PWS JTC SCAT_Tank_6K_Service Maintenance.pdf
PDF 176 KB Posted
- Solicitation number
- ASG-JOCS1119
About this file
This is a Performance Work Statement (PWS) for the initial restoration, testing, and continuous sustainment of 6,000-gallon Self-Contained Aboveground Tank (SCAT) systems at the Joint Training Center (JTC) in Jordan.
The contracting activity is the 1st Theater Sustainment Command (1st TSC) / JTF FLE for the 306th CSC. The contract is a Firm-Fixed-Price (FFP) non-personal services contract with a base period of 12 months from Notice to Proceed (NTP), followed by four optional 12-month renewal periods exercisable at the Government's sole discretion. The primary work location is the Fuel Point at JTC, Jordan, with additional support potentially required at the CRSP Yard, Jordan. The Contractor must furnish all labor, supervision, tools, test equipment, consumable parts, and transportation, while the Government furnishes the existing SCAT tanks, Retail Dispensing Skids (RDS), generators, fuel for testing, and site access. Key deliverables include an Initial Condition and Restoration Report within 5 business days of Task 1 completion, monthly maintenance reports within 5 business days of each visit, immediate verbal notification with written confirmation within 24 hours for any Non-Mission Capable (NMC) or safety/environmental incidents, and out-of-scope repair quotes within 5 business days of evaluation.
Task 1 requires initial restoration and functional testing within 30 calendar days of NTP, returning all systems to Fully Mission Capable (FMC) status per OEM manuals and the MSCAT Installation, Operation, and Maintenance Manual (IOM WM059). Task 2 specifies scheduled preventive maintenance on a monthly, quarterly, and annual basis, including visual inspections, component checks, filter replacements, battery replacements, paint condition assessment, and generator servicing. Task 3 mandates contingency mobilization of replacement Retail Dispensing Skids and generator sets from the Contractor's dedicated spares container within 48 hours of notification of major component failure. Performance standards require 100% on-time completion of initial restoration, 95% on-time completion of monthly preventive maintenance visits, 100% completion of quarterly and annual maintenance events, 100% compliance with contingency mobilization, and 95% on-time submission of reports. Out-of-scope repairs—including damage from vehicle impact, fuel contamination, misuse, major component failures, and structural damage—require Government authorization through written modification by the Contracting Officer and are priced separately via firm-fixed-price quotes. The Contractor must comply with all JTC and ASG-J security and force protection requirements, obtain base access credentials, comply with applicable U.S. and host-nation safety and environmental regulations, and may utilize local subcontractors provided personnel are trained and the Contractor retains full responsibility for performance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI_JTC_6K_SCAT_Tank_Sustainment_Sources_Sought Notice.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PERFORMANCE WORK STATEMENT
JTC SCAT Tank 6K Service Maintenance – Joint Training Center, Jordan
| Page 1 of 5 | USARCENT / 1st TSC
PERFORMANCE WORK STATEMENT (PWS)
Non-Personal Services Initial Restoration, Testing, and Continuous Sustainment of ASG-J Owned 6K SCAT Tanks
Joint Training Center (JTC), Jordan Requiring Activity: 1st Theater Sustainment Command (1st TSC) / JTF FLE for 306th CSC
1.0 GENERAL INFORMATION
1.1 Scope of Work
The Contractor shall provide all personnel, equipment, tools, materials, supervision, and other items and services necessary to perform initial restoration, functional testing, and continuous preventive maintenance and sustainment of the Area Support Group – Jordan (ASG-J) owned 6,000-gallon Self-Contained Aboveground Tank (SCAT) systems located at the fuel point, Joint Training Center (JTC), Jordan. This is a non-personal services contract. The Contractor shall perform to the standards in this PWS.
1.2 Background
The 6K SCAT tanks provide critical MOGAS and DF2 fuel storage and dispensing capability supporting persistent operations throughout the JTC area of responsibility. Current demand has increased (TF Castle +450 gal/week; Space Brigade requesting +800 gal/week beginning 05 October 2026). One Fully Mission Capable (FMC) SCAT tank is currently on-site with a service obligation expiring April 2027. Additional tanks previously under lease require restoration and sustainment to prevent degradation of fuel point operations and avoid significantly higher full-system replacement costs.
1.3 Period of Performance
Base Period: 12 months from Notice to Proceed (NTP).
Option Periods: Four (4) successive 12-month option periods may be exercised at the sole discretion of the Government.
1.4 Place of Performance
Primary Location: Fuel Point, Joint Training Center (JTC), Jordan.
Additional support may be required at the CRSP Yard, Jordan, for any SCAT assets staged or undergoing restoration.
1.5 Type of Contract
Firm-Fixed-Price (FFP) non-personal services contract.
2.0 DEFINITIONS AND ACRONYMS
ASG-J – Area Support Group – Jordan COR – Contracting Officer’s Representative DF2 – Diesel Fuel Grade 2 FMC / NMC – Fully Mission Capable / Non-Mission Capable JTC – Joint Training Center MOGAS – Motor Gasoline MSCAT / SCAT – Modular / Self-Contained Aboveground Tank NTP – Notice to Proceed OEM – Original Equipment Manufacturer PWS – Performance Work Statement RDS – Retail Dispensing Skid 1st TSC – 1st Theater Sustainment Command
| Page 2 of 5 | USARCENT / 1st TSC
3.0 GOVERNMENT-FURNISHED PROPERTY AND SERVICES
3.1 Government-Furnished Property (GFP)
The Government will furnish the existing ASG-J owned 6K SCAT tank(s), associated Retail Dispensing Skid(s) (RDS), and any Government-owned generators currently installed at the JTC fuel point. Serial numbers of all covered equipment shall be confirmed in writing prior to contract start.
3.2 Government-Furnished Services / Access
• Site access and escort coordination through the COR or designated site representative.
• Fuel product (MOGAS / DF2) for system testing, if required, will be Government-furnished.
• Workspace or laydown area for temporary storage of contingency equipment during mobilization, subject to availability and site security requirements.
4.0 CONTRACTOR-FURNISHED ITEMS AND SERVICES
The Contractor shall furnish all labor, supervision, tools, test equipment, consumable parts used during scheduled maintenance, transportation, and any other resources required to perform the services described herein, except for items identified as Government-furnished.
The Contractor shall maintain a dedicated spares container (held at the Contractor’s maintenance facility, not at the fuel site) that includes, at a minimum, a contingency Retail Dispensing Skid (RDS) and generator set ready for deployment within 48 hours of notification of a major component failure.
5.0 SPECIFIC TASKS AND PERFORMANCE REQUIREMENTS
5.1 Task 1 – Initial Restoration and Functional Testing
Within thirty (30) calendar days of NTP, the Contractor shall:
Conduct a joint inventory and condition assessment of all covered SCAT, RDS, and generator assets with the COR or designated Government representative.
Perform initial restoration services necessary to return any Non-Mission Capable (NMC) or degraded systems to Fully Mission Capable (FMC) status, or document in writing any conditions that require out-of-scope repair (see paragraph 5.5).
Conduct functional testing of all systems in accordance with OEM manuals and the MSCAT Installation, Operation, and Maintenance Manual (IOM WM059 or current equivalent).
Submit a written Initial Condition and Restoration Report to the COR within five (5) business days of completion of Task 1.
5.2 Task 2 – Scheduled Preventive Maintenance
The Contractor shall perform preventive maintenance in accordance with the following schedule and the OEM / MSCAT IOM requirements:
5.2.1 Monthly Maintenance
Visual inspection of SCAT, RDS, and generators for leaks, damage, and corrosion.
Inspect hoses, couplings, gaskets, nozzles, and safety breaks.
Test E-stops and tank high-level / bund alarms.
Check bund and interstitial space for water or fuel; remove water from the tank as required.
Check level gauge operation and earthing / bonding connections.
Review operator daily check logs and report discrepancies to the COR.
5.2.2 Quarterly Maintenance
Operate all ball valves; check stem seals and joints.
| Page 3 of 5 | USARCENT / 1st TSC
Check emergency vent (E-Vent) operation.
Grease door and hatch hinges.
Check RDS filter condition and flow rate; replace cartridges as needed.
Check RDS drive belt tension and condition.
Check bolt tightness on walkways and ladders.
5.2.3 Annual Maintenance
Replace RDS fuel filters.
Inspect dispenser display seals and cable glands.
Replace tank alarm batteries (or equivalent OEM-specified batteries).
Inspect paint condition, distortion, and corrosion on the SCAT and RDS; document findings.
Service generators in accordance with the OEM handbook.
5.3 Task 3 – Contingency Mobilization and Spares Support
Upon notification of a major component failure that renders a system NMC, the Contractor shall mobilize contingency equipment (RDS and/or generator set from the dedicated spares container) to the site within forty-eight (48) hours to restore temporary operational capability while the failed component is evaluated and repaired.
5.4 Task 4 – Reporting and Documentation
Monthly Maintenance Report: Submitted to the COR within five (5) business days after each monthly visit.
Report shall include work performed, parts consumed, discrepancies noted, and system status (FMC/NMC).
Quarterly and Annual reports shall be incorporated into the corresponding monthly report for that period.
Immediate notification to the COR (verbal followed by written confirmation within 24 hours) of any condition that renders a system NMC or that poses a safety or environmental hazard.
5.5 Out-of-Scope Repairs
Repairs beyond scheduled preventive maintenance are not included in the firm-fixed price. Examples include, but are not limited to:
Damage from vehicle impact or drive-aways with the nozzle still connected.
Fuel contamination.
Misuse or operation outside equipment manuals.
Major component failures (pumps, motors, meters).
Structural damage to tanks or skids.
Process for out-of-scope work:
1. Government notifies Contractor of the issue.
2. Contractor evaluates and provides a firm-fixed-price quote to the Contracting Officer / COR.
3. Work proceeds only upon written authorization / modification by the Contracting Officer.
Replacement of any spares or contingency equipment used during an authorized out-of-scope repair shall be included in that repair quote.
6.0 PERFORMANCE STANDARDS AND QUALITY ASSURANCE
6.1 Performance Standards
Performance Objective Performance Standard Acceptable Quality Level (AQL)
Initial Restoration & Testing (Task 1) Completed within 30 calendar days of NTP;
systems returned to FMC or deficiencies documented
100% on-time completion
Monthly Preventive Maintenance Performed in accordance with PWS §5.2.1 each calendar month
≥ 95% of scheduled visits completed on time
| Page 4 of 5 | USARCENT / 1st TSC
Quarterly / Annual Maintenance Performed in accordance with PWS §5.2.2 and §5.2.3
100% of scheduled events completed
Contingency Mobilization Contingency equipment on-site within 48 hours of notification
100% compliance
Reporting Quaterly reports submitted within 5 business days of visit; NMC notification within 24 hours
≥ 95% on-time submission
6.2 Quality Assurance Surveillance Plan (QASP)
The Government will use the performance standards above and random or scheduled inspections by the COR to evaluate Contractor performance. The COR will document results and provide feedback to the Contractor. Continued unsatisfactory performance may result in cure notices, show-cause notices, or termination for default in accordance with the terms of the contract.
7.0 DELIVERABLES
# Deliverable Frequency / Due Recipient 1 Initial Condition and Restoration Report Within 5 business days after Task
1 completion
COR
2 Quarterly Maintenance Report Within 5 business days after each monthly visit
COR
3 NMC / Safety / Environmental Notification Immediate (verbal) + written within 24 hours
COR
4 Out-of-Scope Repair Quote As required, within 5 business days of evaluation
Contracting Officer / COR
8.0 SPECIAL REQUIREMENTS
8.1 Security and Site Access
Contractor personnel shall comply with all installation access, force protection, and security requirements of JTC and ASG-J. The Contractor is responsible for obtaining necessary base access credentials. Local national personnel (if utilized) shall meet host-nation and U.S. force protection screening requirements.
8.2 Safety and Environmental Compliance
The Contractor shall comply with all applicable U.S. and host-nation safety, occupational health, and environmental regulations, including spill prevention and response. The Contractor shall immediately report any fuel spill or environmental incident to the COR and site environmental officer.
8.3 Key Personnel / Subcontracting
The Contractor may utilize local subcontractors for on-site execution provided personnel are trained on the specific equipment and the Contractor retains full responsibility for performance. Any proposed key personnel changes shall be submitted to the COR for concurrence prior to implementation.
8.4 Government Site Operator Responsibilities (for information) Daily operator checks, weekly generator run-ups, site housekeeping, spill kits, fire extinguishers, and prompt reporting of faults remain the responsibility of Government site personnel in accordance with equipment manuals. These responsibilities are listed for coordination purposes and are not part of the Contractor’s scope.
9.0 APPLICABLE DOCUMENTS
The following documents form a part of this PWS to the extent specified herein. In the event of conflict between this PWS and the referenced documents, this PWS shall take precedence.
• MSCAT Installation, Operation, and Maintenance Manual (IOM) WM059 (or current version)
• OEM equipment manuals for SCAT, RDS, and generators
• Applicable FAR / DFARS clauses incorporated in the contract
| Page 5 of 5 | USARCENT / 1st TSC
• Installation force protection and environmental directives (as provided by the COR)
10.0 POINTS OF CONTACT (Government)
Contracting Officer’s Representative (COR): TBD Contracting Office: Regional Contracting Center – Jordan (RCC-Jordan)
— END OF PERFORMANCE WORK STATEMENT —
This PWS is derived from USARCENT Letter of Justification (JTC SCAT TANK 6K Service Maintenance) and technical requirements consistent with industry standard MSCAT sustainment practices.
File details come from the government source that posted it. Updated .