About this file

This document is the Specifications Sheet for DataSafe HX top terminal batteries, which are being requested by the Maryland Department of Transportation Maryland Transit Administration (MDOT MTA) in Invitation for Bid (IFB) PUR1-24-1088 for Metro UPS Battery Replacement. The DataSafe HX batteries are Valve Regulated Lead Acid (VRLA) batteries designed for Information Technology (IT) and Uninterruptible Power Supply (UPS) applications, offering features such as flame retardant casings, self-resealing vents, and AGM separators. The IFB is soliciting bids for replacement UPS batteries for MDOT MTA's Metro Systems Maintenance Division. The document provides detailed product specifications, dimensions, performance data, and installation requirements for the various DataSafe HX battery models.

The IFB does not provide pricing terms, set-asides, incumbent information, funding sources, or other salient commercial details. It focuses solely on the technical specifications of the requested batteries. Bidders will need to respond to the IFB with their proposed battery models, quantities, and pricing to be considered for this state and local government contract opportunity.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Features and Benefits

The DataSafe® HX top terminal battery range of

Valve Regulated Lead Acid (VRLA) batteries has been designed to offer superior solutions for the

Information Technology (IT) and Uninterruptible

Power Supply (UPS) markets. DataSafe HX top terminal batteries are the ideal source of power to protect vital systems.

DataSafe HX top terminal batteries incorporate select design features that maximize reliability while ensuring superior performance and an excellent service life.

Gas recombination technology for VRLA batteries has completely changed the concept of standby power. The minimal level of gas evolution allows battery installation in cabinets or on stands, in offices or near main equipment, maximizing space utilization and reducing storage and maintenance costs. DataSafe HX top terminal batteries deliver superior performance.

Battery Range Summary

• Flame retardant case and cover (UL94) to meet UL1778

• Self-resealing, flame-arresting vents

• Battery containers and covers are hermetically sealed to provide leak resistance over the life of the product

• Absorbed Glass Mat (AGM) separators – the electrolyte is completely absorbed into the separator

• High performance brass threaded receptacle, bolt terminal or faston terminals

• Increased energy density

• Computer optimized electrochemistry for increased power up to the 15 minute rate to

1.67 Volts Per Cell (VPC)

• 100% initial battery capacity

• Classified as non-spillable

Visit us at www.enersys.com

Construction Brass insert with threaded receptacle (12HX80 -

12HX540), bolt terminal (12HX80-FR - HX150-FR) or faston tabs (HX25-FR - HX150-FR) for maximum conductivity and ease of installation.

Compression grommet (12HX205-FR - 12HX540-FR) or dual welded/epoxy seal (12HX25-FR - 12HX150-FR) designed for long life.

Self-resealing, flame-arresting vents and low pressure non-return valve prevents ingress of atmospheric oxygen.

Rugged high performance positive plates designed to resist corrosion and prolong active life.

Balanced negative plates ensure optimum recombination efficiency.

Thick-wall plastic containers, highly resistant to shock and vibration. Flame retardant material is the standard offering.

Low resistance microporous Absorbed Glass Mat (AGM) separator. The electrolyte is absorbed within this material.

Installation and Operation Normal operating temperature range 12HX25-FR - 12HX150-FR: -4°F (-20°C) to 122°F (50°C)

12HX205-FR - 12HX540-FR: -22°F (-30°C) to 122°F (50°C)

Float charging voltage 2.25-2.28 Volts per cell at 77°F (25°C) DataSafe® HX top terminal batteries can be safely recharged at high current rates.

DataSafe HX top terminal batteries can be stored for up to six months at 77°F (25°C) before a freshening charge is required. At higher temperatures this time interval will be reduced.

Torque specifications (Fig. C) M5 Receptacle - 31 in-lbs (3.5 Nm) ± 5%

(Fig. D) M6 Receptacle - (12HX150-FR) 44 in-lbs (5 Nm) ± 5%

(Fig. D) M6 Receptacle - (12HX205-FR - 12HX540-FR) 60 in-lbs (6.8 Nm) ± 5%

(Fig. E) M5 Bolt - 40 in-lbs (4.5 Nm) ± 5%

(Fig. F) M6 Bolt - 58 in-lbs (6.5 Nm) ± 5%

Standards UL listing – File No MH16464 (12HX25-FR - 12HX150- FR) or MH12544 (12HX205 - 12HX540)

The management systems governing the manufacture of this product are ISO 9001:2008 and ISO 14001:2004 certified.

Approved for shipping as non-hazardous, non-spillable – per IATA Special Provision A67 and 49 CFR.

* Including terminal ** Resistance values are for reference only and not intended to represent an Ohmic Value or Baseline measurement.

All dimensions given are +/-0.08 in (2mm)

General Specifications

L

W

L

W

L

W

M5 M6

Faston Tab: 187 Faston Tab: 250 M5 Threaded Receptacle

M6 Threaded Receptacle

M5 Bolt M6 Bolt

Layout

Terminal

Nominal Ah Watts/Cell Nominal Dimensions Electrolyte (1.300 SG)

Battery Model

Nominal Voltage

(V)

8 hr rate to 1.75 volts/cell end voltage at 77ºF (25ºC)

@ 15 min rate to

1.67 volts/cell end voltage at 77ºF (25ºC)

Length Width Overall* Height

Typical Weight

Short Circuit Current

(A)

Internal Resistance

(mΩ)** Layout Terminals

Volume Weight in mm in mm in mm lbs kg gals liters lbs kg

12HX25-FR 12 4.8 23 3.5 90 2.8 70 4.2 107 4.4 2.0 300 16.5 1 A/B 0.066 0.250 0.715 0.324

12HX35-FR 12 7.9 36 5.9 151 2.6 65 3.9 100 6.1 2.8 500 13.2 3 A/B 0.102 0.386 1.10 0.501

6HX50-FR 6 12 54 5.9 151 2.0 50 3.9 99 4.7 2.1 720 6.1 1 A/B 0.070 0.265 0.76 0.344

12HX50-FR 12 12 54 6.0 152 3.9 99 3.9 99 9.1 4.1 720 12.2 3 A/B 0.133 0.503 1.44 0.653

12HX80-FR 12 18 80 7.1 181 3.0 76 6.6 167 14.0 6.4 1000 8.5 2 C/E 0.250 0.946 2.71 1.23

12HX100-FR 12 26 104 6.5 166 4.9 125 6.9 175 22.0 10.0 1500 7.1 2 C/E 0.375 1.42 4.06 1.84

12HX135B-FR 12 31 136 7.8 198 5.1 130 7.1 180 26.0 11.8 1800 5.6 1 F 0.438 1.66 4.74 2.15

12HX135R-FR 12 31 136 7.7 196 5.1 130 6.7 169 26.0 11.8 1800 5.6 1 C 0.438 1.66 4.74 2.15

12HX150-FR 12 38 160 7.8 197 6.5 165 6.7 170 32.0 14.5 2400 5.0 2 D/F 0.570 2.16 6.17 2.80

12HX205-FR 12 43 206 8.9 226 5.5 140 8.1 206 43.0 19.5 2775 4.5 1 D 0.700 2.65 7.58 3.44

12HX300-FR 12 71 284 10.2 259 6.9 175 8.2 208 60.0 27.2 3175 3.9 1 D 1.11 4.20 12.02 5.45

12HX330-FR 12 83 336 11.8 300 6.8 173 8.4 213 71.0 32.2 3700 3.4 1 D 1.25 4.73 13.54 6.14

12HX400-FR 12 94 381 13.3 338 6.8 173 8.3 211 80.0 36.3 4225 3.0 1 D 1.33 5.03 14.40 6.53

12HX505-FR 12 119 506 13.3 338 6.8 173 10.7 272 103.0 46.7 4510 2.8 1 D 1.66 6.28 17.98 8.15

12HX540-FR 12 123 540 13.3 338 6.8 173 10.7 272 106.0 48.1 4775 2.6 1 D 1.70 6.44 18.41 8.35

2 AM-HX-RS AA March 2018 ahidey Highlight

Battery Range Summary

Constant Power Discharge (Watts per Cell) to 1.75Vpc at 77°F (25°C) Constant Power Discharge (Watts per Cell) to 1.70Vpc at 77°F (25°C)

Standby Time (Minutes)

12HX25-FR 47 30 23 18 13 10 8

12HX35-FR 70 47 36 29 21 15 12

6HX50-FR 105 70 53 43 32 23 18

12HX50-FR 105 70 53 43 32 23 18

12HX80-FR 144 101 79 64 47 34 27

12HX100-FR 180 128 100 82 62 46 37

12HX135-FR 244 171 134 110 82 60 47

12HX150-FR 270 195 152 127 96 71 57

12HX205-FR 373 258 197 160 118 85 67

12HX300-FR 513 357 277 227 173 128 102

12HX330-FR 590 418 328 272 204 150 120

12HX400-FR 671 479 371 308 230 170 136

12HX505-FR 783 600 479 398 298 218 173

12HX540-FR 835 638 511 425 318 233 186

Standby Time (Minutes)

12HX25-FR 49 31 23 19 13 10 8

12HX35-FR 73 48 36 29 21 15 12

6HX50-FR 111 72 54 44 32 23 18

12HX50-FR 111 72 54 44 32 23 18

12HX80-FR 152 104 80 65 47 34 27

12HX100-FR 192 133 103 84 63 46 37

12HX135-FR 256 176 136 111 82 60 47

12HX150-FR 289 205 158 130 97 71 57

12HX205-FR 400 269 204 164 119 85 67

12HX300-FR 545 369 283 231 174 128 102

12HX330-FR 624 431 336 276 206 150 120

12HX400-FR 708 493 380 313 232 170 136

12HX505-FR 845 637 499 410 301 218 173

12HX540-FR 898 675 532 439 326 236 186

Standby Time (Minutes)

Constant Power Discharge (Watts per Cell) to 1.67Vpc at 77°F (25°C)

12HX25-FR 50 32 23 19 13 10 8

12HX35-FR 74 48 36 29 21 15 12

6HX50-FR 113 73 54 44 32 23 18

12HX50-FR 113 73 54 44 32 23 18

12HX80-FR 156 105 80 65 47 34 27

12HX100-FR 197 135 104 84 63 46 37

12HX135-FR 260 177 136 111 82 60 47

12HX150-FR 299 209 161 131 97 71 57

12HX205-FR 412 274 206 164 119 85 67

12HX300-FR 558 373 284 231 174 128 102

12HX330-FR 637 435 336 276 206 150 120

12HX400-FR 722 498 381 313 232 170 136

12HX505-FR 877 653 506 412 301 218 173

12HX540-FR 931 691 540 444 326 236 186

Standby Time (Minutes)

Constant Power Discharge (Watts per Cell) to 1.65Vpc at 77°F (25°C)

12HX25-FR 50 32 23 19 13 10 8

12HX35-FR 74 48 36 29 21 15 12

6HX50-FR 114 73 54 44 32 23 18

12HX50-FR 114 73 54 44 32 23 18

12HX80-FR 157 106 80 65 47 34 27

12HX100-FR 200 136 104 84 63 46 37

12HX135-FR 262 177 136 111 82 60 47

12HX150-FR 304 211 161 131 97 71 57

12HX205-FR 420 276 206 164 119 85 67

12HX300-FR 563 375 284 231 174 128 102

12HX330-FR 643 437 336 276 206 150 120

12HX400-FR 729 500 381 313 232 170 136

12HX505-FR 897 661 510 412 301 218 173

12HX540-FR 951 699 545 446 326 236 186

Constant Power Discharge (Watts per Cell) to 1.63Vpc at 77°F (25°C)

12HX25-FR 51 32 23 19 13 10 8

12HX35-FR 74 48 36 29 21 15 12

6HX50-FR 115 73 54 44 32 23 18

12HX50-FR 115 73 54 44 32 23 18

12HX80-FR 158 106 80 65 47 34 27

12HX100-FR 202 137 104 84 63 46 37

12HX135-FR 263 177 136 111 82 60 47

12HX150-FR 309 212 160 131 97 71 57

12HX205-FR 426 278 206 164 119 85 67

12HX300-FR 567 375 284 231 174 128 102

12HX330-FR 648 437 336 276 206 150 120

12HX400-FR 734 500 381 313 232 170 136

12HX505-FR 916 667 511 412 301 218 173

12HX540-FR 970 706 549 446 326 236 186

Standby Time (Minutes)

Constant Power Discharge (Watts per Cell) to 1.60Vpc at 77°F (25°C)

12HX25-FR 51 32 23 19 13 10 8

12HX35-FR 75 48 36 29 21 15 12

6HX50-FR 116 73 54 44 32 23 18

12HX50-FR 116 73 54 44 32 23 18

12HX80-FR 160 106 80 65 47 34 27

12HX100-FR 204 137 104 84 63 46 37

12HX135-FR 264 177 136 111 82 60 47

12HX150-FR 315 214 161 131 97 71 57

12HX205-FR 433 279 206 164 119 85 67

12HX300-FR 571 375 284 231 174 128 102

12HX330-FR 652 437 336 276 206 150 120

12HX400-FR 739 500 381 313 232 170 136

12HX505-FR 941 675 511 412 301 218 173

12HX540-FR 995 715 550 446 326 236 186

Standby Time (Minutes)

5 10 15 20 30 45 60

5 10 15 20 30 45 60 5 10 15 20 30 45 60

5 10 15 20 30 45 60

5 10 15 20 30 45 60 Battery Model 5 10 15 20 30 45 60

AM-HX-RS AA March 2018 3

Battery Model

Battery Model

Battery Model

Battery Model

Battery Model ahidey Highlight ahidey Highlight ahidey Highlight ahidey Highlight ahidey Highlight ahidey Highlight

File details come from the government source that posted it. Updated .