AG-32KW-S-11-0255 Attachment B.doc

DOC document 232 KB Posted

Attached to
IDIQ - Facility Condition Assessment/Re-Assessments Federal contract opportunity
Solicitation number
AG-32KW-S-11-0255
Issued by
Department of Agriculture Animal and Plant Health Inspection Service Headquarters Headquarters Administrative Service Headquarterss Division

About this file

Green Assessment Checklist

View the file

Other files for this federal contract opportunity

Other files attached to IDIQ - Facility Condition Assessment/Re-Assessments, newest first.
File Type Posted
AG-32KW-S-11-0255 IDIQ Questions.docx DOCX document
FCA IDIQ AG-32KW-S-11-0255.doc DOC document
SF1442 AG-32KW-S-11-0255.pdf PDF
AG-32KW-S-11-0255 Attachments.doc DOC document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment B Green Scorecard and Criteria Sustainable Building Spreadsheet for USDA Agencies

Fiscal Year 2010

Asset Name
Gross Sq. Ft.
Owned, Leased, Other
Asset Physical Location, City
Asset Physical Location, State
Asset Physical Location, Street Address
Energy Conservation
Energy Efficiency (5 points possible)
Energy Efficient Products (3 points possible)
Onsite Renewable Energy & REC's (8 points possible)
Measurement and Verification (6 points possible)
Operations & Maintenance Energy Management (3 points possible)
Water Management & Conservation Measures
Sustainable Site Strategies
Indoor Water (3 points possible)
Outdoor Water (3 to 5 points)
Measurement of Water Use (4 points possible)
Water Efficient Products (3 points possible)
Conservation Land Management Practices (4 points possible)
Site Operations & Maintenance (4 points possible)
Site Hydrology and Stormwater runoff (4 points possible)
Building Technologies and Practices (8 points possible)

Materials Selection and Natural Resources Conservation

Waste and Materials Management (8 points possible)
Recycled Content (3 points possible)
Biobased Content (4 points possible)
Environmentally Preferable Products (4 points possible)
Ozone-Depleting Compounds (4 points possible)

Note scoring instructions below!

Indoor Environmental Quality
Scoring
Ventilation and Thermal Comfort (2 points possible)
Moisture Control (1 point possible)
Daylighting and Lighting Controls (3 points possible)
Low-Emitting Materials (1 point possible)
Integrated Pest Management (2 points possible)
Total points
100% Scale
Sustainable?
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

USDA Existing Building Sustainability Ranking FY 2010

Owned or Leased Building, Name and Address:

Lease #

category
sub-category

Optimize Energy Performance

Up to 25 points

Energy Efficiency

Use one of the following three options to measure energy performance:

Receive an ENERGY STAR® rating of 75 or higher or an equivalent Labs21 Benchmarking Tool score for laboratory buildings;
5
Reduce energy use, and energy intensity per foot, by 20% compared to building energy use in 2003 or a year thereafter with quality energy use data: 1 point for 4%, 2 points 8%, 3 points 12%, 4 points 16%, 5 points 20% reduction; or
5
Practice energy conservation measures to gain at least 30% in energy efficiency relative to ASHRAE 90.1-2004.
5
Energy Efficient Products
Use ENERGY STAR® and FEMP-designated Energy Efficient Products - Estimate percentage use of ENERGY STAR® and FEMP-designated Energy Efficient products:1 point for 30%, 2 points 60%, 3 points 90% or more.
3
Renewable Energy
Implement renewable energy generation projects for agency use, on agency-managed property, when lifecycle cost effective, or purchase Renewable Energy Credits – 2 points for 10%, 4 points for 12.5%, 6 points for 15%, 7 points for 17.5%, 8 points for 20% or more of total energy use.
8
Measurement & Verification
Per DR 5500-001 sec. 8, Policy, a. (5), the Energy Policy Act of 2005 (EPACT), and the Energy Independence & Security Act of 2007 (EISA), utilize advanced energy metering for buildings over 10,000 SF. As required, include natural gas and steam, where used.
6

Energy Management and Operations and Maintenance (O & M)

Use one of the following two strategies to conserve and manage energy in O & M:

Use a comprehensive Energy and Water Conservation plan and, per EISA 2007 sec. 432(3), ensure that energy audits are completed on a four-year cycle; and use building operational measures to shave peak load during high demand seasons, working with local utilities, or
3
Use a commissioning and recommissioning plan, and recommission building, coinciding with Energy audits, on a four-year cycle per EISA 2007 sec. 432(3). Establish O & M strategies, e.g., for HVAC and electrical systems, to assure preventative maintenance and optimal equipment operation.
3
category
sub-category
Water Management & Conservation Measures
Up to 15 points
Indoor Water
Reduce building measured potable water use by 20% compared to building water use in 2003 or compared to a year thereafter with good water data or compared to a calculated water baseline for building of same use and size, without water conservation measures: 1 point for 7%, 2 points 14% 3 points for 20%.
3

Outdoor Water

Use one of the following three options to measure conservation of outdoor potable water:

Reduce potable irrigation water use by 50% compared to site of same characteristics and size without water conservation measures methods, or
3
Reduce building related potable irrigation water use by 50% compared to measured irrigation water use in 2003 or a year thereafter with quality water data, or
4
Use no potable irrigation water.
5
Measurement of Water Use
Reduce the potable water use (indoor and outdoor combined) by at least 20% compared to building water use in 2003 or a year thereafter by monitoring water consumption using existing building water meter.
4
Water Efficient Products
Use EPA’s WaterSense-labeled products or other water conserving products, and where applicable choose irrigation contractors who are certified through a WaterSense-labeled program - Estimate percentage use of available products: 1 point for 30%, 2 points 60%, 3 points 90% or more.
Up to 3
category
sub-category
Sustainable Sites
Up to 20 points

Conservation Land Management practices

Use one of the following two options to re-forest and introduce plants:

In rural and suburban settings, conserve forest and wilderness areas, or
4
In urban settings, use existing buildings and infill sites and plant trees.
4

Site Operations and Maintenance

Use of chemicals for fertilization, de-icing, pest control, etc. is reduced, or replaced by environmentally preferred product alternatives, by at least 50%.
1
Provide preferred parking for carpool and/or alternative fuel vehciles (5% of total)
1
Native plant species are used for landscaping; therefore, permanent landscape irrigation systems are eliminated or utilize only collected rainwater (no potable water).
2

Site Hydrology and Stormwater Runoff

Natural site hydrology (drainage patterns, natural streams, infiltration, etc.) is maintained or restored over a significant area of the site per EPA’s EISA sec. 438 Guidance.
4

or utilize one or both of the following strategies over a significant area of the site:

Rain gardens, rainwater recycling, ground water recharge systems, etc. are utilized to reduce site runoff, and/ or
2
Permeable and porous pavements, bio-swales, vegetated buffers and islands, and infiltration areas are utilized to reduce or treat pollutants from runoff on site.
2

Building Technologies and Practices

The building employs vegetative and landscape strategies to reduce building heat island contribution and reduce storm-water runoff /storm sewer use from roof. Examples: green roofs and living walls, rain gardens, and downspout absorption beds - Estimate percentage reduction, over entire roof area, of heat gain and runoff: 1 point for 20%, 2 points 40%, 3 points 60%, 4 points 80% or more.
Up to 4
The building takes advantage of natural light, prevailing winds and other site conditions, exterior plantings or façade treatments for shading, natural lighting via windows or skylights, earth sheltering, building orientation, sun angle, and other natural features for indoor environmental quality and energy efficiency for a significant portion of the building.
4
category
sub-category
Materials Selection and Natural Resources Conservation (construction, building modifications, maintenance, solid waste management, and cleaning)
Up to 23 points
Recycled Content
Where such products meet performance requirements and are available at a reasonable cost, use products that meet or exceed EPA's recycled content recommendations or are EPA certified - Estimate percentage use of recycled content products: 1 point for 30%, 2 points 60%, 3 points 90% or more.
Up to 3

Biobased Content

Use products with the highest Biobased content level per USDA's Biobased content recommendations, made from rapidly renewable resources and certified sustainable wood products - Estimate percentage use of Biobased content products: 1 point for 20%, 2 points 40%, 3 points 60%, 4 points 80% or more.
Up to 4
Environmentally Preferable Products
Use products that have a lesser or reduced effect on human health and the environment over their lifecycle, when compared with competing products or services that serve the same purpose- Estimate percentage use of Environmentally Preferable products: 1 point for 20%, 2 points 40%, 3 points 60%, 4 points 80% or more.
Up to 4
Ozone Depleting Compounds
Eliminate the use of ozone depleting compounds where alternative environmentally preferable products are available.
4

Waste and Materials Management

Use a Solid Waste Reduction, Materials Management, and Recycling plan;
8

or utilize one of the following three strategies:

Manage trash collection and handling so as to recycle a minimum of 25% of solid waste
2
Manage trash collection and handling so as to recycle a minimum of 50% of solid waste
5
Manage trash collection and handling so as to recycle a minimum of 75% of solid waste
8
category
sub-category

Indoor Environmental Quality (IEQ)

Up to 9 points

Ventilation and Thermal Comfort
Meet ASHRAE Standard 55-2004 Thermal Environmental Conditions for Human Occupancy and ASHRAE 62.1-2007 Ventilation fo Acceptable Indoor Air Quality
2
Moisture Control
Building utilizes appropriate moisture control strategy for climate, to prevent building damage, minimize mold contamination, and reduce health risks due to moisture. For façade renovations, Dew Point analysis and a plan for cleanup or infiltration of moisture into building materials are required.
1
Daylighting and Lighting Controls
Provide automated lighting controls (occupancy sensors) for offices and intermittenly occupied spaces
1
Achieve a minimum daylight factor of 2% in 50% of all spaces occupied for critical visual tasks.
1
Provide occupant controlled lighting, allowing adjustments for individual task needs for 50% of regularly occupied spaces.
1
Low Emitting Materials
Use low emitting materials for building modifications, maintenance and cleaning.
1
Integrated Pest Management
Use Integrated Pest Management techniques as appropriate to minimize pesticide usage. Use EPA registered pesticides only when needed.
2
Total
92 points