1900 Prospect Court, Appleton, WI 54914

Analyte Result MCLUnit

24-Mar-16

WATER-RIGHT, INC.

1900 PROSPECT CRT.

APPLETON, WI 54911

Report Date

VAN DYHEN DRILLING

W.Y. JUMP CENTER

Home Owner

Well Address

403458Lab #

BENCollected By

3/10/2016Collection Date

Well City

Analyte Result MCLUnit

Anions Bromide ND PPM Chlorides 10.7 250PPM

Fluoride 3.84 4PPM Nitrate - IC 0.23 10PPM

Orthophosphate ND PPM Sulfate 4.13 250PPM

Cations Arsenic - ICP 10.1 10PPB Barium ND 2000PPB

Beryllium ND 4PPB Boron 126 PPB

Cadmium 1.0 5PPB Calcium 7.4 PPM

Chromium ND 100PPB Cobalt ND PPB

Copper - ICP 7.9 1300PPB Iron ND 0.3PPM

Lithium 96.0 PPB Magnesium 4.3 PPM

Manganese ND 50PPB Molybdenum 16.1 PPB

Nickel ND PPB Phosphorus, Total 19.3 PPB

Potassium 3.9 PPM Silicon 19500 PPB

Silver ND 100PPB Sodium 34.0 PPM

Strontium 32.0 PPB Vanadium 6.2 PPB

Zinc 49.0 5000PPB

Other Tests pH 8.1 0pH Solids, Total Dissolved 105 500PPM

Tannin/Lignins ND PPM

Calculated Values Hardness 2 Grains Silica SiO2 42 PPM

MCL = Maximum Contamination Limit PPM = Parts Per Million PPB = Parts Per Billion

Tests listed above over the MCL

ND = Not Detected = Result was less than the LOD

ARSENIC: This is not a certified method for drinking water, and is for informational purposes only. If a certified result with a lower detection limit is necessary please contact Clean Water Testing for more information. Possible Health Effects: Skin damage or problems with circulatory systems, and may have increased risk of getting cancer Possible Sources: Erosion of natural deposits; runoff from orchards, runoff from glass & electronicsproduction wastes pH: EPA Secondary Standard. A measure of the acidity or alkalinity of the water. The EPA MCL is 6.5 - 8.5. NOTE – Due to the influence of dissolved gases on a pH test, it is recommended that a pH test is also performed in the field (at the location the sample was collected).