ATTACHMENT 1 - SPECIFICATIONS

SECTION 282300 - VIDEO SURVEILLANCE

PART 1 - GENERAL

1.1 SUMMARY

A. This project includes the installation of a new video surveillance system at the Missoula Forestry Sciences Laboratory to provide coverage of all entry and exit points within the building. This includes 2 basement cameras, 2 second floor cameras, 3 main floor cameras, and one exterior loading area camera.

B. This section includes a video surveillance system consisting of cameras, digital video recorder, data transmission wiring, and a control station with its associated equipment.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product indicated. Include dimensions and data on features, performance, electrical characteristics, ratings, and finishes.

B. Shop Drawings: For video surveillance. Include plans, elevations, sections, details, and attachments to other work.

1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

2. Functional Block Diagram: Show single-line interconnections between components for signal transmission and control. Show cable types and sizes.

3. Dimensioned plan and elevations of equipment racks, control panels, and consoles. Show access and workspace requirements.

4. UPS: Sizing calculations.

5. Wiring Diagrams: For power, signal, and control wiring.

C. Equipment List: Include every piece of equipment by model number, manufacturer, serial number, location, and date of original installation.

1.3 INFORMATIONAL SUBMITTALS

A. Field quality-control reports.

1.4 CLOSEOUT SUBMITTALS

A. Operation and maintenance data.

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with NECA 1.

C. Comply with NFPA 70.

1.6 PROJECT CONDITIONS

A. Environmental Conditions: Capable of withstanding the following environmental conditions without mechanical or electrical damage or degradation of operating capability:

1. Control Station: Rated for continuous operation in ambient temperatures of 60 to 85 deg F and a relative humidity of 20 to 80 percent, noncondensing.

2. Interior, Controlled Environment: System components, except central-station control unit, installed in temperature-controlled interior environments shall be rated for continuous operation in ambient temperatures of 36 to 90 deg dry bulb and 20 to 80 percent relative humidity, noncondensing. Use NEMA 250, Type 1 enclosures.

3. Interior, Uncontrolled Environment: System components installed in non-temperature-controlled interior environments shall be rated for continuous operation in ambient temperatures of 30 to 122 deg F dry bulb and 20 to 80 percent relative humidity, noncondensing. Use NEMA 250, Type 12K enclosures.

4. Exterior Environment: System components installed in locations exposed to weather shall be rated for continuous operation in ambient temperatures of minus 0 to plus 122 deg F dry bulb and 20 to 80 percent relative humidity, condensing. Rate for continuous operation when exposed to rain as specified in NEMA 250, winds up to 85 mph. Use NEMA 250, Type 4X enclosures.

5. Security Environment: Camera housing for use in high-risk areas where surveillance equipment may be subject to physical violence.

1.7 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of cameras, equipment related to camera operation, and control-station equipment that fail in materials or workmanship within specified warranty period.

1. Warranty Period: One years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 SYSTEM REQUIREMENTS

A. Video-signal format shall comply with NTSC standard, composite interlaced video. Composite video-signal termination shall be 75 ohms.

B. Surge Protection: Protect components from voltage surges entering through power, communication, signal, control, or sensing leads. Include surge protection for external wiring of each conductor's entry connection to components.

1. Minimum Protection for Power Connections 120 V and More: Auxiliary panel suppressors complying with requirements in Section 264313 "Surge Protection for Low- Voltage Electrical Power Circuits."

2. Minimum Protection for Communication, Signal, Control, and Low-Voltage Power Connections: Comply with requirements recommended by manufacturer for type of line being protected.

2.2 STANDARD CAMERAS

A. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:

B. Automatic Color Dome Camera: Assembled and tested as a manufactured unit, containing dome assembly, color camera, motorized pan and tilt, zoom lens, and receiver/driver.

1. Pickup Device: CCD interline transfer, 380,000 768(H) by 494(V)pixels.

2. Horizontal Resolution: 480 lines.

3. Signal-to-Noise Ratio: Not less than 50 dB, with camera AGC off.

4. With AGC, manually selectable on or off.

5. White Balance: Auto-tracing white balance, with manually settable fixed balance option.

6. Motion Detector: Built-in digital.

2.3 LENSES

A. Description: Optical-quality coated lens, designed specifically for video-surveillance applications and matched to specified camera. Provide color-corrected lenses.

1. Auto-Iris Lens: Electrically controlled iris with circuit set to maintain a constant video level in varying lighting conditions.

2.4 POWER SUPPLIES

A. Low-voltage power supplies matched for voltage and current requirements of cameras and accessories, and of type as recommended by manufacturer of camera and lens.

1. Enclosure: NEMA 250, Type 4X

2.5 CAMERA-SUPPORTING EQUIPMENT

A. Mounting Brackets for Fixed Cameras: Type matched to items supported and mounting conditions. Include manual pan-and-tilt adjustment.

B. Protective Housings for Fixed and Movable Cameras: Steel or 6061 T6 aluminum enclosures with internal camera mounting and connecting provisions that are matched to camera/lens combination and mounting and installing arrangement of camera to be housed.

http://www.specagent.com/LookUp/?ulid=2495&mf=04&src=wd

1. Camera Viewing Window: Polycarbonate or Lexan window, aligned with camera lens.

2. Duplex Receptacle: Internally mounted.

3. Alignment Provisions: Camera mounting shall provide for field aiming of camera and permit removal and reinstallation of camera lens without disturbing camera alignment.

4. Sun shield shall not interfere with normal airflow around the housing.

5. Mounting bracket and hardware for wall or ceiling mounting of the housing. Bracket shall be of same material as the housing; mounting hardware shall be stainless steel.

6. Finish: Housing and mounting bracket shall be factory finished using manufacturer's standard finishing process suitable for the environment.

2.6 COLOR MONITORS

A. Screen Size (Diagonal Dimension): 14 inch

B. Horizontal Resolution: 300 lines.

C. Minimum Front Panel Devices and Controls: Power switch; power-on indicator; and brightness, contrast, color, and tint controls.

D. Degaussing: Automatic.

E. Mounting: Single, 14-inch vertical, EIA 19-inch (483-mm) electronic equipment rack or cabinet complying with CEA 310-E.

F. Electrical: 120-V ac, 60 Hz.

2.7 DIGITAL VIDEO RECORDERS

A. Basis-of-Design Product: Subject to compliance with requirements, provide Lenel goVision 2.0 or comparable product.

B. Description: Digital, time-lapse type, full-frame and motion recorder, with removable hard drive.

1. Recording Time: 1500 hours minimum.

2. Resolution: 720 by 480 lines, minimum.

3. Programming settings shall be displayed on any video monitor connected to the recorder.

Programming shall include the following:

a. Motion analysis graph.

b. Password protection.

c. Alarm and timer controls.

d. Continuous recording option.

e. Time-lapse operating modes.

f. Search video by time, event, or motion.

4. Programming: SmartMedia card for software updating, image archiving, and image transfer to a PC.

5. Storage: 1 TB removable hard drive.

http://www.specagent.com/LookUp/?ulid=2503&mf=04&src=wd

6.

7. Time and Date Generator: Records time (hr:min:sec) and date legend of each frame.

8. Audio Recording: 70 to 7000 Hz. Phono and microphone input; phono output.

9. Mounting: Standard 19-inch (483-mm) rack complying with CEA 310-E, or freestanding desktop.

2.8 CONTROL STATIONS

A. Description: Heavy-duty, freestanding, modular, metal furniture units arranged to house electronic equipment. Coordinate component arrangement and wiring with components and wiring of other systems.

B. Equipment Mounting: Standard 19-inch (483-mm) rack complying with CEA 310-E.

C. Normal System Power Supply: 120 V, 60 Hz, through a locked disconnect device and an isolation transformer in central-station control unit. Central-station control unit shall supply power to all components connected to it unless otherwise indicated.

D. Power Continuity for Control Station: Batteries in power supplies of central-station control units and individual system components shall maintain continuous system operation during outages of both normal and backup ac system supply.

1. Batteries: Rechargeable, valve-regulated, recombinant, sealed, lead-acid type with nominal 10-year life expectancy. Capacity adequate to operate portions of system served including audible trouble signal devices for up to four hours and audible and visual alarm devices under alarm conditions for an additional 10 minutes.

2. Battery Charger: Solid-state, fully automatic, variable-charging-rate type. Charger shall recharge fully discharged battery within 24 hours.

E. Annunciation: Indicate change in system condition and switching of system or component to backup power.

2.9 SIGNAL TRANSMISSION COMPONENTS

A. Cable: Coaxial cable elements have 75-ohm nominal impedance. Comply with requirements in Section 280513 "Conductors and Cables for Electronic Safety and Security."

B. Video Surveillance Coaxial Cable Connectors: BNC type, 75 ohms. Comply with requirements in Section 280513 "Conductors and Cables for Electronic Safety and Security."

PART 3 - EXECUTION

3.1 WIRING

A. Wiring Method: Install cables in raceways unless otherwise indicated.

1. Except raceways are not required in accessible indoor ceiling spaces and attics.

2. Except raceways are not required in hollow gypsum board partitions.

3. Conceal raceways and wiring except in unfinished spaces.

B. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools.

C. Splices, Taps, and Terminations: For power and control wiring, use numbered terminal strips in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B.

D. For LAN connection and fiber-optic and copper communication wiring, comply with Section 271300 "Communications Backbone Cabling" and Section 271500 "Communications Horizontal Cabling."

E. Grounding: Provide independent-signal circuit grounding recommended in writing by manufacturer.

3.2 VIDEO SURVEILLANCE SYSTEM INSTALLATION

A. Install cameras with 84-inch- minimum clear space below cameras and their mountings. Change type of mounting to achieve required clearance.

B. Set pan-and-tilt unit stops to suit final camera position and to obtain the field of view required for camera. Connect all controls and alarms, and adjust.

C. Avoid ground loops by making ground connections only at the control station.

1. For 12- and 24-V dc cameras, connect the coaxial cable shields only at the monitor end.

D. Identify system components, wiring, cabling, and terminals according to Section 260553 "Identification for Electrical Systems."

3.3 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Tests and Inspections:

1. Inspection: Verify that units and controls are properly installed, connected, and labeled, and that interconnecting wires and terminals are identified.

2. Pretesting: Align and adjust system and pretest components, wiring, and functions to verify that they comply with specified requirements. Conduct tests at varying lighting levels, including day and night scenes as applicable. Prepare video-surveillance equipment for acceptance and operational testing as follows:

a. Verify operation of auto-iris lenses.

b. Set back-focus of fixed focal length lenses. At focus set to infinity, simulate nighttime lighting conditions by using a dark glass filter of a density that produces a clear image. Adjust until image is in focus with and without the filter.

c. Set back-focus of zoom lenses. At focus set to infinity, simulate nighttime lighting conditions by using a dark glass filter of a density that produces a clear image.

Additionally, set zoom to full wide angle and aim camera at an object 50 to 75 feet (17 to 23 m) away. Adjust until image is in focus from full wide angle to full telephoto, with the filter in place.

d. Set and name all preset positions; consult Owner's personnel.

e. Set sensitivity of motion detection.

f. Connect and verify responses to alarms.

g. Verify operation of control-station equipment.

3. Test Schedule: Schedule tests after pretesting has been successfully completed and system has been in normal functional operation for at least 14 days. Provide a minimum of 10 days' notice of test schedule.

4. Operational Tests: Perform operational system tests to verify that system complies with Specifications. Include all modes of system operation.

C. Video surveillance system will be considered defective if it does not pass tests and inspections.

D. Prepare test and inspection reports.

3.4 DEMONSTRATION

A. Train Owner's maintenance personnel to adjust, operate, and maintain video-surveillance equipment.

END OF SECTION 282300

PART 1 - GENERAL
1.1 SUMMARY
A. This project includes the installation of a new video surveillance system at the Missoula Forestry Sciences Laboratory to provide coverage of all entry and exit points within the building. This includes 2 basement cameras, 2 second floor cameras, ...
B. This section includes a video surveillance system consisting of cameras, digital video recorder, data transmission wiring, and a control station with its associated equipment.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product indicated. Include dimensions and data on features, performance, electrical characteristics, ratings, and finishes.
B. Shop Drawings: For video surveillance. Include plans, elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
2. Functional Block Diagram: Show single-line interconnections between components for signal transmission and control. Show cable types and sizes.
3. Dimensioned plan and elevations of equipment racks, control panels, and consoles. Show access and workspace requirements.
4. UPS: Sizing calculations.
5. Wiring Diagrams: For power, signal, and control wiring.

C. Equipment List: Include every piece of equipment by model number, manufacturer, serial number, location, and date of original installation.

1.3 INFORMATIONAL SUBMITTALS
A. Field quality-control reports.
1.4 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.5 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Comply with NECA 1.
C. Comply with NFPA 70.
1.6 PROJECT CONDITIONS
A. Environmental Conditions: Capable of withstanding the following environmental conditions without mechanical or electrical damage or degradation of operating capability:
1. Control Station: Rated for continuous operation in ambient temperatures of 60 to 85 deg F and a relative humidity of 20 to 80 percent, noncondensing.
2. Interior, Controlled Environment: System components, except central-station control unit, installed in temperature-controlled interior environments shall be rated for continuous operation in ambient temperatures of 36 to 90 deg dry bulb and 20 to ...
3. Interior, Uncontrolled Environment: System components installed in non-temperature-controlled interior environments shall be rated for continuous operation in ambient temperatures of 30 to 122 deg F dry bulb and 20 to 80 percent relative humidity,...
4. Exterior Environment: System components installed in locations exposed to weather shall be rated for continuous operation in ambient temperatures of minus 0 to plus 122 deg F dry bulb and 20 to 80 percent relative humidity, condensing. Rate for co...
5. Security Environment: Camera housing for use in high-risk areas where surveillance equipment may be subject to physical violence.
1.7 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of cameras, equipment related to camera operation, and control-station equipment that fail in materials or workmanship within specified warr...
1. Warranty Period: One years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 SYSTEM REQUIREMENTS
A. Video-signal format shall comply with NTSC standard, composite interlaced video. Composite video-signal termination shall be 75 ohms.
B. Surge Protection: Protect components from voltage surges entering through power, communication, signal, control, or sensing leads. Include surge protection for external wiring of each conductor's entry connection to components.
1. Minimum Protection for Power Connections 120 V and More: Auxiliary panel suppressors complying with requirements in Section 264313 "Surge Protection for Low-Voltage Electrical Power Circuits."
2. Minimum Protection for Communication, Signal, Control, and Low-Voltage Power Connections: Comply with requirements recommended by manufacturer for type of line being protected.
2.2 STANDARD CAMERAS
A. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:
B. Automatic Color Dome Camera: Assembled and tested as a manufactured unit, containing dome assembly, color camera, motorized pan and tilt, zoom lens, and receiver/driver.
1. Pickup Device: CCD interline transfer, 380,000 768(H) by 494(V)pixels.
2. Horizontal Resolution: 480 lines.
3. Signal-to-Noise Ratio: Not less than 50 dB, with camera AGC off.
4. With AGC, manually selectable on or off.
5. White Balance: Auto-tracing white balance, with manually settable fixed balance option.
6. Motion Detector: Built-in digital.
2.3 LENSES
A. Description: Optical-quality coated lens, designed specifically for video-surveillance applications and matched to specified camera. Provide color-corrected lenses.
1. Auto-Iris Lens: Electrically controlled iris with circuit set to maintain a constant video level in varying lighting conditions.
2.4 POWER SUPPLIES
A. Low-voltage power supplies matched for voltage and current requirements of cameras and accessories, and of type as recommended by manufacturer of camera and lens.
1. Enclosure: NEMA 250, Type 4X
2.5 CAMERA-SUPPORTING EQUIPMENT
A. Mounting Brackets for Fixed Cameras: Type matched to items supported and mounting conditions. Include manual pan-and-tilt adjustment.
B. Protective Housings for Fixed and Movable Cameras: Steel or 6061 T6 aluminum enclosures with internal camera mounting and connecting provisions that are matched to camera/lens combination and mounting and installing arrangement of camera to be housed.
1. Camera Viewing Window: Polycarbonate or Lexan window, aligned with camera lens.
2. Duplex Receptacle: Internally mounted.
3. Alignment Provisions: Camera mounting shall provide for field aiming of camera and permit removal and reinstallation of camera lens without disturbing camera alignment.
4. Sun shield shall not interfere with normal airflow around the housing.
5. Mounting bracket and hardware for wall or ceiling mounting of the housing. Bracket shall be of same material as the housing; mounting hardware shall be stainless steel.
6. Finish: Housing and mounting bracket shall be factory finished using manufacturer's standard finishing process suitable for the environment.
2.6 COLOR MONITORS
A. Screen Size (Diagonal Dimension): 14 inch
B. Horizontal Resolution: 300 lines.
C. Minimum Front Panel Devices and Controls: Power switch; power-on indicator; and brightness, contrast, color, and tint controls.
D. Degaussing: Automatic.
E. Mounting: Single, 14-inch vertical, EIA 19-inch (483-mm) electronic equipment rack or cabinet complying with CEA 310-E.
F. Electrical: 120-V ac, 60 Hz.
2.7 DIGITAL VIDEO RECORDERS
A. Basis-of-Design Product: Subject to compliance with requirements, provide Lenel goVision 2.0 or comparable product.
B. Description: Digital, time-lapse type, full-frame and motion recorder, with removable hard drive.
1. Recording Time: 1500 hours minimum.
2. Resolution: 720 by 480 lines, minimum.
3. Programming settings shall be displayed on any video monitor connected to the recorder. Programming shall include the following:
a. Motion analysis graph.
b. Password protection.
c. Alarm and timer controls.
d. Continuous recording option.
e. Time-lapse operating modes.
f. Search video by time, event, or motion.
4. Programming: SmartMedia card for software updating, image archiving, and image transfer to a PC.
5. Storage: 1 TB removable hard drive.
6.
7. Time and Date Generator: Records time (hr:min:sec) and date legend of each frame.
8. Audio Recording: 70 to 7000 Hz. Phono and microphone input; phono output.
9. Mounting: Standard 19-inch (483-mm) rack complying with CEA 310-E, or freestanding desktop.
2.8 CONTROL STATIONS
A. Description: Heavy-duty, freestanding, modular, metal furniture units arranged to house electronic equipment. Coordinate component arrangement and wiring with components and wiring of other systems.
B. Equipment Mounting: Standard 19-inch (483-mm) rack complying with CEA 310-E.
C. Normal System Power Supply: 120 V, 60 Hz, through a locked disconnect device and an isolation transformer in central-station control unit. Central-station control unit shall supply power to all components connected to it unless otherwise indicated.
D. Power Continuity for Control Station: Batteries in power supplies of central-station control units and individual system components shall maintain continuous system operation during outages of both normal and backup ac system supply.
1. Batteries: Rechargeable, valve-regulated, recombinant, sealed, lead-acid type with nominal 10-year life expectancy. Capacity adequate to operate portions of system served including audible trouble signal devices for up to four hours and audible and...
2. Battery Charger: Solid-state, fully automatic, variable-charging-rate type. Charger shall recharge fully discharged battery within 24 hours.

E. Annunciation: Indicate change in system condition and switching of system or component to backup power.

2.9 SIGNAL TRANSMISSION COMPONENTS
A. Cable: Coaxial cable elements have 75-ohm nominal impedance. Comply with requirements in Section 280513 "Conductors and Cables for Electronic Safety and Security."
B. Video Surveillance Coaxial Cable Connectors: BNC type, 75 ohms. Comply with requirements in Section 280513 "Conductors and Cables for Electronic Safety and Security."
PART 3 - EXECUTION
3.1 WIRING
A. Wiring Method: Install cables in raceways unless otherwise indicated.
1. Except raceways are not required in accessible indoor ceiling spaces and attics.
2. Except raceways are not required in hollow gypsum board partitions.
3. Conceal raceways and wiring except in unfinished spaces.
B. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools.
C. Splices, Taps, and Terminations: For power and control wiring, use numbered terminal strips in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures. Tighten electrical connectors and terminals according to manufacturer's pu...
D. For LAN connection and fiber-optic and copper communication wiring, comply with Section 271300 "Communications Backbone Cabling" and Section 271500 "Communications Horizontal Cabling."
E. Grounding: Provide independent-signal circuit grounding recommended in writing by manufacturer.
3.2 VIDEO SURVEILLANCE SYSTEM INSTALLATION
A. Install cameras with 84-inch- minimum clear space below cameras and their mountings. Change type of mounting to achieve required clearance.
B. Set pan-and-tilt unit stops to suit final camera position and to obtain the field of view required for camera. Connect all controls and alarms, and adjust.
C. Avoid ground loops by making ground connections only at the control station.
1. For 12- and 24-V dc cameras, connect the coaxial cable shields only at the monitor end.

D. Identify system components, wiring, cabling, and terminals according to Section 260553 "Identification for Electrical Systems."

3.3 FIELD QUALITY CONTROL
A. Perform tests and inspections.
B. Tests and Inspections:
1. Inspection: Verify that units and controls are properly installed, connected, and labeled, and that interconnecting wires and terminals are identified.
2. Pretesting: Align and adjust system and pretest components, wiring, and functions to verify that they comply with specified requirements. Conduct tests at varying lighting levels, including day and night scenes as applicable. Prepare video-surveill...
a. Verify operation of auto-iris lenses.
b. Set back-focus of fixed focal length lenses. At focus set to infinity, simulate nighttime lighting conditions by using a dark glass filter of a density that produces a clear image. Adjust until image is in focus with and without the filter.
c. Set back-focus of zoom lenses. At focus set to infinity, simulate nighttime lighting conditions by using a dark glass filter of a density that produces a clear image. Additionally, set zoom to full wide angle and aim camera at an object 50 to 75 fe...
d. Set and name all preset positions; consult Owner's personnel.
e. Set sensitivity of motion detection.
f. Connect and verify responses to alarms.
g. Verify operation of control-station equipment.
3. Test Schedule: Schedule tests after pretesting has been successfully completed and system has been in normal functional operation for at least 14 days. Provide a minimum of 10 days' notice of test schedule.
4. Operational Tests: Perform operational system tests to verify that system complies with Specifications. Include all modes of system operation.
C. Video surveillance system will be considered defective if it does not pass tests and inspections.
D. Prepare test and inspection reports.
3.4 DEMONSTRATION
A. Train Owner's maintenance personnel to adjust, operate, and maintain video-surveillance equipment.