Air compressor specification.pdf

PDF 105 KB Posted

Attached to
Air Compressor - FMS #2 Auburn
Solicitation number
RFQ - 15A - 26042900000000000280
Issued by
Androscoggin County, Maine

About this file

This specification document outlines technical requirements for general-service packaged air compressors and receivers for the State of Maine's FMS #2 Auburn facility. The project specifies one oil-injected, rotary-screw air compressor with a capacity of 56.9 actual cubic feet per minute (acfm) delivered at 130 psig discharge pressure, powered by a 15-horsepower, three-phase 208-volt motor operating at 60 hertz. The system includes a 120-gallon ASME-construction steel receiver tank rated for 200 psig minimum pressure with an automatic drain valve, inlet-air filters with 99 percent retention efficiency for particles larger than 10 micrometers, and a control panel enclosure with automatic load control and protection functions. The specification requires factory-assembled, wired, piped, and tested equipment with air-cooled continuous-duty operation. Additional components include thermometers, pressure gages, safety valves, pressure regulators, and automatic drain valves. The equipment must comply with NEMA and UL standards, ASME Boiler and Pressure Vessel Code requirements, and NFPA 70 electrical standards.

Installation requirements mandate placement on cast-in-place concrete equipment bases with vibration isolation devices, proper anchoring to substrate, and maintenance of manufacturer-recommended clearances for service access. The contractor must provide startup service including completion of installation and startup checks per manufacturer instructions, verification of proper motor rotation and unit operation, testing and adjustment of controls and safeties, and training for the Owner's maintenance personnel on equipment adjustment, operation, and maintenance. The specification also requires submission of product data, shop drawings for power and control wiring, operation and maintenance documentation, and maintenance materials including inlet-air filter elements equal to 100 percent of installed amounts and one complete set of belts for belt-driven compressors. The contract includes provisions for notification to the Owner no fewer than two days in advance of any interruption to existing compressed-air service and coordination with the Owner regarding concrete base sizing and locations.

View the file

Other files

File Type Posted
RFQ 15A260429-0280 Air Compressor - resoliciting.docx DOCX document
RFQ 15A260429-0280 Air Compressor.docx DOCX document
air compressor spreadsheet.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS 221519 - 1

SECTION 221519 - GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Oil-flooded, rotary-screw air compressors.

2. Inlet-air filters.

3. Computer interface cabinet.

1.3 DEFINITIONS

A. Actual Air: Air delivered from air compressors. Flow rate is delivered compressed air measured in acfm.

B. Standard Air: Free air at 68 deg F and 1 atmosphere before compression or expansion and measured in scfm.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.

B. Shop Drawings:

1. Include diagrams for power, signal, and control wiring.

C. Delegated-Design Submittal: For compressed-air equipment mounting.

1. Detail fabrication and assembly of supports.

1.5 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For compressed-air equipment to include in emergency, operation, and maintenance manuals.

GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS 221519 - 2

1.6 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Air-Compressor, Inlet-Air-Filter Elements: Equal to 100 percent of amount installed, but no fewer than 1 unit.

2. Belts: One set for each belt-driven compressor.

1.7 FIELD CONDITIONS

A. Interruption of Existing Compressed-Air Service: Do not interrupt service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary service according to requirements indicated:

1. Notify Owner no fewer than two days in advance of proposed interruption of compressed-air service.

2. Do not proceed with interruption of compressed-air service without Owner's written permission.

1.8 COORDINATION

A. Coordinate sizes and locations of concrete bases with actual equipment provided.

PART 2 - PRODUCTS

2.1 SYSTEM DESCRIPTION

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. ASME Compliance: Fabricate and label receivers to comply with ASME Boiler and Pressure

Vessel Code.

2.2 PERFORMANCE REQUIREMENTS

A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000

"Quality Requirements," to design compressed-air equipment mounting.

2.3 GENERAL REQUIREMENTS FOR PACKAGED AIR COMPRESSORS AND RECEIVERS

A. General Description: Factory-assembled, -wired, -piped, and -tested; electric-motor-driven; air-cooled; continuous-duty air compressors and receivers that deliver air of quality equal to intake air.

GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS 221519 - 3

B. Control Panels: Automatic control station with load control and protection functions. Comply with NEMA ICS 2 and UL 508.

1. Enclosure: NEMA ICS 6, Type 12 control panel unless otherwise indicated.

2. Motor Controllers: Full-voltage, combination magnetic type with undervoltage release feature and motor-circuit-protector-type disconnecting means and short-circuit protective device.

3. Control Voltage: 120-V ac or less, using integral control power transformer.

4. Motor Overload Protection: Overload relay in each phase.

5. Starting Devices: Hand-off-automatic selector switch in cover of control panel, plus pilot device for automatic control.

6. Instrumentation: Include discharge-air pressure gage, air-filter maintenance indicator, hour meter, compressor discharge-air and coolant temperature gages, and control transformer.

7. Alarm Signal Device: For connection to alarm system to indicate when backup air compressor is operating.

C. Receivers: Steel tank constructed according to ASME Boiler and Pressure Vessel Code:

Section VIII, Division 1.

1. Pressure Rating: At least as high as highest discharge pressure of connected compressors, and bearing appropriate code symbols.

2. Interior Finish: Corrosion-resistant coating.

3. Accessories: Include safety valve, pressure gage, drain, and pressure-reducing valve.

2.4 OIL-INJECTED, ROTARY-SCREW AIR COMPRESSORS

A. Available Manfacturers:

1. Gardner Denver

B. Compressor(s): Oil-injected, rotary-screw type with lubricated helical screws and lubricated gear box.

1. Coupling: Nonlubricated, flexible type.

2. Cooling/Lubrication System: Unit-mounted, air-cooled exchanger package prepiped to unit; with air pressure circulation system with coolant stop valve, full-flow coolant filter, and thermal bypass valve.

3. Air Filter: Dry type, with maintenance indicator and cleanable, replaceable filter element.

4. Air/Coolant Receiver and Separation System: 150-psig- rated steel tank with ASME safety valve, coolant-level gage, multistage air-coolant separator element, minimum pressure valve, blowdown valve, discharge check valve, coolant stop valve, full-flow coolant filter, and thermal bypass valve.

5. Capacity Control: Capacity modulation between zero and 100 percent air delivery, with operating pressures between 50 and 100 psig. Include necessary control to hold constant pressure. When air demand is zero, unload compressor by using pressure switch and blowdown valve.

C. Capacities and Characteristics:

GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS

221519 - 4

1. Air Compressor(s): One; single stage.

2. Actual-Air Capacity of Each Air Compressor: 56.9 acfm delivered.

3. Discharge-Air Pressure: 130 psig.

4. Intake-Air Temperature: 65 deg F.

5. Discharge-Air Temperature: deg F.

6. Motor (Each Air Compressor):

a. Horsepower: 15.

b. Speed: rpm.

7. Electrical Characteristics:

a. Volts: 208.

b. Phase(s): Three.

c. Hertz: 60.

d. Full-Load Amperes:.

e. Minimum Circuit Ampacity: .

f. Maximum Overcurrent Protection: .

8. Receiver: ASME construction steel tank.

a. Arrangement: Horizontal.

b. Capacity: 120 gal..

c. Interior Finish: Epoxy coating.

d. Pressure Rating: 200 psig minimum.

e. Pressure Regulator Setting: 100 psig.

f. Drain: Automatic valve.

9. Enclosure: Steel with sound-attenuating material lining.

2.5 INLET-AIR FILTERS

A. Description: Combination inlet-air filter-silencer, suitable for remote installation, for each air compressor.

1. Construction: Weatherproof housing for replaceable, dry-type filter element, with silencer tubes or other method of sound reduction.

2. Capacity: Match capacity of air compressor, with filter having collection efficiency of 99 percent retention of particles larger than 10 micrometers.

A. Description:

1. Wall mounting.

2. Welded steel with white enamel finish.

3. Gasketed door.

4. Grounding device.

5. Factory-installed, signal circuit boards.

6. Power transformer.

7. Circuit breaker.

8. Wiring terminal board.

9. Internal wiring capable of interfacing 20 alarm signals.

http://www.specagent.com/LookUp/?ulid=2359&mf=04&src=wd

221519 - 5

2.8 MOTORS

A. Comply with NEMA designation, temperature rating, service factor, and efficiency requirements for motors specified in Section 220513 "Common Motor Requirements for

Plumbing Equipment."

1. Enclosure: Open, dripproof.

2. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven load does not require motor to operate in service factor range above 1.0.

3.1 EQUIPMENT INSTALLATION

A. Equipment Mounting:

1. Install air compressors and air dryers on cast-in-place concrete equipment base(s).

Comply with requirements for equipment bases and foundations specified in

Section 033000 "Cast-in-Place Concrete."

2. Comply with requirements for vibration isolation devices specified in Section 220548.13

"Vibration Controls for Plumbing Piping and Equipment."

B. Install compressed-air equipment anchored to substrate.

C. Arrange equipment so controls and devices are accessible for servicing.

D. Maintain manufacturer's recommended clearances for service and maintenance.

E. Install the following devices on compressed-air equipment:

1. Thermometer, Pressure Gage, and Safety Valve: Install on each compressed-air receiver.

2. Pressure Regulators: Install downstream from air compressors and dryers.

3. Automatic Drain Valves: Install on aftercoolers, receivers, and dryers. Discharge condensate over nearest floor drain.

3.2 CONNECTIONS

A. Comply with requirements for piping specified in Section 221513 "General-Service

Compressed-Air Piping." Drawings indicate general arrangement of piping, fittings, and specialties.

B. Where installing piping adjacent to machine, allow space for service and maintenance.

3.3 IDENTIFICATION

A. Identify general-service air compressors and components. Comply with requirements for identification specified in Section 220553 "Identification for Plumbing Piping and Equipment."

3.4 STARTUP SERVICE

GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS 221519 - 6

A. Perform startup service.

1. Complete installation and startup checks according to manufacturer's written instructions.

2. Check for lubricating oil in lubricated-type equipment.

3. Check belt drives for proper tension.

4. Verify that air-compressor inlet filters and piping are clear.

5. Check for equipment vibration-control supports and flexible pipe connectors, and verify that equipment is properly attached to substrate.

6. Check safety valves for correct settings. Ensure that settings are higher than air-compressor discharge pressure, but not higher than rating of system components.

7. Drain receiver tanks.

8. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.

9. Test and adjust controls and safeties.

3.5 DEMONSTRATION

A. Train Owner's maintenance personnel to adjust, operate, and maintain air compressors and air dryers.

END OF SECTION 221519