About this file

The document is a Material and Performance Specifications document for Grand Rapids Community College (GRCC), dated September 11, 2024, which provides detailed specifications for materials and products across multiple construction and renovation divisions. The document comprehensively lists preferred manufacturers, model numbers, and specific requirements for materials ranging from general requirements and wood products to electrical systems, HVAC equipment, plumbing fixtures, and exterior improvements. The specifications cover 32 divisions, providing explicit guidance on acceptable manufacturers, model numbers, and comments for each product category, which will be used to ensure consistency and quality in GRCC's construction and renovation projects.

The specifications demonstrate GRCC's detailed approach to procurement, with a strong emphasis on specific manufacturers and models across various product categories. Notable requirements include preferences for energy-efficient equipment, specific brands like Trane for HVAC systems, Sloan for plumbing fixtures, and Square D for electrical components. The document also includes specific technical requirements such as no grooved piping for domestic water, preferences for single-source products in certain categories, and detailed guidelines on everything from elevator components to irrigation systems. These specifications appear designed to standardize procurement, ensure quality, maintain consistency across campus facilities, and potentially streamline maintenance and replacement processes.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Grand Rapids Community College Material and Performance Specifications

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

1 Division 01 ‐ General Requirements Rebates GRCC participates in energy optimization programs provided through local utilities.

Equipment eligible for rebates include, but not limited to lighting, HVAC equipment, compressors, exit signs, occupancy sensors, transformers, commercial refrigeration equipment, vfd, pumps, & custom rebates. Contracting companies should ensure purchased equipment meets eligibility requirements based on yearly program standards. Catalogs outlining qualifications can be found at each utilities website.

Additional documentation may also be required including submittals, shop drawings, and detailed invoices.

2 Division 01 ‐ General Requirements Asbestos No asbestos, nor any asbestos containing product, will be purchased or installed on GRCC projects. No exceptions.

3 Division 01 ‐ General Requirements Plumbing All plumbing to be installed straight, level, and true.

4 Division 06 ‐ Wood & Plastics Wood Board Paneling Wood board paneling should be a wood veneer laminate, not a particle board composite.

5 Division 06 ‐ Wood & Plastics Plastic‐Laminate‐Faced Wood Paneling GRCC accepts only melamine. Applied laminated surfaces are not accepted.

6 Division 06 ‐ Wood & Plastics Casework Locks Timberline Casework locks shall be Timerline IC cabinet locks. GRCC lockshop shall determine numbering for the locks

7 Division 07 ‐ Thermal & Moisture Protection Bituminous Dampproofing GRCC prefers oil borne products and does not accept water based products without prior approval.

8 Division 07 ‐ Thermal & Moisture Protection Cementitious Dampproofing Lucas

9 Division 07 ‐ Thermal & Moisture Protection Sheet Dampproofing Lucas

10 Division 07 ‐ Thermal & Moisture Protection Roof Type Firestone & Carlisle White EPDM. Mechanical fasteners shall not be used on the top layer under the membrane. The top layer of insulation and membrane shall be fully adhered.

11 Division 07 ‐ Thermal & Moisture Protection Bituminous Sheet Waterproofing Lucas

12 Division 07 ‐ Thermal & Moisture Protection Acrylic Water Repellents Acrylic water repellents are only accepted by GRCC approval.

13 Division 07 ‐ Thermal & Moisture Protection Asphalt Shingles GAF w/30 year warranty

14 Division 07 ‐ Thermal & Moisture Protection Fiberglass‐Reinforced Asphalt Shingles GAF w/30 year warranty

15 Division 07 ‐ Thermal & Moisture Protection Roof Hatches Bilco Minimum opening to be 30”X54”

16 Division 07 ‐ Thermal & Moisture Protection Roof Ballast Pavers GRCC does not accept pavers

17 Division 07 ‐ Thermal & Moisture Protection Roof Decking Pavers GRCC does not accept pavers.

18 Division 07 ‐ Thermal & Moisture Protection Roof Flashing Counter flashing with reglet over termination bar is mandatory.

19 Division 07 ‐ Thermal & Moisture Protection Joint Protection GRCC does not accept LYMTAL products

20 Division 08 ‐ Doors & Windows Exterior Door Specialite or Cross + Insulated No knock down frames unless approved by GRCC

21 Division 08 ‐ Doors & Windows Refer to the GRCC Door Hardware Spec Guide

22 Division 08 ‐ Doors & Windows Locker Locks Keyless Company Keyless 360 Single use 2 stage combination lock with a key override. Digital/battery single use locks are not accepted.

23 Division 09 ‐ Finishes PVC‐Free Sheet Flooring GRCC will not accept PVC Free Sheet Flooring. Where applicable, concrete grinding should be considered

24 Division 09 ‐ Finishes Resilient Tile Flooring Luxury Vinyl Tile: SHAW, Home Legend, Karndean

25 Division 09 ‐ Finishes Tiling Foreign manufacturers of tile are not accepted. Only U.S standard units of measurement will be accepted.

26 Division 09 ‐ Finishes Plastic Tiling Plastic tiling is not accepted.

27 Division 09 ‐ Finishes Metal Tiling Metal tiling is not accepted.

September 11, 2024

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

September 11, 2024

28 Division 09 ‐ Finishes Acoustical Panel Ceilings U.S.G. U.S.G. 707 Glacier White U.S.G. 707 Glacier White with tegular/reveal edge (2’x2’ Only). No substitutions unless approved by GRCC.

29 Division 09 ‐ Finishes Barisol Stretched Ceilings Barisol stretched ceilings and products are not accepted.

30 Division 09 ‐ Finishes Curved Profile Ceiling Suspension Assemblies 200 series Chicago Metals. No naroline unless approved by GRCC

31 Division 09 ‐ Finishes Tile Carpeting Shaw

32 Division 09 ‐ Finishes Tile All tile must have uncoupling membrane or backer board

33 Division 09 ‐ Finishes Wallpapering Wallpapering is not accepted by GRCC

34 Division 09 ‐ Finishes Exterior Painting Primer: Rust inhibitive, oil base

35 Division 09 ‐ Finishes Exterior Painting ‐ Metals PPG PPG PITTHANE® ULTRA Gloss Urethane Enamel

36 Division 09 ‐ Finishes Exterior Painting ‐ Exterior Primer RepcoLite RepcoLite #65 Exterior Primer Oil based paint for exterior wood finishes

37 Division 09 ‐ Finishes Exterior Painting ‐ Exterior Acrylic Latex RepcoLite RepcoLite Endura Satin Sheen

38 Division 09 ‐ Finishes Interior Painting Benjamin Moore & Company, Repcolite, Sherwin Williams

Paint sheen shall be eggshell for walls.

39 Division 09 ‐ Finishes Gypsum Board Standard 5/8" gypsum board

40 Division 09 ‐ Finishes Plaster & Gypsum Board: High Impact 5/8" ToughRock® Fireguard X™ Abuse‐Resistant Gypsum Board (http://www.buildgp.com/toughrock‐abuse‐resistant‐gypsum‐board)

41 Division 09 ‐ Finishes Resilient Stair Treads and Risers Roppe Rubber tread raised circular vantage design with riser

42 Division 09 ‐ Finishes Resilient Stair Nosings Rubber tread raised circular vantage design with riser

43 Division 09 ‐ Finishes Vinyl Wall Base 1/8" minimum nominal thickness

44 Division 10 ‐ Specialties Markerboards VisComm VisComm products only

45 Division 10 ‐ Specialties Toilet Compartments Global Partitions, Accurate Partition Corp, Specialite HDPE material; floor mounted

46 Division 12 ‐ Furnishings Furniture Fabric Do not use Customers Only Material (COM) fabrics to upholster furnishings.

47 Division 12 ‐ Furnishings Roller Window Shades Draper Inc, Hunter Douglas Contract, MechoShade Systems Inc, Nyson Solar Control Inc; Hunter Douglas

48 Division 12 ‐ Furnishings Manufactured Wood‐Veneer‐Faced Casework Wood veneer & composite casework is not accepted. GRCC only accepts solid wood casework.

49 Division 12 ‐ Furnishings Manufactured Plastic‐Laminate‐Clad Casework No laminate casework unless approved by GRCC. Only factory applied laminates.

50 Division 12 ‐ Furnishings Plastic‐Laminate‐Clad Countertops No laminate counters unless approved by GRCC. Solid surface only. Minimum thickness:

¼”. No EOS solid surface or (preventive Biocidal Solid Surface Products)

51 Division 12 ‐ Furnishings Bicycle Racks CycleSafe, Landscape Forms, Forms & Surfaces Bike racks shall be U‐Shape only

52 Division 12 ‐ Furnishings Trash and Litter Receptacles Landscape Forms, Conceptual Site Furnishings Inc, Forms & Surfaces

53 Division 12 ‐ Furnishings Manufactured Planters Landscape Forms, Conceptual Site Furnishings Inc, Forms & Surfaces

54 Division 12 ‐ Furnishings Site Seating and Tables Landscape Forms, Conceptual Site Furnishings Inc, Forms & Surfaces

55 Division 12 ‐ Furnishings Site Seating Landscape Forms, Conceptual Site Furnishings Inc, Forms & Surfaces

56 Division 12 ‐ Furnishings Site Tables Landscape Forms, Conceptual Site Furnishings Inc, Forms & Surfaces

57 Division 12 ‐ Furnishings Seating Steelcase, Hon, Herman Miller, Haworth Local vendors are Custer Workplace Interiors, Kentwood Office Furniture, Interphase, & Maxmoda

58 Division 12 ‐ Furnishings Systems Furniture Steelcase, Hon, Herman Miller, Haworth Local vendors are Custer Workplace Interiors, Kentwood Office Furniture, Interphase, & Maxmoda. Keys for locks shall be single bit. The college requires 2 keys to be included

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

September 11, 2024

59 Division 12 ‐ Furnishings Systems Furniture: Computer Lab Tables Computer lab tables shall have a base power infeed. The electrical contrator is responsible to connect the tables to building power.

60 Division 14 ‐ Conveying Systems Elevators All elevators and associated equipment to be non proprietary and universally servicable

61 Division 14 ‐ Conveying Systems Elevators Hollister Whittney & Elsco Roller guide assemblies

62 Division 14 ‐ Conveying Systems Elevators GAL Manufacturing MOVFR2 Door operating equipment

63 Division 14 ‐ Conveying Systems Elevators Innovation Industries Car operating fixtures (push buttons)

64 Division 14 ‐ Conveying Systems Elevators Hollister Whittney Car slings & platforms

65 Division 14 ‐ Conveying Systems Elevators Bostock, G&R Elevator, H&B Elevators Cab interiors. Cab lighting to be LED.

66 Division 14 ‐ Conveying Systems Electric Traction Elevators Motion Control Engineering & Virginia Controls Motion 4000 & MVFCL Series For elevator controls

67 Division 14 ‐ Conveying Systems Electric Traction Elevators Hollister Whittney Models 201‐210 For overspeed governors and tension weights

68 Division 14 ‐ Conveying Systems Electric Traction Elevators Hollister Whittney Rope Gripper Safety for unintended movement

69 Division 14 ‐ Conveying Systems Hydraulic Elevators Motion Control Engineering, Virginia Controls, Vertitron Midwest

Motion 2000, MH3000, VHC102 For elevator controls

70 Division 14 ‐ Conveying Systems Hydraulic Elevators Minnesota Elevator Inc, Quality Elevator Products Submersible power units. Maxton valves to be used.

71 Division 21 ‐ Fire Suppression Fire Suppression Systems Rigid threaded schedule 40 piping only. No flexible piping, hose fittings, heads, etc.

72 Division 21 ‐ Fire Suppression Fire Alarms Performance specification systems only

73 Division 22 ‐ Plumbing Domestic Water Piping No grooved piping for domestic piping

74 Division 22 ‐ Plumbing Domestic Water Piping All domestic piping shall be copper with soldered joints and fittings. Type L copper pipe

75 Division 22 ‐ Plumbing Domestic Water Pumps B & G Bronze‐Lead free

76 Division 22 ‐ Plumbing Commercial Domestic Water Softeners Watts All cross‐connection control devices shall be Watts 909

77 Division 22 ‐ Plumbing Commercial Water Closets Sloan, Kohler, Mansfield, Amstd ST‐2459‐STG Preference for Sloan product with SloanTec glaze

78 Division 22 ‐ Plumbing Commercial Urinals Sloan SU‐1009‐STG

79 Division 22 ‐ Plumbing Commercial Sinks Just, Acorn, Elkay

80 Division 22 ‐ Plumbing Commercial Bathtubs Kohler or Eljer Cast Iron

81 Division 22 ‐ Plumbing Commercial Disposers ISE

82 Division 22 ‐ Plumbing Commercial Laundry Trays Acorn, Elkay

83 Division 22 ‐ Plumbing Commercial Faucets, Supplies, and Trim Sloan EFX‐277‐X0X‐0XXX, EAF150ISM, or EAF275ISM

Type dependent on building (confirm with GRCC). All faucets to have a flow rate of 1.5 gpm with laminar stream.

84 Division 22 ‐ Plumbing Flushometers Sloan ECOS 8111‐1.6/1.1, ECOS 8186‐

ECOS 8111‐1.6/1.1 for water closets and ECOS 8186‐1 for urinals

85 Division 22 ‐ Plumbing China & Supports Sloan ST‐2459‐STG Preference for Sloan product with SloanTec glaze

86 Division 22 ‐ Plumbing Water Closet Seats Bemis 1955CT, 2L2155T

87 Division 22 ‐ Plumbing Tubular Drainage Wolverine Brass Drainage Single source Wolverine Brass Drainage products

88 Division 22 ‐ Plumbing Faucets & Flush Valves Sloan Faucets EAF275‐ISM, or EAF‐

150‐ISM

89 Division 22 ‐ Plumbing Faucets T&S Brass For kitchen/ service sink

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

September 11, 2024

90 Division 22 ‐ Plumbing Showers Symmons 1‐1000, 1‐25‐T36‐V

91 Division 22 ‐ Plumbing Emergency Showers Haws or Bradley

92 Division 22 ‐ Plumbing Eyewash Equipment Haws or Bradley

93 Division 22 ‐ Plumbing Self‐Contained Eyewash Equipment Haws or Bradley

94 Division 22 ‐ Plumbing Personal Eyewash Equipment Haws or Bradley

95 Division 22 ‐ Plumbing Eye/Face Wash Equipment Haws or Bradley

96 Division 22 ‐ Plumbing Hand‐Held Emergency Drench Hoses Haws or Bradley

97 Division 22 ‐ Plumbing Combination Emergency Fixture Units Haws or Bradley 98 Division 22 ‐ Plumbing Emergency Fixture Water‐Tempering Equipment Symmons

99 Division 22 ‐ Plumbing Water‐Station Water Coolers Elkay , Murdock ELKAY LZSTL8WSLK Bilevel Cooler or EZH20 Station & Water Cooler; Murdock A171408F‐ BF12‐BCD, Murdock A172408F‐BF12‐BCD

100 Division 22 ‐ Plumbing Reverse‐Osmosis Water Equipment Watts Purified water by distillation only

101 Division 22 ‐ Plumbing Fixture Shut Offs Brass Craft SCR14XC and SCR19XC Single source for fixture shut offs

102 Division 22 ‐ Plumbing Cleanout Covers Cleanout covers for plumbing systems shall never be secured by screwing into pipe or pipe fittings.

103 Division 22 ‐ Plumbing Floor Drains Rectangular floor drains shall be used

104 Division 22 ‐ Plumbing Valves Jomar T‐301, T‐301G, F‐351, T‐351G, & F‐361

Any valve 2" and other shall be a full port ball valve. Any valve 2.5" or greater shall be a rising stem gate valve. Gate valves that are installed in the horizontal run shall be

105 Division 23 ‐ HVAC Commercial‐Kitchen Hoods CaptiveAire, Larkin, American Hood Systems No indirect fire for makeup air units

106 Division 23 ‐ HVAC Radiant‐Heating Hydronic Piping No Prohydronic specialties. Piping to be either solder (copper) or threaded (black steel) joints.

107 Division 23 ‐ HVAC Duct Sealant Use mastic to seal ductwork. Duct sealing using tape is not accepted by GRCC.

108 Division 23 ‐ HVAC AHU Trane, McQuay, York Air Handling Units must have Trane controls

109 Division 23 ‐ HVAC Frequency Drive Yaskawa, ABB, DanFos GRCC does not accept Square D frequency drives

110 Division 23 ‐ HVAC Common Motor Requirements for HVAC Equipment

Motors should be ball bearing & meet minimum energy efficiency standards. GRCC requires frequency drive specification motors.

111 Division 23 ‐ HVAC General‐Duty Valves for HVAC Piping Spartan, Erie, Honeywell, Belimo No balanced port belimo valves smaller than 2"

112 Division 23 ‐ HVAC Hangers and Supports for HVAC Piping and Equipment

Threaded rod and angle are required for duct supports above 14” wide. Due to space constraints and cost, straps may be allowed for large ducts in areas of limited space.

113 Division 23 ‐ HVAC Heat Tracing for HVAC Piping Should be wrapped around the full length of pipe. Heat trace pipe should be alarmed to tracer.

114 Division 23 ‐ HVAC Instrumentation and Control Devices for HVAC Trane

115 Division 23 ‐ HVAC Actuators and Operators Belimo, Honeywell, Keystone Belimo (dampers & small valves); Honeywell & Baber Coleman (valves 2"and above);

Keystone (valves 6" and above)

116 Division 23 ‐ HVAC Sensors and Transmitters Trane, Honeywell No dials on units. Units to be hard wired when possible. No combination C02 and temperature sensors are allowed.

117 Division 23 ‐ HVAC Control Valves Belimo, Honeywell, Spartan For control valves below 2"

118 Division 23 ‐ HVAC Control Valves Belimo, Honeywell For control valves above 2"

119 Division 23 ‐ HVAC Control Valves Terminal unit control valve may be floating point. Air handling unit control valves shall be spring return.

120 Division 23 ‐ HVAC Ball Valves To be used on domestic water and hydronic systems for shut‐off in lines 2” and smaller.

No Prohydronic specialties.

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

September 11, 2024

121 Division 23 ‐ HVAC Butterfly Valves May be used in chilled water lines above 2”.

122 Division 23 ‐ HVAC Control Dampers Greenheck, Ruskin, Titus, Johnson Control

123 Division 23 ‐ HVAC Direct‐Digital Control System for HVAC Trane Trane Tracer or Trane ES

124 Division 23 ‐ HVAC Electric and Electronic Control System for HVAC Trane Trane Tracer or Trane ES

125 Division 23 ‐ HVAC Refrigerants Consult with GRCC personnel

126 Division 23 ‐ HVAC Water Treatment for Closed‐Loop Hydronic Systems

Broadmoor Products

127 Division 23 ‐ HVAC Water Treatment for Open Hydronic Systems Broadmoor Products

128 Division 23 ‐ HVAC Water Treatment for Steam System Feedwater Broadmoor Products

129 Division 23 ‐ HVAC Water Treatment for Humidification Steam System Feedwater

Broadmoor Products

130 Division 23 ‐ HVAC Metal Ducts Do not line ductwork interior with insulation. Ductwork should be sealed to SMACNA Class A standards.

131 Division 23 ‐ HVAC Axial HVAC Fans Trane, McQuay, York, Greenheck, Twin City, Loren Cook

132 Division 23 ‐ HVAC Centrifugal HVAC Fans Trane, McQuay, York, Greenheck, Twin City, Loren Cook

133 Division 23 ‐ HVAC HVAC Power Ventilators Loren Cook, Greenheck, Dayton

134 Division 23 ‐ HVAC Variable‐Air‐Volume Units Trane, Siemens, Titus VAV boxes must have Trane controls. VAV boxes to have reheat.

135 Division 23 ‐ HVAC Diffusers, Registers, and Grilles Titus, Kreuger, Price, Tuttle and Bailey Supply air diffusers shall be a 3‐cone adjustable pattern type. Return/exhaust air grilles shall be an egg‐crate type.

136 Division 23 ‐ HVAC Fabric Air Distribution Devices Fabric Air Distribution Services are not accepted.

137 Division 23 ‐ HVAC Fume Hoods Supreme Air, Hemco, Labconco, Hamilton

138 Division 23 ‐ HVAC High‐Efficiency Particulate Filtration Camfil Farr

139 Division 23 ‐ HVAC Fabricated Stacks Hart, Cooley, Metal‐Fab

140 Division 23 ‐ HVAC Gas Vents Hart, Cooley, Metal‐Fab

141 Division 23 ‐ HVAC Condensing Boilers Raypack, Lochinvar, Fulton

142 Division 23 ‐ HVAC Cast‐Iron Boilers Weil Mclain, Burnham, Cleaver Brooks

143 Division 23 ‐ HVAC Fire‐Tube Boilers Lochinvar, Erie, Kewanee

144 Division 23 ‐ HVAC Gas‐Fired Duct Heaters Modine, Reznor, Trane

145 Division 23 ‐ HVAC Gas‐Fired Unit Heaters Modine, Reznor

146 Division 23 ‐ HVAC Steam‐to‐Water Heat Exchangers B&G, Armstrong

147 Division 23 ‐ HVAC Plate‐Type, Liquid‐to‐Liquid Heat Exchangers B&G, Armstrong, Dricooler, Taco

148 Division 23 ‐ HVAC Reciprocating Refrigerant Compressors Tecumseh, Copeland, Trane

149 Division 23 ‐ HVAC Centrifugal Refrigerant Compressors Trane, York

150 Division 23 ‐ HVAC Rotary‐Screw Refrigerant Compressors Trane, York

151 Division 23 ‐ HVAC Packaged Air‐Cooled Refrigerant Compressor and Condenser Units

Tecumseh, Copeland, Bohn

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

September 11, 2024

152 Division 23 ‐ HVAC Packaged Water‐Cooled Refrigerant Compressor and Condenser Units

Tecumseh, Copeland, Bohn

153 Division 23 ‐ HVAC Refrigerant Condensers Tecumseh, Copeland

154 Division 23 ‐ HVAC Absorption Water Chillers Trane, York

155 Division 23 ‐ HVAC Centrifugal Water Chillers Trane, York, Carrier

156 Division 23 ‐ HVAC Scroll Water Chillers Trane, York

157 Division 23 ‐ HVAC Rotary‐Screw Water Chillers Trane, York

158 Division 23 ‐ HVAC Forced‐Draft Cooling Towers Marley, Baltimore Air Coil, Evapco

159 Division 23 ‐ HVAC Thermal Heat Storage Calmac

160 Division 23 ‐ HVAC Heat‐Wheel Air‐to‐Air Energy‐Recovery Equipment

Heat Recovery Products, Trane, Driheat

161 Division 23 ‐ HVAC Modular Indoor Central‐Station Air‐Handling Units Trane, York, McQuay

162 Division 23 ‐ HVAC Packaged, Outdoor, Central‐Station Air‐Handling Units

Trane, York, McQuay, Haakon

163 Division 23 ‐ HVAC Packaged, Outdoor, Heating‐Only Makeup‐Air Units

Captive Air, Trane, Rapid, Absolute

164 Division 23 ‐ HVAC Packaged, Direct‐Fired, Outdoor, Heating‐Only Makeup‐Air Units

Captive Air, Trane, Rapid, Absolute

165 Division 23 ‐ HVAC Custom‐Packaged, Outdoor, Central‐Station Air‐ Handling Units

Haakon, Trane

166 Division 23 ‐ HVAC Room Air‐Conditioners GRCC does not accept room air conditioners

167 Division 23 ‐ HVAC Self‐Contained Air‐Conditioners Mitsubishi, Daikin

168 Division 23 ‐ HVAC Split‐System Air‐Conditioners Trane, York, Mitsubishi

169 Division 23 ‐ HVAC Fan Coil Units Trane

170 Division 23 ‐ HVAC Unit Ventilators Trane

171 Division 23 ‐ HVAC Radiators Vulcan, Sterling

172 Division 23 ‐ HVAC Unit Heaters Modine, Dayton, Trane

173 Division 23 ‐ HVAC Cabinet Unit Heaters Trane, Modine

174 Division 23 ‐ HVAC Direct‐Steam‐Injection Humidifiers Dri Steam

175 Division 23 ‐ HVAC Self‐Contained Steam Humidifiers Nortec

176 Division 23 ‐ HVAC Circulation Pumps B&G Preference to single source all circulation pumps with B&G 177 Division 23 ‐ HVAC HVAC Filters Filters shall have a minimum rating of MERV‐13 (or greater as code requires) or equivalent through dynamic air filtering 178 Division 23 ‐ HVAC Variable‐Frequency Motor Controllers ABB, Yaskawa

179 Division 23 ‐ HVAC HVAC Filters During renovations, AHU's need new filters after ductwork has been altered AND before start up. Filters need to be replaced again before contractor leaves at the end of

180 Division 26 ‐ Electrical Wiring Connections 3M

181 Division 26 ‐ Electrical Medium‐Voltage Fuses Bussman

182 Division 26 ‐ Electrical Low‐Voltage Distribution Transformers Square D

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

September 11, 2024

183 Division 26 ‐ Electrical Panelboards Square D

184 Division 26 ‐ Electrical Electricity Metering Square D

185 Division 26 ‐ Electrical Wiring Devices Hubbell, Leviton

186 Division 26 ‐ Electrical Enclosed Circuit Breakers Square D

187 Division 26 ‐ Electrical Enclosed Switches Square D

188 Division 26 ‐ Electrical Controllers for Fire Pump Drivers ABB

189 Division 26 ‐ Electrical Diesel‐Engine‐Driven Generator Sets ONAN

190 Division 26 ‐ Electrical Natural Gas Genators ONAN

191 Division 26 ‐ Electrical Automatic Transfer Switches ONAN

192 Division 26 ‐ Electrical Lighting Control Devices Hubbell, Leviton Lighting Control Systems

193 Division 26 ‐ Electrical Lighting Control Devices Hubbell, Leviton Occupancy Sensors

194 Division 26 ‐ Electrical Lighting Control Devices Dimmable Lighting All classrooms to have dimmable LED lighting. Controls should be located at room entrance and teacher's station.

195 Division 26 ‐ Electrical Lighting Control Wiring Color All wiring used for lighting controls shall be white.

196 Division 26 ‐ Electrical Electrical Conduit Minimum size of 3/4" dia. Conduit.

197 Division 26 ‐ Electrical Branch Circuit 120V Use No. 10 AWG minimum wire size from panelboard to first outlet for any 120 volt branch circuit exceeding 75 feet. Use an individual neutral conductor for each phase conductor of branch circuits. A ground wire needs to be pulled in every conduit.

Common neutral conductors are NOT allowed.

198 Division 26 ‐ Electrical Branch Circuit 277V Use No. 10 AWG minimum wire size from panelboard to first outlet for any 277 volt branch circuit exceeding 150 feet. Use an individual neutral conductor for each phase conductor of branch circuits. A ground wire needs to be pulled in every conduit.Common neutral conductors are NOT allowed.

199 Division 26 ‐ Electrical Cover Plates Cover plates shall be white for switches, and stainless steel for covers.

200 Division 26 ‐ Electrical Electric Keyed Switches Hubbell Single source Hubbell for electric keyed switches 201 Division 26 ‐ Electrical Powering up Furniture The electrical contractor is responsible to connect base power infeeds to building power 202 Division 26 ‐ Electrical ARC Flash Studies All ARC flash studies shall use SKM Power Tools software. The native file shall be turned over to GRCC with the report upon completion.

203 Division 26 ‐ Electrical Identification for Electrical Systems Identify each receptacle with panelboard identification and circuit number. Use hot, stamped, or engraved machine printing with black‐filled lettering on face of plate, and durable wire markers or tags inside outlet boxes.

204 Division 26 ‐ Electrical RF Motion Detectors RF sensors are not approved on campus. Instead, use infrared, microwave pulse, or dual mode sensors. Do NOT use 5Ghz frequencies on campus.

205 Division 26 ‐ Electrical Metal Clad Cable Metal clad cabling is NOT ALLOWED to feed circuits, or to be used in lieu of conduit.

Metal clad cabling is allowable to be fished in walls and for use as light fixture whips so long as the length of the whip does not exceed 6'.

206 Division 27 ‐ Communications Wireless Clock System Primex 14155 12.5” (31.75cm) Black;

14289 Black ‐ Fits 12.5” (31.8cm) Traditional Series Clock

Single source Primex products for wireless clock systems. Clocks shall be analog.

207 Division 28 ‐ Electronic Safety & Security Fire Detection and Alarm Systems Honeywell Notifier The college single sources Honeywell Notifier systems. All other systems (Tyco, Simplex/Grinnel, Edwards, etc.) systems are not accepted.

208 Division 32 ‐ Exterior Improvements Irrigation Controllers Hunter All Irrigation Controllers to be Hunter with Lockable Faces 209 Division 32 ‐ Exterior Improvements Irrigation Rotators Rainbird 5004PC Irrigation Rotators to be Rainbird 5004PC's 210 Division 32 ‐ Exterior Improvements Irrigation Popup Sprinklers Rainbird 150‐PGA Rainbird 150‐PGA Pop up sprinklers ranging from 2" to 11" heads 211 Division 32 ‐ Exterior Improvements Irrigation Popup Heads Toro 570Z Popup Heads to be Toro 570's 212 Division 32 ‐ Exterior Improvements Grass Seed Wear & Tear Mixture 20% Perennial Ryegrass 20% Kentucky Bluegrass 20% Annual Ryegrass 40% Turf‐

Type Tall Fescue 213 Division 32 ‐ Exterior Improvements Mulch Brown standard shredded Mulch

LINE ITEM DIVISION PRODUCT/MATERIAL MANUFACTURER(S) MODEL NUMBER(S) COMMENTS

September 11, 2024

214 Division 32 ‐ Exterior Improvements Landscaping Clearances Trees, light fixtures, shrubs, etc. shall be spaced a minimum of 72" from buildings, site furnishings, landscaping to give grounds proper clearance to mow/maintain the grounds

File details come from the government source that posted it. Updated .