Pre-Bid Q&A

Q – Did not see a mulch spec included.

A – See attached mulch specification.

Q – Will minor alignment changes be permitted to avoid large trees?

A – Yes, minor alignments may be permitted as long as it is approved by FS prior to implementation, and the re-alignment would not damage root systems of the trees the re-alignment was intended to protect or avoid. In that event, we would recommend just to remove the tree per the Clearing and Grubbing specifications.

Q – Will the contractor be required to perform trench compaction testing?

A – No, the contractor is not required to perform compaction testing. However, the government could perform its own testing if it appears that the intent of the compaction specification is not being met.