Amendment No. 5.pdf
PDF 1 MB Posted
- Attached to
- RECOVERY - Replace 100 Ton Air Conditioning and Cooling Tower at the Mississippi State, MS location
- Solicitation number
- AG-4431-S-10-0002
About this file
Amendment No. 5 Adds DDC Control specifications and drawing to this solicitation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3. EFFECTIVE DA
03118t2010
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
I/MODIFICATION NO.2.
USDA, ARS, Mid South Area Procurement Assistance Offi ce 141 Experiment Station road P. O. Box 225 Stoneville, MS 3 87 7 6 -0225
7. ADMINISTERED BY (f other rhan lrem 6)
Same as Block No. 6
5. PROJECT NO. (If applicable)
ATION NOOR (No.. street, county, Stare and ZIP Codel
11. THIS ITEM
AG-4431-S-r 0-0002
(SEE ITEM ] ])
02101t2010
1OA, IVODIFICATION
(sEE ITEM t 3)
DMENTS OF SOL
X Tneaoovenumberedsolicrtationisamendedassetforthinltem14. ThehouranddatespecifiedforrecejptofOffers X isextended, I ,.notextenoeO
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing ltems 8 and 15, and returning I copies of the amendment; (b) By acknowledging receipt of this amendment on each mpy of the offer submitted: or (c)ByseparateletterortelegramwhichincludesarefEre.ncefothesolicitationandamendmentnumbers. FAILUREoFYoURACKNoWLEDGMENTToBEREcEtvEDATTHE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPEC|F|ED MAy RESULT tN REJECTTON OF YOUR OFFER. tf by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTMCT/ORDER NO. AS DESCRIBED IN ITEM 14.
(r' A. THIS ISSUED PURSUANf f O: (Specify qurhority) IN ITEM 14 ARE MADE IN IN ITEM lOA
B. THE ABOVE NUMBERED CONTMCT/ORDER lS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying olfice, applopriqlion (tate,etc.)
sET FORTH tN |TEM 14, PURSUANT TO THE AUTHORtry OF FAR 43.103(b).
C. THIS SUPPLEI\iIENTAL AGREEMENT lS EN TO AUTHORITY OF
(Spectfy type oJ modrfcation and authorit!)
E. IMPORTANT: Contractor [l is not, X is required to sign this document and return copies to the issuing office
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by LlCF section heddings, including solicitatioirortroit rtiut *tt"*tnuVotml
This amendment extends the bid date and time to March 30, 2010 @ 2:00 p.m. cental time. This amendment includes the new specifications and drawing for the inclusion of DDC Controls. Previously the controls were to be part of another contract but are now made part of this contract. All other terms and conditions remain unchanged.
AS A REMINDER: This solicitation is a 100% set-aside for Service Disabled Veteran Owned Businesses (SDVOB).
SUBMIT BIDS TO:
USDA, ARS, MSA, Procurement Office P. O. Box 225,141 Experiment Station Road Stoneville, MS 38776 Except as provided herein, all terms and conditions of the document referenced in ltem 9A or 1 OA, as heretofore changed, remains unchanged and in full force and effect.
TITLE OF or print) 164. NAME (Iype or print) qulhorized to
PREVIOUS EDITION UNUSABLE
This fom was electrcnlcally produ@d by USDA,/ARS/OCIO/ADB
3 -/{-/o STANDARD FORM 30 (Rev. 'io-83)
Prescribed by GSA FAR (48 CFR) s3.243
TERRY A. KRUTZ
CHILLER REPLACEMENT HARNED, USDA, ARS, STARKVILLE, MS MSU3
SECTION 23 09 23 Page 1
SECTION 23 09 23
DIRECT DIGITAL CONTROL SYSTEMS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced.
The publications are referred to in the text by the basic designation only.
ASME INTERNATIONAL (ASME)
ASME B16.5 (2003) Pipe Flanges and Flanged Fittings
ASME B31.1 (2007; Addenda 2008) Power Piping
ASTM INTERNATIONAL (ASTM)
ASTM A 126 (2004) Gray Iron Castings for Valves, Flanges, and
Pipe Fittings
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41 (2002) Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits
IEEE C62.45 (2002) Surge Testing for Equipment Connected to
Low-Voltage AC Power Circuits
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2007; AMD 1 2008) National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 506 (2000; Rev thru May 2006) Specialty Transformers
UL 916 (2007) Energy Management Equipment
UL 1449 (2006) Transient Voltage Surge Suppressors
1.2 RELATED REQUIREMENTS
Section 23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS, applies to this section, with the additions and modifications specified herein.
SECTION 23 09 23 Page 2
1.3 SUBCONTRACTOR SPECIAL REQUIREMENTS
All contract requirements of this section shall be accomplished directly by a first tier subcontractor. No work required shall be accomplished by a second tier subcontractor.
1.4 DEFINITIONS
1.4.1 Digital Controller
A control module which is microprocessor based, programmable by the user, has integral input/output within the module or on network connected modules, and performs stand-alone operations.
1.4.2 Direct Digital Control (DDC)
Digital controls, as defined in this specification, performing control logic. The controller directly senses building environment and makes control decisions based on user defined, controller resident programs. The controller outputs control signals that directly operate valves, dampers, and motor controllers. No conventional control devices, pneumatic or electronic, such as receiver-controllers, thermostats, and logic units are present within or interface with a direct digital control loop. Actuators are electric, and the controller output is converted to the appropriate type of signal.
1.4.3 DDC System
A system made up of one or more digital controllers. Required climate control and energy management functions for complete operation of an HVAC system are provided by DDC from digital controllers. No conventional control devices (pneumatic or electronic) such as receiver-controllers, thermostats, and logic units are used.
Digital controllers in a system are linked in a communications network composed of one or more levels of local area networks (LAN).
1.4.4 Distributed Control
The intent of distributed control is to install the controllers near their respective controlled equipment. The control system consists of stand-alone controllers, with the total number of input and output points limited to 48 or less per controller. Failure of any single controller will not cause the loss of more then 48 control points.
1.4.5 Dynamic Control
A process that optimizes energy efficiency of HVAC systems (air handling units and chillers) by increasing and decreasing setpoints or starting and stopping equipment in response to heating and cooling needs of the facility. A requirement of dynamic
SECTION 23 09 23 Page 3 control is knowing the heating/cooling demand status of the process. Therefore dynamic control requires controllers connected in a communications network.
1.4.6 Firmware
Firmware is software programmed into read only memory (ROM) and erasable programmable read only memory (EPROM) chips. Software may not be changed without physically altering the chip.
1.4.7 Input/Output (I/O) Points
I/O points refer to analog inputs (AI), digital inputs (DI), analog outputs (AO), and digital outputs (DO) in a digital controller. Another term for digital inputs and outputs is binary inputs and outputs. Inputs are from analog sensors (temperature, pressure, humidity, flow) and digital sensors (motor status, flow switches, switch position, and pulse output devices). Outputs operate modulating and on/off control devices.
1.4.8 I/O Expansion Unit
An I/O expansion unit provides additional point capacity to a digital controller and communicates with the stand-alone digital controller on a LAN. An I/O unit is not stand-alone because the control program does not reside in the I/O unit. An I/O expander which connects directly to a stand alone controller through a multi-line microprocessor bus is restricted to reside within 3 feet of the stand alone controller and is considered part of the stand alone controller.
1.4.9 Microprocessor
A microprocessor refers to the central processing unit (CPU) that contains all registers and logic circuitry that allow digital controllers to function.
1.4.10 Output Signal Conversion
Output signal conversion refers to changing one kind of control output into a proportionally related signal appropriate for direct actuation of the controlled device.
An example is converting a 4 to 20 mA or 0 to 10 VDC signal to a proportional 3 to 15 psig signal to operate a pneumatic actuator.
1.4.11 Optimum Start
Optimum start is a method of starting HVAC equipment prior to scheduled occupancy in order to have the building at setpoint when occupied. Optimum start is based on the zone temperatures, zone setpoints, and outdoor temperature.
1.4.12 Peer-to-Peer
SECTION 23 09 23 Page 4
Peer-to-peer refers to controllers connected on a communications LAN that act independently, as equals, and communicate with each other to pass information.
1.4.13 PID
PID refers to proportional, integral, and derivative control; the three types of action that are used in controlling modulating equipment.
1.4.14 Resolution
Refers to the number of possible states an input value or output value can take and is a function of the digital controller I/O circuitry; the A/D converter for input and the D/A converter for output. Ten bit resolution has 1024 possible states.
1.4.15 Stand-Alone Control
Refers to the digital controller performing required climate control, and energy management functions without connection to another digital controller or computer.
Requirements for stand-alone control are a time clock, a microprocessor, resident control programs, PID control, and I/O. All stand-alone controllers have a communication port and firmware for direct connection and interrogation with a laptop computer or similar hand-held device. This interrogation includes parameter changes and program downloads.
1.4.16 Terminal Control Unit (TCU)
An off-the-shelf, stand-alone digital controller equipped for communication on a lower level LAN. TCUs may deviate from stand-alone only in receiving energy management and time information from a stand alone digital controller. A TCU is commonly application specific and is used for distributed control of specific HVAC subsystems.
A TCU communicates with other digital controllers. Typically, a TCU communicates on a lower level LAN. Examples where TCUs are used include small air handling units (AHUs), variable air volume (VAV) boxes, fan coil units, and heat pumps.
1.5 DDC SYSTEM DESCRIPTION
a. Provide new DDC systems including associated equipment and accessories. Manufacturer's products, including design, materials, fabrication, assembly, erection, examination, inspection, and testing shall be in accordance with ASME B31.1 and NFPA 70, except as modified herein or indicated otherwise.
b. Provide the DDC systems to maintain stable temperature control and all other conditions as indicated. The end-to-end accuracy of the system, including temperature sensor error, wiring error, A/D conversion, and display, shall be 1 degree F or less.
SECTION 23 09 23 Page 5
1.5.1 Design Requirements
1.5.1.1 Control System Schematic
Provide control system schematic that includes the following:
a. Location of each input and output device
b. Flow diagram of each HVAC component, for instance flow through coils, fans, dampers
c. Name or symbol for each component such as V-1, DM-2, and T-1 for a valve, damper motor, and temperature sensor, respectively
d. Setpoints
e. Sensor range
f. Actuator range
g. Valve and damper schedules and normal position
h. Switch points on input switches
i. Written sequence of operation for each schematic
j. Schedule identifying each sensor and controlled device with the following information:
(1) LAN and Software point name with send and receive address if applicable
(2) Point type (AO, AI, DO, DI)
(3) Point range
(4) Digital controller number for each point
1.5.1.2 Electrical Equipment Ladder Diagrams
Submit diagrams showing electrical equipment interlocks, including voltages and currents.
1.5.1.3 Component Wiring Diagrams
Submit a wiring diagram for each type of input device and each type of output device.
Diagram shall show how the device is wired and powered; showing typical
SECTION 23 09 23 Page 6 connections at the digital controller and each power supply, as well as at the device itself. Show for all field connected devices, including, but not limited to, control relays, motor starters, electric or electronic actuators, and temperature, pressure, flow, proof, and transmitters.
1.5.1.4 Terminal Strip Diagrams
Submit a diagram of each terminal strip, including digital controller terminal strips, terminal strip location, termination numbers and associated point names.
1.5.1.5 Communication Architecture Schematic
Submit a schematic showing communication networks used for all DDC system controllers and field interface devices.
1.6 SUBMITTALS
The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
List of Drawings
List of Symbols and Abbreviations Used on Drawings
List of I/O Points
Equipment Components List
AC Power Table
SD-02 Shop Drawings
Control system schematic
Ladder diagrams
Component wiring diagrams
Terminal strip diagrams
Communication architecture schematic
SD-03 Product Data
DDC hardware
SECTION 23 09 23 Page 7
DDC capabilities
Input devices
Output devices
Surge and Transient Protection
Smoke detectors
SD-06 Test Reports
Field Tests
Performance Verification Tests
SD-07 Certificates
Contractors Qualifications
Training
SD-10 Operation and Maintenance Data
Controls and HVAC System Operators Manual
DDC Manufacturer's Hardware and Software Manuals
SD-11 Closeout Submittals
Training Course Documentation
Service organizations
Contractor certification
1.7 OPERATING ENVIRONMENT
Protect components from humidity and temperature variations, dust, and other contaminants, within limits published by the manufacturer.
1.8 QUALITY ASSURANCE
1.8.1 Standard Products
SECTION 23 09 23 Page 8
a. Material and equipment shall be standard products of manufacturer regularly engaged in the manufacturing of such product, using similar materials, design and workmanship. The standard products shall have been in commercial or industrial use for 2 years prior to bid opening. The 2-year use shall include applications of similarly sized equipment and materials used under similar circumstances and sold on the commercial market through advertisements, manufacturers' catalogs, or brochures.
b. Products are supported by a local service organization.
1.8.1.1 DDC Hardware
a. I/O type and characteristics
b. Resident programs
c. Communications ports
d. Protected memory
e. Operating temperature limits
1.8.1.2 DDC Capabilities
a. Communications; baud rates, communication ports, hierarchy
b. Trending capabilities
c. Alarming capabilities; capable of alarm generation as defined in this specification
d. Messaging capabilities
e. Self diagnostic capabilities
f. PID control capabilities
1.8.1.3 Input Devices
a. Transmitters
b. Temperature sensors
c. Flow or motor proof
d. Sensor wells
SECTION 23 09 23 Page 9
1.8.1.4 Output Devices
a. Dampers
b. Valves
c. Actuators
d. Control relays
1.8.1.5 Surge and Transient Protection
a. Power line
b. Communications lines
c. Controller I/O
1.8.2 Nameplates and Tags
a. Nameplates and tags bearing device unique identifiers shall be engraved or stamped. Permanently attach nameplates to HVAC control panel doors and back plates.
b. For each field mounted piece of equipment attach a plastic or metal tag with equipment name and point identifier.
1.8.3 Verification of Dimensions
The contractor shall verify all dimensions in the field, and shall advise the Contracting Officer of any discrepancy before performing work.
1.8.4 Drawings
Because of the small scale of the drawings, it is not possible to indicate all offsets, fittings, and accessories that may be required. The Contractor shall carefully investigate the mechanical, electrical, and finish conditions that could affect the work, and shall furnish all work necessary to meet such conditions.
1.8.4.1 List of Drawings
Provide a list of drawings.
1.8.4.2 List of Symbols and Abbreviations Used on Drawings
Provide an index of symbols and abbreviations used on the drawings.
SECTION 23 09 23 Page 10
1.8.4.3 List of I/O Points
For each input and output physically connected to a digital controller provide, on a controller by controller basis, provide the following:
a. Point description: for example: mixed air temperature, supply fan start/stop, etc.
b. Point type: AO, AI, DO, or DI.
c. Point range
d. Sensor range associated with point range:
e. Software name(s) associated with point, if any.
f. Point connection terminal number
1.8.4.4 Equipment Components List
Submit a listing of controllers and connected devices shown on control system schematic. List the following:
a. Control system schematic name
b. Description
c. Manufacturer of controller
d. Controller's name
e. Equipment part numbers
f. Cv for valves
g. For actuators:
(1) Motive force (such as pneumatic, or electric)
(2) Normal position
(3) Nominal operating range (such as 3 to 7 psi, 4 to 8 mA)
1.8.4.5 AC Power Table
Submit a table listing each controller and the circuit breaker number, panel box number, and physical location of each controller's source of AC power.
SECTION 23 09 23 Page 11
1.8.5 Contractors Qualifications
a. The Contractor or subcontractor performing the work shall have completed at least three DDC systems installations of a similar design and have successfully operated a similar sequence of operation for at least three years.
1.8.6 Training Course Documentation
Training course documentation including a manual for each trainee plus two additional copies and one copy of audiovisual training aids, if used. Documentation shall include an agenda, defined objectives for each lesson and detailed description of the subject matter of each lesson.
1.8.7 Service Organizations
Qualified service organization list including the names and telephone numbers of organizations qualified to service the HVAC control systems.
1.8.8 Contractor Certification
Provide certification that installation of the control system is complete and meets the technical requirements of this section.
1.8.9 Controls and HVAC System Operators Manual
Provide two copies of a Control and HVAC Systems Operators Manual. Provide in a 3 ring binder with a minimum of the following 7 sections. Use tabs to divide each section.
a. Description of HVAC Systems: Provide a description of the HVAC system components and control system. Include sequence of operation and a complete points list.
b. Controls Drawings: Provide drawings as specified in submittal paragraph.
c. Control Program Listings: Provide listing of all control programs, including terminal equipment controller setup pages if used.
d. Current Operating Parameters: Provide printouts of input and output setup information, (database setups). This section provides information such as point addresses, slopes and offsets for all points, database of points, etc.
e. Design Information: Include relevant design data and calculations.
SECTION 23 09 23 Page 12
f. Control Equipment Technical Data Sheets: Provide technical data sheets for all controller hardware and accessories.
g. Backup of Control Program: Provide backup copies of the control program and ACAD control drawings on CD-ROM.
1.8.10 DDC Manufacturer's Hardware and Software Manuals
Provide the following manuals.
a. Installation and Technical Manuals for all digital controller hardware.
b. Installation and Technical Manuals for workstation.
c. Operator Manuals for all digital controllers.
d. Operator Manuals for all workstation software.
e. Programming Manuals for all digital controllers.
1.8.11 Modification of References
The advisory provision in ASME B31.1 and NFPA 70 are mandatory. Substitute the word "shall" for "should" wherever it appears and interpret all references to the "authority having jurisdiction" and "owner" to mean the Contracting Officer.
PART 2 PRODUCTS
2.1 DDC SYSTEM
a. Provide a DDC system as a distributed control system. The system shall have stand-alone digital controllers only.
b. Provide an operator programmable system to perform closed-loop, modulating control of building equipment.
c. Provide the quantity of digital controllers to perform required climate control, energy management, and alarm functions. All material used shall be currently in production.
2.1.1 Direct Digital Controllers
DDC hardware shall be UL 916 rated.
2.1.1.1 Distributed Control
SECTION 23 09 23 Page 13
Apply digital controllers in a distributed control manner.
2.1.1.2 I/O Point Limitation
Total number of I/O hardware points, including those communicated over a LAN, used by a single stand-alone digital controller, including I/O expansion units shall not exceed 48.
2.1.1.3 Environmental Operating Limits
Provide digital controllers that operate in environmental conditions between 32 and 120 degrees F.
2.1.1.4 Stand-Alone Control
Provide stand-alone digital controllers.
2.1.1.5 Internal Clock
Provide a clock with each stand-alone controller. Each controller shall have its clock backed up by a battery or capacitor with sufficient capacity to maintain clock operation for a minimum of 72 hours during power outage.
2.1.1.6 Memory
a. Provide sufficient memory for each controller to support required control, communication, trends, alarms, and messages
b. Memory Protection: Programs residing in memory shall be protected either by using EEPROM, flash memory, or by an uninterruptible power source (battery or uninterruptible power supply (UPS)). The backup power source shall have sufficient capacity to maintain volatile memory during an AC power failure. Where the uninterruptible power source is rechargeable (a rechargeable battery), provide sufficient back-up capacity for a minimum of seventy-two hours. The rechargeable power source shall be constantly charged while the controller is operating under normal line power. Where a non-rechargeable power source is used, provide sufficient capacity for a minimum of two years accumulated power failure. Batteries shall be replaceable without soldering.
2.1.1.7 Inputs
Provide input function integral to the direct digital controller. Provide input type(s) as required by the DDC design. For each type of input used on high-level controllers, provide at least one similar spare input point per controller.
SECTION 23 09 23 Page 14
a. Analog Inputs: Allowable input types are 100 ohm (or higher) platinum RTDs, thermistors, 4 to 20 mA, and 0-10 VDC. Thermistor and direct RTD inputs must have appropriate conversion curves stored in controller software or firmware. Analog to digital (A/D) conversion shall have 10-bit minimum resolution.
b. Digital Inputs: Digital inputs shall sense open/close, on/off, or other two state indications.
2.1.1.8 Outputs
Provide output function integral to the direct digital controller. Provide output type(s) as required by the DDC design. For each type of output used on high-level controllers, provide at least one similar spare output point per controller.
a. Analog Outputs: Provide controllers with 10 bit minimum output resolution. Output shall be 4 to 20 mA, 0 to 10 VDC, or 0 to 20 psig. Each pneumatic output shall have feedback for monitoring of the actual pneumatic signal.
b. Digital Outputs: Provide contacts rated at a minimum of 1 ampere at 24 volts.
2.1.1.9 PID Control
Provide controllers with proportional integral, and derivative control capability.
Terminal controllers (TCV) are not required to have the derivative component.
2.1.1.10 Digital Controller Networking Capabilities
The upper level digital controllers shall be capable of networking with other similar upper level controllers. Upper level controllers shall also be capable of communicating over a network between buildings.
2.1.1.11 Communications Ports
a. Controller-to-Controller LAN Communications Ports: Controllers in the building DDC system shall be connected in a communications network.
Controllers shall have controller to controller communication ports to both peer controllers (upper level controllers) and terminal controllers (lower level controllers). Network may consist of more than one level of local area network and one level may have multiple drops. Communications network shall permit sharing information between controllers, allowing execution of dynamic control strategies, and coordinated response to alarm conditions.
Minimum baud rate for the lowest level LAN is 9600 Baud. Minimum baud rate for the highest level LAN shall be 9600 Baud. Minimum baud rate for a DDC system consisting of a single LAN is 9600 Baud.
SECTION 23 09 23 Page 15
b. On-Site Interface Ports: Provide a RS-232, RS-485, or RJ-11 communications port for each digital controller that allows direct connection of a computer or hand held terminal and through which the controller may be fully accessed. Controller access shall not be limited to access through another controller. On-site interface communication ports shall be in addition to the communications port(s) supporting controller to controller communications. Communication rate is 9600 Baud minimum. Every controller on the highest level LAN shall have a communications port supporting direct connection of a computer; a hand held terminal port is not sufficient. By connecting a computer to this port, every controller in the direct digital control system shall be accessible and programmable.. The following operations shall be available: downloading and uploading control programs, modifying programs and program data base, and retrieving or accepting trend reports, status reports, messages, and alarms.
c. Remote Work Station Interface Port: Provide one additional direct connect computer port in each DDC system for permanent connection of a remote operator's work station, unless the workstation is a node on the LAN.
All operations possible by directly connecting a computer to a controller at the highest level LAN shall be available through this port.
d. Telecommunications Interface Port: Provide one additional telecommunications port in each DDC system permitting remote communications via telephone. All operations possible by directly connecting a computer to a controller at the highest level LAN shall be available through the telecommunications port. A telecommunications port provided on a digital controller shall be in addition to the port required for directly connecting a computer to the controller. Telecommunication baud rate is 28000 minimum.
2.1.1.12 Digital Controller Cabinet
Each indoor digital controller cabinet shall protect the controller from dust and rated NEMA 1, unless specified otherwise. Each outdoor digital controller cabinet shall protect the controller from all outside conditions and rated NEMA 4. Cabinets for high level controllers shall be hinged door, lockable, and have offset removable metal back plate.
2.1.1.13 Main Power Switch
Each controller on the highest level LAN or each control cabinet shall have a main external power switch for isolation of the controller from AC power. The switch shall be located in the DDC cabinet.
2.1.2 Terminal Control Units
SECTION 23 09 23 Page 16
a. The same company as the digital controllers shall manufacture TCUs.
b. TCUs shall automatically start-up on return of power after a failure, and previous operating parameters shall exist or shall be automatically downloaded from a digital controller on a higher level LAN.
c. TCUs do not require an internal clock if they get time information from a higher level digital controller.
2.1.3 DDC Software
2.1.3.1 Sequence of Control
Provide, in the digital controllers, software to execute the sequence of control. Provide one registered copy of all software used to program control sequences in all direct digital controllers. Provide any access keys which restrict programming language software functions or the ability to compile or prepare programming for download to controllers. Provide final copy of each program used in the system in both compiled and editable formats. Where specially programmed factory configured smart controllers are used in the system, provide minimum factory programming tools and specialized controller programs ready for download to replacement controllers. At minimum, controllers must be capable of performing programming functions outlined in the following "Parameter Modification" section.
2.1.3.2 Parameter Modification
Provide software to modify control parameters. Parameter modification for all controllers (high level and low level application specific) is through the main workstation computer. Modifications accomplished without having to make changes directly in line-by-line programming. When the control program is of the line-by-line type, database parameters in the following list that take real number values require assignment of variable names so parameters can be changed without modifying programming. Alternatively, block programming languages shall provide for modification of these database parameters in fill-in-the-blank screens. Parameters of like type, including those in different high level and low level controllers, may be grouped together for a single, global change. For example, an operator may group all second floor space temperature setpoints into a group and raise the setpoint by two degrees with a single command. The following parameters shall be modifiable in this way:
a. Setpoints
b. Dead band limits and spans
c. Reset schedules
d. Switch over points
SECTION 23 09 23 Page 17
e. PID gains and time between control output changes
f. Time
g. Timed local override time
h. Occupancy schedules
i. Holidays
j. Alarm points, alarm limits, and alarm messages
k. Point definition database
l. Point enable, disable, and override
m. Trend points, trend intervals, trend reports
n. Analog input default values
o. Passwords
p. Communications parameters including network and telephone communications setups
2.1.3.3 Differential
Where setpoint is in response to some analog input such as temperature, pressure, or humidity, include a setpoint differential to prevent short cycling of control devices.
2.1.3.4 Motor and Flow Status Delay
Provide an adjustable delay between when a motor is commanded on or off and when the control program looks to the motor or flow status input for confirmation of successful command execution.
2.1.3.5 Run time Accumulation
Provide resettable run time accumulation for each controlled digital output.
2.1.3.6 Timed Local Override
Provide user definable adjustable run time for each push of a momentary contact timed local override. Pushes shall be cumulative with each push designating the same length of time. Provide a user definable limit on the number of contact closures
SECTION 23 09 23 Page 18 summed, such as 6, before the contact closures are ignored. Timed local overrides are disabled during occupancy periods.
2.1.3.7 Time Programs
Provide programs to automatically adjust for leap years, daylight savings time, and operator time adjustments.
2.1.3.8 Scheduling
a. Individual controlled equipment shall be schedulable with schedule based on time of day, day of week, and day of year. Equipment may be associated into groups. Each group may be associated with a different schedule.
Changing the schedule of a group shall change the schedule of all equipment in the group. Groups may be modified, created and deleted by the operator.
b. Provide capability to view and modify schedules in a seven-day week format. When control program does not automatically compute holidays, provide capability to enter holiday schedules one full year at a time.
2.1.3.9 Point Override
I/O and virtual points shall accept software overrides to any possible value.
2.1.3.10 Alarming
I/O points and software points shall be alarmable. Alarms may be enabled and disabled for every point. Alarm limits shall be adjustable on analog points.
Controllers connected to an external communications device such as a printer, terminal, or computer, shall download alarm and alarm message when alarm occurs.
The following conditions shall generate alarms:
a. Motor is commanded on or off but motor status input indicates no change
b. Temperature, humidity, or pressure strays outside selectable limits
c. An analog input takes a value indicating sensor failure
d. A module is not communicating on the LAN
e. A power outage occurs
2.1.3.11 Status Display
Current status of I/O and virtual points shall be displayed on command.
SECTION 23 09 23 Page 19
2.1.3.12 Diagnostics
Each controller shall perform self-diagnostic routines and provide messages to an operator when errors are detected. The DDC system shall be capable of recognizing a non-responsive module on a LAN. The remaining, responsive modules on a LAN shall not operate in a degraded mode.
2.1.3.13 Power Loss
During a power outage, each controller shall assume a disabled status and outputs shall go to a user definable state. Upon restoration of power, DDC system shall perform an orderly restart, with sequencing of outputs.
2.1.3.14 Program Transfer
Provide software for download of control programs and database from a computer to controllers and upload of same to computer from controllers. Every digital controller in the DDC system shall be capable of being downloaded and uploaded to through a single controller on the highest level LAN.
2.1.3.15 Password Protection
Provide at least three levels of password protection to the DDC system permitting different levels of access to the system. The lowest level allows monitoring only. The highest level allows full control of all functions, including setting new passwords.
2.2 SENSORS AND INPUT HARDWARE
2.2.1 Field Installed Temperature Sensors
2.2.1.1 Thermistors
Precision thermistors may be used in temperature sensing applications below 200 degrees F. Sensor accuracy over the application range shall be 0.36 degree F or less between the range of 32 to 150 degrees F. Stability error of the thermistor over five years shall not exceed 0.25 degree F cumulative. Sensor element and leads shall be encapsulated. Bead thermistors are not allowed. A/D conversion resolution error shall be kept to 0.1 degree F. Total error for a thermistor circuit shall not exceed 0.5 degree F, which includes sensor error and digital controller A/D conversion resolution error. Provide 18 gage twisted and shielded cable for thermistors.
2.2.1.2 Resistance Temperature Detectors (RTDs)
Provide RTD sensors with 1000 ohm, or higher, platinum elements that are compatible with the digital controllers. Sensors shall be encapsulated in epoxy, series 300 stainless steel, anodized aluminum, or copper. Temperature sensor accuracy shall be 0.1 percent (1 ohm) of expected ohms (1000 ohms) at 32 degrees F.
SECTION 23 09 23 Page 20
Temperature sensor stability error over five years shall not exceed 0.25 degree F cumulative. Direct connection of RTDs to digital controllers, without transmitters, is preferred provided controller supports direct connection of RTDs. When RTDs are connected directly to the controller, keep lead resistance error to 0.25 degree F or less. Total error for a RTD circuit shall not exceed 0.5 degree F, which includes sensor error, lead resistance error or 4 to 20 mA or 0 to 10 VDC transmitter error, and A/D conversion resolution error.
2.2.1.3 Temperature Sensor Details
a. Room Type: Conceal element behind protective cover matched to the room interior. Room temperature sensors connected directly to application specific controllers shall have integral pushbutton, system override digital input button, and a setpoint adjustment lever. Provide a connection to allow interrogation of the digital controller.
b. Duct Averaging Type: Continuous averaging RTDs for ductwork applications shall be one foot in length for each 4 square feet of ductwork cross-sectional area with a minimum length of 6 feet. Probe type duct sensors of one foot length minimum are acceptable in ducts 12 feet square and less.
c. Immersion Type: Three inches total immersion for use with sensor wells, unless otherwise indicated.
d. Sensor Wells: Stainless steel material. Provide heat-sensitive transfer agent between exterior sensor surface and interior well surface.
e. Outside Air Type: Provide element on the buildings north side with sunshade to minimize solar effects. Mount element at least 3 inches from building outside wall. Sunshade shall not inhibit the flow of ambient air across the sensing element. Shade shall protect sensing element from snow, ice, and rain.
2.2.2 Transmitters
Transmitters shall have 4 to 20 mA or 0 to 10 VDC output linearly scaled to the temperature, pressure, humidity, or flow range sensed. Transmitter shall be matched to the sensor, factory calibrated, and sealed. Total error shall not exceed 0.1 percent at any point across the measured span. Supply voltage shall be 24 volts AC or DC.
Transmitters shall have non-interactive offset and span adjustments. For temperature sensing, transmitter stability shall not exceed 0.05 degrees C a year.
2.2.2.1 Spans and Ranges
Transmitter spans or ranges shall meet the following:
SECTION 23 09 23 Page 21
a. Temperature:
(1) 50 degrees F span: Room, chilled water, cooling coil discharge air, return air sensors
(2) 100 degrees F span: Outside air, hot water, heating coil discharge air, mixed air sensors
(3) 200 degrees F span: High temperature hot water, heating hot water, chilled/hot water system sensors.
b. Relative Humidity:
(1) 10 to 90 percent minimum relative humidity range
2.2.3 Relative Humidity Transmitters
Provide integral humidity transducer and transmitter. Output of relative humidity instrument shall be a 4 to 20 mA or 0 to 10 VDC signal proportional to full range of relative humidity input. Accuracy shall be 2 percent of full scale, long-term stability shall be less than one percent drift per year. Sensing element shall be polymer type.
2.2.4 Current Transducers
Provide current transducers to monitor amperage of motors. Select current transducer for normal measured amperage to be near 50 percent of full-scale range.
Current transducers shall have an accuracy of one percent and 4 to 20 mA or 0 to 10 VDC output signal.
2.2.5 Input Switches
2.2.5.1 Timed Local Override
Provide momentary contact push button override with override time set in controller software. Provide to override DDC time of day program and activate occupancy program for assigned units. Upon expiration of override time, the control system shall return to time-of-day program. Time interval for the length of operation shall be software adjustable and shall expire unless reset.
2.2.5.2 Hand-Off-Auto Switch
Provide hand-off-auto switch with name plate to manually switch between off, DDC (auto) and manual (hand) control. Size and wire hand-off-auto switch to switch control (120 VAC or less), not line, circuitry. Wire all safety controls to protect circuit and equipment during both hand and auto operation.
SECTION 23 09 23 Page 22
2.2.5.3 Insertion Freeze Protection Switch
Electric switch shall be capillary type. Provide special purpose insertion thermostats with flexible elements a minimum of 20 feet in length for coil face areas up to 40 square feet. Switch contacts shall be rated for motor starter circuit voltage being interrupted. Switch shall be equipped with auxiliary set of contacts for input of switch status to digital controller. Provide additional elements or longer elements for larger coils at the rate of 1-foot of element per 4 square feet of coil. Serpentine capillaries perpendicular to the air flow to uniformly sense the entire airflow. A freezing condition at 18-inch increments along the sensing element shall activate the thermostatic switch. Switch shall require manual reset after activation.
2.3 OUTPUT HARDWARE
2.3.1 Valves
2.3.1.1 Valve Assembly
Valves shall have stainless steel stems. Valves shall be ANSI Class 125 or ANSI Class 150, as required by the following pressure-temperature design criteria: 150 percent of the system operating pressure at the system operating temperature. Valve leakage rating shall be 0.01 percent of rated Cv. Class 125 copper alloy valve bodies and Class 150 steel or stainless steel valves shall conform to ASME B16.5 as a minimum. Cast iron valve components shall conform to ASTM A 126 Class B or C as a minimum.
2.3.1.2 Butterfly Valve Assembly
Butterfly valves shall be threaded lug type suitable for dead-end service and for modulation to the fully closed position, with noncorrosive discs, stainless steel shafts supported by bearing, and EPDM seats suitable for temperatures from minus 20 degrees F to plus 250 degrees F. Valves shall have a manual means of operation independent of the actuator.
2.3.1.3 Three-Way Valves
Three-way valves shall have equal percentage characteristics.
2.3.1.4 Valves for Hot Water Service
Valves for hot water service below 250 Degrees F:
a. Bodies for valves larger than 2 inches shall have flanged-end connections. Water valves shall be sized for a 3 psi differential through the valve at rated flow, except as indicated otherwise. Select valve flow coefficient (Cv) for an actual pressure drop not less than 50 percent or greater than 125 percent of the design pressure drop at design flow.
SECTION 23 09 23 Page 23
b. Internal trim, including seats, seat rings, modulation plugs, and springs, of valves controlling water hotter than 210 degrees F shall be Type 316 stainless steel.
c. Internal trim for valves controlling water 210 degrees F or less shall be brass or bronze.
d. Non-metallic parts of hot water control valves shall be suitable for a minimum continuous operating temperature of 250 degrees F or 50 degrees F above the system design temperature, whichever is higher.
e. Valves 4 inches and larger shall be butterfly valves.
2.3.2 Actuators
2.3.2.1 Electric Actuators
Provide direct drive electric actuators for all control applications, except where indicated otherwise. When operated at rated voltage, each actuator shall be capable of delivering torque required for continuous uniform motion and shall have end switch to limit travel, or shall withstand continuous stalling without damage. Actuators shall function properly with range of 85 to 110 percent of line voltage.
Provide gears manufactured from steel, copper alloy, fiber, or reinforced nylon.
Provide hardened steel running shafts in sleeve bearing of copper alloy, hardened steel, nylon, or ball bearing. Provide two-position actuators of the single direction, spring return, or reversing type. Provide proportioning actuators capable of stopping at all points in the cycle and starting in either direction, from any point.
Provide reversing and proportioning actuators with limit switches to limit travel in either direction unless operator is stall type. Actuators shall have a simple switch for reversing direction, and a button to disengage clutch for manual adjustments. Provide reversible shaded pole, split capacitor, synchronous, or steper type electric motors.
2.3.3 Output Switches
2.3.3.1 Control Relays
Shall be double pole, double throw (DPDT), UL listed, with contacts rated to the application, indicator light, and dust proof enclosure. Light indicator is lit when coil is energized and is off when coil is not energized. Relays shall be socket type, plug into a fixed base, and replaceable without need of tools or removing wiring. Encapsulated "PAM" type relays are permissible for terminal control applications.
2.3.3.2 Solenoid Air Valves
SECTION 23 09 23 Page 24
Each valve shall have three port operation: common, normally open, and normally closed. Internal parts shall be brass, bronze, or stainless steel. Valves shall be rated at 50 psig minimum when used in a control system operating at 25 psig or less, or 150 psig when used in a control system operating in the range 25 to 100 psig.
2.4 ELECTRICAL POWER AND DISTRIBUTION
For controller power provide a new, dedicated 120 VAC 60 Hz source, three wire (black, white, and green). Run green ground wire to panel ground; conduit grounds are not sufficient.
2.4.1 Transformers
Transformers shall conform to UL 506. Power digital controllers and terminal control units (TCU's) from dedicated circuit breakers with surge protection specified.
Transformers for digital controllers serving terminal equipment on lower level LANs may be grouped to have specified surge protection sized for the number of controllers on a single transformer. Provide a fuse on the transformer secondary side.
2.4.2 Surge Protection
Surge and transient protection consist of devices installed externally to digital controllers.
2.4.2.1 Power Line Surge Protection
Surge suppressors external to digital controller, shall be installed on all incoming AC power. Surge suppressor shall be rated by UL 1449, have a fault indicating light, and have clamping voltage ratings below the following levels:
a. Unit is a transient voltage surge suppressor 120 VAC/1 phase/2 wire plus ground, hard wire individual equipment protector.
b. Unit must react within 5 nanoseconds and automatically reset.
c. Voltage protection threshold, line to neutral, starts at no more than 211 volts peak on the 120 VAC line.
d. The transient voltage surge suppressor must have an independent secondary stage equal to or greater than the primary stage joule rating.
e. The primary suppression system components must be pure Silicon Avalanche Diodes.
f. Silicon Avalanche Diodes or Metal Oxide Varistors are acceptable in the independent secondary suppression system.
SECTION 23 09 23 Page 25
g. The Transient Suppression System shall incorporate an indication light which denotes whether the primary and/or secondary transient protection components is/are functioning.
h. All system functions of the Transient Suppression System must be individually fused and not short circuit the AC power line at any time.
i. The Transient Suppression System shall incorporate an EMI/RFI noise filter with a minimum attenuation of 13 dB at 10 kHz to 300 MHz.
j. The system must comply with IEEE C62.41, Class "B" requirements and be tested according to IEEE C62.45.
k. The system shall operate at -20 degrees C to +50 degrees C.
2.4.2.2 Controller Input/Output Protection
Controller input/output points shall surge protection with optical isolation, metal oxide varistors (MOV), or silicon avalanche devices. Fuses are not permitted for surge protection.
2.4.3 Wiring
Provide complete electric wiring for DDC System, including wiring to transformer primaries. Control circuit wiring shall not run in the same conduit as power wiring over 100 volts. Circuits operating at more than 100 Volts shall be in accordance with NFPA 70. Circuits operating at 100 Volts or less shall be defined as low voltage and shall be run in rigid or flexible conduit, metallic tubing, metal raceways or wire trays, or armored cable. Provide circuit and wiring protection as required by NFPA 70.
Aluminum-sheathed cable or aluminum conduit may be used but shall not be buried in concrete. Use conduit or plenum-rated cable in HVAC plenums. HVAC plenums include the space between a drop ceiling and the architectural ceiling, within walls, and within ductwork. Protect exposed wiring from abuse and damage.
2.4.3.1 AC Control Wiring
a. Control wiring for 24 V circuits shall be insulated copper 18 AWG minimum and rated for 300 VAC service.
b. Wiring for 120 V shall be 14 AWG minimum and rated for 600 V service.
2.4.3.2 Analog Signal Wiring
Analog signal wiring shall be 18 AWG single or multiple twisted pair. Each cable shall be 100 percent shielded, and have 20 AWG drain wire. Each wire shall have insulation rated to 300 V AC. Cables shall have an overall aluminum-polyester or
SECTION 23 09 23 Page 26 tinned-copper (cable-shield tape). Install analog signal wiring in conduit separate from AC power circuits.
2.5 INDICATORS
2.5.1 Thermometers
Provide bi-metal thermometers in locations as indicated. Bi-metal thermometers shall have either 9 inch scales or 3.5 inch dials and shall have insertion, immersion or averaging elements as indicated. Provide thermowells for liquid sensing applications.
Select thermometer ranges so normal temperatures are approximately equal to midpoint readings on the scale.
PART 3 EXECUTION
3.1 INSTALLATION
Perform installation under supervision of competent technicians regularly employed in the installation of DDC systems.
3.1.1 Wiring Criteria
a. Input/output identification: Permanently label each field wire, cable, or pneumatic tube at each end with unique descriptive identification.
b. Rigid or flexible conduit shall be terminated at all sensors, panels, troughs, and output devices.
c. Surge Protection: Install surge protection per manufacturer's specification.
d. Grounding: Ground controllers and cabinets to a good earth ground.
Ground controller to a ground. Conduit grounding alone is not sufficient; all grounding must have a direct path to building earth ground. Ground sensor drain wire shields at controller end.
e. Contractor is responsible for correcting all associated ground loop problems.
f. Wiring in panel enclosures shall run in covered wire track.
3.1.2 Digital Controllers
Do not divide control of a single mechanical system such as an air handling unit, boiler, chiller, or terminal equipment between two or more controllers. A single controller shall manage control functions for a single mechanical system. It is
SECTION 23 09 23 Page 27 permissible, however, to manage more than one mechanical system with a single controller.
3.1.3 Temperature Sensors
Provide temperature sensors in locations to sense the appropriate condition. Provide sensor where they are easy to access and service without special tools. Calibrate sensors to accuracy specified. In no case will sensors designed for one application be installed for another application.
3.1.3.1 Immersion Temperature Sensors
Provide thermowells for sensors measuring temperatures in liquid applications or pressure vessels. Locate wells to sense continuous flow conditions. Do not install wells using extension couplings. Where piping diameters are smaller than the length of the wells, provide wells in piping at elbows to sense flow across entire area of well.
Wells shall not restrict flow area to less than 70 percent of pipe area.