APP C_REPORT OF INSPECTION TESTING AND MAINTENANCE FORM.pdf

PDF 224 KB Posted

Attached to
Load Bank Testing of Emergency Power Supply Systems and Fuel Quality Testing
Solicitation number
75H70625Q00030
Issued by

About this file

This document is a Report of Inspection, Testing & Maintenance form for Emergency and Standby Power Systems, specifically a Load Bank Test Report template for the Great Plains Area Indian Health Service. The form is designed to document detailed testing of up to three generators (Gen #1, #2, #3), with space to record comprehensive technical data including generator specifications, nameplate data, voltage, amperage, frequency, hours, oil pressure, water temperature, and kilowatt measurements. The report requires technicians to exercise generators with supplemental loads at 50% of nameplate kW rating for 30 continuous minutes and 75% of nameplate kW rating for 1 continuous hour, totaling 1.5 continuous hours of testing.

The form is associated with Solicitation Number 75H70625Q00030, a 100% Small Business Set-Aside procurement for load bank testing and fuel quality testing at Indian Health Service facilities in North Dakota and South Dakota. The contract will be awarded using Lowest Price Technically Acceptable (LPTA) methodology, with contractors required to provide all materials, labor, equipment, and supervision for generator load bank tests. The period of performance is set for 60 days maximum, with testing to be completed within 30 days of the notice to proceed and report submission within 20 days after the final site visit.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

23.8 Cover Sheet Rev:

Report of Inspection, Testing & Maintenance of Emergency and Standby Power Systems

Type of Inspection/Testing/Maintenance: Load Bank Annual 3−Year Date:

Inspecting Firm:

Street Address:

City: State: Zip:

Phone: Fax:

Inspector Name:

Name of Property:

Street Address:

City: State: Zip:

Phone: Fax:

Designated Representative:

Gen #1 Manufacturer: Gen Model:

Gen Spec: Gen S/N: Gen CPL:

Engine Model: Engine S/N:

Fuel Type: Gasoline Diesel LPG CNG

Rated KW: Rated KVA: Hour Meter:

Gen #2 Manufacturer:

Gen Model:

Engine Model: Engine S/N:

Gen #3 Manufacturer:

Gen Model:

Engine Model: Engine S/N:

ATS #1 Model:

Spec:

S/N:

ATS #2 Model: Spec: S/N:

ATS #3 Model: Spec: S/N:

ATS #4 Model: Spec: S/N:

ATS #5 Model: Spec: S/N:

ATS #6 Model: Spec: S/N:

INSPECTOR’S SIGNATURE:

DATE:

Technician:

(Print)

Signature:

23.8 Rev:

GREAT PLAINS AREA INDIAN HEALTH SERVICE

LOAD BANK TEST REPORT

Facility: Date:

Generator ID#: Gen #1

Model #:

NAMEPLATE DATA

KW: KVA: PF:

VOLTS: AMPS: HZ:

Generator shall be exercised with supplemental loads at not less than 50% of the EPS nameplate kW rating for 30 continuous minutes and at not less than 75% of the EPS nameplate kW rating for 1 continuous hour for a total test duration of not less than 1.5 continuous hours.

Load Rate 50%: 0

Load Rate 75%: 0

(kW) = 50% of Nameplate Data

(kW) = 75% of Nameplate Data

TIME

VOLTS AMPS

HZ

HOURS

OIL

PRESS

WATER

TEMP

KW A-B B-C C-A A B C

Generator ID#: Gen #2

Generator shall be exercised with supplemental loads at not less than 50% of the EPS nameplate kW rating for 30 continuous minutes and at not less than 75% of the EPS nameplate kW rating for 1 continuous hour for a total test duration of not less than 1.5 continuous hours.

PRESS

Generator ID#: Gen #3

Generator shall be exercised with supplemental loads at not less than 50% of the EPS nameplate kW rating for 30 continuous minutes and at not less than 75% of the EPS nameplate kW rating for 1 continuous hour for a total test duration of not less than 1.5 continuous hours.

PRESS