCX document | |
| ATCH 06 GPP.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F I L E
N
A M
E
P
C
A D
T
R A
C E
S
R e p a i r
W e a t h e r
T o w e r s a t
K
S C
C S h e e t s G d w g
Y O
U T
M
E
G
P
O
T T
E D
T h u r s d a y
F e b r u a r y a m
S E
R p e t e r r
BASE CIVIL ENGINEERING
KENNEDY SPACE CENTER
CAPE CANAVERAL, FLORIDA
REPAIR WEATHER TOWERS AT KSC
DRAWING INDEX
REV INDEX DRAWING DESCRIPTION
- G-100 COVER SHEET AND INDEX
- S-001
STRUCTURAL ABBREVIATIONS, LEGEND AND NOTES
- S-100 TOWER 506
S-101 TOWER 506 PHOTOS AND NOTES
S-102 GUY WIRE DETAIL
S-200 TOWER 415
S-201 TOWER 415 PHOTOS AND NOTES
S-300 PLAYALINDA WEATHER POLE 0015
S-301 PLAYALINDA WEATHER POLE 0015 DETAILS AND NOTES
E-100 TOWER 506 PLAN AND PHOTOS
E-101 TOWER 415 PLAN AND PHOTOS
E-102 POLE 0015 PLAN AND PHOTOS
U S
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
B
I
D
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C
O
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
G
R C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d e s b r i t o
H
A
LOCATION MAP
N
G-100
P R
V B
C O
V E
R
S
H E
D E
X
L M
K S
F
L
M
I Z
E D
K S
FINAL SUBMITTAL
R E
P A
W
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L
PROJECT NUMBER: KSCC 18-1543
YES NO
NOYES
IF THE CONTRACTOR SUSPECTS THE PRESENCE OF ANY
HEAVY METAL COATING MATERIAL NOT IDENTIFIED ON THESE DRAWINGS,
BUT IS REQUIRED TO BE DISTURBED TO PERFORM THE CONTRACT WORK,
INFORM THE CONTRACTING OFFICER AT ONCE.
IF THE CONTRACTOR SUSPECTS THE PRESENCE OF ANY
ASBESTOS CONTAMINATED MATERIAL NOT IDENTIFIED ON THESE
DRAWINGS, BUT IS REQUIRED TO BE DISTURBED TO PERFORM THE
CONTRACT WORK, INFORM THE CONTRACTING OFFICER AT ONCE.
TOWER 415
TOWER 506
PLAYALINDA
BEACH
TOWER 415
TOWER 415
N
K
E
N
N
E
Y
K
WEATHER POLE 0015
AT PLAYALINDA BEACH
N
TOWER 506
N
TOWER 506
WEATHER POLE
P
L
A
Y
A
L
I
N
A
S
E
G
A v e
E
5TH ST SE
USER:
CHIEF, ENGINEERING FLIGHT:
PROJECT MANAGER:
ENVIRONMENTAL:
FIRE:
BASE OPERATIONS:
COMMUNICATIONS:
SAFETY:
SECURITY FORCES:
ATO:
OTHER:
A
P
P
R
O
V
E
D
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
ASBESTOS IDENTIFIED
AutoCAD SHX Text
HEAVY METALS IDENTIFIED
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NOT TO SCALE
S-001
R
V B
S T
R U
C T
U R
B
R E
V I A
T I O
N S
L
E G
E N
D
A
N D
N O
T E
S
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
STRUCTURAL STEEL NOTES:
MIN. SERVICE DESIGN LOAD ON ANY CONNECTION
MIN. WELD SIZE
MIN. BOLT DIAMETER
MIN. PLATE THICKNESS
: 10 KIPS
: 3/16"
: 3/4"
: 3/8"
1. ALL STRUCTURAL STEEL SHALL HAVE THE FOLLOWING MINIMUM YIELD STRENGTHS, UNLESS
OTHERWISE NOTED ON THE DRAWINGS:
WIDE FLANGE "W" SHAPES ASTM A992
S, M, HP AND CHANNELS ASTM A572, GRADE 50
ANGLES AND PLATES ASTM A36
STRUCTURAL TUBES AND PIPES ASTM A500, GRADE C
2. ALL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO AISC SPECIFICATIONS AND
CODES, INCLUDING THE SECTION ON COMMENTARY, LATEST EDITION.
3. ALL BOLTS, NUTS AND WASHERS SHALL CONFORM TO THE REQUIREMENTS OF ASTM A325.
BOLTS, NUTS AND WASHERS SHALL BE HOT DIPPED GALVANIZED WITH MATCHING NUTS.
4. ALL WELDING ELECTRODES SHALL BE E70XX.
5. ALL WELDING SHALL BE DONE BY AWS CERTIFIED WELDERS AND SHALL CONFORM TO THE AWS
"CODE FOR ARC AND GAS WELDING TO BUILDING CONSTRUCTION," LATEST EDITION.
6. ALL BEAM CONNECTIONS SHALL BE SIMPLE SHEAR CONNECTIONS WITH BOLTS IN BEARINGS.
THE DESIGN LOAD FOR CONNECTIONS SHALL BE AS INDICATED ON SECTIONS, DETAILS OR
STANDARD AISC CONNECTION.
7. ALL BEAM CONNECTIONS SHALL HAVE ENLARGED OR SLOTTED HOLES TO PROVIDE END
ROTATION AS PER THE REQUIREMENTS OF THE AISC SPECIFICATIONS, SECTION J1.2, AND THE
LATEST SUPPLEMENTS AND SHALL ALSO REFLECT THE LOAD ECCENTRICITY IN THE DESIGN OF
THE CONNECTION.
8. NO CONNECTION SHALL CONSIST OF LESS THAN (2) 3/4" DIA. (A325-X) BOLTS OR WELD
DEVELOPING A MINIMUM OF 10,000 LBS. UNLESS INDICATED ON THE DRAWINGS.
9. ALL FILLET WELDS SHALL BE A MINIMUM OF 3/16" UNLESS NOTED OTHERWISE, BUT NOT LESS
THAN THE AISC MINIMUM.
10. THE FABRICATOR SHALL FURNISH A STRUCTURAL SUBMITTAL WHICH SHALL BE CHECKED BY THE
CONTRACTOR FOR COMPLETENESS AND CONTENT PRIOR TO SUBMITTAL TO THE CONTRACTING
OFFICER FOR REVIEW. THE SUBMITTAL SHOULD INCLUDE FABRICATION AND ERECTION
DRAWINGS AND DESIGN CALCULATIONS FOR CONNECTIONS AS SPECIFIED ON THE
CONSTRUCTION DOCUMENTS. THE DESIGN CALCULATIONS SHALL BEAR THE SEAL AND
SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF FLORIDA. FABRICATION
SHALL NOT COMMENCE UNTIL THIS REVIEW IS COMPLETED.
11. SIZES OF STRUCTURAL STEEL CANNOT BE VARIED FROM THOSE SHOWN ON THE DRAWINGS
WITHOUT WRITTEN PERMISSION FROM THE CONTRACTING OFFICE.
12. CUTS, HOLES AND THEIR REINFORCEMENT (REQUIRED BY OTHER TRADES) SHALL BE SHOWN ON
THE STRUCTURAL STEEL SHOP DRAWINGS AND SHALL BE MADE IN THE SHOP. FIELD BURNING OF
HOLES AND CUTS IN STRUCTURAL STEEL SHALL NOT BE PERMITTED EXCEPT BY WRITTEN
PERMISSION FROM THE CONTRACTING OFFICE.
13. ALL STRUCTURAL STEEL SHALL BE COATED WITH INORGANIC ZINC PER STRUCTURAL AND LIGHT
GAUGE STEEL COATINGS REQUIREMENTS ON DWG S-001.
14. AFTER ERECTION, ALL STEEL SHALL BE INSPECTED, AND CLEANED OF ANY FOREIGN MATERIALS.
ANY SCUFFS, ABRASIONS, (AND DAMAGED FINISH) SHALL BE FIELD TOUCHED-UP WITH AN
APPROVED COATING REPAIR SYSTEM.
15. TESTING OF WELDS AND BOLTS SHALL BE AS FOLLOWS: CHECK 100% OF ALL STRUCTURAL
STEEL, JOISTS, AND METAL DECK AND THEIR CONNECTIONS BY VISUAL INSPECTION AND REVIEW
TEST REPORTS OF THE FABRICATOR'S QUALITY CONTROL TESTS. CHECK ALL BOLTS IN 10% OF
ALL CONNECTIONS BY THE CALIBRATED TORQUE WRENCH METHOD OR BY THE TURN-OF-NUT
METHOD.
16. THE FOLLOWING MINIMUM STANDARDS APPLY:
STRUCTURAL ABBREVIATION LIST
A. A ANCHOR
AB ANCHOR BOLTS
ACI AMERICAN CONCRETE INSTITUTE
ADD'L ADDITIONAL
AFF ABOVE FINISH FLOOR
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
AL ALUMINUM
ALT ALTERNATE/ALTERNATIVE
APP'D APPROVED
ARCH ARCHITECTURAL, ARCHITECT
ASPH ASPHALT
ASTM AMERICAN SOCIETY OF TESTING
MATERIALS
AWS AMERICAN WELDING SOCIETY
B. B.⅊ BASE PLATE
B/ BOTTOM OF
BIT BITUMINOUS
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BRG BEARING
BU BUILT UP
C. C/C CENTER TO CENTER
CB CONCRETE BEAM
CC CONCRETE COLUMN
CE CONCRETE ENCASED
CF CUBIC FOOT/FEET
C CHANNEL
CHK CHECKERED
CI CAST IRON
CIP CONCRETE IN PLACE
CJ CONTRACTION JOINT
CL CLEAR/CLEARANCE
℄ CENTER LINE
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO COMPANY
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CON'T CONTINUOUS
COORD COORDINATE
COR CONTRACTING OFFICER
REPRESENTATIVE
CS CARBON STEEL
CJ CONSTRUCTION JOINT
CY CUBIC YARD
D. D DECK DIAPHRAGM LOAD (PLF)
DBA DOWEL BAR ANCHOR
DEG DEGREE
DEP DEPARTMENT
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIST DISTANCE
DN DOWN
DR DRAIN
DWG DRAWING
E. EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATION
ELEC ELECTRICAL/ELECTRIC
ENG ENGINEER
EOR ENGINEER OF RECORD
ES EQUAL SPACED
EQUIP EQUIPMENT
EW EACH WAY
EXCL EXCLUDING
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F. FB FLAT BAR
FD FLOOR DRAIN
FF FINISHED FLOOR
FG FINISHED GRADE
FL FLOOR
FDN FOUNDATION
FRP FIBERGLASS REINFORCED PLASTIC
FS FAR SIDE
FT FOOT/FEET
FTG FOOTING
G. GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GR GRADE
H. HORIZ HORIZONTAL
HDA HEADED STUD ANCHOR
HT HEIGHT
HDG HOT DIPPED GALVANIZED
I. ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INT INTERIOR
INV INVERT
J. JST JOIST
JT JOINT
K. K KIP
KO KNOCK OUT
KWY KEY WAY
L. L LENGTH
LDG LANDING
LONG LONGITUDE
LP LOW POINT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LWIC LIGHT WEIGHT INSULATING CONCRETE
M. MANUF MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MB MASONRY BEAM
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MJ MASONRY JOINT
MO MASONRY OPENING
MOM MOMENT
MTL METAL
N. NIC NOT IN CONTRACT
NS NEAR SIDE
N.T.S. NOT TO SCALE
O. OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
ORIENT ORIENTATION
P. P/C PRE CAST CONC
PAR PARALLEL
PENN PENETRATION
PERIM PERIMETER
⅊ PLATE
PLF POUNDS PER LINEAR FOOT
PLY PLYWOOD
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
Q. QTY QUANTITY
R. RA ROOF ACCESS
R/W REINFORCED WITH
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCING
REQ'D REQUIRED
RM ROOM
S. SCH SCHEDULE
SF SQUARE FEET
SIM SIMILAR
SJ SAW JOINT
SP SPACING
SPA SPACE(S)
SPEC SPECIFICATION
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIRR STIRRUPS
STL STEEL
SYM SYMMETRICAL
T. T&B TOP & BOTTOM
T/ TOP OF
T/C TOP OF CONCRETE
T/S TOP STEEL
TB TIE BEAM
TEMP TEMPORARY
TENS TENSION
THD THREAD(ED)
THK THICK
TJ TIE JOIST
TOL TOLERANCE
TOT TOTAL
TRANS TRANSVERSE
TS THICKENED SLAB
TYP TYPICAL
U. UON UNLESS OTHERWISE NOTED
U/N UNDERSIDE
V. VERT VERTICAL
VOL VOLUME
W. W WIDE
W/ WITH
W/O WITHOUT
WD WOOD
WF WIDE FLANGE
WH WEEP HOLE
WP WORKING POINT
WT WEIGHT
WWR WELDED WIRE REINFORCING
W FTG WALL FOOTING
X. XFMR TRANSFORMER
Y. Y WYE
Z. Z ZONE
1. DESIGN LOADS ARE BASED ON INTERNATIONAL BUILDING CODE (IBC) 2015. WIND LOAD
REFERENCE - ASCE, 7-10
(A) ULTIMATE WIND SPEED, Vult = 158 MPH (3-SEC GUST)
NOMINAL WIND SPEED, Vasd = 122 MPH (3-SEC GUST)
RISK CATEGORY: III
EXPOSURE: D
ENCLOSURE: OPEN
2. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH PROJECT DRAWINGS AND
SPECIFICATIONS. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO OBTAIN ALL
CONTRACT DOCUMENTS AND LATEST ADDENDA AND TO SUBMIT SUCH DOCUMENTS TO ALL
SUBCONTRACTORS AND MATERIALS SUPPLIERS PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS,
FABRICATION OF ANY STRUCTURAL MEMBERS, AND ERECTION IN THE FIELD.
3. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONNECTIONS AND ANCHOR BOLT
LOCATIONS FROM CERTIFIED DRAWINGS AND FABRICATOR'S ANCHOR BOLT SETTING PLANS.
4. DETAILS LABELED "TYPICAL DETAILS" ON THE DRAWINGS SHALL APPLY TO ALL SITUATIONS
OCCURRING ON THE PROJECT THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY
DETAILED. THE APPLICABILITY OF THE DETAIL TO ITS LOCATION ON THE PLANS CAN BE
DETERMINED BY THE TITLE OF THE DETAIL. SUCH DETAILS SHALL APPLY WHETHER OR NOT
THEY ARE KEYED IN AT EACH LOCATION. QUESTIONS REGARDING APPLICABILITY OF TYPICAL
DETAILS SHALL BE DETERMINED BY THE CONTRACTING OFFICE.
5. THE STRUCTURAL INTEGRITY OF THE COMPLETED STRUCTURE DEPENDS UPON THE
INTERACTION OF VARIOUS CONNECTED COMPONENTS. PROVIDE ADEQUATE BRACING, SHORING,
AND OTHER TEMPORARY SUPPORTS AS REQUIRED TO SAFELY COMPLETE THE WORK.
6. THE GENERAL CONTRACTOR SHALL COMPARE THE STRUCTURAL AND ELECTRICAL DRAWINGS
AND REPORT ANY DISCREPANCIES BETWEEN EACH SET OF DRAWINGS AND WITHIN EACH SET OF
DRAWINGS TO THE CONTRACTING OFFICE PRIOR TO THE FABRICATION AND INSTALLATION OF
ANY STRUCTURAL MEMBERS. WHERE CONFLICTS EXIST AMONG VARIOUS PARTS OF THE
STRUCTURAL CONTRACT DOCUMENTS, STRUCTURAL DRAWINGS, GENERAL NOTES AND
SPECIFICATIONS, THE STRICTEST REQUIREMENTS SHALL GOVERN.
7. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE AND DO NOT INDICATE THE METHOD OR MEANS OF CONSTRUCTION. THE
CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY RESPONSIBLE
FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, SEQUENCE, AND
SAFETY. THE ENGINEER DOES NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE
RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, OR
PROCEDURES, SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, THE
ACTS OR OMISSION OF THE CONTRACTOR, SUBCONTRACTOR, OR ANY OTHER PERSONS
PERFORMING ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE
WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS.
8. ALL STRUCTURES REQUIRE PERIODIC MAINTENANCE TO EXTEND LIFE SPAN AND TO ENSURE
STRUCTURAL INTEGRITY FROM EXPOSURE TO THE ENVIRONMENT. A PLANNED PROGRAM OF
MAINTENANCE SHALL BE ESTABLISHED BY THE OWNER. THIS PROGRAM SHALL INCLUDE ITEMS
SUCH AS, BUT NOT LIMITED TO, PAINTING OF STRUCTURAL STEEL, PROTECTIVE COATINGS FOR
CONCRETE, SEALANTS, CAULKED JOINTS, EXPANSION JOINTS, CONTROL JOINTS, SPALLS AND
CRACKS IN CONCRETE, AND PRESSURE WASHING OF EXPOSED STRUCTURAL ELEMENTS
EXPOSED TO SALT ENVIRONMENT OR OTHER HARSH CHEMICALS.
9. THE USE OF REPRODUCTIONS OF THESE CONTRACT DOCUMENTS AND USE OF CAD FILES BY ANY
CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR, OR MATERIAL SUPPLIER IN LIEU OF
PREPARATION OF SHOP DRAWINGS SIGNIFY HIS ACCEPTANCE OF ALL INFORMATION SHOWN
HEREON AS CORRECT, AND OBLIGATES HIM TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING
DUE TO ANY ERRORS THAT MAY OCCUR HEREON.
10. EXPANSION ANCHORS MAY BE SUBSTITUTED FOR ANCHOR BOLTS ONLY WITH THE WRITTEN
APPROVAL OF THE CONTRACTING OFFICE. EXPANSION ANCHORS USED SHALL BE HILTI, RAWL,
OR APPROVED EQUAL.
11. PROVIDE DISSIMILAR METAL SEPARATORS AT ALL JUNCTIONS OF ALUMINUM SOFFIT, FRAMING, STRUCTURAL STEEL, AND DISSIMILAR METALS.
GENERAL NOTES
1. POST INSTALLED ANCHORS SHALL BE USED ONLY WHERE SPECIFIED ON STRUCTURAL
DRAWINGS
2. THE INSTALLATION OF POST INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST IN-PLACE
ANCHORS SHALL BE APPROVED BY THE ENGINEER OF RECORD (EOR).
3. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE OR CMU SHALL NOT BE CUT
UNLESS APPROVED BY THE STRUCTURAL EOR.
4. SUBMITTAL OF ALL PROPOSED PRODUCTS, WITH TECHNICAL DATA AND CURRENT ICC-ESR
REPORTS IS REQUIRED FOR REVIEW AND APPROVAL BY EOR. ADDITIONAL APPLICATION
CALCULATIONS MAY BE REQUIRED BY THE EOR
5. ALL ANCHORS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED
INSTALLATION INSTRUCTIONS (MPII) IN CONJUNCTION WITH EDGE DISTANCE, SPACING AND
EMBEDMENT DEPTH AS INDICATED ON THE DRAWINGS
6. THE CONTRACTOR SHALL ARRANGE FOR A MANUFACTURER'S FIELD REPRESENTATIVE TO
PROVIDE INSTALLATION TRAINING FOR ALL PRODUCTS TO BE USED, PRIOR TO COMMENCEMENT
OF WORK. ONLY TRAINED INSTALLAERS SHALL PERFORM POST INSTALLED ANCHOR
INSTALLATION. A RECORD OF TRAINING SHALL BE KEPT ON SITE AND BE MADE AVAILABLE TO
THE EOR AS REQUESTED.
7. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION TO
SUPPORT SUSTAINED TENSION LOADS SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR
INSTALLER (AAI) AS CERTIFIED THROUGH ACI/CRSI (ACI 318-14 17.8.2.2). PROOF OF CURRENT
CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO
COMMENCEMENT OF INSTALLATION.
8. ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS (ACI
318-14 17.1.2).
9. THE FOLLOWING MANUFACTURERS HAVE BEEN PREAPPROVED FOR SUBMITTAL.
A. POWERS FASTENERS
B. HILTI INC
C. SIMPSON
D. APPROVED EQUALS
CONCRETE ANCHORS
11. MECHANICAL ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE
WITH ACI 355.2 AND ICC-ES AC193 FOR CRACKED, UNCRACKED AND SEISMIC CONCRETE
RECOGNITION.
12. ADHESIVE ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE
WITH ACI 355.4 AND ICC-ES AC308 FOR CRACKED, UNCRACKED AND SEISMIC CONCRETE
RECOGNITION.
13. CAST-IN-PLACE INSERTS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE
WITH ICC-ES AC446 FOR CRACKED, UNCRACKED AND SEISMIC CONCRETE RECOGNITION.
SPECIAL INSPECTION
14. SPECIAL INSPECTION REQUIREMENTS
A. PROVIDE SPECIAL INSPECTION FOR ALL MECHANICAL AND ADHESIVE ANCHORS PER THE
APPLICABLE BUILDING CODE AND PER THE CURRENT ICC-ES REPORT (IBC 2015 TABLE
1705.3 NOTE B).
B. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL OR UPWARDLY INCLINED ORIENTATIONS
TO RESIST SUSTAINED TENSION LOADS SHALL BE CONTINUOUSLY INSPECTED DURING
INSTALLATION BY AN INSPECTOR SPECIALLY APPROVED FOR THAT PURPOSE BY THE
BUILDING OFFICIAL (ACI 318-14 17.8.2.2)
ANCHORS IN CONCRETE AND MASONRY
WORK SITE SHALL BE KEPT ORGANIZED AND MEASURES TO REDUCE DUST AND FOD GENERATION
SHALL REMAIN IN PLACE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING ALL EQUIPMENT AND
TRUCK ROUTES CLEAR OF FOREIGN OBJECT DEBRIS DURING THE COURSE OF AND AT THE END OF
THE WORK DAY.
CLEAN WORK AREA/FOD PREVENTION
CONTRACTOR SHALL ALLOW FOR SUSPENSION OF WORK BASED ON BASE OPERATIONS AND SEVERE
WEATHER WORK RESTRICTIONS.
OPERATIONS/WEATHER DELAYS
MULTIPLE SHEETS
= CUT FROM
DIRECTION OF CUT
CUT ON SHEET
SHOWN ON SHEET
DESIGNATION
SECTION CALLOUT
(C) SEISMIC PARAMETERS:
a. RISK CATEGORY: III
b. SEISMIC SITE CLASS: D
c. MAPPED RESPONSE (SS): 0.073
d. MAPPED RESPONSE (S1): 0.039
e. DESIGN CATEGORY (SDC): A
f. SEISMIC IMPORTANCE: 1.25
g. SITE COEFFICIENT (FA): 1.6
h. SITE COEFFICIENT (FV): 2.4
i. DESIGN RESPONSE (SMS): 0.117
j. DESIGN RESPONSE (SM1): 0.093
k. DESIGN RESPONSE (SDS): 0.078
l. DESIGN RESPONSE (SD1): 0.062
m. RESPONSE MOD FACTOR, R: 3
n. APP PERIOD: 0.376
NOTE: THE SEISMIC ANALYSIS PROCEDURE USED ON THIS STRUCTURE IS THE
EQUIVALENT LATERAL FORCE PROCEDURE
1. STRUCTURAL ALUMINUM SHALL BE DOMESTIC ALLOY 6061-T6. DESIGNED IN ACCORDANCE WITH
THE ALUMINUM ASSOCIATION'S SPECIFICATIONS FOR ALUMINUM STRUCTURES, LATEST EDITION
2. FASTENERS: UNLESS DETAILED OTHERWISE, All FASTENERS SHALL BE 316 STAINLESS STEEL.
ALUMINUM BOLTS, WHERE SPECIFIED, SHALL BE 2024-14 OR 6061-T6 ALLOY.
3. All WELDING SHALL COMPLY WITH THE AWS D1.2, LATEST STRUCTURAL WELDING
CODE-ALUMINUM. FILLER ALLOYS SHALL BE SELECTED FROM TABLES M.9.1 AND M.9.2
4. VISUAL INSPECTION OF WELDS IS REQUIRED BY AWS CERTIFIED INSPECTORS.
5. WHERE UNCOATED ALUMINUM IS PLACED IN CONTACT WITH STEEL SURFACES THE STEEL
SURFACES SHALL BE PAINTED WITH A COATING SUITABLE FOR THE SURFACE. ALUMINIZED OR
GALVANIZED STEEL IN CONTACT WITH ALUMINUM SHALL NOT BE COATED.
6. ALUMINUM, STAINLESS STEEL, AND PLATED SURFACES SHALL NOT NORMALLY BE PAINTED.
7. DO NOT PAINT FASTENER THREADS. TO PRESERVE THREADS, COAT TAPPED HOLES WITH
STM0807-01.
ALUMINUM NOTES
GOPHER TORTOISE AND OSPREY NESTING: CONTRACTOR
SHALL NOT BEGIN ANY WORK ON TOWER UNTIL EXISTING
GOPHER TORTOISE AND OSPREY NEST HAS BEEN RELOCATED.
CONTRACTOR SHALL NOTIFY CONTRACTING OFFICER TO
COORDINATE NEST RELOCATION WITH KSC ENVIRONMENTAL
1. ALL CONCRETE SHALL BE AS DESIGNED TO DEVELOP A COMPRESSIVE STRENGTH AS FOLLOWS:
FOUNDATIONS 5000 PSI
2. ALL REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A-615 GRADE 60
(FY=60 KSI).
3. ALL CONCRETE REINFORCEMENT SHALL BE DETAILED, FABRICATED, LABELED, SUPPORTED AND
SPACED IN FORMS AND SECURED IN PLACE IN ACCORDANCE WITH THE PROCEDURES AND
REQUIREMENTS OUTLINED IN THE LATEST EDITION OF THE "BUILDING CODE REQUIREMENTS FOR
REINFORCED CONCRETE", ACI 318-14 AND THE "MANUALS OF STANDARD PRACTICE FOR DETAILING
REINFORCED CONCRETE STRUCTURES", ACI SP-66 (94). SHOP DRAWINGS SHALL BE SUBMITTED TO
THE CONTRACTING OFFICER FOR REVIEW PRIOR TO FABRICATION.
4. ALL BAR SPLICES SHALL BE AS FOLLOWS:
A. HORIZONTAL BARS WHERE 12" OF CONCRETE WILL BE PLACED BELOW BOTTOM
B. ALL OTHER BARS
5. CALCIUM CHLORIDE SHALL NOT BE USED IN ANY FORM.
6. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS (U.O.N.):
7. UNLESS OTHERWISE PERMITTED OR SPECIFIED, THE CONCRETE SHALL BE PROPORTIONED AND
PRODUCED TO HAVE A SLUMP PER SPECIFICATIONS. IMMEDIATELY AFTER DEPOSITING, CONCRETE
SHALL BE THOROUGHLY CONSOLIDATED BY MEANS OF MECHANICAL VIBRATION.
8. WELDED WIRE REINFORCING SHALL CONFORM TO ASTM A-185.
3 INCHES
1.5 INCHES
MINIMUM CLEAR COVER
EXPOSED TO EARTH
ALL OTHER CONDITIONS
STRUCTURAL PART
CONCRETE CAST AGAINST AND PERMANENTLY
SLABS, WALLS, NOT EXPOSED TO EARTH OR WEATHER 1 INCHES
1098764 53
BAR SIZES #
3 54 6 7 8 9 10
BAR SIZES #
5000 PSI LAP (IN)
9122 3629 43 63 72 81
6355493322 2817 70
LAP (IN)5000 PSI
CONCRETE NOTES
9. PROVIDE CORNER BARS IN FOOTINGS AND IN TIE BEAMS (CAST IN PLACE & BOND
BEAMS), TYPICAL.
10. NON-SHRINK GROUT FOR BASE PLATES AND BEARING PLATES SHALL MEET THE
FOLLOWING:
A. NON-METALLIC, SHRINKAGE RESISTANT PREMIXES NON-CORROSIVE, NON-STAINING
PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE COMPENSATING
AGENTS, AND FLUIDITY IMPROVING COMPOUNDS, AND SHALL CONFORM TO CORPS OF
ENGINEERS SPECIFICATION FOR NON-SHRINK GROUT, CRD-C621-83.
B. TWENTY-EIGHT DAY COMPRESSIVE STRENGTH SHALL BE A MINIMUM OF 10,000 PSI.
11. PROVIDE MINIMUM TEMPERATURE REINFORCEMENT AS REQUIRED BY ACI 318 IN ALL
SLABS AND WALLS WHERE REINFORCEMENT IS NOT INDICATED ON DRAWINGS.
12. HOOKS SHOWN AT THE ENDS OF REINFORCING BARS SHALL BE ACI STANDARD 90°
HOOKS OF THE FOLLOWING LENGTHS, (U.O.N.):
13. WALL FOOTINGS (W FTG) SHALL EXTEND PAST THE END OF A WALL A MINIMUM OF 12".
14. COORDINATE SIZE AND LOCATION OF ALL OPENINGS AND PIPE SLEEVES WITH ARCH AND
MECH DRAWINGS. MINIMUM CONCRETE BETWEEN SLEEVES SHALL BE 6 INCHES.
15. ALL EMBEDDED ITEMS, SUCH AS PLATES AND ANCHOR BOLTS, SHALL BE TIED TO
REINFORCING STEEL AND/OR FORMWORK PRIOR TO CONCRETE PLACEMENT. "WET"
PLACEMENT OF BARS OR EMBED ITEMS SHALL NOT BE PERMITTED.
16. ALL WELDABLE DEFORMED BARS SHALL BE A706.
CONCRETE NOTES (CONTINUED)
BARS SIZES (#)
LENGTH
3 4 5 6 7 8 9 10
22"19"16"14"12"10"8"6"
AutoCAD SHX Text
(SOME MAY NOT BE USED)
AutoCAD SHX Text
AutoCAD SHX Text
S-100
R
V B
T O
W E
R
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
S-100 S-100
S-100 S-100
S-100 S-100
S-100 S-100
1/4" = 1'-0"
ELEVATION
NORTH
S-100 S-100 1/4" = 1'-0"
ELEVATION
WEST
S-100 S-100 1/4" = 1'-0"
ELEVATION
SOUTH
S-100 S-100 1/4" = 1'-0"
ELEVATION
EAST
S-100 S-100
N
LARGE HOLE
SECTION LOSS
CORRODED
GUY WIRE
LOOSE CLAMP
CORRODED
EXISTING
CONCRETE
FOUNDATION
CORRODED
GUY WIRE
CORRODED
GUY WIRE
CORRODED
GUY WIRE
GENERAL NOTES:
1. SEE S-101 FOR PHOTOS AND REPAIR PROCEDURES.
2. SEE S-102 FOR NEW GUY WIRE ASSEMBLY DETAIL AND
SCHEDULE.
3. CONTRACTOR TO PROTECT EXISTING WEATHER
INSTRUMENTATION WHILE PERFORMING WORK.
4. ALL GUY WIRE ASSEMBLIES ARE TO BE REPLACED.
5. CONTRACTOR TO RESURVEY TOWER FOR PLUMBNESS
AFTER INSTALLATION OF NEW GUY WIRE ASSEMBLIES.
6. THE EXISTING FALL PROTECTION SYSTEM SHALL BE
REPLACED WITH A NEW SYSTEM MEETING ALL OSHA
REQUIREMENTS.
7. FALL PROTECTION SYSTEM SHALL HAVE STAINLESS STEEL
COMPONENTS AND CABLE COMPATIBLE WITH DBI SALA
LAD-SAF OR APPROVED EQUAL
CORRODED
GUY WIRE
CORRODED
GUY WIRE
CORRODED
GUY WIRE
CORRODED
GUY WIRE
GUY WIRE
(TYP)
FULL GUY WIRE IS NOT
SHOWN FOR CLARITY
REPAIR PROCEDURES:
REPAIR #1 - REPAIR PIPE WITH SECTION LOSS BY WELDING ALUMINUM
ROUND TUBE 2.500 OD X 0.25 WALL X 1'-0” LONG AROUND AFFECTED
AREA. CLEAN AND PREPARE AREA AROUND PIPE SECTION LOSS FOR
WELDING, REMOVING ANY PROTRUSIONS OR BURS AND ENSURING A
SNUG FIT. CUT ROUND TUBE IN HALF ALONG LENGTH AND CLAMP
OVER REPAIR AREA CENTERING REPAIR AREA IN CENTER OF 1'-0”
SECTION. ENSURE SEAM OF REPAIR TUBE DOES NOT OVERLAP AREA
OF SECTION LOSS. WELD ENDS OF TUBE TO EXISTING PIPE USING
3/16” WELD AND BUTT WELD SEAM OF TUBE ON BOTH SIDES.
REPAIR #2 - REPLACE ALL CORRODED OUTRIGGER CLAMP BOLTS
WITH NEW STAINLESS-STEEL HARDWARE TO MATCH EXISTING
ASSEMBLY.
REPAIR #3 - REPLACE GUY WIRE ASSEMBLY. WIRE ROPE FOR GUY
CABLES SHALL BE A TYPE M GUY STRAND, SIZE 10M, WITH A
BREAKING STRENGTH OF 10,000 LBS. (10 KIPS). ALUMOWELD
COMPANY OR APPROVED EQUAL. TURNBUCKLES SHALL BE SIZES AS
NOTED AND BE HOT-DIPPED GALVANIZED STEEL, 5/8” X 12” TAKE-UP,
JAW & JAW TYPE. TURNBUCKLE SHALL MEET THE PERFORMANCE
REQUIREMENTS OF FED-SPEC FF-T791B, TYPE 1, FORM 1, CLASS 7
AND ASTM F1145. CROSBY P/N HG-228 OR APPROVED EQUAL. ANCHOR
SHACKLES SHALL BE 3.8” SIZE AND BE HOT-DIPPED GALVANIZED
STEEL. CROSBY P/N G-2130 OR APPROVED EQUAL. WIRE ROPE
THIMBLES SHALL BE 3/8” SIZE AND BE STAINLESS STEEL. CROSBY P/N
SS-414 OR APPROVED EQUAL. SUBCONTRACTOR SHALL SUBMIT ALL
MANUFACTURER'S PRODUCT DATA FOR ENGINEERING APPROVAL.
CORRODED
GUY WIRE
CORRODED
GUY WIRE
S-101
S-101
S-101
S-101
GRAPHIC SCALE
1/8"=1'-0"
4' 20'15'10'5'
GRAPHIC SCALE
1/4"=1'-0"
2' 10'4'2' 6' 8'
S-101
R
V B
T O
W E
R
O
T O
S
A
T
E S
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
REPAIR PROCEDURES:
REPAIR #1 - REPAIR PIPE WITH SECTION LOSS BY WELDING ALUMINUM
ROUND TUBE 2.500 OD X 0.25 WALL X 1'-0” LONG AROUND AFFECTED
AREA. CLEAN AND PREPARE AREA AROUND PIPE SECTION LOSS FOR
WELDING, REMOVING ANY PROTRUSIONS OR BURS AND ENSURING A
SNUG FIT. CUT ROUND TUBE IN HALF AND CLAMP OVER REPAIR AREA
CENTERING REPAIR AREA IN CENTER OF 1'-0” SECTION. ENSURE SEAM
OF REPAIR TUBE DOES NOT OVERLAP AREA OF SECTION LOSS. WELD
ENDS OF TUBE TO EXISTING PIPE USING 3/16” WELD AND BUTT WELD
SEAM OF TUBE ON BOTH SIDES.
REPAIR #2 - REPLACE ALL CORRODED OUTRIGGER CLAMP BOLTS
WITH NEW STAINLESS-STEEL HARDWARE TO MATCH EXISTING
ASSEMBLY.
REPAIR #3 - REPLACE GUY WIRE ASSEMBLY. WIRE ROPE FOR GUY
CABLES SHALL BE A TYPE M GUY STRAND, SIZE 10M, WITH A
BREAKING STRENGTH OF 10,000 LBS. (10 KIPS). ALUMOWELD
COMPANY OR APPROVED EQUAL. TURNBUCKLES SHALL BE SIZES AS
NOTED AND BE HOT-DIPPED GALVANIZED STEEL, 5/8” X 12” TAKE-UP,
JAW & JAW TYPE. TURNBUCKLE SHALL MEET THE PERFORMANCE
REQUIREMENTS OF FED-SPEC FF-T791B, TYPE 1, FORM 1, CLASS 7
AND ASTM F1145. CROSBY P/N HG-228 OR APPROVED EQUAL. ANCHOR
SHACKLES SHALL BE 3.8” SIZE AND BE HOT-DIPPED GALVANIZED
STEEL. CROSBY P/N G-2130 OR APPROVED EQUAL. WIRE ROPE
THIMBLES SHALL BE 3/8” SIZE AND BE STAINLESS STEEL. CROSBY P/N
SS-414 OR APPROVED EQUAL. SUBCONTRACTOR SHALL SUBMIT ALL
MANUFACTURER'S PRODUCT DATA FOR ENGINEERING APPROVAL.
N.T.S.
PHOTO 2
N.T.S.
PHOTO
N.T.S.
PHOTO 4
N.T.S.
PHOTO
48'-0"
FACE OF TOWER LEG
SYMMETRICAL ABOUT CENTERLINE
F
I E
V
R
I F
Y
C
O N
N E
C T
I O
N
P O
I N
T
H
E I G
H T
F
I E
R
I F
Y
C
O N
N E
C T
I O
N
P O
I N
T
H
E I G
H T
Z
M
F
I
E
R
I
N
G
Q
U
I
R
E
D
R
Z
M
F
I
E
R
I
N
G
Q
U
I
R
E
D
TURNBUCKLE
REGULAR NUT EYE BOLT
THIMBLE
SHACKLE
S-102
P R
V B
G U
Y
W
I R
E
D
E T
A
W
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
GUY WIRE DATA TABLE
GUY
ELEVATION
(FT.)
# OF WIRES
AND SIZE
TYPE
ULTIMATE
STRENGTH
(KIPS)
INITIAL
TENSION
(KIPS)
TURNBUCKLE *
(JAW & JAW)
SHACKLE **
SIZE (IN.)
THIMBLE ***
(IN.)
REMARKS
25'-0" 1-10M
ALUMO
WELD (AM)
10.0 1.0
" x 12' TAKE UP
" SEE REPAIR #3 ON S-101
49'-0" 2-10M
ALUMO
WELD (AM)
10.0
" x 12' TAKE UP
" SEE REPAIR #3 ON S-101
* - PEEN BOLT THREADS PAST NUTS.
** - BOLT TYPE ANCHOR SHACKLE, SEE FLAG NOTE "D" ON THIS SHEET
*** - EXTRA HEAVY STAINLESS STEEL
NOTES:
A. USE
" DIA. STAINLESS STEEL 304 PIPE SLEEVE (SCH. 160).
" LENGTH FOR EACH
SHACKLE/THIMBLE ASSEMBLY
B. USE PREFORM GRIP CABLE CONNECTION WITH END SLEEVE'S FOR 10M
ALUMOWELD CABLE.
C. ALL THREADS SHALL RECEIVE CORROSION CONTROL CORTEC CORP. VCI-368HB
FINISH GRADE
CONNECTION POINT #1
EL. 25'-0"
CONNECTION POINT #2
EL. 49'-0"
TOP OF TOWER
EL. 58'-0"
REPLACE COTTER PIN
WITH STAINLESS
STEEL COTTER PIN
REPLACE COTTER PIN
WITH STAINLESS
STEEL COTTER PIN
1/8" = 1'-0"
GUY WIRE AND TOWER ELEVATION
1/4" = 1'-0"
GUY WIRE TURNUCKLE, THIMBLE AND SHACKLE
1. EXISTING GUY WIRE ANCHOR FOUNDATION.
2. EXISTING GUY WIRE ANCHOR WITH CONNECTION PLATE.
3. STAINLESS STEEL SLEEVE, 3/4" DIA., SCHEDULE 160,
" (L) AT BOTH
ENDS OF THE JAW AND JAW TURNBUCKLE.
4.
" TURNBUCKLE x 12" TAKE UP, JAW AND JAW (PEEN BOLTS THREADS
PAST NUTS, GALVANIZED).
5. FIGURE-8 SAFETY WIRE ASSEMBLY THROUGH TURNBUCKLE JAW AND
JAW BODY.
" DIA. STAINLESS STEEL FLEXIBLE ROPE AND
STAINLESS STEEL U-BOLT TYPE WIRE ROPE.
6.
" EXTRA HEAVY STAINLESS STEEL THIMBLE.
7. PREFORMED WIRE CONNECTOR FOR 10M ALUMOWELD WIRE WITH END
SLEEVES (AT LOWER END).
8. 10M ALUMOWELD GUY WIRE (12" (L) EXTENSION OF GUY WIRE PAST
PREFORM FOR CONNECTION OF GROUNDING AT BOTH ENDS OF THE
WIRE).
9. PREFORMED WIRE CONNECTOR FOR 10M ALUMOWELD WIRE WITH END
SLEEVE (AT HIGH END).
10.
" EXTRA HEAVY STAINLESS STEEL THIMBLE.
11. STAINLESS STEEL SLEEVE, PIPE
" DIA., SCHEDULE 160,
" (L).
12.
" BOLT TYPE ANCHOR SHACKLE (2 PIECES).
13. EXISTING TOWER CONNECTION PADEYE.
NOTE: AT GUY WIRE CONNECTION AT THE SECOND LEVEL, CONNECT ONE
GUY WIRE AT EACH LEG TO PADEYE. CONNECT GUY WIRE TO TOWER LEG
ABOVE PADEYE WITH PREFORMED WIRE CONNECTOR PLACED AROUND
TOWER LEG WITHOUT SHACKLE, THIMBLE AND PIPE SLEEVE.
DESCRIPTION OF NEW GUY WIRE ASSEMBLY:
(FROM THE ANCHOR UP TO THE TOWER PADEYE)
GRAPHIC SCALE
1/8"=1'-0"
4' 20'15'10'5'
GRAPHIC SCALE
1/4"=1'-0"
2' 10'4'2' 6' 8'
S-200
R
V B
T O
W E
R
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
1/8" = 1'-0"
TOWER 415 PLAN
S-200 S-200
S-200 S-200
S-200 S-200
S-200 S-200
1/4" = 1'-0"
ELEVATION
SOUTH
S-200 S-200 1/4" = 1'-0"
ELEVATION
WEST
S-200 S-200 1/4" = 1'-0"
ELEVATION
NORTH
S-200 S-200 1/4" = 1'-0"
ELEVATION
EAST
S-200 S-200
N
SPLIT MEMBER
BOTH SIDES BROKEN
CLAMP, SEE REPAIR
#2
COLUMN CRACK
AT CLAMP
MISSING PIN
SPLIT MEMBER
SEVERE CORROSION
UNDER LPS CLAMP
CORRODED SECTION
LOSS BEHIND CLAMP
SPLIT MEMBER
SEVERE CORROSION
UNDER LPS CLAMP
COMPROMISED
SECTION
SPLIT MEMBER
SPLIT MEMBER
SPLIT MEMBER
GENERAL NOTES:
1. SEE S-201 FOR PHOTOS AND REPAIR PROCEDURES.
2. CONTRACTOR TO PROTECT EXISTING WEATHER
INSTRUMENTATION WHILE PERFORMING WORK.
3. ACCESS IS RESTRICTED TO TOWER 415 BY A GATE.
CONTRACTOR TO COORDINATE ACCESS TO TOWER 415
WITH GOVERNMENT.
4. THE EXISTING FALL PROTECTION SYSTEM SHALL BE
REPLACED WITH A NEW SYSTEM MEETING ALL OSHA
REQUIREMENTS.
5. FALL PROTECTION SYSTEM SHALL HAVE STAINLESS STEEL
COMPONENTS AND CABLE COMPATIBLE WITH DBI SALA
LAD-SAF OR APPROVED EQUAL.
EXISTING
CHAIN-LINK
FENCE
EXISTING
CONCRETE PAD
CORRODED
BASE PLATE
CORRODED BASE
PLATE SEE REPAIR
#6 TYPICAL
CORRODED
BASE PLATE
SEVERE CORROSION
UNDER LPS CLAMP
SEVERE CORROSION
UNDER LPS CLAMP
COMPROMISED
SECTION
SPLIT MEMBER
SEVERE CORROSION
UNDER LPS CLAMP
SEVERE CORROSION
UNDER LPS CLAMP
SEVERE CORROSION
UNDER LPS CLAMP
SEVERE CORROSION
UNDER LPS CLAMP
GUY WIRE
(TYP)
FULL GUY WIRE IS NOT
SHOWN FOR CLARITY
REPAIR PROCEDURES:
REPAIR #1 - REPAIR PIPE WITH SECTION LOSS BY WELDING
ALUMINUM ROUND TUBE 2.500 OD X 0.25 WALL X 1'-0” LONG
AROUND AFFECTED AREA. REMOVE LPS CLAMP, CLEAN AND
PREPARE AREA AROUND PIPE SECTION LOSS FOR WELDING,
REMOVING ANY PROTRUSIONS OR BURS AND ENSURING A SNUG
FIT. CUT ROUND TUBE IN HALF AND CLAMP OVER REPAIR AREA
CENTERING REPAIR AREA IN CENTER OF 1'-0” SECTION. ENSURE
SEAM OF REPAIR TUBE DOES NOT OVERLAP AREA OF SECTION
LOSS. WELD ENDS OF TUBE TO EXISTING PIPE USING 3/16” WELD
AND BUTT WELD SEAM OF TUBE ON BOTH SIDES.
REPAIR #2 - REPAIR CRACKED/SPLIT BRACKET. BRACE EXISTING
STRUCTURE AROUND BRACKET TO ALLOW REMOVAL. REMOVE
CRACKED/SPLIT BRACKET AND ATTACHED MEMBER FROM
STRUCTURE. REMOVE ANY PREVIOUS WELDING, PROTRUSIONS OR
BURS FROM CONNECTION AREA. CLEAN AND PREPARE AREA
ALLOW FOR REINSTALLATION OF BRACKET. REPLACE BRACKET IN
KIND AND REINSTALL ONTO STRUCTURE USING 3/16” WELD.
REPAIR #3 - REPAIR CRACKED/SPLIT MEMBER. BRACE EXISTING
STRUCTURE AROUND MEMBER TO ALLOW REMOVAL. REMOVE
MEMBER WITH BRACKETS FROM STRUCTURE, REMOVING WELD
AND ENSURING NOT TO DAMAGE COLUMN. REMOVE ANY PREVIOUS
WELDING, PROTRUSIONS OR BURS FROM CONNECTION AREA.
CLEAN AND PREPARE AREA ALLOW FOR REINSTALLATION OF
BRACKET. REPLACE PIPE SECTION IN KIND AND REINSTALL ONTO
STRUCTURE USING 3/16” WELD.
REPAIR #4 - BRACE EXISTING STRUCTURE AROUND BRACKET TO
ALLOW REMOVAL OF SURROUND MEMBERS. REPAIR COLUMN
SECTION SIMILAR TO REPAIR #1. FABRICATE NEW BRACKETS TO
ACCOMMODATE NEW DIAMETER OF REPAIRED COLUMN SECTION.
REPAIR #5 - MEMBER WITH MISSING PIN. FIELD DRILL 5/16” HOLE IN
BRACKET AND THROUGH CENTER OF PIPE MEMBER. INSTALL 1/4”
DIA. STAINLESS STEEL BOLT THROUGH BRACKET AND PIPE
SECTION.
REPAIR #6 - REPAIR BASE PLATE. SHORE TOWER TO ALLOW
REMOVAL OF EXISTING BASE PLATE AND ANCHOR BOLTS. SUBMIT
SHORING PLAN FOR REVIEW. RE-FABRICATE BASE PLATE TO
MATCH EXISTING DIMENSIONS AND CONFIGURATION. REINSTALL
BASE PLATE ASSEMBLY, ATTACHING TO CONCRETE PAD USING (4)
1/2" DIA. STAINLESS STEEL HILTI HIT-Z ANCHOR RODS BY FIELD
DRILLING AND EPOXY INSTALL USING HILTI HY-200 WITH MINIMUM
EMBEDMENT OF 4”.
GRAPHIC SCALE
1/8"=1'-0"
4' 20'15'10'5'
GRAPHIC SCALE
1/4"=1'-0"
2' 10'4'2' 6' 8'
S-201
S-201
S-201
S-201
S-201
S-201
S-201
S-201
R
V B
T O
W E
R
O
T O
S
A
T
E S
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
N.T.S.
PHOTO 2
N.T.S.
PHOTO 3
N.T.S.
PHOTO
N.T.S.
PHOTO 5
N.T.S.
PHOTO 6
N.T.S.
PHOTO
REPAIR PROCEDURES:
REPAIR #1 - REPAIR PIPE WITH SECTION LOSS BY WELDING
ALUMINUM ROUND TUBE 2.500 OD X 0.25 WALL X 1'-0” LONG
AROUND AFFECTED AREA. REMOVE LPS CLAMP, CLEAN AND
PREPARE AREA AROUND PIPE SECTION LOSS FOR WELDING,
REMOVING ANY PROTRUSIONS OR BURS AND ENSURING A SNUG
FIT. CUT ROUND TUBE IN HALF AND CLAMP OVER REPAIR AREA
CENTERING REPAIR AREA IN CENTER OF 1'-0” SECTION. ENSURE
SEAM OF REPAIR TUBE DOES NOT OVERLAP AREA OF SECTION
LOSS. WELD ENDS OF TUBE TO EXISTING PIPE USING 3/16” WELD
AND BUTT WELD SEAM OF TUBE ON BOTH SIDES.
REPAIR #2 - REPAIR CRACKED/SPLIT BRACKET. BRACE EXISTING
STRUCTURE AROUND BRACKET TO ALLOW REMOVAL. REMOVE
CRACKED/SPLIT BRACKET AND ATTACHED MEMBER FROM
STRUCTURE. REMOVE ANY PREVIOUS WELDING, PROTRUSIONS OR
BURS FROM CONNECTION AREA. CLEAN AND PREPARE AREA
ALLOW FOR REINSTALLATION OF BRACKET. REPLACE BRACKET IN
KIND AND REINSTALL ONTO STRUCTURE USING 3/16” WELD.
REPAIR #3 - REPAIR CRACKED/SPLIT MEMBER. BRACE EXISTING
STRUCTURE AROUND MEMBER TO ALLOW REMOVAL. REMOVE
MEMBER WITH BRACKETS FROM STRUCTURE, REMOVING WELD
AND ENSURING NOT TO DAMAGE COLUMN. REMOVE ANY PREVIOUS
WELDING, PROTRUSIONS OR BURS FROM CONNECTION AREA.
CLEAN AND PREPARE AREA ALLOW FOR REINSTALLATION OF
BRACKET. REPLACE POPE SECTION IN KIND AND REINSTALL ONTO
STRUCTURE USING 3/16” WELD.
REPAIR #4 - BRACE EXISTING STRUCTURE AROUND BRACKET TO
ALLOW REMOVAL OF SURROUND MEMBERS. REPAIR COLUMN
SECTION SIMILAR TO REPAIR #1. FABRICATE NEW BRACKETS TO
ACCOMMODATE NEW DIAMETER OF REPAIRED COLUMN SECTION.
REPAIR #5 - MEMBER WITH MISSING PIN. FIELD DRILL 5/16” HOLE IN
BRACKET AND THROUGH CENTER OF PIPE MEMBER. INSTALL 1/4”
DIA. STAINLESS STEEL BOLT THROUGH BRACKET AND PIPE
SECTION.
REPAIR #6 - REPAIR BASE PLATE. SHORE TOWER TO ALLOW
REMOVAL OF EXISTING BASE PLATE AND ANCHOR BOLTS. SUBMT
SHORING PLAN FOR REVIEW. REFABRICATE BASE PLATE TO MATCH
EXISTING DIMENSIONS AND CONFIGURATION. REINSTALL BASE
PLATE ASSEMBLY, ATTACHING TO CONCRETE PAD USING (4) 1/2"
DIA. STAINLESS STEEL HILTI HIT-Z ANCHOR RODS BY FIELD
DRILLING AND EPOXY INSTALL USING HILTI HY-200 WITH MINIMUM
EMBEDMENT OF 4”. EXECUTION METHOD MUST BE SUBMITTED FOR
APPROVAL.
N.T.S.
PHOTO
TYP
TYP
C
L
5'-0" DIA FDN
C
L
F
D N
REPLACEMENT POLE
(PRECAST PRESTRESSED
CONCRETE)
DOMED FOR DRAIN
" SLOPE MIN.
GRADE
#4 TIES
AT 12" MAX
(TYPICAL)
(24) #10 EQUAL SPACED
ON 60" DIA CIRCLE
CENTERED ON FDN
CONCRETE POLE
FOUNDATION
C
L
3" CLEARANCE
FROM TIES (TYP)
PROVIDE TEMPORARY 5'-0" DIA
x 4'-0" (EMBED) STEEL SHAFT
LINER TO ENSURE STABILITY OF
SIDES DURING EXCAVATION.
BACKFILL AND COMPACT
AROUND COMPLETED FOOTING
TO 95% MODIFIED PROCTOR
(ASTM D-1557), TO 2' DEPTH
P
A
#4 TIES
24 #10 VERT
R
T
Y
P
BOTTOM
OF POLE
S-300
P R
V B
P L
A Y
A L
I N
A
T H
L
E
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
POLE INFORMATION
ULTIMATE CAPACITY (AT G.L.)
--- KIP#FT
CRACKING CAPACITY (AT G.L.)
-- KIP#FT
ZERO TENSION CAPACITY (AT G.L.)
-- KIP#FT
POLE WEIGHT --- LBS
CONCRETE STRENGTH STATIC ---- PSI
POLE TAPER 0.216 IN/FT
GENERAL NOTES:
1. WORK TO THE TOWER SHALL BE COORDINATED WITH CONTRACTING OFFICER.
2. BASED ON UTILITY LOCATES, THE CONTRACTOR SHALL INSTALL THE NEW POLE WITHIN 10
(TEN) FEET OF THE EXISTING WOODEN POLE LOCATION NORTHWARD PARALLEL TO THE
ACCESS ROAD AT THE SAME NOMINAL GROUND ELEVATION, AVOID EASTERLY LOW ELEVATION
AREA. THE CONTRACTOR SHALL GIVE THE CONTRACTING OFFICER 60 (SIXTY) WORKING DAYS
ADVANCE NOTICE FOR THE REMOVAL OF THE EQUIPMENT FROM THE EXISTING POLE. ONCE
THE EQUIPMENT HAS BEEN REMOVED, THE CONTRACTOR SHALL PULL OUT THE EXISTING
WOODEN POLE AND FILL THE HOLE WITH SATISFACTORY SOILS MATERIAL.THE CONTRACTOR
SHALL VERIFY EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE CALLED TO THE
ATTENTION OF THE CONTRACTING OFFICER BEFORE STARTING ANY WORK.
3. THE CONTRACTOR SHALL DRILL A 5'-0" DIAMETER x 15'-0" DEEP HOLE FOR THE INSTALLATION
OF NEW 64' POLE, WITH 54 FEET ABOVE GRADE AS INDICATED. PROVIDE WELL POINT
EQUIPMENT AS REQUIRED TO MAINTAIN SITE POSITIVE DRAINAGE. CONTRACTOR SHALL
SUBMIT INSTALLATION METHOD FOR APPROVAL PRIOR TO PERFORMING WORK.
4. THE CONTRACTOR SHALL INSTALL THE POLES CENTERED ON THE EXCAVATION AND PLUMB.
SEE POLE ORIENTATION PLAN.
5. A STAINLESS STEEL LADDER WITH A SAFETY RAIL, AS DETAILED ON THE LADDER DETAIL (SEE
SHEET S-301), SHALL BE INSTALLED BY CONTRACTOR ON THE CONCRETE POLE BY MEANS OF
MOUNTING ADAPTERS. THE LADDER WILL EXTEND FROM 10 FT. UP TO 50 FT. ABOVE GRADE.
THERE WILL BE REMOVABLE STEPS FROM 0 FT. UP TO 10 FT. ABOVE GRADE.
6. AFTER THE WORK IS COMPLETE, THE WORK AREA SHALL BE LEFT CLEAN OF TRASH, DEBRIS, AND WASTE MATERIAL.
7. ACCESS IS RESTRICTED TO POLE 0015 BY A GATE. CONTRACTOR TO COORDINATE ACCESS TO
POLE 0015 WITH GOVERNMENT.
8. NEW CONCRETE POLE WILL BE SURVEYED AND INFORMATION PROVIDED TO GOVERNMENT.
SEE SPECIFICATION SECTION 01 11 00.00 FOR SURVEY REQUIREMENTS.
WIND ASCE 7-10
ULTIMATE WIND SPEED, Vult = 158 MPH (3-SEC GUST)
NOMINAL WIND SPEED, Vasd = 122 MPH (3-SEC GUST)
RISK CATEGORY: III
EXPOSURE: D
ENCLOSURE: OPEN
ALL SOIL PROPERTIES ARE OUTLINED IN GEOTECHNICAL REPORT #18-23-5293
PERFORMED BY ARDAMAN & ASSOCIATES, INC DATED NOVEMBER 29, 2018.
SEE SOIL BORING PROFILE ON THIS SHEET.
DESIGN CRITERIA:
CONCRETE POLE AND INSTALLATION NOTES:
SCALE:
CONCRETE POLE FOUNDATION - NEW CONSTRUCTION
3/4" = 1'-0"
FLAG NOTES:
CONTRACTOR TO PROVIDE AND INSTALL NEW 64' PRECAST, PRE-STRESSED CONCRETE
SQUARE TAPER POLE AS SHOWN, WITH STAINLESS STEEL LADDER AND SAFETY RAIL.
LOCATION IS WITHIN 10' OF EXISTING.
SCALE:
SECTION
3/4"=1'-0"
A
SC-202
A. CONCRETE FOR FOUNDATIONS SHALL HAVE 5000 PSI COMPRESSIVE STRENGTH AT 28 DAYS.
CALCIUM CHLORIDE SHALL NOT BE USED IN ANY FORM.
B. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A 615.
C. THE PRE-STRESSED CONCRETE POLE SHALL BE DESIGNED FOR THE ALLOWABLE STRESS
DESIGN BENDING MOMENT OF 290.5 KIP-FT, OCCURRING AT LOCATION OF 10' FROM POLE
BOTTOM.
SCALE:
SOIL BORING PROFILES
3/4"=1'-0"
GRAPHIC SCALE
3/4"=1'-0"
6"12" 3'2'1'0
NOTE:
POLE INFORMATION TO BE FILLED OUT PER FINAL
APPROVED SHOP DRAWING SUBMITTAL.
FACE 1 FACE 3
FACE 2
(LIGHTNING PROTECTION)
SEE SHEET E-101
3'-4"
5'-6"
10'-0"
16'-0"
22'-0"
28'-0"
33'-0"
34'-0"
40'-0"
46'-0"
48'-0"
49'-0"
52'-6"
53'-0"
52'-0"
5'-8"
2'-9"
3'-10"
5'-0"
11'-6"
12'-3"
33'-0"
50'-6"
51'-3"
3/8"
3/8"
3/8"
FACE 4
(LADDER)
2'-0"
MIN. PER POLE
MANUFACTURER
(TYP)
MIN. PER POLE
MANUFACTURER
(TYP)
FACE 4
FACE 1
FACE 2
FACE 3
SIDE ELEVATION
(LADDER)
EL. + 50'-0"
EL. + 40'-0"
EL. + 30'-0"
EL. + 20'-0"
EL. + 10'-0"
EL. + 54'-0"
NOTE:
P R
O V
I D
E
I N
S E
R T
S
F
O R
R E
M O
V A
B
E
P S
F
T
T
O
F
T
ALL INSERTS SHALL BE STD. COARSE THREAD, 5/16" DIA.,
UNLESS NOTED OTHERWISE. DEPTH = 1 1/2".
MOUNTING
ADAPTER (TYP)
7"
L
A D
D E
R
S
E C
T I O
PRE-STRESSED
CONCRETE POLE
GRADE EL 0'-0"GRADE EL 0'-0"
A
RIGID SAFETY RAIL
LADDER
1" DIA RUNG (TYP)
AT 12" C/C
GRADE EL 0'-0"
GRADE
EL 0'-0"
16"
GRADE
EL 0'-0"
LADDER
C
L
POLE, LADDER
AND SAFETY RAIL
5" AT TOP ADAPTER
6" AT INT. ADAPTER
8" AT INT. ADAPTER
10" AT INT. ADAPTER
12" AT BOTTOM ADAPTER
SAFETY RAIL
LADDER
RUNG (TYP)
ON ADAPTER DRILL 5/8" DIA
HOLE FOR 1/2" DIA BOLT (TYP)
SP
S-301
P R
V B
P L
A Y
A L
I N
A
T H
L
E
D
E T
A I L
S
A N
D
N
O T
E S
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
SCALE:
POLE INSERTS DETAIL
NONE
1. LADDER: SHALL BE SHOP FABRICATED FROM TYPE 316 STAINLESS STEEL, WITH 300LB
CAPACITY MEETING OSHA AND ANSI A14.3 REQUIREMENTS, MATCHING CONFIGURATION OF THE VERSATILE-MOUNT
STEEL LADDER, 4 EACH, 10 FT. LONG SECTIONS PER NO. 8142T64, MCMASTER-CARR CATALOG 116 (OR APPROVED
EQUAL).
2. LADDER SECTIONS MOUNTING ADAPTER: SHALL BE 5 EACH, SHOP FABRICATED FROM 316 STAINLESS STEEL, MATCHING CONFIGURATION OF NO. 8073T5, MCMASTER-CARR CATALOG 116 (OR APPROVED EQUAL).
3. LADDER SAFETY CLIMBING SYSTEM: SHALL BE A RIGID RAIL, 40 FEET LONG, INCLUDING
MOUNTING BRACKETS AND HARDWARE, SAFETY SLEEVE WITH CARABINER, ALL MATERIAL TYPE 316 STAINLESS
STEEL, PER 'RAILOK SYSTEM' BY DBI/SALA LADDER SYSTEMS (OR APPROVED EQUAL).
4. THE LADDER MOUNTING ADAPTERS SHALL BE ATTACHED TO THE PRESTRESSED CONCRETE POLES USING 1/2" X 3"
HCA "HILTI COIL ANCHORS", OR APPROVED EQUAL, INSTALLED ALL INSERTS SHALL BE STD. COARSE THREAD, 5/16"
DIA., UNLESS NOTED OTHERWISE. DEPTH = 1 1/2". ANCHORS INDICATED ON DETAIL "A" THIS DRAWING.
GENERAL NOTES:
SCALE:
MOUNTING ADAPTER DETAIL
NONE
A
SCALE:
LADDER DETAIL
NONE
SCALE:
TOWER KEY PLAN
NONE
E-100
R
J W
T O
W E
R
A
N
A
O
T O
S
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
N.T.S.
TOWER 506 PLAN
N
EXISTING
CONCRETE
FOUNDATION
TO REMAIN
FLAG NOTES:
ALL GUY WIRES WILL BE REPLACED.
BOND NEW GUY WIRES TO EXISTING TOWER STRUCTURE (TYP.)
BOND NEW GUY WIRES TO EXISTING COUNTERPOISE AND GROUND RODS
(TYP.). REMOVE EXISTING BONDING CONDUCTOR ALL THE WAY DOWN TO
THE GROUND ROD OR COUNTERPOISE AND REPLACE WITH NEW.
(TYP.)
(TYP.)
3 3
N.T.S.
PHOTO
N.T.S.
PHOTO
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
E-101
R
J W
T O
W E
R
A
N
A
O
T O
S
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
N.T.S.
TOWER 415 PLAN
N
FLAG NOTES:
EXISTING AIR TERMINAL TO REMAIN.
REMOVE EXISTING DOWN CONDUCTOR COMPLETE. PROVIDE NEW DOWN
CONDUCTOR AND STRAP TO STRUCTURE EVERY 24" INCHES. PROVIDE
HEAVY DUTY SOLID COPPER CLIP.
BOND NEW DOWN CONDUCTOR TO EXISTING COUNTERPOISE. REMOVE
EXISTING BONDING CONDUCTOR ALL THE WAY DOWN TO THE GROUND
ROD OR COUNTERPOISE AND REPLACE WITH NEW. NEW BONDING
CONDUCTOR SHALL BE INSTALLED IN CONDUIT UP TO 72" UP THE
STRUCTURE.
1 2
N.T.S.
PHOTO
N.T.S.
PHOTO
3'-0"
M I N
M I N
FACE 4
FACE 1
FACE 2
FACE 3
M I N
M I N
M I N
MIN
M I N
5'-0" DIA FDN
5'-0" DIA FDN
M
A X
3'-0"
CONCRETE
FOUNDATION
GRADE
CONCRETE
FOUNDATION
GRADE
CONCRETE
FOUNDATION
FACE 1
FACE 3
E-102
P R
J W
P O
P
L A
N
A
O
T O
S
L M
K S
F
L
M
I Z
E D
K S
R E
P A
A
T H
W
E R
S
A
T
K
E N
N E
D Y
S P
A C
E
C
E N
T E
R
F
C C
A F
S
F
L U
S A
F
T
H
C
I V
I L
E
N G
I N
E E
R
S
Q U
A D
R O
N
I
T
E
D E
L I V
E R
Y
N
O
D R
A W
N
B
Y
D E
S I G
N E
D
B
Y
S U
B M
I T
T E
D
B
Y
R E
V I E
W E
D
B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
F
A D
T R
A C
E S
T E
C H
N I C
A L
R
A N
C
H I T
E C
T
E
N G
I N
E E
R I
R
V I C
E S
F A
A
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D r h o d i t
A
5/8" X 10' COPPER AIR TERMINAL.
#2/0 BARE STRANDED COPPER CONDUCTOR.
GROUND ROD, 3/4" X 20' COPPER CLAD STEEL, SECTIONAL.
CONCRETE POLE.
GROUND ACCESS WELL, 24" (DEPTH) X 12" (SQUARE), MADE OF LIGHT WEIGHT POLYMER
CONCRETE. COVER SHALL ALSO BE LIGHT WEIGHT POLYMER CONCRETE, HARGER #GAW121224HD
OR EQUAL. LEAVE 6" OF GROUND ROD EXPOSED. LOCATE ACCESS WELL AWAY FROM ROAD, TO
AVOID VEHICULAR TRAFFIC.
#2/0 BARE STRANDED TINNED COPPER CONDUCTOR GROUND LOOP ENCIRCLING POLE
FOUNDATION. BURY 2'-6" BELOW GRADE AND NOT LESS THAN 3'-0", NOT MORE THAN 8'-0" FROM
FOUNDATION. FIELD ROUTE AROUND ANY OBSTRUCTIONS AS REQUIRED.
EXOTHERMIC WELD.
BRONZE AIR TERMINAL THROUGH-BOLT SUPPORT ATTACHMENT WITH STAINLESS STEEL NUTS AND
WASHERS (THOMPSON #657-5 OR EQUAL). INSTALL TWO NUTS ON BOTH SIDES OF POLE. PROVIDE
THREADED ROD LENGTH AS REQUIRED AND TRIM EXCESS AFTER INSTALLATION.
AIR TERMINAL TO CABLE ADAPTER (THOMPSON #690 OR EQUAL).
HEAVY DUTY SOLID COPPER CLIP. FASTEN WITH 1/4" X 1 3/4" "HILTI COIL ANCHOR" INSTALLED PER
MANUFACTURER'S INSTRUCTIONS (OR APPROVED EQUAL). SUPPORT CABLE ON POLE AND BASE
EVERY THREE FEET MAXIMUM.
HEAVY DUTY STRAIGHT SPLICER.
#2/0 BARE STRANDED TINNED COPPER CONDUCTOR UP TO SPLICER. THE CONDUCTOR SHALL BE
INSTALLED IN CONDUIT UP TO 72" ABOVE GRADE.
APPROXIMATELY 10 FEET OF #2/0 BARE STRANDED TINNED COPPER CONDUCTOR FOR FUTURE
CONNECTION.
CONTRACTING OFFICER TO DISCONNECT ALL EXISTING WEATHER EQUIPMENT, SOLAR PANELS,
SUPPORT CROSSARMS/BRACKETS, CONDUIT AND WIRING. COORDINATE WITH CONTRACTING
OFFICER, 60 DAY LEAD TIME REQUIRED FOR THIS WORK.
CONTRACTOR TO REMOVE EXISTING WOOD POLE (INCLUDING POLE EMBEDMENT).
CONTRACTING OFFICER TO RE-CONNECT ALL EXISTING EQUIPMENT, SUPPORTS, CONDUIT AND
WIRING TO NEW CONCRETE POLE.
1. WORK TO THE TOWER SHALL BE COORDINATED WITH CONTRACTING OFFICER.
2. AIR TERMINAL AND DOWN CONDUCTOR SHALL BE CENTERED ON FACE OF POLE.
3. LIGHTNING PROTECTION SYSTEM DESIGN IS BASED ON MAXIMUM MOUNTING HEIGHT OF
PROTECTED EQUIPMENT LEVEL WITH POLE TOP, AND THREE FEET FROM POLE CENTER.
PROTECTED EQUIPMENT TO BE MOUNTED ON POLE BY OTHERS.
4. FIELD ROUTE GROUND CONDUCTOR AROUND ANY OBSTRUCTIONS AS REQUIRED.
5. TESTING: THE COMPLETE INSTALLATION SHALL HAVE A TOTAL RESISTANCE TO GROUND OF
NOT MORE THAN 25 OHMS. TEST NOT LESS THAN 24 HOURS AFTER RAINFALL. WHEN THE
RESISTANCE OF THE COMPLETE INSTALLATION EXCEEDS THE SPECIFIED VALUE PROVIDE ONE
ADDITIONAL 20' GROUND ROD AT LEAST 6' FROM THE FIRST ROD.
GENERAL NOTES:
FLAG NOTES:
(TYP.)
N.T.S.
PHOTO
N.T.S.
PHOTO
14 16
N.T.S.
PHOTO
14 16
14 16
14 16
N.T.S.
NEW POLE DETAILS
AutoCAD SHX Text C
| Sheets and Views |
| G-100 COVER SHEET AND INDEX |
| S-001 STRUCTURAL ABBREVIATIONS, LEGEND AND NOTES |
| S-100 TOWER 506 |
| S-101 TOWER 506 PHOTOS AND NOTES |
| S-102 GUY WIRE DETAIL FOR TOWER 506 |
| S-200 TOWER 415 |
| S-201 TOWER 415 PHOTOS AND NOTES |
| S-300 PLAYALINDA WEATHER POLE 0015 |
| S-301 PLAYALINDA WEATHER POLE 0015 DETAILS AND NOTES |
| E-100 TOWER 506 PLAN AND PHOTOS |
| E-101 TOWER 415 PLAN AND PHOTOS |
| E-102 POLE 0015 PLAN AND PHOTOS |
File details come from the government source that posted it. Updated .