Approved_BOLTHOLD.pdf

PDF 2 MB Posted

Attached to
Corpyard Phase II - Connex Structural Anchoring & Welding: (REBID)
Solicitation number
26-091-ITB
Issued by
Yolo County, California

About this file

This is a structural engineering calculations document prepared by PSE Consulting Engineers Inc. for the Container Anchorage project located at 4300 Capitol Avenue, West Sacramento, California 95691, associated with the City of West Sacramento's Corpyard Phase II - Connex Structural Anchoring & Welding rebid. The project involves the design and analysis of anchor bolt systems for container anchorage, with calculations completed on March 18, 2026, by engineer Nabil Taha, Ph.D., P.E. The document establishes design criteria based on the 2022 California Building Code and 2021 International Building Code, including seismic parameters for Response Category II with Seismic Design Category D, ultimate wind speeds of 93 mph, and soil bearing capacity of 1,500 psf. The approved calculations specify the use of eight SP58 Bolthold asphalt anchors (configured as two groups of four anchors each) with L-angle base plates measuring 6" x 6" x 3/8" by 16" long and a minimum embedment depth of 10 inches, along with supporting stiffener plates and 3/16" continuous fillet welds.

The structural analysis validates that the provided anchorage system safely accommodates the maximum uplift load of 5,459 pounds against an allowable capacity of 8,320 pounds and the maximum shear load of 4,856 pounds against a total shear capacity of 8,800 pounds. Additional anchor locations at container middle-side bottom rail positions require four SP58 Bolthold anchors with the same base plate specifications to resist maximum uplift of 2,816 pounds and maximum shear of 3,073 pounds. The moment capacity analysis confirms the L-angle base plate, fabricated from A36 grade steel with stiffener plates, provides an available moment capacity of 324.79 kip-inches, exceeding the actual moment demand of 16.377 kip-inches. The calculations were performed using RISA 3D Version 22.0 and Group Calculator software, with design based on allowable stress design methodology and a factor of safety of 2 for shear and uplift considerations.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PSE Consulting Engineers Inc.

STRUCTURAL

ENGINEERING

CALCULATIONS

PROJECT: Container Anchorage

PROJECT LOCATION: 4300 Capitol Avenue, West Sacramento, CA 95691.

PSE PROJECT NUMBER: Haynes Studio Arch

225-001

DATE: March 18, 2026.

BY: Nabil Taha, Ph.D., P.E.

250-A Main Street E-Mail: info@structure1.com ph. (541) 850-6300 Klamath Falls, OR. 97601 Web: www.structure1.com fax (541) 850-6233

Project #: Haynes Studio Arch_225-001_CA_Container Anchorage

Table of Contents:

Subject: Page: Page

1- References / Software: 10 – 99

2- Design Criteria: 100 – 199

3- Anchor Bolt Analysis & Design: 1,000 – 1,999 mailto:info@structure1.com

References:

1- Literature:

a. California Building Code 2022

2021 International Building Code (2021 IBC).

b. Steel Construction Manual, AISC 15th Edition., (AISC 360-16).

c. American Society of Civil Engineers (ASCE): Minimum

Design Loads for Buildings and Other Structures 7-16.

2- Software:

a. RISA 3D Version 22.0, RISA Technologies.

b. Group Calculator – Asphalt Anchors., Asphaltanchors.com.

https://asphaltanchors.com/pages/group-calculator

250-A Main Street E-Mail: info@structure1.com ph. (541) 850-6300

Design Criteria:

1- Location: 4300 Capitol Avenue, West Sacramento CA 95691.

2- Seismic: RC II

SDC D

Site Class Default Sms: 1.050 Sm1 0.670

SDS 0.700

SD1 0.450

IE 1.0

R 2.0

3- Wind: Ultimate wind speed: 93 mph

Exposure: C

IW 1.0

4- Snow Load: 6 psf. (Ground snow load)

5- Roof Live load: 12 to 20 psf. (For Containers by Others) 5 psf. (For canopies by Others)

6- Soil Bearing Capacity: 1500 psf (presumptive value from IBC)

7- Gravity Loads: Container(s): Self Weight DL Floor: 10 to 20 psf Additional DL Roof: 3 to 20 psf LL Floor: 312.5 psf (Refer DOTec Corp Calculation Package for Container for further information)

8- Deflection Criteria: Floor LL Deflection: L/480 Roof TL Deflection: L/180

**Other criteria assumed as stated in design calculations.

Pages 101 – 199 RESERVED FOR FUTURE USE

ANCHORBOLT ANALYSIS & DESIGN:

Pages 1,000 - 1,999

Project Number

Project Name AYPN Date

Subject NT Date

Node Label

Condition X [k] LC Y [k] LC Z [k] LC MX [k-ft] LC MY [k-ft] LC MZ [k-ft] LC

N2572 min -4.856 22 -5.459 20 -1.606 20 0 2 0 2 0 2

N2572 max 0.817 20 21.082 22 4.241 22 0 30 0 30 0 30

N2572 min -4.856 22 -5.459 20 -1.606 20 0 2 0 2 0 2

N2572 max 0.817 20 21.082 22 4.241 22 0 30 0 30 0 30

N3859 min -3.727 4 -5.264 12 -2.764 22 0 2 0 2 0 2

MAXIMUM UPLIFT = 5.459 kips = 5459 lbs (From RISA Reactions by Others)

(4) SP58 BOLTHOLD ANCHOR GROUP CAPACITY = 16640 lbs (From Group Calculator)

ALLOWABLE UPLIFT CAPACITY = 16640 / 2 = 8320 lbs > 5459 lbs

> (Actual Value)

MAXIMUM SHEAR = 4.856 kips = 4856 lbs (From RISA Reactions by Others)

ALLOWABLE SHEAR CAPACITY = 2200 / 2 = 1100 lbs (Consider Factor of Safety as 2)

NO. OF ANCHORS USED HERE = 8 Nos.

SO, TOTAL SHEAR CAPACITY = 8 * 1100 = 8800 lbs > 4856 lbs

> (Actual Value)

USE L-ANGLE AS BASE PLATE WITH SIZE 6" X 6" X 3/8" BY 16" LONG WITH

(8) NOS OF SP58 BOLTHOLD ASPHALT ANCHORS (4) IN AGROUP & ANOTHER (4) IN A GROUP WITH MIN. 10" EMBEDMENT DEPTH

(Available Capacity)

SAFE

(Available Capacity)

Please note that a total of eight (8) anchors shall be provided at Corners. Four (4) anchors shall be placed as a group along the longer side bottom rail, and the remaining four (4) anchors shall be placed as a group in the transverse direction at the rear bottom beam. Refer CAD Drawing for further Details.

NODE REACTIONS FOR ANCHOR BOLT Checked by Mar-17-2026

ANCHOR POINTS AT CONTAINER CORNER CASTING COLUMN LOCATIONS (AA-1)

THE TABLE BELOW SUMMARIZES THE GOVERNING (MAXIMUM) ASD NODE REACTIONS BENEATH THE CONTAINER. NON-GOVERNING NODES

ARE NOT SHOWN. REACTIONS FROM CONTAINER ENGINEERING BY OTHERS.

SAFE

PSE Consulting Engineers Inc.

Haynes Studio Arch_225-001

Container Anchorage Designed by Mar-17-2026

Subject NT Date

Node Label

Condition X [k] LC Y [k] LC Z [k] LC MX [k-ft] LC MY [k-ft] LC MZ [k-ft] LC

N3892 min -3.073 4 -2.6 20 -0.011 3 0 2 0 2 0 2

N2628 max 2.997 22 20.947 6 0.247 16 0 30 0 30 0 30

N2608 min -2.557 4 -2.816 20 -0.28 22 0 2 0 2 0 2

N2607 max 0.497 7 16.564 6 0.346 12 0 30 0 30 0 30

MAXIMUM UPLIFT = 2.816 kips = 2816 lbs (From RISA Reactions by Others)

(4) SP58 BOLTHOLD ANCHOR GROUP CAPACITY = 16640 lbs (From Group Calculator)

ALLOWABLE UPLIFT CAPACITY = 16640 / 2 = 8320 lbs > 2816 lbs

> (Actual Value)

MAXIMUM SHEAR = 3.073 kips = 3073 lbs (From RISA Reactions by Others)

ALLOWABLE SHEAR CAPACITY = 2200 / 2 = 1100 lbs (Consider Factor of Safety as 2)

NO. OF ANCHORS USED HERE = 4 Nos.

SO, TOTAL SHEAR CAPACITY = 4 * 1100 = 4400 lbs > 3073 lbs

> (Actual Value)

USE L-ANGLE AS BASE PLATE WITH SIZE 6" X 6" X 3/8" BY 16" LONG WITH

(4) NOS OF SP58 BOLTHOLD ASPHALT ANCHORS WITH MIN. 10" EMBEDMENT DEPTH

(Available Capacity)

SAFE

(Available Capacity)

**** Please note that a total of (4) anchors shall be provided as a group along the longer side bottom rail, Refer CAD Drawing for further Details.

NODE REACTIONS FOR ANCHOR BOLT Checked by Mar-17-2026

ANCHOR POINTS AT CONTAINER MIDDLE-SIDE BOTTOM RAIL LOCATIONS (AA-1)

THE TABLE BELOW SUMMARIZES THE GOVERNING (MAXIMUM) ASD NODE REACTIONS BENEATH THE CONTAINER. NON-GOVERNING NODES ARE

NOT SHOWN. REACTIONS FROM CONTAINER ENGINEERING BY OTHERS.

SAFE

PSE Consulting Engineers Inc.

Haynes Studio Arch_225-001

Container Anchorage Designed by Mar-17-2026

18" DEEP CEMENT TREATED EXISTING ASPHALT BY OTHERS AS PER SITE CONDITIONS.

HERE AS PER THE SOFTWARE LIMITATIONS, 10" DEEP ASPHALT THICKNESS WAS USED.

L-ANGLE (BASE WITH ANCHORS)

MOMENT CAPACITY CHECK &

ANALYSIS

Company : PSE Consulting Engineers, Inc.

Designer : AYPN Job Number: 224-002_AS#2

Mar 10, 2026

13:18 PM

Checked By:______

Section Properties: L-Angle without Stiffener

Section Information:

Material Type = Hot Rolled Steel

Shape Type = Single Angle

Number of Shapes = 1

Basic Properties:

Total Width = 6.000 in

Total Height = 6.000 in

Centroid, Xo = -1.000 in

Centroid, Yo = -1.000 in

Shear Center, Xs = -1.452 in

Shear Center, Ys = -1.452 in

X-Bar (Right) = 4.384 in

X-Bar (Left) = 1.616 in

Y-Bar (Top) = 4.384 in

Y-Bar (Bot) = 1.616 in

Leg Thick = 0.375 in

Equivalent Properties:

Area, Ax = 3.670 in^2

Inertia, Ixx = 13.000 in^4

Inertia, Iyy = 13.000 in^4

Inertia, Ixy = -7.796 in^4

Sx (Top) = 2.966 in^3

Sx (Bot) = 8.043 in^3

Sy (Left) = 8.043 in^3

Sy (Right) = 2.966 in^3 rx = 1.882 in ry = 1.882 in ro = 3.202 in

Plastic Zx = 5.260 in^3

Plastic Zy = 5.260 in^3

Torsional J = 0.129 in^4 rZ = 1.193 in

Section Diagram

D:\Projects - Ibu\Haynes Studio Architects\225-001 CA Container Anchorage\Dsgn Engineering\04 Anchor Bolt Reactions &... Page 1

Company : PSE Consulting Engineers, Inc.

Designer : AYPN Job Number: 224-002_AS#2

Mar 10, 2026

13:23 PM

Checked By:______

Section Properties: L-Angle with Stiffener Plate_Drawing1.dxf

Section Information:

Material Type = Hot Rolled Steel

Shape Type = Single Angle

Number of Shapes = 2

Basic Properties:

Total Width = 6.000 in

Total Height = 6.000 in

Centroid, Xo = 709.15 in

Centroid, Yo = 1426.81 in

Shear Center, Xs = -1.452 in

Shear Center, Ys = -1.452 in

X-Bar (Right) = 3.882 in

X-Bar (Left) = 2.118 in

Y-Bar (Top) = 3.882 in

Y-Bar (Bot) = 2.118 in

Leg Thick = 0.375 in

Equivalent Properties:

Area, Ax = 20.180 in^2

Inertia, Ixx = 44.471 in^4

Inertia, Iyy = 44.471 in^4

Inertia, Ixy = -21.815 in^4

Sx (Top) = 11.456 in^3

Sx (Bot) = 20.996 in^3

Sy (Left) = 20.996 in^3

Sy (Right) = 11.456 in^3 rx = 1.485 in ry = 1.485 in ro = 3.202 in

Plastic Zx = 24.873 in^3

Plastic Zy = 24.873 in^3

Torsional J = 26.362 in^4 rZ = 1.193 in

Section Diagram

D:\Projects - Ibu\Haynes Studio Architects\225-001 CA Container Anchorage\Dsgn Engineering\04 Anchor Bolt Reactions &... Page 1

Subject ISL Date

*** MAXIMUM TENSION FORCE = 5.459 kips

MOMENT DUE TO MAX. TENSION FORCE = FORCE X PERPENDICULAR DISTANCE

= 5.459 X 3"

MOMENT DUE TO MAX. TENSION FORCE (ACTUAL MOMENT) = 16.377 kip-in

*** PLASTIC SECTION MODULUS OF ANGLE WITH STIFFENER = 24.873 in˄3

PLASTIC SECTION MODULUS OF ANGLE WITHOUT STIFFENER = 5.26 in˄3

*** AVERAGE PLASTIC SECTION MODULUS = 15.07 in˄3

*** MOMENT CAPACITY OF ANGLE = Mn = fy * Z / Ω For A36 Grade, fy = 36 ksi, & Take Ω = 1.67

= 36 * 15.07 / 1.67

MOMENT CAPACITY OF ANGLE(AVAILABLE MOMENT CAPACITY) = 324.787 kip-in

16.377 kip-in < 324.79 kip-in

ACTUAL MOMENT < AVAILABLE MOMENT CAPACITY

PSE Consulting Engineers Inc.

Haynes Studio Arch_225-001

Container Anchorage Designed by Mar-17-2026

SO, THE PROVIDED L-ANGLE OF SIZE 6X6X3/8" THICK WITH (N) 3/8" STIFFENER PLATES A36 GRADE, WITH 3/16" CONTINUOUS

FILLET WELD ALONG ALL CONTACT EDGES IS ACCEPTABLE

Container Base Angle Moment Capcity Check Checked by Mar-17-2026

ANGLE MOMENT CAPCITY CHECK FOR THE MAXIMUM UPLIFT/TENSION LOAD

HENCE SAFE

Pages 1,010 – 1,999 RESERVED FOR FUTURE USE

File details come from the government source that posted it. Updated .