ARL063203P-B25900 REPAIR SEWER LINE PLANS-FINAL.pdf
PDF 6 MB Posted
- Solicitation number
- PANMCC25P0000009647
About this file
These are detailed engineering plans for a sewer line repair project at White Sands Missile Range (WSMR) in New Mexico. The seven-sheet technical drawing set (Project Number B25900, ARL063203P) comprehensively documents the full scope of work, including exterior and interior sewer system demolition, site plan, septic system details, and construction specifications. The project involves completely replacing the existing sanitary sewer system for Building 25900, including interior and exterior drainage piping, plumbing fixtures, septic tank, and drain field.
The project is a HUBZone small business set-aside under NAICS code 237110, with an estimated procurement value between $250,000 and $500,000. The contract requires completing all work within 90 calendar days after the Notice to Proceed, located at White Sands Missile Range in Otero County, New Mexico. The technical drawings provide detailed specifications for sewer pipe trench sections, pavement patches, cleanout configurations, wire fence details, and septic system components, with a planned solicitation release date of approximately July 11, 2025, and a potential bid opening on August 11, 2025.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAIN POST
STALLION RANGE CENTER
SMR
HELSTF
17 9
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
PROJECT LOCATION
MAP
SHEET INDEX
SHEET DESCRIPTION
GENERAL
01 COVER SHEET
02 GENERAL NOTES AND LEGEND
CIVIL
03 DEMOLITION PLAN
B25900 REPAIR SEWER LINE
WHITE SANDS MISSILE RANGE, N.M.
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
NO. DATE DESCRIPTION BY APPROVED
DRAWN BY DESIGNED BY
CHECKED BY
SUBMITTED
PROJECT MANAGER
RECOMMENDED
BRANCH CHIEF
CHIEF, ENGINEERING DIVISION
DATE SCALE
APPROVED DRAWING NUMBER PLATE
01 07SHEET OF
G1 01
REVISIONS
J.SILVA J.SILVA
XX
D.GARCIA
J.NUNEZ
R.LOPEZ
March 18, 2025 NTS
COVER SHEET
PROJECT LOCATION
ISSUED FOR
CONSTRUCTIO
N
04 SITE PLAN
05 INTERIOR SEWER FLOOR PLAN
AMRAD
B25900
VICINITY MAP
ARL063203P
B25900 REPAIR SEWER LINE
NIKE AVE (P RT 2)
JA
R
ILLA
M
O U
N
TA
IN
S
OROGRANDE R.C.
S RT 252
06 SEPTIC SYSTEM DETAILS
07 CONSTRUCTION DETAILS
UNDERGROUND ELECTRIC LINE
OVERHEAD ELECTRIC LINE
W WATER VALVE
SIGNAGE
SS SANITARY SEWER MANHOLE
CO
SS
SANITARY SEWER CLEANOUT
NATURAL GAS VALVE
ELECTRICAL POLE
ELECTRICAL ANCHOR/GUY WIRE
Legend Existing Features New Project Features
FH FIRE HYDRANT
G NATURAL GAS LINE
SANITARY SEWER LINE
STORM DRAIN LINE
ROADWAY EDGE OF ASPHALT
ROADWAY EDGE OF GRAVEL
EDGE OF BUILDING
EXISTING SPOT INDENTIFICATION
POTABLE WATER LINE
VENT THRU ROOF
NEW ASPHALT PAVING
NEW RIP RAP
NEW CONCRETE
VTR
FLOOR CLEANOUTFCO
WALL CLEANOUTWCO
DEMOLITION
EXTERIOR GROUND CLEANOUTGCO
Tue, 18-Mar-2025 - 10:27:am, Plotted by: 1453891964.CIV C:\Users\1453891964.civ\OneDrive - US Army\Documents\Projects\B25900 Repair Sewer Line\Plans\Drawings\02-GENERAL NOTES AND LEGEND.dwg
WHITE SANDS MISSILE RANGE, N.M.
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
NO. DATE DESCRIPTION BY APPROVED
DRAWN BY DESIGNED BY
CHECKED BY
SUBMITTED
PROJECT MANAGER
RECOMMENDED
BRANCH CHIEF
CHIEF, ENGINEERING DIVISION
DATE SCALE
APPROVED DRAWING NUMBER PLATE
02 07SHEET OF
G2 02
REVISIONS
B25900 REPAIR SEWER LINE
J. SILVA J. SILVA
XX
D. GARCIA
J. NUNEZ
R. LOPEZ
March 18, 2025 NTS
GENERAL NOTES AND LEGEND
GENERAL CONSTRUCTION NOTES CONTACT INFORMATION FOR:
XX
ISSUED FOR
CONSTRUCTIO
N
AutoCAD SHX Text
1. ALL CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH ALL CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT CONSTRUCTION PLANS, SPECIFICATIONS AND THE LATEST EDITION OF THE NEW MEXICO STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION AS PREPARED BY THE NEW MEXICO CHAPTER, AMERICAN PUBLIC WORKS ASSOCIATION , IN THAT ORDER OF PRECEDENCE AT THE TIME OF CONSTRUCTION BID. 2. THE CONTRACTOR SHALL ASSUME THE SOLE AND COMPLETE THE CONTRACTOR SHALL ASSUME THE SOLE AND COMPLETE RESPONSIBILITY FOR THE JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THE PROJECT, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY, THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. 3. CONTRACTOR SHALL RESTRICT ALL ACTIVITIES TO THE AREA OF CONTRACTOR SHALL RESTRICT ALL ACTIVITIES TO THE AREA OF CONSTRUCTION. ANY DAMAGE TO AREAS OUTSIDE OF THE AREA OF CONSTRUCTION SHALL BE REPAIRED OR REPLACED TO ORIGINAL CONDITION OR BETTER AT NO ADDITIONAL COST . 4. LOCATIONS OF EXISTING UTILITIES ARE APPROXIMATE ONLY. LOCATIONS OF EXISTING UTILITIES ARE APPROXIMATE ONLY. PRIOR TO CONSTRUCTION, EXISTING UTILITY LOCATIONS SHALL BE FIELD VERIFIED BY THE CONTRACTOR. ANY DAMAGE TO EXISTING UTILITIES DURING CONSTRUCTION IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE REPAIRED AT NO ADDITIONAL COST. 5. THE CONTRACTOR MUST SUBMIT A CABLE LOCATE REQUEST TO THE CONTRACTOR MUST SUBMIT A CABLE LOCATE REQUEST TO WSTC RO-IM TO IDENTIFY ANY COMMUNICATION CABLES WITHIN THE CONSTRUCTION AREA. SUBMITTAL OF REQUEST MUST BE COORDINATED AT (575) 678-3901. 6. ANY DEVIATION OF THE INFORMATION PROVIDED HEREIN AND THE ANY DEVIATION OF THE INFORMATION PROVIDED HEREIN AND THE CONDITIONS EXISTING IN THE FIELD AT THE TIME OF CONSTRUCTION SHOULD BE REPORTED TO THE ENGINEER AS SOON AS POSSIBLE. 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING CONSTRUCTION SIGNS, BARRICADES, ETC. UNTIL COMPLETION OF CONTRACT AND SHALL HAVE PERSONNEL AVAILABLE AT ALL TIMES UNTIL THE PROJECT IS COMPLETE TO REPAIR OR REPLACE SIGNS, BARRICADES, ETC. 8. THE CONTRACTOR SHALL ONLY UTILIZE THE DESIGNATED THE CONTRACTOR SHALL ONLY UTILIZE THE DESIGNATED STAGING AREA FOR STORAGE OF ALL EQUIPMENT AND MATERIALS. WSMR ASSUMES NO RESPONSIBILITY OR LIABILITY FOR CONTRACTOR'S EQUIPMENT AND MATERIAL IN THE STAGING AREA. 9. WORK ON THE PROJECT SHALL BE DONE IN ACCORDANCE WITH WORK ON THE PROJECT SHALL BE DONE IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL ORDINANCES, RULES, AND REGULATIONS CONCERNING CONSTRUCTION SAFETY, HEALTH, AND ENVIRONMENTAL PROTECTION. 10. DISPOSAL OF ALL REMOVAL ITEMS SHALL BE DONE BY THE DISPOSAL OF ALL REMOVAL ITEMS SHALL BE DONE BY THE CONTRACTOR IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS AND ORDINANCES. DISPOSAL ITEMS SHALL BE DISPOSED OF OFF SITE AT A PERMITTED SOLID WASTE FACILITY AND IN ACCORDANCE WITH THE PROJECT STATEMENT OF WORK SECTION 2.6.3. 11. PERSONNEL SHOULD BE AWARE OF SNAKES, AND VARIOUS PERSONNEL SHOULD BE AWARE OF SNAKES, AND VARIOUS OTHER SPECIES OF WILDLIFE IN THE AREA THAT COULD CAUSE HARM IF ENCOUNTERED OR DISTURBED. REPORT ANY NUISANCE, INJURED, OR DEAD WILDLIFE DISCOVERED AT PROJECT SITE IMMEDIATELY. DO NOT HARASS, COLLECT, POSSESS, HARM, OR DESTROY WILDLIFE OR THEIR HABITAT. DO NOT PROVIDE WATER OR FEED WILDLIFE. DO NOT LEAVE UNEATEN FOOD AT BUILDINGS AND IN THE FIELD, TO PREVENT ATTRACTING WILDLIFE.CONTACT DPW ENVIRONMENTAL DIVISION - FOR ASSISTANCE WITH WILDLIFE AT (575) 678-2225. 12. MIGRATORY BIRD NESTING SEASON IS BETWEEN 1 MARCH MIGRATORY BIRD NESTING SEASON IS BETWEEN 1 MARCH THROUGH 31 AUGUST. ANY GROUND DISTURBANCE OR WORK THAT HAS THE POTENTIAL TO REMOVE AN ACTIVE NEST NEEDS TO BE SURVEYED. AREA WILL BE SURVEYED FOR NESTING MIGRATORY BIRDS BY PEOPLE WHO HAVE BEEN DETERMINED TO BE QUALIFIED BY PW ENVIRONMENTAL WITHIN 24 HOURS PRIOR TO START OF WORK. FOR ANY ACTIVE NEST FOUND WITH EGGS OR NESTLINGS, THE AREA OF THE NEST WILL BE AVOIDED BY WORKERS UNTIL IAW PW ENVIRONMENTAL GIVES INSTRUCTIONS. 13. IF CULTURAL ARTIFACTS OR HUMAN REMAINS ARE DISCOVERED IF CULTURAL ARTIFACTS OR HUMAN REMAINS ARE DISCOVERED ON OR BELOW THE SOIL SURFACE, STOP ALL ACTIVITIES AND CONTACT PWE AT 575-678-2225 IMMEDIATELY TO PROVIDE INFORMATION ON LOCATION. IF HUMAN REMAINS ARE DISCOVERED, ALL WORK SHALL STOP AND SHALL RESUME THIRTY (30) DAYS AFTER CONFIRMATION THAT PROPER NOTIFICATIONS HAVE BEEN MADE BY PW ENVIRONMENTAL. 14. ACCESS TO THE BUILDING OR NEIGHBORING BUILDINGS AND ACCESS TO THE BUILDING OR NEIGHBORING BUILDINGS AND PARKING LOTS SHALL BE KEPT OPEN AT ALL TIMES. ANY ACCESS CLOSURE MUST BE SCHEDULED AT LEAST 1 WEEK IN ADVANCE AND APPROVED BY THE COR. 15. EXISTING SITE FEATURES WHICH ARE DAMAGED OR DISPLACED EXISTING SITE FEATURES WHICH ARE DAMAGED OR DISPLACED BY THE CONTRACTOR SHALL BE REMOVED AND REPLACED BY THE CONTRACTOR AT THE CONTRACTOR'S OWN EXPENSE. THE WORK SHALL BE APPROVED BY THE COR PRIOR TO CONSTRUCTION OF THE REPAIRS. REPAIRS MUST BE ACCEPTED BY THE COR PRIOR TO FINAL PAYMENT. 16. CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE WITH THE CONTRACTOR IS RESPONSIBLE FOR COMPLIANCE WITH THE APPLICABLE ORDINANCES AND REGULATIONS FOR DUST CONTROL DURING ALL ACTIVITIES ASSOCIATED WITH THIS CONSTRUCTION. THE COST FOR REQUIRED CONSTRUCTION DUST CONTROL MEASURES SHALL BE INCIDENTAL TO THE PROJECT. 17. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO KEEP IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO KEEP THE JOB SITE FREE FROM TRASH ON A DAILY BASIS, AND ALL MATERIALS WILL BE NEATLY ORGANIZED. TRASH AND/OR NON-USED MATERIALS SHALL NOT BE BURIED ON SITE. 18. CONTRACTOR SHALL PARK EQUIPMENT AND VEHICLES SO AS CONTRACTOR SHALL PARK EQUIPMENT AND VEHICLES SO AS NOT TO INTERFERE WITH NORMAL ACTIVITIES OF BUILDING OCCUPANTS ON SITE. 19. MAINTENANCE OF RECORD DRAWINGS: THE CONTRACTOR SHALL MAINTENANCE OF RECORD DRAWINGS: THE CONTRACTOR SHALL MAINTAIN AN UP-TO-DATE SET OF RECORD DRAWINGS FOR THE PROJECT. THESE PLANS SHALL BE UPDATED CONTINUOUSLY AND SHALL BE SUBJECT TO REVIEW BY THE COR FOR COMPLETENESS. CONTRACTOR SHALL SUBMIT ACCURATE, DETAILED AND COMPLETE "AS-BUILT" RECORD DRAWINGS OF THE FINAL CONSTRUCTION TO WSMR UPON COMPLETION OF THE WORK. RECORD DRAWINGS SHALL INCLUDE EXISTING SITE FEATURES NOT IDENTIFIED IN THE ORIGINAL DRAWINGS IF ENCOUNTERED. 20. WATER FOR CONSTRUCTION IS AVAILABLE FROM WSMR AT WATER FOR CONSTRUCTION IS AVAILABLE FROM WSMR AT DESIGNATED FILLING STATIONS AS WELL AS FIRE HYDRANTS DEPENDING ON PROXIMITY TO THE PROJECT SITE. WHEN CONNECTING TO A HYDRANT THE CONTRACTOR MUST INSTALL A BACK FLOW PREVENTION DEVICE THAT IS APPROVED BY THE WSMR WATER PLANT MANAGER. THE CONTRACTOR SHALL PROVIDE THE BACKFLOW PREVENTOR AND NECESSARY PIPING TO GET WATER FROM A CONNECTION. THE COST OF THE BACKFLOW PREVENTOR, CONNECTIONS, AND PIPING TO MAKE THE CONNECTION SHALL BE INCIDENTAL TO THE PROJECT. 21. ALL EXISTING GROUNDCOVER UNLESS CALLED OUT OTHERWISE ON ALL EXISTING GROUNDCOVER UNLESS CALLED OUT OTHERWISE ON PLANS SHALL BE RETURNED TO THE SURFACING AND GRADE EXISTING PRIOR TO CONSTRUCTION. 22. EXISTING SEWER LINE LOCATIONS ARE APPROXIMATE AND SHALL EXISTING SEWER LINE LOCATIONS ARE APPROXIMATE AND SHALL BE FIELD LOCATED PRIOR CONSTRUCTION. 23. CONTRACTOR SHALL MAINTAIN EXISTING WATER, GAS, ELECTRIC, CONTRACTOR SHALL MAINTAIN EXISTING WATER, GAS, ELECTRIC, AND COMMUNICATION LINES DURING CONSTRUCTION. REMOVE AND REPLACE ANY DAMAGED PORTIONS. COST TO BE INCIDENTAL TO SEWER LINE CONSTRUCTION. 24. WASTE AND VENT PIPING BELOW GRADE USE SOLID CORE WASTE AND VENT PIPING BELOW GRADE USE SOLID CORE SCHEDULE 40 PVC. ABOVE THE SLAB USE CAST IRON NO-HUB PIPE & OR SOLID CORE SCH 40 PVC PIPE AND FITTINGS. IF PERMITTED BY CODE. NO PVC PIPE SHOULD BE USED IF RETURN IS NOT DUCTED. 25. ALL PIPING IS TO BE HUNG AND ANCHORED BY APPROVED ALL PIPING IS TO BE HUNG AND ANCHORED BY APPROVED MEANS AND INTERVALS AS PER APPLICABLE CODES. 26. CONTRACTOR IS TO VERIFY THAT FALL OF THE SEWER LINE WILL CONTRACTOR IS TO VERIFY THAT FALL OF THE SEWER LINE WILL MEET INVERT AT POINT OF CONNECTION BEFORE INSTALLING PIPING. 27. ALL OPEN DRAINS (FLOOR DRAINS, TRENCH DRAINS, SHOWER ALL OPEN DRAINS (FLOOR DRAINS, TRENCH DRAINS, SHOWER DRAINS, FLOOR SINKS, ETC.) MUST HAVE A PRO SET TRAP GUARD. 28. THE CONTRACTOR IS RESPONSIBLE FOR THE TESTING OF THE THE CONTRACTOR IS RESPONSIBLE FOR THE TESTING OF THE SYSTEM PRIOR TO ACCEPTANCE BY THE COR. TESTING SHALL BE PERFORMED TO DEMONSTRATE THE FUNCTIONALITY OF THE SYSTEM. THE COST OF THE TESTING SHALL BE INCIDENTAL TO THE PROJECT.
AutoCAD SHX Text WSMR ENGINEERING SERVICES DIVISION PROJECT MANAGER: DAVID GARCIA 575.678.4672 575.678.4672 DESIGN ENGINEER: JULIAN SILVA 575.678.1261 575.678.1261
AutoCAD SHX Text
WSMR UTILITIES SECTION WATER PLANT MANAGER: 575.678.1917 575.678.1917
CO
SS
CO
SS
MAIN
ENTRANCE
CO
SS
CO
SS
12 4
WHITE SANDS MISSILE RANGE, N.M.
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
NO. DATE DESCRIPTION BY APPROVED
DRAWN BY DESIGNED BY
CHECKED BY
SUBMITTED
PROJECT MANAGER
RECOMMENDED
BRANCH CHIEF
CHIEF, ENGINEERING DIVISION
DATE SCALE
APPROVED DRAWING NUMBER PLATE
03 07SHEET OF
C1 03
REVISIONS
B25900 REPAIR SEWER LINE
J. SILVA J.SILVA
XX
D. GARICA
J. NUNEZ
R. LOPEZ
March 18, 2025 NTS
DEMOLITION PLAN
Thu, 10-Apr-2025 - 12:05:pm, Plotted by: 1453891964.CIV C:\Users\1453891964.civ\OneDrive - US Army\Documents\Projects\B25900 Repair Sewer Line\Plans\Drawings\03-DEMOLITION PLAN.dwg
10 5 0 10
1"=10'
01 EXTERIOR SEWER SYSTEM DEMOLITION PLAN
SCALE: 1" = 10'
EXISTING KEYNOTES
1. EXISTING CONCRETE HEADER CURB TO REMAIN AND
BE PROTECTED DURING CONSTRUCTION.
2. EXISTING BARBED WIRE FENCE TO REMAIN AND BE
PROTECTED DURING CONSTRUCTION.
3. EXISTING LEACHFIELD TO REMAIN AND BE
ABANDONED IN PLACE.
4. EXISTING SHOWER BASE AND WALL KIT TO REMAIN
AND BE PROTECTED DURING CONSTRUCTION.
DEMOLITION KEYNOTES
02 INTERIOR SEWER SYSTEM DEMOLITION PLAN
SCALE: 1" = 4'
1. EXISTING 6-INCH CAST IRON (C.I.) SEWER LINE TO BE REMOVED AND
DISPOSED.
2. EXISTING CONCRETE SEPTIC TANK TO REMOVED AND DISPOSED.
SEPTIC TANK TO REMAIN IN USE UNTIL NEW SEPTIC TANK IS IN
OPERATION.
3. EXISTING DISTRIBUTION BOX TO BE REMOVED AND DISPOSED.
4. EXISTING SEWER LINE TO BE CUT, CAPPED, AND ABANDONED IN
PLACE.
5. SAWCUT CLEAN, REMOVE AND DISPOSE OF EXISTING ASPHALT
PAVEMENT.
6. SAWCUT CLEAN EXISTING 4-INCH C.I. SEWER LINE TO PREPARE FOR
TIE IN.
7. REMOVE EXISTING SEWER PIPE LINE AND DISPOSE AT AN OFF-BASE
PERMITTED SOLID WASTE FACILITY.
8. SAWCUT CLEAN, REMOVE, AND DISPOSE OF EXISTING CONCRETE
SLAB TO INCLUDE REINFORCEMENT AND FLOORING. CERAMIC TILE
FLOORING SHALL BE REMOVED TO THE NEAREST GROUT LINE.
DISPOSE AT PERMITTED OFF-BASE SOLID WASTE FACILITY.
COORDINATE CONCRETE CUTTING WITH COR AND FACILITY
PERSONNEL TO MINIMIZE DISRUPTION TO NORMAL FACILITY
OPERATIONS.
9. EXISTING WALL MOUNTED SINK TO BE REMOVED AND DISPOSED.
10. EXISTING VANITY AND COUNTER MOUNTED SINK TO BE REMOVED
AND DISPOSED.
11. EXISTING WALL MOUNTED URINAL TO BE REMOVED AND DISPOSED.
12. EXISTING FLOOR MOUNTED TOILET TO BE REMOVED AND DISPOSED.
13. EXISTING FLOOR DRAIN TO BE REMOVED AND DISPOSED.
14. EXISTING WALL MOUNTED DRINKING WATER FOUNTAIN TO BE
REMOVED AND REPLACED.
15. EXISTING RESTROOM PARTITIONS AND DOORS TO BE REMOVED,
STORED, AND REPLACED AS NECESSARY FOR CONSTRUCTION.
16. EXISTING CERAMIC TILED WALL TO BE REMOVED AND REPLACED AS
NECESSARY FOR CONSTRUCTION. REPLACED DRYWALL AND TILE TO
MATCH EXISTING AS SIMILARLY AS POSSIBLE.
17. EXISTING METAL GYM LOCKERS TO BE REMOVED, STORED,A ND
REPLACED AS NECESSARY FOR CONSTRUCTION.
EXISTING FLOORING LEGEND
VINYL FLOOR TILES
18-IN SQ. CERAMIC TILES
ISSUED FOR
CONSTRUCTIO
N
CO
CO
SS
CO
SS
CO
SS
4 5
6 6
7 6
10 10 10 10
' M
IN
70' MIN
WHITE SANDS MISSILE RANGE, N.M.
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
NO. DATE DESCRIPTION BY APPROVED
DRAWN BY DESIGNED BY
CHECKED BY
SUBMITTED
PROJECT MANAGER
RECOMMENDED
BRANCH CHIEF
CHIEF, ENGINEERING DIVISION
DATE SCALE
APPROVED DRAWING NUMBER PLATE
04 07SHEET OF
C2 04
REVISIONS
B25900 REPAIR SEWER LINE
J. SILVA J.SILVA
XX
D. GARCIA
J. NUNEZ
R. LOPEZ
March 7, 2025 NTS
SITE PLAN
Tue, 18-Mar-2025 - 11:08:am, Plotted by: 1453891964.CIV C:\Users\1453891964.civ\OneDrive - US Army\Documents\Projects\B25900 Repair Sewer Line\Plans\Drawings\04-SITE PLAN.dwg
10 5 0 10
1"=10'
CONSTRUCTION KEYNOTES
1. BEGIN SEWER PIPELINE REMOVAL AND REPLACEMENT.
TIE TO EXISTING C.I. SEWER LINE WITH 4-INCH STANDARD
NO HUB COUPLING. INSTALL NEW FLOOR CLEANOUT AT
CONNECTION POINT ON NEW PIPE.
2. ALL EXISTING SEWER PIPELINES WITHIN THE WOMENS
AND MENS RESTROOMS TO BE REMOVED, DISPOSED,
AND REPLACED WITH NEW SEWER PIPELINES PER THE
INTERNATIONAL PLUMBING CODE. SEE PLUMBING
MATERIAL SCHEDULE.
3. EXISTING 4-IN C.I. SEWER MAINLINE FROM MENS
RESTROOM TO THE NORTH FACE OF THE BUILDING TO BE
REMOVED, DISPOSED, AND REPLACED WITH NEW 4-IN
SEWER PIPELINE PER THE INTERNATIONAL PLUMBING
CODE. SEE PLUMBING MATERIAL SCHEDULE.
4. TIE TO EXISTING 6-IN C.I. SEWER LINE. INSTALL NEW
SINGLE GROUND CLEANOUT. INSTALL WITHIN 5-FT OF
BUILDING. SEE DETAIL 03 SHEET 07. PRIOR TO
CONSTRUCTION CONTRACTOR TO FIELD VERIFY EXISTING
SIZE, LOCATION, AND INVERT OF EXISTING SEWER LINE.
5. TIE TO NEW 4-IN SEWER LINE. INSTALL NEW DOUBLE
GROUND CLEANOUT AND 4-INX6-IN REDUCER. INSTALL
WITHIN 5-FT OF BUILDING. SEE DETAIL 04 SHEET 07.
6. INSTALL 6-IN SEWER LINE. PIPELINE SLOPE TO BE PER
APPLICABLE CODE.
7. INSTALL NEW SEPTIC TANK TO INCLUDE EXCAVATION,
BACKFILL, AND CONNECTIONS. SEE SHEET 06 FOR DETAIL.
8. INSTALL DRAINFIELD DISTRIBUTION BOX. SEE SHEET 06
FOR DETAIL.
9. INSTALL 4-IN SCH 40 PVC DRAINFIELD DISTRIBUTION
PIPING AND REQUIRED FITTINGS WITH SOLVENT WELDED
JOINTS.
10. INSTALL 36-IN HIGH CAPACITY LEACHFIELD CHAMBER. TO
INCLUDE EXCAVATION, BACKFILL, END CAPS, AND
INSPECTION VENT PORTS.
11. INSTALL 4-FT TALL 4-STRAND WIRE FENCE PER DETAIL 08
SHEET 07.
12. INSTALL ACCESS GATE PER DETAIL 09 SHEET 08.
01 SITE PLAN
SCALE: 1" = 8'
MINIMUM PIPE MATERIAL SCHEDULE
SERVICE TYPE
SANITARY WASTE & VENTING
LOCATION
BELOW GRADE 5' OUTSIDE BUILDING FOOTPRINT
MATERIAL REQUIRED*
CAST IRON W/ HUB AND SPIGOT OR
SCHEDULE 40 PVC W/ ELASTOMERIC JOINTS
BELOW GRADE WITHIN 5' OUTSIDE BUILDING FOOTPRINTCAST IRON W/ HUB AND SPIGOT OR
SCHEDULE 40 PVC W/ SOLVENT WELDED JOINTS
ABOVE GRADE WITHIN BUILDING CAST IRON W/ HUB AND SPIGOT OR
SCHEDULE 40 PVC W/ SOLVENT WELDED JOINTS
*NOTE: PVC INSTALLED BELOW GRADE SHALL BE IN STRICT ACCORDANCE TO ASTM STANDARD "D2321-89". ALL SCH40 PVC TO BE SOLID CORE SCH40 PVC.
NO FOAMCORE PVC WILL BE ALLOWED UNDERGROUND OR OVERHEAD.
1. CONTRACTOR SHALL PROVIDE TEMPORARY RESTROOM
FACILITIES DURING PERIODS OF RESTROOM OUTAGES
AS NECESSARY TO ACCOMMODATE FACILITY STAFF.
2. TEMPORARY RESTROOM FACILITIES MUST BE OF THE
MOBILE RESTROOM TRAILER TYPE. WITH A MINIMUM
TRAILER LENGTH OF 14 FEET.
3. CONTRACTOR SHALL PROVIDE A MINIMUM OF 1 MOBILE
RESTROOM TRAILER(S) THAT CONTAIN A MINIMUM OF 4
STALLS.
4. AMENITIES SHALL INCLUDE: HEAT & AC, RUNNING SINKS,
FLUSHING TOILETS, HOT WATER, INSIDE & OUTSIDE
LIGHTING, AND AN ON-BOARD WATER TANK.
5. MOBILE RESTROOM TRAILER SHALL BE CONFIGURED
WITH A MINIMUM OF TWO (2) MEN STATIONS AND TWO(2)
FEMALE STATIONS.
6. CONTRACTOR SHALL PROVIDE HAND SOAP, TOILET
PAPER, AND PAPER TOWELS FOR THE TEMPORARY
FACILITIES. CONTRACTOR IS RESPONSIBLE FOR
DELIVERY, SET-UP, AND REMOVAL OF THE FACILITY.
CONTRACTOR IS ALSO RESPONSIBLE FOR WASTE
REMOVAL AND GENERAL MAINTENANCE AND
CLEANLINESS OF THE TEMPORARY FACILITY.
TEMPORARY RESTROOM FACILITY NOTES
ISSUED FOR
FCO
FD
WC-1
WC-1
WC-1
L-1
L-1L-1SH-1
SH-1
DWF
WHU
WHITE SANDS MISSILE RANGE, N.M.
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
NO. DATE DESCRIPTION BY APPROVED
DRAWN BY DESIGNED BY
CHECKED BY
SUBMITTED
PROJECT MANAGER
RECOMMENDED
BRANCH CHIEF
CHIEF, ENGINEERING DIVISION
DATE SCALE
APPROVED DRAWING NUMBER PLATE
05 07SHEET OF
C3 05
REVISIONS
B25900 REPAIR SEWER LINE
J. SILVA J.SILVA
XX
D. GARCIA
J. NUNEZ
R. LOPEZ
March 18, 2025 NTS
INTERIOR SEWER FLOOR PLAN
Tue, 18-Mar-2025 - 11:19:am, Plotted by: 1453891964.CIV C:\Users\1453891964.civ\OneDrive - US Army\Documents\Projects\B25900 Repair Sewer Line\Plans\Drawings\05-INTERIOR SEWER FLOOR PLAN.dwg
CONSTRUCTION KEYNOTES
01 ENGLARGED SEWER FLOOR PLAN
SCALE: 1" = 4'
02 WASTE AND VENT ISOMETRIC
SCALE: NTS
1. BEGIN NEW SEWER PIPELINE INSTALLATION. TIE TO
EXISTING C.I. SEWER LINE WITH 4-INCH STANDARD NO
HUB COUPLING. INSTALL NEW FLOOR CLEANOUT AT
CONNECTION POINT ON NEW PIPE.
2. EXTEND NEW 4-IN SEWER LINE. SEE SITE PLAN FOR
CONTINUATION.
SH-1
SH-1
DWF
FD
L-1
L-1
L-1
L-2
WCO
WC-1
WC-1
WC-1
WCO
WCO
WCO
WCO
WCO
WCO WCO
WCO
WCO WHU
4"Ø SS
4"Ø SS
4"Ø SS
4"Ø SS
3"Ø SS
4"Ø SS
4"Ø SS
3"Ø SS
3"Ø SS
4"Ø SS
3"Ø SS
3"Ø SS
2"Ø SS
4"Ø SS
4"Ø SS 4"Ø SS
2"Ø V
2"Ø V
2"Ø V
2"Ø V
2"Ø V
2"Ø V
2"Ø V
4"Ø V
4" VTR
IN CLG SPACE
PLUMBING FIXTURE SCHEDULE
ID WASTE
SIZE
4"
VENT
SIZE
-DGCO
DESCRIPTION
4" -FCO
DOUBLE EXTERIOR GROUND CLEANOUT - CAST IRON BODY WITH ROUND ADJUSTABLE SCORIATED
SECURE CAST IRON TOP, GASKET SEAL CAST IRON PLUG WITH RECESSED SOCKET. INSTALL IN A MINIMUM OF 12"x12"x4" REINFORCED CONCRETE PAD WITH BEVELED EDGES.
MANUFACTURER* MODEL*
ZURN Z1400-HD
F LOOR CLEANOUT - CAST IRON BODY WITH SQUARE ADJUSTABLE SCORIATED NICKLE BRONZE TOP, GASKET SEAL BRASS THREADED PLUG WITH RECESSED SOCKET.
3" 2"FD
2" 1 12"L-1
ZURN Z1400-BP
FLOOR DRAIN - 6" ROUND ADJUSTABLE POLISHED NICKLE BRONZE STRAINER, CAST IRON BODY, SEDIMENT BUCKET, ADJUSTABLE FLASHING COLLAR AND 1/2" TRAP PRIMER ADAPTER. ZURN ZN-415B-Y-P-VP
COMMENTS
PROVIDE TRAP PRIMER ADAPTER FITTED WITH VANDAL
RESISTANT HARDWARE AND SURE SEAL TRAP GUARD MODEL SS3009V.
EXTERIOR GROUND CLEANOUT - CAST IRON BODY WITH ROUND ADJUSTABLE SCORIATED SECURE CAST IRON TOP, GASKET SEAL CAST IRON PLUG WITH RECESSED SOCKET. INSTALL IN A MINIMUM OF 12"x12"x4"
REINFORCED CONCRETE PAD WITH BEVELED EDGES.
ZURN Z1400-HD4" -GCO
3" 2"WC-1
- -WCO
ADA WALL MOUNTED LAVATORY - VITEROUS CHINA, NOMINAL 20"x18", BACK AND SIDE SPLASHES FOR CONCEALED ARM CARRIER, FAUCET HOLES 4" ON CENTERS, ADA COMPLIANT CENTER SET FAUCET, LESS ESCUTCHEON PLATE, LESS DRAIN, CAST BRASS CONSTRUCTION, DRAIN OUTLET WITH GRID STRAINER.
AMERICAN
STANDARD 0355.012
FAUCET - DELTA COMMERCIAL 2529LF-HDF. CARRIER - ZURN Z-1231,
OR EQUAL BY WADE OR JR SMITH. DRAIN - AMERICAN STANDARD
2411.015.
WATER CLOSET - ADA FLOOR MOUNTED PRESSURE ASSISTED WATER CLOSET. FLOOR MOUNTED, FLOOR OUTLET, 1.0 GALLONS PER FLUSH, WHITE VITEROUS CHINA, ENLONGATED BOWL, CHROME METAL FLUSH
HANDLE, EXTRA HEAVY DUTY OPEN FRONT WHITE SEAT.
KOHLER
COMPANY HIGHLINE K-3519 SEAT - AMERICAN STANDARD 5321.110.
WALL CLEANOUT - NO-HUB CAST IRON CLEANOUT TEE WITH ROUND STAINLESS STEEL COVER AND CENTER SCREW, GASKETED SEAL IRON THREADED PLUG WITH RECESSED SOCKET. ZURN Z1446-BP
*NOTE: MANUFACTURERS AND MODEL NUMBERS ARE SHOWN FOR BASE ITEM REFERENCE ONLY. PRODUCTS ARE NOT EXCLUSIVELY LIMITED TO THESE SPECIFIC MANUFACTURERS.
WHU WALL MOUNTED, VITREOUS CHINA, 0125 GPF, LOW FLOW FLUSH VALVE.2" 1 12"
DWF DRINKING WATER FOUNTAIN - BOTTLE FILLING STATION AND SINGLE ADA COOLER FILTERED AND
REFRIGERATED ELKAY LZS8WSLK1 12" 1 12"
ISSUED FOR
WHITE SANDS MISSILE RANGE, N.M.
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
NO. DATE DESCRIPTION BY APPROVED
DRAWN BY DESIGNED BY
CHECKED BY
SUBMITTED
PROJECT MANAGER
RECOMMENDED
BRANCH CHIEF
CHIEF, ENGINEERING DIVISION
DATE SCALE
APPROVED DRAWING NUMBER PLATE
06 07SHEET OF
C4 06
REVISIONS
B25900 REPAIR SEWER LINE
J. SILVA J.SILVA
XX
D. GARCIA
J. NUNEZ
R. LOPEZ
March 7, 2025 NTS
SEPTIC SYSTEM DETAILS
Tue, 18-Mar-2025 - 11:21:am, Plotted by: 1453891964.CIV C:\Users\1453891964.civ\OneDrive - US Army\Documents\Projects\B25900 Repair Sewer Line\Plans\Drawings\06-SEPTIC TANK DETAILS.dwg
01 FRP GRAVITY SEPTIC TANK
NTS
24" RIBBED PVC RISER
W/ FRP LID
8" SUBGRADE COMPACTED TO 95% ASTM-D 1557
24" FRP OPENING
30" FRP OPENING 24" FRP OPENING
24" RIBBED PVC RISER
W/ FRP LID
30" RIBBED PVC RISER
W/ FRP LID
FINISHED GRADE
6" SCH. 40 PVC SANITARY
DOUBLE TEE CROSSOVER 6" SCH. 40 PVC OUTLET
PIPING W/ SANITARY TEE
6" SCH. 40 PVC INLET
PIPING W/ SANITARY TEE
SINGLE WALL
FRP TANK
7/8 HIGH FRP BAFFLE WALL
NOTE: TANK MUST BE REGISTERED BY STATE OF NEW MEXICO AS AN APPROVED SEPTIC TANK.
NOTE: CUT HOLE STAMPED IN MIDDLE OF CHAMBER, INSERT RISER AND SILICON SEAL.
4"
1'- 3 1
/2"
6'-3"
3'-0"
4" SCREW CAP
12"X12"X4"
CONC. COLLAR
(4) - 3/4" DIA. HOLES
DRILLED ON CENTER ALL
AROUND
RISER PIPE PLAN VIEW
4" COUPLING
4" SCREW CAP
12"X12"X4"
CONC. COLLAR
6" NIPPLE
(4) - 3/4" DIA. HOLES
DRILLED @ 1/4 POINTS
ALL AROUND
NATIVE COMPACTED FILL
4" SDR-35 PIPE
(HEIGHT VARIES)
SILICON SEAL
INFILTRATOR
UNDISTURBED
NATURAL
GROUND
INSPECTION RISER DETAIL
1'- 4"
HIGH CAPACITY
INFILTRATION GALLERY
UNDISTURBED
NATURAL GROUND
NATIVE COMPACTED FILL
RESTORE FINISHED GRADE TO MATCH
GRADE BEFORE CONSTRUCTION. ENSURE
GRADE SLOPES AWAY FROM INFILTRATORS
VA
RI
ES
1'- 4"
1'- 8"
M
IN
02 INFILTRATOR CHAMBER DETAIL
NTS
SEPTIC TANK SIZING CALCULATION
(SIZED PER IPC 802.7.2)
LEACH FIELD SIZING CALCULATION
(SIZED PER IPC 604.1)
HIGH RATE INFILTRATOR CAPACITY2
MINIMUM LIQUID CAPACITY: 750 GAL
ADDITIONAL CAPACITY FOR OFFICES (T802.7.2) : 20 GAL / PERSON
NUMBER OF PERSONNEL: 25
TANK CAPACITY = 750 GAL + 20 (25) = 1250 GAL.
MINIMUM PIPE REQUIREMENTS:
PIPE MATERIAL SDR 35 OR BETTER
PIPE SLOPE FROM BUILDING TO SEPTIC TANK (%)2%
PIPE DIAMETER (IN) 6
MINIMUM TANK LIQUID CAPACITY 1250 GAL
AREA OF DISPOSAL FIELD:
NUMBER OF UNITS (U): 25
CONVERSION FACTOR (CF): 0.25
ABSORPTION AREA (AA): 1651
MINIMUM ABSORPTION AREA REQUIRED = U X CF X AA 1032 FT2
DISPOSAL FIELD:
NUMBER OF DRAIN FIELDS 1
NUMBER OF CHAMBER TRENCHES 4
LENGTH OF CHAMBER TRENCH (FT) 55
CAPACITY W (IN) L (IN) H (IN) ABSORPTION AREA FT2
110 GAL 34 75 16 33.6
NOTE:
1. SEPTIC TANK AND LEACHING CHAMBER DETAILS SHOWN ARE
FOR REPRESENTATIVE PURPOSES ONLY. CONTRACTOR IS TO
CONFIRM THAT ACTUAL COMPONENTS USED MEET MINIMUM
MATERIAL, CAPACITY, AND FLOW REQUIREMENTS AS
OUTLINED ON THIS SHEET. FINAL FLOW AND CAPACITY
DETERMINATION TO BE SUBMITTED FOR APPROVAL PRIOR TO
CONSTRUCTION.
2. SEPTIC TANK AND INFILTRATOR CHAMBER PRODUCTS TO BE
SELECTED FROM NMED APPROVED PRODUCTS LIST.
3. SEPTIC TANK DESIGN, PLACEMENT, AND INSTALLATION TO BE
IN ACCORDANCE WITH THE IPC SECTION 802.
4. LEACH FIELD SHALL BE CONSTRUCTED IN ACCORDANCE WITH
MANUFACTURES INSTALLATION INSTRUCTIONS.
5. DISTRIBUTION BOX SHALL BE CONSTRUCTED IN ACCORDANCE
WITH NMAC 20.7.3.501.
6. ALL CONNECTIONS TO DISTRIBUTION BOX SHALL BE
WATERTIGHT.
NOTE:
1. CONTRACTOR TO CONFIRM PERCOLATION CLASS BEFORE CONSTRUCTION IN
ACCORDANCE WITH TABLE 604.1(1) OF THE IPC SECTION 604.1.
2. INFILTRATOR SYSTEMS INC. HC CHAMBERS IS THE BASIS OF DESIGN.
CONTRACTOR TO CONFIRM CAPACITY OF THE FINAL SYSTEM INSTALLED TO
ENSURE THE SYSTEM MEETS THE RECOMMENDED REQUIREMENTS.
3. ABSORPTION AREA SHALL BE DETERMINED USING THE NMED DRAIN FIED
SIZING FACT SHEET.
6"6" 2'-4"
4'- 0"
6" 1'- 6"
1'- 6"
6"
5'-0"
B
A
DISTRIBUTION BOX
NTS
1'- 3"
6"
4'-0"
6"
A DISTRIBUTION BOX
NTS
1'- 3"
B
90°
03 DISTRIBUTION BOX PLAN
NTS
4" PVC TYP. OF 4
4" PVC INLET PIPE
FROM SEPTIC TANK
#4 BAR @ 8" O.C.E.W.
MANHOLE RING AND COVER
14" ALUM. WEIR PLATE
CONTINUOUS
8" SUBGRADE PREP
COMPACTED TO 95%
ASTM D-1557
MANHOLE RING AND COVER
14" ALUM. WEIR PLATE
MANHOLE RING AND COVERPRECAST CONCRETE
SPLITTER BOX
FROM SEPTIC TANK
6"
ISSUED FOR
WHITE SANDS MISSILE RANGE, N.M.
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION
NO. DATE DESCRIPTION BY APPROVED
DRAWN BY DESIGNED BY
CHECKED BY
SUBMITTED
PROJECT MANAGER
RECOMMENDED
BRANCH CHIEF
CHIEF, ENGINEERING DIVISION
DATE SCALE
APPROVED DRAWING NUMBER PLATE
07 07SHEET OF
C5 07
REVISIONS
B25900 REPAIR SEWER LINE
J. SILVA J.SILVA
XX
D. GARCIA
J. NUNEZ
R. LOPEZ
March 18, 2025 NTS
CONSTRUCTION DETAILS
Tue, 18-Mar-2025 - 11:23:am, Plotted by: 1453891964.CIV C:\Users\1453891964.civ\OneDrive - US Army\Documents\Projects\B25900 Repair Sewer Line\Plans\Drawings\07-CONSTRUCTION DETAILS.dwg
24" MIN.
8"
6" METALLIC TRACING TAPE
(GREEN-SEWER) ALL TRENCHES
FINAL BACKFILL ZONE
COMPACTED 95% ASTM D-1557
INITIAL BACKFILL ZONE
COMPACTED 95% ASTM D-1557
BEDDING ZONE
COMPACTED SUBGRADE
90% ASTM D-1557
BACKSLOPE OR TRENCHBOX
AS PER OSHA 29CFR1926.652
NOTE: EXISTING GRADE FOR TOP OF TRENCH IS GROUNDLINE AT TRENCH
OR THE ADJACENT ROADWAY WHICH EVER IS LOWER.
01 SEWER PIPE TRENCH SECTION
NTS
PIPE OD+1" MIN
6"
6"
2-0" SQ. 3000 PSI
CONCRETE COLLAR
FINISH GRADE
COMPACTED FILL
IMPORTED PIPE BASE
MATERIAL AS
REQUIRED CONCRETE
BLOCKING
BRASS SST.
STOP PLUG
WATERTIGHT
PIPE PLUG
6" PVC PIPE
45° BEND
6" PVC
PIPE OD+1" MIN
6"
6"
2-0" SQ. 3000 PSI
CONCRETE COLLAR
FINISH GRADE
BRASS SST.
STOP PLUG
WATERTIGHT
PIPE PLUG
COMPACTED FILL
IMPORTED PIPE BASE
MATERIAL AS REQUIRED
CONCRETE
BLOCKING
6" PVC PIPE
45° BEND
6" PVC
04 CLEANOUT-DOUBLE
NTS
03 CLEANOUT-SINGLE
NTS
PIPE PLUG & GROUT
SEAL IF TERMINATION
SANITARY MAIN
COLLECTION PIPE
SANITARY MAIN
COLLECTION PIPE
02 PAVEMENT PATCH DETAIL
NTS
EXISTING ASPHALT
SURFACING
SAWCUT AND APPLY TACK
COAT AT SURFACING SEAM
PER NMDOT SPEC SECTION 407
6" AGGREGATE BASE
COURSE, NMDOT TYPE I OR
TYPE II COMPACTED TO 95%
OF ASTM-D 1557
8" SUBGRADE PREP
95% OF ASTM D-1557
PRIME COAT PER
NMDOT SPEC
SECTION 408
2" NMDOT SP-IV HOT MIX ASPHALT
PAVING (1-LIFT) PER NMDOT STD
SPEC SECTION 423
10' SQ. MIN.
CLEANOUT TEE W/
ACCESS COVER
CLEANOUT PIPE
VENT PIPE
ACCESS COVER
FINISHED WALL
05 WALL CLEANOUT DETAIL
NTS
8'-3" 8'-3"
16'-6" MAX.
4'- 2"
T-POST
STAY, 36" LONG12-1/2 GA. GALV. BARBED WIRE
OR BARBLESS CABLE. SEE
PLANS FOR TYPE.
08 TYPICAL WIRE FENCE DETAIL
NTS
BRASS PLUG CONCRETE SLAB
FINISHED FLOOR,
SEE SITE PLAN
FLOOR CLEANOUT
AND COVER PLATE
NO-HUB CLAMP
ANNACO HUSKY
OR EQUAL
06 FLOOR CLEANOUT
NTS
6'- 6"
M
IN
STUDDED TEE OR U POST TYP.
SEPTIC
DRAINFIELD
SEPTIC DRAINFIELD SIGN
9"
18"
SIGNAGE SEE DETAIL THIS
SHEET. TYP. EACH SIDE.
3'- 6"
1'-8"
0.1 8'
MI
N.
2'-0"
1'-8"
2'-0"
3'- 6"
3"3"
12' WIDE GATE
3'- 8"
4'- 0"
4'- 2"
3000 PSI CONCRETE
SCH. 40
NEW CHAIN AND LOCK TO BE
WELDED TO 6" POST. GALV.
PAINT WELD TO MATCH
1-1/4" DIA. SCH. 40
GATE POST
6.625" (18 LBS/FT)
12" Ø X 10"
GALV. BOLT
2" X 2" X 14" STRUCTURAL
STEEL ANGLE
END POST AND BRACE BOLTED
TOGETHER W/ 516" BOLT, LOCK
WASHER AND NUT
2 12" X 2 12" X 14" STRUCTURAL
STEEL ANGLE TYP.
09 TYPICAL WIRE FENCE GATE DETAIL
NTS
#3 X 8" LONG DOWEL
SPACED EVERY 12 IN.
4"
EXISTING
CONCRETE SLAB
VARIES
#3 @ 12" O.C.
NEW CONCRETE SLAB PATCH
COMPACT SUBGRADE TO A MINIMUM
OF 95% MAX DENSITY
NOTE: CONCRETE FOR ALL FOUNDATION SLAB PATCHES WILL HAVE
A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI IN 24 HOURS
07 CONCRETE SLAB PATCH DETAIL
NTS
ISSUED FOR
| 01 COVER SHEET |
| Sheets and Views |
| 01 COVER SHEET |
| 02 GENERAL NOTES AND LEGEND |
| Sheets and Views |
| GENERAL NOTES AND LEGEND |
| 03 DEMOLITION PLAN |
| Sheets and Views |
| DEMOLITION PLAN |
| 04 SITE PLAN |
| Sheets and Views |
| SITE PLAN |
| 05 INTERIOR SEWER FLOOR PLAN |
| Sheets and Views |
| INTERIOR SEWER FLOOR PLAN |
| 06 SEPTIC SYSTEM DETAILS |
| Sheets and Views |
| SEPTIC SYSTEM DETAILS |
| 07 CONSTRUCTION DETAILS |
| Sheets and Views |
| CONSTRUCTION DETAILS |
File details come from the government source that posted it. Updated .