ANNUAL_513_Gaylord OLIVER BERRY.doc

DOC document 63 KB Posted

Attached to
52000QR260023806 USCGC OLIVER BERRY FIRE SURPRESSION SYSTEM INSPECTION
Solicitation number
52000QR260023806
Issued by

About this file

This document is a Performance Work Statement (PWS) for cleaning and inspecting the Gaylord Hood ventilation system aboard the USCGC OLIVER BERRY. The contractor shall clean approximately 15 linear feet of interior ducting and associated component surfaces within the galley's supply and exhaust ventilation system, from air intake to discharge point. The work requires the contractor to furnish and install all protective coverings to seal off non-affected vessel components, document the system's initial condition through digital photography, perform the cleaning work, and conduct post-cleaning inspections with before-and-after images. Additionally, the contractor must test and recertify the Gaylord Hood fire extinguishing system in accordance with manufacturer requirements upon completion of cleaning work. The contractor shall provide 48 hours written notification to the Contracting Officer's Representative (COR) before commencing work and must perform an initial operational test in the presence of Coast Guard personnel to establish baseline conditions, with a final operational test to demonstrate satisfactory operating condition upon completion.

The work is to be performed aboard the USCGC OLIVER BERRY located at 400 Sand Island Parkway, Honolulu, Hawaii 96819, with a performance period from April 1, 2026 through April 26, 2026. The point of contact is Engineering Petty Officer Samuel Dudley at samuel.t.dudley@uscg.mil or (571) 613-2106. Coast Guard personnel will operate all shipboard machinery and equipment, and known interferences include existing piping and electrical wiring. All work must be documented through a Contractor Final Report (CFR) submission that includes digital photographs, fire extinguishing system recertification documentation, and confirmation of system restoration to original cleanliness conditions.

View the file

Other files

File Type Posted
FAR Matrix2026.pdf PDF
ANNUAL_555_FM-200_Test OLIVER BERRY.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

51300_ENV_0319_154WPC

WORK ITEM 1: Gaylord Hood Ventilation System, Clean and Inspect

1. SCOPE

1.1 Intent. This work item describes the requirements for the Contractor to clean and inspect the interior of the Galley’s Gaylord Hood supply and exhaust ventilation system and recertify the fix fire extinguishing system.

1.2 Government-furnished property.

None

2. REFERENCES

None.

3. REQUIREMENTS

None.

3.1.1 CIR.

None.

3.1.2 Tech Rep.

Not applicable.

3.1.3 Protective measures. The Contractor shall furnish and install all protective coverings to seal off and protect all non-affected vessel's components, equipment, and spaces near the work area against contamination during the performance of work. Upon completion of work, the Contractor shall remove all installed protective measures, inspect for the presence of contamination, and return all contaminated equipment, components, and spaces to original condition of cleanliness.

3.1.4 Interferences. Known interferences include, but are not limited to the following:

· Piping

· Electrical wiring

3.2 Notification. The Contractor shall give written notification to the COR, 48 hours before starting ventilation cleaning work.

Note

Coast Guard personnel will operate all shipboard machinery and equipment.

3.3 Operational test, initial. Prior to commencement of work, the Contractor shall witness Coast Guard Personnel perform an initial operational test of the Galley’s Gaylord Hood supply and exhaust ventilation systems to ascertain its operational condition.

3.3.1 The Contractor shall take digital photos of all ducting interior surfaces at each opening to show the condition of the duct work prior to cleaning. Document any and all modifications to the system (e.g. new holes in existing duct, etc.) that will be required to perform the cleaning work. Do not perform modifications without Coast Guard authorization. Submit a CFR.

3.4 Cleaning requirements. The Contractor shall clean and inspect approximately 15 linear feet of interior ducting and associated component surfaces of the entire Galley’s Gaylord Hood supply and exhaust ventilation system from the point where the air enters the system to the point where the air is discharged from the system.

3.4.1 Galley hood fire extinguishing system recertification. After completion of cleaning work, the Contractor shall test and recertify the Gaylord Hood fire extinguishing system in accordance with the manufacturer’s requirements and instructions. Provide associated documentation with the final CFR submission.

3.4.2 Duct Interior Images for Final Report. After completion of work and prior to closing the duct work accesses, the Contractor shall take post-cleaning images of the same areas originally photographed in paragraph 3.3.1. Provide these before and after images in the final report.

3.5 Operational test, post repairs. The Contractor shall thoroughly test, in the presence of the Coast Guard Inspector, and demonstrate that the Gaylord Hood supply and exhaust ventilation systems is in satisfactory operating condition. Submit a CFR to include all images in the final report.

4. NOTES

4.1 Additional information. The COR may provide additional information if requested.

Inspection and certification will be conducted onboard CGC OLIVER BERRY located at 400 Sand Island Parkway, Honolulu, HI 96819. Period of performance will be from 01APR26 to 26APR26. Point of Contact will be the Engineering Petty Officer, Samuel Dudley samuel.t.dudley@uscg.mil (571) 613-2106