List of Job Plan Tasks
| Sequence | Task | Description | Nested Job Plan | Duration | Meter |
| 10 | Notify facility manager and facility occupants prior to testing any alarm systems | 0:05 | |||
| 20 | Notify fire department/coordinate testing with alarm shop (when applicable) | 0:05 | |||
| 30 | Visually inspect panel wiring and connections for tightness | 0:16 | |||
| 40 | Test monitored Control Panel/Annunciator Equipment to verify proper receipt of alarm, supervisory, trouble signals (inputs). | 0:03 | |||
| 50 | Test monitored Control Panel/Annunciator Equipment to verify proper operation of notification appliances & auxiliary functions (outputs). | 0:03 | |||
| 60 | Verify monitored Control Panel & Annunciator Equipment that all lamps and LEDs are illuminated. | 0:03 | |||
| 70 | Load test Control Panel & Annunciator Equipment backup batteries (when provided). | 0:02 | |||
| 80 | Initiating Devices-Manual Fire Alarm Stations verify station is accessible | 0:17 | |||
| 90 | Test Initiating Devices-Radiant Energy Detectors (Optical Detectors) to verify alarm initiation & receipt. | 0:30 | |||
| 100 | Verify no facility change that affects performance of Initiating Devices-Radiant Energy Detectors (Optical Detectors). | 0:15 | |||
| 110 | "Initiating Devices-Gas Detectors 1. Test to verify alarm initiation and receipt. 2. Verify no facility change that affects performance. | 0:45 | |||
| 120 | Notification Appliances and Voice Communication (telephone, speakers, horns, and strobe lights) Test to verify operability. | 0:42 | |||
| 130 | Digital Alarm Transmitters and Receivers. Test to verify operability | 0:09 | |||
| 140 | "Visually check entire system: Detectors unblocked & uncovered, Manual stations in place & unobstructed. | 0:10 | |||
| 150 | "Visually check entire system: Panels secured & indicator lamps functional, Notification appliances in place, | 0:20 | |||
| 160 | "Entire System: Exercise evacuation notification appliances for audibility, clarity, and visibility. | 0:20 | |||
| 170 | Check all air handler and exhaust fan shut down circuit for proper operation (for HVAC Systems of 2000 cfm and greater) | 0:40 | |||
| 180 | Check binary transmitter (BT) (radio control box) to ensure all alarm activations, tampers & AC power fails transmit to the fire dept. alarm monitoring desk | 0:34 | |||
| 190 | Perform battery load tests on backup batteries in both fire control panel & (BT) (radio control box). | 0:09 | |||
| 200 | Inspect Fire Alarm Control Panel (FACP) for proper labeling | 0:50 | |||
| 210 | Restore system to proper operating condition | 0:09 | |||
| 220 | Notify facility manager/facility occupants of test completion | 0:05 | |||
| 230 | Notify fire department of test completion | 0:05 | |||
| 240 | Compile list of discrepancies and open corrective maintenance job order(s) to make the repair(s) | 0:17 | |||
| 250 | Only Trained or Qualified Personnel shall perform Inspection, Testing & Maintenance (ITM) tasks on Fire Suppression Systems. | 0:00 | |||
| 260 | Units with qualified personnel can accomplish tasks within their level of qualifications or utilize contractors meeting state qualifications & licensing requirements. | 0:00 |