List of Job Plan Tasks

SequenceTaskDescriptionNested Job PlanDurationMeter
10Notify facility manager and facility occupants prior to testing any alarm systems0:05
20Notify fire department/coordinate testing with alarm shop (when applicable)0:05
30Visually inspect panel wiring and connections for tightness0:16
40Test monitored Control Panel/Annunciator Equipment to verify proper receipt of alarm, supervisory, trouble signals (inputs).0:03
50Test monitored Control Panel/Annunciator Equipment to verify proper operation of notification appliances & auxiliary functions (outputs).0:03
60Verify monitored Control Panel & Annunciator Equipment that all lamps and LEDs are illuminated.0:03
70Load test Control Panel & Annunciator Equipment backup batteries (when provided).0:02
80Initiating Devices-Manual Fire Alarm Stations verify station is accessible0:17
90Test Initiating Devices-Radiant Energy Detectors (Optical Detectors) to verify alarm initiation & receipt.0:30
100Verify no facility change that affects performance of Initiating Devices-Radiant Energy Detectors (Optical Detectors).0:15
110"Initiating Devices-Gas Detectors 1. Test to verify alarm initiation and receipt. 2. Verify no facility change that affects performance.0:45
120Notification Appliances and Voice Communication (telephone, speakers, horns, and strobe lights) Test to verify operability.0:42
130Digital Alarm Transmitters and Receivers. Test to verify operability0:09
140"Visually check entire system: Detectors unblocked & uncovered, Manual stations in place & unobstructed.0:10
150"Visually check entire system: Panels secured & indicator lamps functional, Notification appliances in place,0:20
160"Entire System: Exercise evacuation notification appliances for audibility, clarity, and visibility.0:20
170Check all air handler and exhaust fan shut down circuit for proper operation (for HVAC Systems of 2000 cfm and greater)0:40
180Check binary transmitter (BT) (radio control box) to ensure all alarm activations, tampers & AC power fails transmit to the fire dept. alarm monitoring desk0:34
190Perform battery load tests on backup batteries in both fire control panel & (BT) (radio control box).0:09
200Inspect Fire Alarm Control Panel (FACP) for proper labeling0:50
210Restore system to proper operating condition0:09
220Notify facility manager/facility occupants of test completion0:05
230Notify fire department of test completion0:05
240Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s)0:17
250Only Trained or Qualified Personnel shall perform Inspection, Testing & Maintenance (ITM) tasks on Fire Suppression Systems.0:00
260Units with qualified personnel can accomplish tasks within their level of qualifications or utilize contractors meeting state qualifications & licensing requirements.0:00