Ag Barn MAPS Ag Barn Plans - Bidding - 6.30.26.pdf
PDF 7 MB Posted
- Attached to
- Agricultural Classroom and Barn Construction
- Solicitation number
- RFP MONT 260000002368 1
- Issued by
- Oakland County, Michigan
About this file
This construction document package comprises architectural, structural, civil, mechanical, plumbing, and electrical design drawings for an Agricultural Classroom and Barn facility being constructed by Montague Area Public Schools in Montague, Michigan. The project totals 3,338 square feet and is designed to accommodate 65 occupants, including administrative staff and students. The facility includes a 1,144.16 square foot classroom, a 1,371.74 square foot barn space, storage areas, mechanical mezzanine, toilet facilities, and a chicken housing area with a capacity of 300 birds. The structure is classified as Use Group E (educational occupancy) with Construction Type IIB (non-combustible) and is designed in compliance with the 2021 Michigan Building Code, 2012 NFPA 101 Life Safety Code, and 2021 Michigan Energy Code. The project incorporates a pre-engineered metal building (PEMB) with rigid and portal frames, 2-hour fire-rated double firewall construction separating the barn from the classroom, insulated metal panel exterior cladding, standing seam metal roofing with minimum R-30 insulation, and concrete slab-on-grade flooring with proper drainage and vapor barriers. The design includes multiple means of egress with travel distances of 37 to 73 feet, all within the 75-foot maximum permitted distance.
The structural design accommodates live loads of 20 psf for roof areas, 60 psf for mechanical mezzanine, and specific loading for the chicken room dust cap. Wind design parameters include an ultimate design wind speed of 107 mph with exposure category B, while seismic design category B applies with mapped acceleration parameters of Ss=0.066 and S1=0.043. Foundation design is based on an allowable soil bearing pressure of 2,000 psf for sandy soils, with spread footings, wall footings, and concrete piers supporting the structure. Concrete specifications require 4,000 psi compressive strength for footings and slabs with 6-inch by 6-inch welded wire fabric reinforcement. Masonry construction includes 4,000 psi compressive strength concrete masonry units with horizontal joint reinforcement every other course and vertical reinforcement at specified intervals. The project requires continuous and periodic special inspections for cold-formed metal framing, concrete construction, masonry work, and structural steel connections in accordance with AISC 360-16 standards. The document was issued for preliminary review with a construction document date of June 30, 2026, and includes comprehensive details for all building systems with coordination requirements across multiple design disciplines.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Ag Barn Project Manual Vol 1.pdf | ||
| Ag Barn CM Requirements.pdf | ||
| Ag Barn Project Manual Vol 2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN TEAM
ARCHITECT/ENGINEER
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
AGRICULTURAL CLASSROOM AND BARN
MONTAGUE AREA PUBLIC SCHOOLS
Montague, Michigan
CONSTRUCTION DOCUMENTS
C O
V E
R S
H E
E T
-1
.0
G
J U
N E
A G
R
IC
U L
T U
R A
L C
L A
S S
R O
O M
A N
D B
A R
N
M o n ta g u e
M ic h ig a n
M O
N T
A G
U E
A R
E A
P U
B L
IC
S
C H
O O
L S
DRAWING INDEX
MONTAGUE HIGH SCHOOL
4882 STANTON BLVD
MONTAGUE, MI 49437
CONSTRUCTION MANAGER
SITE ADDRESS
4 EAST FULTON STREET, SUITE 200
GRAND RAPIDS, MICHIGAN 49503
PHONE: 616.456.9944
FAX: 616.456.5936
8868 WATER STREET
MONTAGUE, MI 49437
PHONE: 231.894.8409
GENERAL
G 001 COVER SHEET
G 002 TYP. SYMBOLS, GEN. NOTES, INTERIOR PARTITION TYPES, DEVICE
ALIGNMENT GUIDELINES
G 101 CODE COMPLIANCE PLAN
CIVIL DEMOLITION
CD 100 EXISTING CONDITIONS AND DEMO
CIVIL
C 100 SITE LAYOUT SHEET
C 200 SITE GRADING SHEET
C 300 SITE UTILITY SHEET
C 400 SITE DETAILS
STRUCTURAL GENERAL
SG 001 STRUCTURAL GENERAL NOTES
SG 002 STATEMENT OF SPECIAL INSPECTIONS
STRUCTURAL
S 101 FOUNDATION PLAN
S 201 FRAMING PLAN
S 301 TYPICAL FOUNDATION DETAILS
ARCHITECTURAL
A 101 OVERALL FLOOR PLAN
A 102 ROOF PLAN
A 201 OVERALL REFLECTED CEILING PLAN
A 301 EXTERIOR ELEVATIONS
A 311 BUILDING SECTIONS
A 321 WALL SECTION, ELEVATION AND PLAN DETAILS
A 501 DOOR SCHEDULES, FRAME ELEVATIONS, WINDOWS & ACCESS
PANEL INFORMATION
MECHANICAL
M 100 MECHANICAL FIRST FLOOR PLAN
M 101 MECHANICAL MEZZANINE PLAN
M 500 MECHANICAL DETAILS
M 700 MECHANICAL SCHEDULES
PLUMBING
P 100 DOMESTIC PLUMING FIRST FLOOR PLAN
P 200 SANITARY PLUMBING FIRST FLOOR PLAN
P 500 PLUMBING DETAILS
P 700 PLUMBING SCHEDULES
ELECTRICAL GENERAL
E 001 ELECTRICAL ABBREVIATIONS AND SYMBOLS
ELECTRICAL SITE
ES 101 ELECTRICAL SITE PLAN
ELECTRICAL
E 100 ELECTRICAL POWER FIRST FLOOR PLAN
E 101 ELECTRICAL POWER MEZZANINE PLAN
E 200 ELECTRICAL LIGHTING FIRST FLOOR PLAN
E 201 ELECTRICAL LIGHTING MEZZANINE PLAN
E 500 ELECTRICAL DETAILS
ISSUED FOR DATE
CIVIL CONSULTANT
2800 SOUTH 11TH STREET
KALAMAZOO, MI 49009
PHONE: 269.552.4960
FAX: 269.552.4961
MEP CONSULTANT
4801 HENRY ST.
MUSKEGON, MI 49441
PHONE: 231.798.4328
FAX: 231.798.2981
INTERSECTION OF NON-RATED AT
1 HOUR RATED PARTITION
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U425
1 HOUR RATED
PARTITION - REFER
TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
2 HOUR RATED
PARTITION -
REFER TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U438
2 HOUR RATED
PARTITION -
REFER TO PLAN
CH STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF
CONCRETE/MASONRY AT 1 HOUR
RATED PARTITION
CONCRETE OR MASONRY
WALL - REFER TO PLAN
1 HOUR RATED PARTITION -
REFER TO PLAN
METAL FURRING
GYPSUM BOARD CONTROL
JOINT NON-RATED PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
BACKER ROD
AND SEALANT
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 1 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
(2) LAYERS TYPE "X"
GYPSUM BOARD
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 2 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
METAL STUD FRAMING
(2) LAYERS TYPE "X"
GYPSUM BOARD
CONTROL JOINT
(2) LAYERS TYPE "X"
GYPSUM BOARD
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD BOTH SIDES;
(1 HOUR FIRE) U.L. ASSEMBLY U465
WHERE NOTED ON PLANS
METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS (AT CHASE
WALLS ONLY) - UNLESS
NOTED OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD ON ROOM SIDE - BRACE
WALL @ 4'-0" O.C. MAXIMUM.
METAL STUD CHASE WALL OR
FURRING
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH
5/8" TYPE "X" GYPSUM BOARD BOTH
SIDES TO DECK
STRUCTURAL METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
FLOOR CONSTRUCTION
METAL CH STUDS @ 16" O.C. WITH 5/8"
TYPE "X" GYPSUM BOARD ON ROOM
SIDE AND 1" TYPE "X" GYPSUM BOARD
PANEL ON CHASE SIDE
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM
BOARD BOTH SIDES
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN ALL
WALLS - UNLESS
NOTED OTHERWISE -
WEAVE IN-BETWEEN
STUDS
FLOOR CONSTRUCTION
6" TOP AND BOTTOM TRACK WITH 3 5/8"
METAL STUD FRAMING @ 16" O.C.
(OFFSET) WITH 5/8" GYPSUM BOARD BOTH
SIDES
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
BOND BEAM
SEALANT
FLOOR CONSTRUCTION
4" CONCRETE MASONRY UNITS
CMU WALL
U.L. ASSEMBLY - U905 (1 HOUR AND 2 HOUR)
HEAD
PLAN
SILL
CMU WALL WITH FURRING CMU WALL WITH FURRING BOTH SIDES
C H A S E S
ID
E
R O
O M
S
ID
E
METAL STUD CHASE WALL (1 HOUR FIRE)
U.L. ASSEMBLY U415
METAL STUD WALL (2 HOUR FIRE)
U.L. ASSEMBLY U425 METAL STUD SOUND WALL
6" CONCRETE MASONRY UNITS
8" CONCRETE MASONRY UNITS
10" CONCRETE MASONRY UNITS
STRUCTURE /
DECK ABOVE
BOND BEAM
FLOOR CONSTRUCTION
STRUCTURE /
DECK ABOVE
BOND BEAM
FLOOR CONSTRUCTION
HEAD
PLAN
SILL
4" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
6" CONCRETE MASONRY UNITS METAL FURRING
AND 5/8" GYPSUM BOARD
8" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
10" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
4" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
12" CONCRETE MASONRY UNITS 12" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
1X 2X 4X
5X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
FLOOR CONSTRUCTION
METAL CH STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM BOARD
ON ROOM SIDE AND 1" TYPE "X"
GYPSUM BOARD PANEL ON CHASE SIDE
METAL STUD CHASE WALL (2 HOUR FIRE)
U.L. ASSEMBLY U438
6X 7X 8
6" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
8" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
10" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD - BOTH SIDES
12" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD - BOTH SIDES
9X
10X
11X
12X
13X
9XX
10XX
11XX
12XX
13XX
SEALANT SEALANT
METAL STUDS @ 16" O.C. WITH
1/2" RATED PLYWOOD ONE SIDE
AND 5/8" GYPSUM BOARD ON
BOTH SIDES.
3X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
1/2" RATED
PLYWOOD
FLOOR CONSTRUCTION
METAL STUD WALL WITH
PLYWOOD BACKING
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
NOTE:
MOUNT EQUIPMENT AS SHOWN UNLESS SPECIFIED OTHERWISE.
MAX TWO DEVICES IN ONE HIGHER MOUNT
LOCATION AT LATCH SIDE OF DOOR, PROVIDE RFI
IF MORE DEVICES ARE NECESSARY. WHERE THERE
IS ONE DEVICE, CENTER OVER LOWER DEVICE. (TO
BE WITHIN ADA HEIGHT). (IF SWITCH CANNOT BE
LOCATED ON LATCH SIDE, LOCATE ONE DOOR
LEAF AWAY ON HINGE SIDE.)
DOOR
LOW DEVICES
RECEPTACLEVOICE/DATA
MASONRY COURSING
(WHERE APPLICABLE)
LIGHT SWITCH
F.A. AUDIO/VISUAL
ALIGNMENT NOTES
• ALIGN AND LOCATE CLOSE TOGETHER ANY DEVICES INSTALLED WITHIN 6' HORIZONTALLY.
• CENTER ALL DEVICES WHERE INDICATED ON COLUMN WRAP OR BUMP OUT; STACK AND ALIGN VERTICALLY.
• INSTALL DEVICES AT HEIGHTS INDICATED IN SYMBOL LEGEND UNLESS STACKING PER THIS DETAIL.
• WHERE HEIGHT IS SPECIFICALLY NOTED ON FLOOR PLANS, USE THAT MOUNTING HEIGHT
• CENTER ON DOORFRAME OR WHITEBOARDS ANY DEVICES INDICATED ABOVE.
O R L
A N D
IN
G
F R O
M F
LO
O
R
F R O
M F
LO
O
R O
R L
A N D
IN
G
6' - 0" MIN.
4" MAX
CAMERAS, CLOCKS, WALL
OCCUPANCY SENSORS
WHITE BOARD (WHERE APPLICABLE -
VERIFY WITH DETAILS/PLANS PROPER
INSTALL HEIGHT) CENTER ANY SINGLE
DEVICE WITH CENTER OF WHITE BOARD
ANY DEVICES
SHOWN OVER DOOR
TO BE CENTERED.
EQ EQ
EQ EQ
F R O
M F
LO
O
R O
R L
A N D
IN
G
SHORT THROW PROJECTOR
WHERE APPLICABLE
~12"
FA PULL STATION - HINGE SIDE
OF DOOR 1-LEAF AWAY WITHIN
5'-0" OF EXTERIOR OR STAIR
DOORS, WHEN WALL MOUNT
STROBES ARE ON PROJECT,
ALIGN ABOVE.
WHEN DEVICES ARE WITHIN DIMENSION, STACK
HIGH/LOW VERTICALLY AND GROUP DEVICES AT
SAME HEIGHT. UNLESS DEVICES IS PART OF
TECHNOLOGY DETAIL GROUPING OR SERVING A
FURNITURE GROUP.
CASEWORK, COORDINATE DEVICE BOTTOM
TO BE 2" OVER BACKSPLASH OR OVER
COUNTERTOP (IF NO BACKSPLASH). FOR
LARGE FORMAT TILE, ALIGN EDGE OF DEVICE
WITH HORIZONTAL GROUT LINE CLOSEST TO
COUNTERTOP.
COORDINATE OUTLET LOCATIONS WITH
GROUT LINES, EDGE OF DEVICE ON GROUT
LINE IF POSSIBLE. COORDINATE WITH
INTERIOR DESIGN DRAWINGS.
TYPICAL COLUMN
ENCLOSURE, CHASE OR
BUMP-OUT WITH DEVICES
INDICATED IN PLANS.
EQ EQ
EQEQEQEQ
THERMOSTAT,
SENSORS OR AV
CONTROLLER, CARD
READER, ETC.
A101A
TYPICAL SYMBOLS & REFERENCES
NOTE:
ROOM NAMES AND NUMBERS ON PLANS ARE
FOR CONSTRUCTION PURPOSES ONLY.
COORDINATE WITH OWNER REGARDING
PROPOSED NUMBERS FOR ALL SIGNAGE,
SCHEDULE AND PANEL DESIGNATIONS.
ROOM IDENTIFICATION TAG
ROOM NAME
ROOM NUMBER
DETAIL TITLE
1 DETAIL TITLE
1" = 0'-1"A101
DETAIL NUMBER
SHEET NUMBER
UNIT MATCHLINES
U N
IT
A
U N
IT
B
TYPICAL NOTATION SYMBOLS
CALLOUT REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
EXTERIOR ELEVATION REFERENCE BUBBLE
A301
A
ELEVATION LETTER
SHEET NUMBER
INTERIOR ELEVATION REFERENCE BUBBLE
A 652
ELEVATION NUMBER
SHEET NUMBER
DETAIL REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
BUILDING SECTION REFERENCE BUBBLE
A 311
DETAIL NUMBER
SHEET NUMBER
ELEVATION AND SECTION REFERENCE TOOLS
ELEVATION TAG - EXISTING
FINISH FLOOR
ELEVATION 100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
100'-0" ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
ELEVATION TAG - NEW
FINISH FLOOR
ELEVATION 100'-0"
100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
WORKING POINT LAYOUT TAG
100'-0" : 100'-0"
DISTANCE IN THE "Y" DIRECTION FROM THE
"X" BASE LINE
DISTANCE IN THE "X" DIRECTION FROM THE
"Y" BASE LINE
BORROWED LIGHT AND DOOR IDENTIFICATION
A 502
SHEET NUMBER
ELEVATION NUMBER
DOOR NUMBER - CORRESPONDS TO THE ROOM NUMBER
LETTER DESIGNATES MORE THAN ONE IN ROOM
SYMBOLS
BARRIER-FREE
B1 REVISION IDENTIFIER (ADDENDUM AND BULLETIN)
COLUMN BUBBLE AND LINE
CLASSROOM
A000A
GENERAL NEW CONSTRUCTION - ARCHITECTURAL
1. THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT PRIOR
TO COMMENCEMENT OF CONTRACTED DEMOLITION WORK.
2. ALL EXISTING CONDITIONS SHOULD BE FIELD VERIFIED BEFORE WORK BEGINS.
3. DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR TO
THE FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.
4. DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR
CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN QUESTION.
5. EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/DECK ABOVE
UNLESS NOTED OR DETAILED OTHERWISE.
6. STUD WALLS SPANNING OVER 12'-0" IN HEIGHT SHALL BE A MINIMUM OF 20 GAGE.
STUD WALL SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20 GAGE.
7. DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR DIMENSIONED
OTHERWISE.
8. FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES
AND CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.
9. FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH
FIRE AND/OR SMOKE RATED ASSEMBLIES.
10. FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR
FLOOR PLANS.
11. PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT
FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.
12. PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT OR
ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY MANUFACTURER.
ACCESSORY NOTES
1. OP = OWNER PURCHASED, OI = OWNER INSTALLED, CP = CONTRACTOR PURCHASED,
CI = CONTRACTOR INSTALLED.
2. DIMENSIONS INDICATED ARE TYPICAL UNLESS NOTED OTHERWISE ON PLANS.
3. GENERIC PLUMBING FIXTURES ARE SHOWN. REFER TO PLUMBING DRAWINGS AND
SPECIFICATIONS FOR FIXTURE TYPES, MANUFACTURERS AND MOUNTING HEIGHTS.
4. CODE REQUIRED INTERIOR SIGNAGE - INCLUDES MINIMUM REQUIRED SIGN TYPES
REQUIRED FOR OCCUPANCY AS DICTATED BY IBC, IFC, AND NFPA. COORDINATE WITH
ANY OWNER-PROVIDED SIGNAGE.
GENERAL PARTITION NOTES
1. NOT ALL WALL TYPES MAY BE USED ON PROJECT.
2. REFER TO CODE COMPLIANCE PLANS FOR LOCATIONS OF SMOKE AND FIRE-RATED
PARTITIONS.
3. ALL PARTITIONS EXTEND TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.
4. LINE OF STRUCTURE/DECK AS SHOWN AT THE HEAD CONDITION OF EACH PARTITION
TYPE IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION
CONDITIONS. TERMINATE RATED PARTITIONS AT UNDERSIDE OF STRUCTURAL DECK TO
MAINTAIN RATING. PROVIDE APPROPRIATE FRAMING AND GYPSUM BOARD TO OFFSET
AROUND STRUCTURE OR OTHER OBSTRUCTIONS, SUCH AS PIPING OR DUCTWORK.
5. PARTITIONS MAY TERMINATE AT STRUCTURAL MEMBERS WITH A RATING GREATER THAN
OR EQUAL THE PARTITION, PROVIDED THAT RATING IS CONTINUOUS TO STRUCTURAL
DECK ABOVE.
6. NON-RATED PARTITIONS THAT EXTEND TO STRUCTURE SHALL TERMINATE AT
UNDERSIDE OF STRUCTURAL DECK TO MAINTAIN A CONTINUOUS PLANE OF GYPSUM
BOARD AS A NOISE, SMOKE OR OTHER TYPE OF BARRIER.
7. ALL PARTITIONS EXTENDING TO STRUCTURE ABOVE SHALL TERMINATE WITH
DEFLECTION TRACK - SEE TYPICAL DETAILS ON THIS SHEET.
8. ALL GYPSUM BOARD PARTITIONS NOT EXTENDING TO THE STRUCTURE MUST BE
BRACED.
9. UL DESIGN NUMBERS REFER TO THE FIRE RESISTANCE DIRECTORY; UNDERWRITERS
LABORATORY, LATEST EDITION.
10. MISCELLANEOUS NON-RATED CHASES TO BE 5/8" GYPSUM BOARD ON 3 5/8" METAL
STUD FRAMING AT 16" O.C., UNLESS NOTED OTHERWISE.
11. MISCELLANEOUS FURRING AROUND COLUMNS TO BE 5/8" GYPSUM BOARD ON 11/2"
STUDS, UNLESS NOTED OTHERWISE.
12. FIRE-RATED PARTITIONS TO HAVE FIRE-STOPPING SEALANTS AT HEAD, SILL JUNCTURE
WITH DISSIMILAR MATERIALS, ETC. AND AROUND ALL PENETRATIONS AND OPENINGS.
13. CONSTRUCT ALL PARTITIONS WITH SOUND ATTENUATION BATTS WITH THE FOLLOWING
SOUND BATT THICKNESS: 2 1/2" OR LESS METAL STUD - 1 1/2" THICKNESS, 3 5/8"
OR LARGER METAL STUD - 3" THICKNESS. UNLESS NOTED OTHERWISE.
1X
METAL STUD/FURRING, CH STUD AND WOOD STUD KEY
METAL STUD/FURRING
DESIGNATION SIZE
A GYPSUM BOARD DIRECT APPLIED TO CMU
B 7/8"
C 1 1/2"
D 1 5/8"
E 2 1/2"
F 3 1/2"
G 3 5/8"
H 4"
J 5 1/2"
K 6"
L 8"
M 10"
N 12"
P (OPEN)
Q (OPEN)
CH STUD
DESIGNATION SIZE
R 2 1/2"
S 4"
T 6"
PARTITION TYPE TAG (REFER TO FLOOR PLANS)
PARTITION TYPE
NUMBER
METAL STUD, FURRING OR
CH STUD FRAMING LETTER
FIRE-RATING, IF REQUIRED
1X
WOOD STUD
DESIGNATION SIZE
U 2"x4"
V 2"x6"
W 2"x8"
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T Y
P
S Y
M B
O L
S
G E
N
N O
T E
S
IN
T
E R
IO
R
P A
R T
IT
IO
N T
Y P
E S
D
E V
IC
E
A L
IG
N
M E
N T
G U
ID
E
L
IN
E S
-1
.0
G
J U
N E
A G
R
IC
U L
T U
R A
L C
L A
S S
R O
O M
A N
D B
A R
N
M o n ta g u e
M ic h ig a n
M O
N T
A G
U E
A R
E A
P U
B L
IC
S
C H
O O
L S
NOT TO SCALE
DEVICE ALIGNMENT GUIDELINES
ISSUED FOR DATE
F
F
F
F
SD
SD
W/DW
1. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION SHOULD BE
SEALED WITH AN APPROVED U.L. RATED PRODUCT.
2. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE
CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR ASSEMBLY.
3. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE NON-COMBUSTIBLE
TREATED WOOD.
4. REFER TO SPECIFICATION U.L. RATING INFORMATION.
5. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE THE FLUTES
FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC DECK' SHOWN ON THIS
SHEET.
• FOR MASONRY WALLS THE MASON SHALL FILL VOIDS AND FIRE SPRAY WITH UL LISTED
MATERIAL.
• FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK.
CODE COMPLIANCE KEY
EGRESS SYMBOLS
EGRESS EXIT NUMBER FROM ROOM OR SPACE
MAXIMUM NUMBER OF OCCUPANTS PERMITTED
BY EGRESS WIDTH
ROOM OR SPACE EGRESS IS FROM
TRAVEL DISTANCE : 100'-0"
PERMITTED TRAVEL DISTANCE - 200'-0"
EXISTING TRAVEL DISTANCE
TO EGRESS DOOR
PERMITTED MAXIMUM TRAVEL
DISTANCE PER CONDITION
DIRECTION OF EGRESS
FIRE SAFETY SYMBOLS
FIRE-RATING KEY
EGRESS
Door #
EGRESS ROOM
XFE
XFEC
FE
FEC
EXISTING FIRE EXTINGUISHER
EXISTING FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
AED
AUTOMATED EXTERNAL DEFIBRILLATOR (AED)
RECESSED CABINET
DESIGNATION RATING PRIORITY
2 HOUR (NEW CONSTRUCTION) 1
1 HOUR (NEW CONSTRUCTION) 2
SMOKE RESISTANT 3
COORDINATE ALL REQUIRED DAMPERS WITH MECHANICAL.
2 HOUR (EXISTING)
1 HOUR (EXISTING WALL,
FORMERLY NOT FR)
NFPA 101 LIFE SAFETY CODE
MEANS OF EGRESS
MAXIMUM EXIT ACCESS TRAVEL: 75 FEET
1. BUILDING USE GROUPS AND CONSTRUCTION TYPE
BUILDING USE GROUP: E
CONSTRUCTION TYPE: IIB
NON-COMBUSTIBLE (TABLE 601)
EXTERIOR LOAD BEARING - 0 HR
EXTERIOR NON-LOAD BEARING - 0 HR (PER TABLE 705.5)
STRUCTURAL FRAME - 0 HR
5. PROTECTION FROM HAZARDS
FIRE WALLS (SECTION 706.1) - EACH PORTION OF A BUILDING SEPARATED BY ONE OR
MORE FIRE WALLS THAT COMPLY WITH THE PROVISIONS OF THIS SECTION SHALL BE
CONSIDERED A SEPARATE BUILDING.
*FIRE RESISTANCE RATING: 2 HR (PER TABLE 706.4)
** MUST MEET 717.5.2 EXCEPTION #3 TO VOID FIRE DAMPERS
***SEAL PENETRATIONS WITH SMOKE RESISTIVE SEALANT (NO TRANSFER GRILLES)
7. FIRE STOPPING AND SMOKE STOPPING
FILL ALL HOLES AND JOINTS IN FIRE RATED PARTITIONS ASSEMBLIES AROUND ALL
MECHANICAL PLUMBING, F.P. PIPING, ELECTRICAL PENETRATIONS WITH FIRE RATED FIRE
STOP MATERIALS PER SPECIFICATIONS IN DIVISION 7 AND PER ASTM E814. FILL GAPS
BETWEEN TOP OF FIRE RATED WALLS AND FLOOR / ROOF DECKS ABOVE WITH
FIRESTOPPING. SUBMIT FIRE STOP TEST REPORTS AND PRODUCT LITERATURE AS
REQUESTED BY AUTHORITIES HAVING JURISDICTION. M&E PENETRATIONS THROUGH
SMOKE RESISTIVE PARTITIONS SHALL BE SEALED SMOKE TIGHT WITH SMOKE RESISTIVE
SEALANT. (MBC 714.4.1.2)
2021 MICHIGAN BUILDING CODEPLUMBING COUNTS
NEW CONSTRUCTION: EDUCATIONAL OCCUPANCY
TOTAL OCCUPANCY = 65
ADMINISTRATION, STUDENTS
CODE REQ'D PROVIDED
WATER CLOSETS - MALE 1 1
WATER CLOSETS - FEMALE 1 1
LAVATORIES - MALE 1 1
LAVATORIES - FEMALE 1 1
DRINKING FOUNTAINS 0 0
10. MEANS OF EGRESS
MINIMUM REQUIRED EGRESS WIDTH (SECTION 1005) THE MEANS OF EGRESS WIDTH
SHALL NOT BE LESS THAN REQUIRED BY THIS SECTION. THE TOTAL WIDTH OF MEANS
OF EGRESS IN INCHES SHALL NOT BE LESS THAN THE TOTAL OCCUPANT LOAD SERVED
BY THE MEANS OF EGRESS.
EGRESS WIDTH PER OCCUPANT SERVED (SECTION 1005.3): REFER TO NFPA 101 LSC
NOTES (MORE RESTRICTIVE)
MEANS OF EGRESS LIGHTING: PROVIDE EMERGENCY EGRESS LIGHTING IN ALL MEANS
OF EGRESS SPACES HAVING 2 OR MORE MEANS OF EGRESS, IN COMMON TOILET
ROOMS AND AT EXTERIOR SIDES OF EXITS. PROVIDE PHOTOMETRIC PLAN
CALCULATIONS OF LIGHTING LEVELS IN ACCORDANCE WITH 1008.3.5 AND REQUESTED
BY AUTHORITIES HAVING JURISDICTION.
EGRESS THROUGH INTERVENING SPACES (1016.2) NOT ALLOWED EXCEPT WHERE
ADJOINING ROOMS ARE ACCESSORY TO ONE OR THE OTHER AND PROVIDE A
DISCERNABLE PATH OF EGRESS TRAVEL TO AN EXIT.
EGRESS FROM CLASSROOMS IN GROUP E OCCUPANCIES SHALL BE LIMITED TO PASS
THROUGH I INTERVENING SPACE BEFORE REACHING AN EXIT ACCESS DOOR LEADING
DIRECTLY TO A CORRIDOR OR EXIT.
WHERE TWO EXITS, EXIT ACCESS DOORWAYS, EXIT ACCESS STAIRWAYS OR RAMPS, OR
ANY COMBINATION THEREOF, ARE REQUIRED FROM ANY PORTION OF THE EXIT ACCESS,
THEY SHALL BE PLACED A DISTANCE APART EQUAL TO NOT LESS THAN ONE HALF OF
THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN THEM. (1007.1.1)
• PER MEC REFERENCE TO ASHRAE 90.1 – 2019 – TABLE 5.5-5, ASSEMBLY USE,
• PROJECT IS IN CLIMATE ZONE 5A,
• MINIMUM R-VALUES;
NON-RESIDENTIAL ASHRAE 90.1 – 2019 – TABLE 5.5-5
AT CONVENTIONAL CONSTRUCTION:
ROOF / CEILING (INSUL. ABOVE DECK) R-30 C.I. (MIN.)
WALLS, MASS (MASONRY) R-11.4 C.I. (MIN.)
AT METAL BUILDING:
ROOF / CEILING R-19 + R-11 LS (MIN.)
WALLS R-13 + R-14 C.I. (MIN.)
VERTICAL FENESTRATION
METAL FRAMING, FIXED U-0.36 (MAX.)
METAL FRAMING, OPERABLE U-0.45 (MAX.)
METAL FRAMING, ENTRANCE DOORS U-0.63 (MAX.)
ALL FRAME TYPES SHGC – 0.40 (MAX.)
VT / SHGC – 1.10 (MIN.)
2021 MICHIGAN ENERGY CODE SUMMARY
COMMON PATH OF TRAVEL (SECTION 1030.8) SHALL NOT EXCEED 75' FOR
OCCUPANCIES UNDER 50 AND 50' FOR A SMOKE PROTECTED ASSEMBLY SEATING.
COMMON PATH OF EGRESS TRAVEL -THAT PORTION OF EXIT ACCESS WHICH THE
OCCUPANTS ARE REQUIRED TO TRAVERSE BEFORE TWO SEPARATE AND DISTINCT PATHS
OF EGRESS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON PATHS OF TRAVEL.
COMMON PATHS OF EGRESS TRAVEL SHALL BE INCLUDED WITHIN THE PERMITTED TRAVEL
DISTANCE.
EXIT ACCESS TRAVEL DISTANCE (TABLE 1017.2) - A OCCUPANCY TRAVEL DISTANCE IS
75'.
MINIMUM NUMBER OF EXITS (TABLE 1006.3.3)
1 TO 500 OCCUPANTS = 2 EXITS REQUIRED
(1028.1) EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF THE BUILDING. THE
EXIT DISCHARGE SHALL BE AT GRADE OR SHALL PROVIDE A DIRECT PATH OF EGRESS
TRAVEL TO GRADE. EXCEPTIONS PERMITTED PER 1028.1
1144.16
SF
CLASSROOM
1371.74
SF
BARN
STORAGE
JAN
EGRESS
BUILDING EXPANSION JOINT
BASED ON EMSEAL "COLORSEAL"
TYPICAL BOTH SIDES
1 HR FR
4'-0"
EGRESS
FE
FEC
NOX BOX
1 HR FR
4'-0"
1 HR FR
4'-0"
E G
R E
S S
TRAVEL DISTANCE: 46' - 8"
PERMITTED TRAVEL DISTANCE - 75' - 0"
1 HR FR
4'-0"
TOILET
PASSAGE
394.35
SF
CHICKENS
KNOX
94 SQ. FT
TRAVEL
DIS
TANCE :
53' -
8"
PERM
IT
TED T
RAVEL
DIS
TANCE -
75'
TR
A V E L
D
IS
TA
N C E
7"
P E R M
IT
TE
D T
R A V E L
D
IS
TA
N C E
TR
AVEL
D
IS
TAN
C E :
2"
PER
M
IT
TED
T R
AVEL
D
IS
TAN
C E -
FE
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
C O
D E
C O
M P
L
IA
N C
E P
L A
N
-1
.0
G
J U
N E
A G
R
IC
U L
T U
R A
L C
L A
S S
R O
O M
A N
D B
A R
N
M o n ta g u e
M ic h ig a n
M O
N T
A G
U E
A R
E A
P U
B L
IC
S
C H
O O
L S
THIS DRAWING SHEET IS INTENDED TO BE PLOTTED IN
COLOR. IF THIS TEXT APPEARS IN BLACK AND WHITE,
IT IS PLOTTED INCORRECTLY. DISCARD AND OBTAIN
AN ACCURATE DRAWING
1/4" = 1'-0"
CODE PLAN
BUILDING:
LIFE SAFETY:
ENERGY:
PLUMBING:
MECHANICAL:
FUEL GAS:
ELECTRICAL:
BARRIER-FREE:
USE GROUP:
CONSTRUCTION TYPE:
AUTOMATIC SPRINKLERS:
E - CLASSROOM
IIB (000)
PROJECT AREA
REFERENCED CODES
TOTAL FINAL BUILDING AREA:
TOTAL OCCUPANCY:
3338 SQ. FT.
2021MICHIGAN BUILDING CODE
2012 NFPA 101 LIFE SAFETY CODE (LSC)
2021 MICHIGAN ENERGY CODE (MEC)
2021 MICHIGAN PLUMBING CODE (MPC)
2021 MICHIGAN MECHANICAL CODE (MMC)
(IFCG) 2021 INTERNATIONAL FUEL GAS CODE
2023 MICHIGAN ELECTRICAL CODE, PART 8
2021 MICHIGAN BUILDING CODE & 2017 ICC & C A117.1
NO
U - AG BARN
CAUTION!!!
STANTON BLVD
BM #01
BM #02
NOT FOR CONSTRUCTION
PRELIMINARY
ISSUED FOR DATE
TO
W
ER
PI
N
KS
TE
R
.C O
M
AL
L R
IG
H
TS
R
ES
ER
VE
D
SH
EE
T
TI
TL
E
SH
EE
T N
U M
B
ER
6.
O W
N
ER
M O
N
TA
G U
E
AG
B
AR
N C
O N
ST
R
U C
TI
O
N D
R
AW
IN
G
S
M on ta gu e, M ic hi ga n
M O
N
TA
G U
E
PU
BL
IC
S C
H O
O
LS
PR
O
JE
C
T
TI
TL
E
D A
TE
BENCHMARKS
REMOVALS LEGEND
hurley & stewart, llc 2800 s. 11th street kalamazoo, michigan 49009
269.552.4960 fax 269.552.4961 www.hurleystewart.com
REMOVAL NOTES
C D
JU
N
E
, 2
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
AN
D D
EM
O http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM
STANTON BLVD
BM #01
BM #02
PROPOSED
BUILDING
F.F. = 658.50
NOT FOR CONSTRUCTION
PRELIMINARY
ISSUED FOR DATE
TO
W
ER
PI
N
KS
TE
R
.C O
M
AL
L R
IG
H
TS
R
ES
ER
VE
D
SH
EE
T
TI
TL
E
SH
EE
T N
U M
B
ER
6.
O W
N
ER
M O
N
TA
G U
E
AG
B
AR
N C
O N
ST
R
U C
TI
O
N D
R
AW
IN
G
S
M on ta gu e, M ic hi ga n
M O
N
TA
G U
E
PU
BL
IC
S C
H O
O
LS
PR
O
JE
C
T
TI
TL
E
D A
TE
SITE LEGEND
LEGEND
GENERAL NOTES
C
JU
N E
, 2
SI
TE
L
AY
O U
T
SH
EE
T hurley & stewart, llc 2800 s. 11th street kalamazoo, michigan 49009
269.552.4960 fax 269.552.4961 www.hurleystewart.com http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM
PROPOSED
BUILDING
F.F. = 658.50
CAUTION!!!
STANTON BLVD
BM #01
BM #02
NOT FOR CONSTRUCTION
PRELIMINARY
ISSUED FOR DATE
TO
W
ER
PI
N
KS
TE
R
.C O
M
AL
L R
IG
H
TS
R
ES
ER
VE
D
SH
EE
T
TI
TL
E
SH
EE
T N
U M
B
ER
6.
O W
N
ER
M O
N
TA
G U
E
AG
B
AR
N C
O N
ST
R
U C
TI
O
N D
R
AW
IN
G
S
M on ta gu e, M ic hi ga n
M O
N
TA
G U
E
PU
BL
IC
S C
H O
O
LS
PR
O
JE
C
T
TI
TL
E
D A
TE
GRADING & SESC NOTES
E8
S59
SOIL EROSION AND
SEDIMENTATION CONTROL MEASURES
WHERE USEDSYMBOLKEY
BEST
MANAGEMENT
PRACTICES
GRADING PLAN LEGEND
BM #XX
C
JU
N E
, 2
SI
TE
G R
AD
IN
G S
H
EE
T hurley & stewart, llc 2800 s. 11th street kalamazoo, michigan 49009
269.552.4960 fax 269.552.4961 www.hurleystewart.com http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM
PROPOSED
BUILDING
F.F. = 658.50
CAUTION!!!
STANTON BLVD
BM #01
BM #02
NOT FOR CONSTRUCTION
PRELIMINARY
ISSUED FOR DATE
TO
W
ER
PI
N
KS
TE
R
.C O
M
AL
L R
IG
H
TS
R
ES
ER
VE
D
SH
EE
T
TI
TL
E
SH
EE
T N
U M
B
ER
6.
O W
N
ER
M O
N
TA
G U
E
AG
B
AR
N C
O N
ST
R
U C
TI
O
N D
R
AW
IN
G
S
M on ta gu e, M ic hi ga n
M O
N
TA
G U
E
PU
BL
IC
S C
H O
O
LS
PR
O
JE
C
T
TI
TL
E
D A
TE
UTILITY NOTES
C
JU
N E
, 2
SI
TE
U
TI
LI
TY
S H
EE
T hurley & stewart, llc 2800 s. 11th street kalamazoo, michigan 49009
269.552.4960 fax 269.552.4961 www.hurleystewart.com http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM http://WWW.HURLEYSTEWART.COM
NOT FOR CONSTRUCTION
PRELIMINARY
ISSUED FOR DATE
TO
W
ER
PI
N
KS
TE
R
.C O
M
AL
L R
IG
H
TS
R
ES
ER
VE
D
SH
EE
T
TI
TL
E
SH
EE
T N
U M
B
ER
6.
O W
N
ER
M O
N
TA
G U
E
AG
B
AR
N C
O N
ST
R
U C
TI
O
N D
R
AW
IN
G
S
M on ta gu e, M ic hi ga n
M O
N
TA
G U
E
PU
BL
IC
S C
H O
O
LS
PR
O
JE
C
T
TI
TL
E
D A
TE
C
JU
N E
, 2
SI
TE
D
ET
AI
LS
STANDARD DUTY ASPHALT DETAIL
SIDEWALK DETAIL
INSTALLATION DETAIL
ISOMETRIC VIEW
S58 INLET PROTECTION
FABRIC DROP
TWO-WAY CLEANOUT DETAIL
ROOF LEAD/ DOWNSPOUT DETAIL
SANITARY LEAD DETAIL
TRENCH DETAILS
UNDER PAVED AREA NOT UNDER PAVED AREA
WATER SERVICE DETAIL
TYPICAL GRAVEL SECTION
LEGEND
BM #XX
90° HOOK LENGTH
0°
H O
O K
L
EN
G
TH
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T O
W E
R P
IN
K
S T
E R
.C O
M
A L
L R
IG
H
T S
R E
S E
R V
E D
/2
/2
:0
:2
A
M
S T
R U
C T
U R
A L G
E N
E R
A L
N O
T E
S
-1
.0
S G
J U
N E
A G
R
IC
U L
T U
R A
L C
L A
S S
R O
O M
A N
D B
A R
N
M o n ta g u e
M ic h ig a n
M O
N T
A G
U E
A R
E A
P U
B L
IC
S
C H
O O
L S
D R
A W
N B
Y
B A
R
STRUCTURAL LOADS
1. BUILDING CODE:
MICHIGAN BUILDING CODE 2021
2. STRUCTURAL DESIGN CODES AND STANDARDS:
DESIGN LOADS ASCE 7-16
STEEL AISC 360-16
CONCRETE ACI 318-19
MASONRY TMS402-16/ACI 530-16
WOOD ANSI/AWC NDS-18
COLD FORMED METAL AISI S100-16 (2020)
3. BUILDING RISK CATEGORY II
4. DESIGN LOADS:
ROOF DEAD:
ROOFS SEE PEMB
DESIGN LIVE LOADS:
ROOFS 20 PSF
MECH MEZZANINE 60 PSF
CHICKEN ROOM DUST CAP 10 PSF (NO STORAGE)
SNOW:
GROUND SNOW Pg = 35.0 PSF
IMPORTANCE FACTOR I = 1.0
THERMAL FACTOR Ct = 1.0
EXPOSURE FACTOR Ce = 1.0
FLAT ROOF SNOW Pf = 24.5 PSF
SLOPE FACTOR Cs = 1.0
WIND:
ULTIMATE DESIGN WIND SPEED Vult = 107 MPH
NOMINAL DESIGN WIND SPEED Vasd = 83 MPH
EXPOSURE CATEGORY B
INTERNAL PRESSURE COEFFICIENT ± 0.18
TOPOGRAPHIC FACTOR Kzt = 1.0
DIRECTIONALITY FACTOR Kd = 0.85
GROUND ELEVATION FACTOR Ke = 1.0
GUST EFFECT FACTOR G = 0.85
END ZONE WIDTH FOR COMPONENTS AND CLADDING a = 4 FT
SEISMIC:
SEISMIC IMPORTANCE FACTOR Ie = 1.00
MAPPED ACCELERATION PARAMETERS Ss = 0.066 & S1 = 0.043
SITE CLASS D (ASSUMED)
DESIGN ACCELERATION PARAMETERS Sds = 0.070 & Sd1 = 0.068
SEISMIC DESIGN CATEGORY B
SEISMIC FORCE RESISTING SYSTEM SEE PEMB
GENERAL
1. THESE DRAWINGS REPRESENT THE COMPLETED PROJECT WHICH HAS BEEN DESIGNED FOR THE DEAD LOAD WEIGHT OF MATERIALS
INDICATED PLUS THE SUPERIMPOSED LIVE LOADS INDICATED IN THE DESIGN DATA. IT IS THE CONTRACTOR’S RESPONSIBILITY TO
DETERMINE ALLOWABLE CONSTRUCTION LOADS AND TO PROVIDE PROPER DESIGN AND CONSTRUCTION OF FALSEWORK, FORMWORK, STAGING, BRACING, AND SHORING. CONTRACTOR HAS SOLE RESPONSIBILITY FOR CONSTRUCTION MEANS AND METHODS, SEQUENCES, AND PROCEDURES OF CONSTRUCTION. THE STRUCTURE IS STABLE ONLY IN ITS COMPLETED FORM, WITH COMPLETED
CONNECTIONS, AND FIELD INSTALLED MATERIALS HAVING REACHED SPECIFIED DESIGN STRENGTH.
2. CROSS CHECK ALL DIMENSIONS AND ELEVATIONS INDICATED. REPORT DISCREPANCIES FOR CLARIFICATION PRIOR TO STARTING
CONSTRUCTION OR ORDERING MATERIALS. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT INDICATED ON THE
STRUCTURAL DRAWINGS. DO NOT SCALE THESE DRAWINGS.
3. IN THE CASE OF A CONFLICT WITHIN THE CONTRACT DOCUMENTS THE MOST STRINGENT REQUIREMENTS WILL GOVERN.
4. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND CIVIL DRAWINGS FOR SIZE AND LOCATION OF OPENINGS, SLEEVES, CONCRETE HOUSEKEEPING PADS, INSERTS, EMBEDDED ITEMS, CURBS, RAMPS, DRAINS, DEPRESSIONS, ETC. NOTIFY
STRUCTURAL ENGINEER OF ANY DISCREPANCIES.
5. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DETAILED INFORMATION REGARDING SPECIAL FINISHES ON
STRUCTURAL MEMBERS, FIREPROOFING, WATERPROOFING, ETC.
6. REFER TO ARCHITECTURAL DRAWINGS FOR MASONRY AND DRYWALL NON-LOADBEARING PARTITIONS. PROVIDE SLIP CONNECTIONS
THAT ALLOW VERTICAL MOVEMENT AT THE HEADS OF SUCH PARTITIONS. CONNECTIONS SHALL SUPPORT THE TOP OF THE WALLS
LATERALLY FOR THE CODE REQUIRED LATERAL LOAD.
7. REPRODUCTION OF THE STRUCTURAL DRAWINGS FOR SUBMISSION AS SHOP DRAWINGS IS PROHIBITED. SUBMITTALS PRODUCED IN
THIS MANNER WILL BE REJECTED.
8. DELEGATED DESIGN SUBMITTALS: PORTIONS OF THE DESIGN HAVE BEEN DELEGATED AND WILL BE DESIGNED BY PRODUCT
MANUFACTURERS QUALIFIED LICENSED ENGINEERS. THE STRUCTURAL ENGINEER OF RECORD WILL ONLY REVIEW SUBMITTALS OF THESE
SYSTEMS FOR GENERAL CONFORMANCE WITH THE PROJECT PARAMETERS INDICATED AND IS NOT RESPONSIBLE FOR DELEGATED
DESIGN SUBMITTAL. DELEGATED DESIGN SUBMITTALS INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING. REFER TO SPECIFICATIONS
FOR ANY ADDITIONAL DELEGATED DESIGNS REQUIRED.
PRE-FABRICATED AWNINGS AND SUNSHADES
PRE-ENGINEERED METAL BUILDING
9. CONTRACTOR TO PROVIDE A SUBMITTAL FOR ENGINEER REVIEW FOR THE FOLLOWING. REFER TO SPECIFICATIONS FOR ANY
ADDITIONAL SUBMITTALS REQUIRED.
CONCRETE MIX
CONCRETE REINFORCEMENT
MASONRY REINFORCEMENT
PRE-ENGINEERED METAL BUILDING
STRUCTURAL GENERAL NOTES
ABBREVIATIONS
ARCH ARCHITECTURAL
BS BOTTOM OF STEEL ELEVATION
CIP CAST-IN-PLACE
CJ CONTROL OR CONSTRUCTION JOINT
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONT CONTINUOUS
CVR COVER
DBE DECK BEARING ELEVATION
DF DOUG FIR-LARCH
DIA DIAMETER
EA EACH
EC EPOXY COATED
EF EACH FACE
EL ELEVATION
EQ EQUAL
EW EACH WAY
FDN FOUNDATION
FO FLOOR OPENING
GA GAUGE
HDG HOT-DIP GALVANIZED
HORIZ HORIZONTAL
k KIP = 1,000 POUNDS
MAX MAXIMUM
MIN MINIMUM
NTS NOT TO SCALE
OC ON-CENTER
PEMB PRE-ENGINEERED METAL BUILDING
PL PLATE
PSF POUNDS PER SQUARE FOOT
PT PRESSURE TREATED
RO ROOF OPENING
SIM SIMILAR
T&B TOP AND BOTTOM
TF TOP OF FOOTING ELEVATION
TP TOP OF PIER ELEVATION
TS TOP OF STEEL ELEVATION
TW TOP OF WALL ELEVATION
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
w/ WITH
WWF WELDED WIRE FABRIC
FOUNDATIONS
1. LOCATE ALL UNDERGROUND UTILITIES BEFORE STARTING WORK. CONTACT UTILITY LOCATING SERVICES PRIOR TO EXCAVATION. IN
MICHIGAN CALL "MISS DIG" 800-482-7171 AT LEAST 72 HOURS PRIOR TO STARTING WORK.
2. ANY EXISTING UTILITIES INDICATED ON DRAWINGS ARE BASED ON ORIGINAL CONSTRUCTION DRAWINGS AND SITE SURVEYS. EXACT
UTILITY LOCATIONS AND ELEVATIONS OF UTILITIES MUST FIELD VERIFIED BY THE CONTRACTOR PRIOR TO BEGINNING WORK.
3. FOUNDATION DESIGN IS BASED ON AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSF FOR SANDY SOILS PER MBC 1806.2
PRESUMPTIVE LOAD BEARING VALUES AND TABLE 1806.2. TESTING AGENCY SHALL VERIFY ALLOWABLE BEARING CAPACITY PRIOR TO
PLACING FOUNDATIONS.
4. FOOTINGS SHALL BEAR ON UNDISTURBED SOIL AT ELEVATIONS SHOWN ON THE DRAWINGS. IF OVER-EXCAVATION IS REQUIRED, ENGINEERED COMPACTED FILL SHALL BE PLACED PER SPECIFICATIONS UP TO BEARING ELEVATION. ALL ENGINEERED COMPACTED FILL
SHALL BE PLACED IN THE PRESENCE OF AND AS DIRECTED BY A QUALIFIED GEOTECHNICAL ENGINEERING FIRM. LOCATION AND EXTENT
OF AREAS TO RECEIVE ENGINEERED COMPACTED FILL SHALL BE PER THE GEOTECHNICAL REPORT AND TESTING OF SOILS SHALL BE
ACCORDING TO SPECIFICATIONS PRIOR TO PLACEMENT OF FOOTINGS.
5. CONTRACTOR SHALL PROVIDE SLEEVES FOR ALL OPENINGS REQUIRED IN WALLS. NO CORE DRILLING WILL BE ALLOWED WITHOUT
PRIOR APPROVAL BY THE STRUCTURAL ENGINEER. COORDINATE LOCATION AND SIZE OF OPENINGS WITH APPLICABLE CONTRACTORS.
6. DO NOT REPAIR MISPLACED OR DAMAGED COLUMN ANCHOR BOLTS WITHOUT PRIOR APPROVAL BY THE STRUCTURAL ENGINEER.
7. WHERE FOUNDATION WALLS ARE TO HAVE EARTH PLACED ON EACH SIDE, PLACE FILL ON ALTERNATING SIDES OF WALL IN SHALLOW
LIFTS.
8. COORDINATE ELECTRICAL SERVICE GROUNDING REQUIREMENTS TO FOUNDATION REINFORCING WITH ELECTRICIAN. REFER TO
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
LOCATION 28 DAY f'c (PSI) AIR CONTENT MAX W/C
FOOTINGS & FOUNDATION WALLS 4,000 6% ± 1% 0.50
INTERIOR SLABS 4,000 NO TEST 0.50
RETAINING WALLS & ALL OTHER CONCRETE EXPOSED TO WEATHER 4,500 6% ± 1% 0.45
CONCRETE
1. ALL MATERIAL AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH APPLICABLE AMERICAN CONCRETE INSTITUTE (ACI) DOCUMENTS
REFERENCED IN SPECIFICATIONS.
2. MATERIAL PROPERTIES:
3. REINFORCEMENT BARS SHALL BE ASTM A615 GRADE 60 UNO.
4. SUBMIT EACH CONCRETE MIX DESIGN FOR REVIEW. SUBMITTAL SHALL CONSIST OF DESIGN MIXES FOR EACH TYPE AND STRENGTH OF
CONCRETE AND INCLUDE DATA BY EITHER LABORATORY TRIAL MIX OR FIELD TEST DATA BASE PER ACI 318.
5. ALL CONCRETE SHALL BE CURED FOR A MINIMUM OF 7 DAYS PRIOR TO REMOVAL OF FORMS. IF FORMS ARE REMOVED BEFORE THE
END OF CURING PERIOD, COAT SURFACES WITH LIQUID CURING COMPOUND.
6. PROVIDE DOWELS IN WALL FOOTINGS WITH EQUAL SIZE AND SPACING AS VERTICAL WALL STEEL, UNO.
7. ALL OPENINGS IN SLABS AND WALLS SHALL HAVE REINFORCEMENT ON EACH SIDE EQUAL TO HALF THE AMOUNT OF REINFORCING
DISPLACED. REFER TO TYPICAL DETAIL.
8. ALL CONCRETE SLABS ON GRADE SHALL BE REINFORCED WITH 6"x6"- W1.4xW1.4 WELDED WIRE FABRIC UNO.
9. REFER TO ARCHITECTURAL DRAWINGS FOR SIZE, DEPTH, AND LOCATION OF DEPRESSED FLOOR SLABS REQUIRED.
10. PROVIDE CLASS "B" TENSION LAP SPLICES FOR ALL BARS UNO.
11. TOP BARS ARE DEFINED AS HORIZONTAL REINFORCEMENT POSITIONED SUCH THAT MORE THAN 12" OF FRESH CONCRETE IS PLACED
BELOW THE REINFORCEMENT. ALL HORIZONTAL BARS IN WALLS SHALL BE CONSIDERED TOP BARS.
12. MECHANICAL COUPLERS DEVELOPING AT LEAST 125% OF THE BAR YIELD STRENGTH MAY BE USED AT CONTRACTOR'S OPTION IN LIEU
OF LAP SPLICES. CONTRACTOR SHALL SUBMIT MECHANICAL COUPLER PRODUCT DATA TO ENGINEER FOR REVIEW PRIOR TO STARTING
CONSTRUCTION OR ORDERING MATERIAL.
13. TOP AND BOTTOM HORIZONTAL REINFORCEMENT IN WALLS TO BE LOCATED NO LESS THAN 2" AND NO MORE THAN 3" FROM TOP OR
BOTTOM OF THE WALL.
14. WHERE BAR LENGTHS ARE GIVEN ON DRAWINGS, THE LENGTH OF ANY HOOK, IF REQUIRED, IS NOT INCLUDED.
15. THE HARDENED CONCRETE OF CONSTRUCTION JOINTS SHALL BE CLEANED TO REMOVE ALL DEBRIS AND LAITANCE. DAMPEN SURFACE
OF HARDENED CONCRETE TO A SATURATED SURFACE DRY CONDITION IMMEDIATELY BEFORE PLACING FRESH CONCRETE.
16. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A1064 DELIVERED IN FLAT SHEETS.
17. LAP WELDED WIRE FABRIC ONE SPACE (TWO CROSS WIRES) + 2" AT ALL EDGES AND ENDS OF SHEETS.
18. WELDING OF REINFORCEMENT STEEL IS NOT PERMITTED UNO.
19. PROVIDE 3/4" CHAMFERS ON EXPOSED CORNERS OF COLUMNS, BEAMS, AND WALLS UNLESS OTHERWISE INDICATED ON THE
ARCHITECTURAL DRAWINGS. MINIMUM CLEAR COVER FOR REINFORCEMENT BARS SHALL CONFORM WITH THE CLEAR COVER
REQUIREMENTS NOTED BELOW.
20. COMPLY WITH THE ARCHITECTURAL DRAWINGS FOR LOCATION AND EXTENT OF SPECIAL FINISHES OR TREATMENTS TO EXPOSED
CONCRETE.
BAR SIZE
LAP LENGTH (fc = 4,000 PSI)
STANDARD 90°
HOOK LENGTH
STANDARD
180° HOOK
LENGTHTOP BARS OTHER BARS
#3 25" 19" 6" 4"
#4 33" 25" 8" 4 1/2"
#5 41" 31" 10" 5"
#6 49" 37" 12" 6"
#7 71" 54" 14" 7"
#8 81" 62" 16" 8"
CONCRETE REINFORCEMENT CLEAR COVER REQUIREMENTS
OCCURANCES COVER
1. CONCRETE CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3"
2. CONCRETE EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
A. #5 BAR AND SMALLER 1 1/2"
B. #6 BAR AND LARGER 2"
3. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
A. SLABS, JOISTS, AND WALLS (NOT LARGER THAN #11 BAR) 3/4"
B. BEAMS, COLUMNS, AND PIERS 1 1/2"
NOTE: CLEAR COVER DIMENSIONS LISTED ARE CODE-REQUIRED MINIMUMS. PROVIDE GREATER COVER
WHERE SPECIFICALLY REQUIRED BY DETAILS.
CONCRETE TESTING
1. TESTING AGENCY: OWNER WILL ENGAGE A QUALIFIED INDEPENDENT TESTING AND INSPECTING AGENCY TO SAMPLE MATERIALS, PERFORM TESTS, AND SUBMIT TEST REPORTS DURING CONCRETE PLACEMENT. SAMPLING AND TESTING FOR QUALITY CONTROL MAY
INCLUDE THOSE SPECIFIED IN THIS ARTICLE.
2. TESTING SERVICES: TESTING OF COMPOSITE SAMPLES OF FRESH CONCRETE OBTAINED ACCORDING TO ASTM C172 SHALL BE
PERFORMED ACCORDING TO THE FOLLOWING REQUIREMENTS:
A. TESTING FREQUENCY: OBTAIN AT LEAST ONE COMPOSITE SAMPLE FOR EACH 100 CUBIC YARD OR FRACTION THEREOF OF EACH
CONCRETE MIX PLACED EACH DAY. WHEN FREQUENCY OF TESTING WILL PROVIDE FEWER THAN FIVE COMPRESSIVE-STRENGTH TESTS
FOR EACH CONCRETE MIX, TESTING SHALL BE CONDUCTED FROM AT LEAST FIVE RANDOMLY SELECTED BATCHES OR FROM EACH
BATCH IF FEWER THAN FIVE ARE USED.
B. SLUMP: ASTM C143, ONE TEST AT POINT OF PLACEMENT FOR EACH COMPOSITE SAMPLE, BUT NOT LESS THAN ONE TEST FOR EACH
DAY'S POUR OF EACH CONCRETE MIX. PERFORM ADDITIONAL TESTS WHEN CONCRETE CONSISTENCY APPEARS TO CHANGE.
C. AIR CONTENT: ASTM C231, PRESSURE METHOD, FOR NORMAL-WEIGHT CONCRETE; ONE TEST FOR EACH COMPOSITE SAMPLE, BUT NOT
LESS THAN ONE TEST FOR EACH DAY'S POUR OF EACH CONCRETE MIX.
D. CONCRETE TEMPERATURE: ASTM C1064, ONE TEST HOURLY WHEN AIR TEMPERATURE IS 40 DEGREES F AND BELOW AND WHEN 80
DEGREES F AND ABOVE, AND ONE TEST FOR EACH COMPOSITE SAMPLE.
E. COMPRESSIVE-STRENGTH TESTS: ASTM C39, TEST TWO LABORATORY-CURED SPECIMENS AT 7 DAYS AND THREE AT 28 DAYS. A
COMPRESSIVE-STRENGTH TEST SHALL BE THE AVERAGE COMPRESSIVE STRENGTH FROM SPECIMENS OBTAINED FROM THE SAME
COMPOSITE SAMPLE AND TESTED AT THE AGE INDICATED. CAST AND FIELD CURE ADDITIONAL SETS OF STANDARD CYLINDER
SPECIMENS IN SETS OF THREE FOR EACH COMPOSITE SAMPLE WHEN REQUIRED TO VERIFY STRENGTH OF IN PLACE CONCRETE FOR
REMOVAL OF SHORING. SPECIMENS SHALL BE STORED ADJACENT TO AND CURED SIMILAR TO CONCRETE TO BE VERIFIED.
3. WHEN STRENGTH OF FIELD-CURED CYLINDERS (IF REQUIRED) IS LESS THAN 85 PERCENT OF COMPANION LABORATORY-CURED
CYLINDERS, CONTRACTOR SHALL EVALUATE OPERATIONS AND PROVIDE CORRECTIVE PROCEDURES FOR PROTECTING AND CURING
IN-PLACE CONCRETE.
4. STRENGTH OF EACH CONCRETE MIX WILL BE SATISFACTORY IF EVERY AVERAGE OF ANY THREE CONSECUTIVE COMPRESSIVE-STRENGTH
TESTS EQUALS OR EXCEEDS SPECIFIED COMPRESSIVE STRENGTH AND NO COMPRESSIVE-STRENGTH TEST VALUE FALLS BELOW
SPECIFIED COMPRESSIVE STRENGTH BY MORE THAN 500 PSI.
5. TEST RESULTS SHALL BE REPORTED IN WRITING TO ENGINEER, CONCRETE MANUFACTURER, AND CONTRACTOR WITHIN 48 HOURS OF
TESTING. REPORTS OF COMPRESSIVE-STRENGTH TESTS SHALL CONTAIN PROJECT IDENTIFICATION NAME AND NUMBER, DATE OF
CONCRETE PLACEMENT, NAME OF CONCRETE TESTING AND INSPECTING AGENCY, LOCATION OF CONCRETE BATCH IN WORK, DESIGN
COMPRESSIVE STRENGTH AT 28 DAYS, CONCRETE MIX PROPORTIONS AND MATERIALS, COMPRESSIVE BREAKING STRENGTH, AND TYPE
OF BREAK FOR BOTH 7- AND 28-DAY TESTS.
6. NONDESTRUCTIVE TESTING: IMPACT HAMMER SONOSCOPE, OR OTHER NONDESTRUCTIVE DEVICE MAY BE PERMITTED BY ENGINEER
BUT WILL NOT BE USED AS SOLE BASIS FOR APPROVAL OR REJECTION OF CONCRETE.
7. ADDITIONAL TESTS: TESTING AND INSPECTING AGENCY SHALL MAKE ADDITIONAL TESTS OF CONCRETE WHEN TEST RESULTS INDICATE
THAT SLUMP, AIR ENTRAINMENT, COMPRESIVE STRENGTHS, OR OTHER REQUIREMENTS HAVE NOT BEEN MET, AS DIRECTED BY
ENGINEER. TESTING AND INSPECTING AGENCY MAY CONDUCT TESTS TO DETERMINE ADEQUACY OF CONCRETE BY CORED CYLINDERS
COMPLYING WITH ASTM C42 OR BY OTHER METHODS AS DIRECTED BY ARCHITECT.
POST-INSTALLED ANCHORS
1. POST-INSTALLED ADHESIVE ANCHORS:
A. INSTALL PER MANUFACTURERS PRINTED INSTALLATION INSTRUCTIONS (MPII).
B. DO NOT INSTALL ANCHORS IN WET OR SATURATED CONCRETE.
C. DO NOT INSTALL ANCHORS IN CONCRETE LESS THAN 21 DAYS OLD OR UNTIL CONCRETE HAS REACHED ITS DESIGN STRENGTH, WHICHEVER COMES FIRST.
D. VERIFY ADHESIVE EXPIRATION DATE PRIOR TO INSTALLATION.
E. DO NOT CORE DRILL HOLES FOR ADHESIVE ANCHORS.
F. CLEAN HOLES PER MPII.
G. CURE ADHESIVE PER MPII PRIOR TO LOADING ANCHORS.
H. ADHESIVE FOR REBAR AND ANCHORS SHALL HAVE BEEN TESTED IN ACCORDANCE WITH ACI355.4 AND ICC-ES ACI 308 FOR CRACKED
CONCRETE AND SEISMIC APPLICATIONS.
I. ANCHOR DESIGN IS BASED ON ADHESIVE BOND STRENGTH PER ACI 355.4 TEMPERATURE CATEGORY B WITH INSTALLATIONS INTO DRY
HOLES DRILLED USING A CARBIDE DRILL BIT INTO CRACKED CONCRETE THAT HAS CURED FOR AT LEAST 21 DAYS.
2. POST-INSTALLED MECHANICAL ANCHORS:
A. INSTALL PER MANUFACTURERS PRINTED INSTALLATION INSTRUCTIONS (MPII).
B. DO NOT CORE DRILL HOLES FOR MECHANICAL ANCHORS.
C. CLEAN HOLES PER MANUFACTURERS REQUIREMENTS.
D. INSTALL IN STRICT COMPLIANCE WITH MANUFACTURERS REQUIREMENTS.
MASONRY
1. MASONRY WORK SHALL CONFORM TO TMS 402/602.
2. MATERIAL PROPERTIES:
3. ALL MASONRY WALLS SHALL BE REINFORCED WITH LADDER TYPE HORIZONTAL JOINT REINFORCEMENT PLACED EVERY OTHER COURSE
FOR RUNNING BOND AND EVERY COURSE FOR STACK BOND. PROVIDE GALVANIZED WIRE REINFORCEMENT WITH #9 GAGE SIDE RODS
AND #9 GAGE CROSS RODS SPACED 16" OC. FOR TWO WYTHE WALLS, PROVIDE HOOK AND PINTEL TIES.
4. SPLICES OF JOINT REINFORCEMENT SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT LEAST ONE CROSS WIRE OF EACH PIECE OF
REINFORCEMENT WITHIN THE LAP.
5. PROVIDE LINTELS OVER ALL OPENINGS WIDER THAN 8" IN MASONRY WALLS. REFER TO THE ARCHITECTURAL AND MECHANICAL
DRAWINGS FOR LOCATION, NUMBER, AND SIZES OF OPENINGS.
6. PROVIDE LINTELS PER THE FOLLOWING TABLE UNO ON THE DRAWINGS:
7. PROVIDE A MINIMUM OF 8" BEARING AT EACH END OF ALL LINTELS UNO.
8. ALL REINFORCEMENT BARS SHALL BE LAP SPLICED. VERTICAL BARS SHALL BE HELD IN POSITION WITH BAR POSITIONERS.
9. MECHANICAL COUPLERS DEVELOPING AT LEAST 125% OF THE BAR YIELD STRENGTH MAY BE USED AT CONTRACTOR'S OPTION IN LIEU
OF LAP SPLICES. CONTRACTOR SHALL SUBMIT MECHANICAL COUPLER PRODUCT DATA TO ENGINEER FOR REVIEW PRIOR TO STARTING
CONSTRUCTION OR ORDERING MATERIAL.
10. NO OPENINGS, PENETRATIONS, OR VERTICAL PIPE OR CONDUIT RISERS SHALL OCCUR IN MASONRY WALLS WITHIN 16" OF CENTERLINE
11. GROUT MASONRY CELLS AS FOLLOWS:
A ALL CELLS CONTAINING REINFORCEMENT BARS.
B ALL CELLS BELOW GRADE / SLAB-ON-GRADE.
C ALL CELLS BELOW LINTEL AND BEAM BEARING, DOWN TO FOUNDATION.
D ALL CELLS WHERE REQUIRED FOR ANCHORING TO MASONRY, AND WHERE SPECIFICALLY SHOWN IN THE DETAILS.
12. UNITS SHALL BE MANUFACTURED AND INSTALLED SO THE CORES AND WEBS ALIGN WHEN LAID IN RUNNING BOND. ALL
OVERHANGING MORTAR, OBSTRUCTIONS AND DEBRIS SHALL BE CLEANED FROM THE INSIDE OF CELLS PRIOR TO GROUTING.
13. REINFORCEMENT SHALL BE PLACED PRIOR TO GROUTING.
14. MAXIMUM HEIGHT OF GROUT POURS SHALL NOT EXCEED 5’-0” . BETWEEN GROUT POURS, A HORIZONTAL CONSTRUCTION JOINT
SHALL BE FORMED BY STOPPING GROUT 1 1/2" BELOW MORTAR JOINT EXCEPT AT THE TOP OF THE WALL.
15. ALL CMU WALLS SHALL BE REINFORCED VERTICALLY AS SPECIFIED ON DRAWINGS WITH THE SPECIFIED BAR FOR THAT WALL AT THE
ENDS OF WALLS, AT CORNERS, AT EACH SIDE OF CONTROL OR EXPANSION JOINTS, AND AT EACH SIDE OF OPENING, ALL IN FULLY
GROUTED CELLS. IF REINFORCEMENT IS NOT SHOWN ON DRAWINGS, REINFORCE w/ #5 BARS AT 4'-0" ON CENTER.
16. PROVIDE DOWELS INTO FLOOR OR FOUNDATION AT BOTTOM OF WALL TO MATCH SIZE AND SPACING OF VERTICAL WALL
REINFORCEMENT.
17. DO NOT CONSTRUCT MASONRY WALLS ON SUPPORTED CONCRETE DECKS UNTIL CONCRETE HAS REACHED 28 DAY STRENGTH AND
ALL SHORING HAS BEEN REMOVED.
18. STABILIZE TOP OF ALL WALLS PER TYPICAL DETAILS.
19. ALL MASONRY WALL INTERSECTIONS SHALL BE CONSTRUCTED AS FOLLOWS UNO ON PLANS OR DETAILS:
A. ALL INTERSECTING 90° CORNERS SHALL BE BONDED AND SHALL BE REINFORCED WITH ONE VERTICAL BAR IN A GROUTED CELL AT THE
WALL INTERSECTION AND PREFABRICATED L-SHAPED HORIZONTAL JOINT REINFORCEMENT AT 16" OC.
B. UNLESS NOTED OTHERWISE, ALL TEE INTERSECTIONS SHALL BE JOINED WITH 1/4"x1/4" GALVANIZED MESH HARDWARE CLOTH @ 16"
OC IN SOLID GROUTED CELLS WITH MESH EXTENDING A MINIMUM OF 3" INTO EACH WALL.
20. PROVIDE TEMPORARY BRACING OF MASONRY WALLS UNTIL ALL FINAL ROOF AND FLOOR FRAMING IS COMPLETE INCLUDING ALL
FINAL CONNECTIONS TO METAL DECK AND CONCRETE FLOOR SLABS AND MASONRY HAS REACHED DESIGN STRENGTH.
21. CMU CONTROL JOINTS: PROVIDE CONTROL JOINTS AS SHOWN ON THE STRUCTURAL DRAWINGS. IF NO CONTROL JOINTS ARE SHOWN
ON THE DRAWINGS, PROVIDE CONTROL JOINTS AT A MAXIMUM SPACING OF 25 FEET OR 1.5 TIMES THE WALL HEIGHT, WHICHEVER IS
LESS. LOCATE JOINTS NOT MORE THAN ONE HALF THE MAXIMUM SPACING IN FROM EACH SIDE OF OUTSIDE CORNERS, AT ABRUPT
CHANGES IN WALL HEIGHT, AND AT CHANGES IN WALL THICKNESS.
MASONRY 28 DAY COMPRESSIVE STRENGTH f'm = 2,000 PSI
CONCRETE MASONRY UNITS 2,000 PSI ASTM C90, NORMAL WEIGHT UNITS
MORTAR (TYPE S) 2,000 PSI ASTM C270
GROUT ASTM C476
GROUT 28 DAY COMPRESSIVE STRENGTH 2,000 PSI
OPENING SIZE STEEL LINTEL PER 4" OF WALL MASONRY LINTEL
0' TO 4'-0" L4x3 1/2x1/4 8" DEEP w/ (2) #4
2'-0" TO 3'-4" L5x3 1/2x1/4 16" DEEP w/ (2) #4
BAR SIZE
LAP LENGTH FOR BARS
CENTERED IN WALL
LAP LENGTH FOR BARS
EACH FACE OF WALL
#3 18" 18"
#4 24" 24"
#5 30" 30"
#6 38" 54"
#7 52" 63"
PRE-ENGINEERED METAL BUILDING
1. PROVIDE BUILDING IN COMPLIANCE WITH CURRENT MICHIGAN BUILDING CODE AND METAL BUILDING MANUFACTURERS
ASSOCIATION DESIGN STANDARDS.
2. FABRICATE PRIMARY BUILT-UP MEMBERS IN ACCORDANCE WITH MBMA METAL BUILDING SYSTEMS MANUAL AND PROVIDE HOT
ROLLED MEMBERS FABRICATED IN ACCORDANCE WITH AISC SPECIFICATION FOR PIPE, TUBE, AND ROLLED STRUCTURAL SHAPES, USING
ASTM A325 HIGH STRENGTH BOLTS.
3. DELEGATED DESIGN SUBMITTAL: SUBMIT ANALYSIS DATA INDICATING PERFORMANCE REQUIREMENTS AND DESIGN DATA SIGNED AND
SEALED BY QUALIFIED PROFESSIONAL ENGINEER LICENSED IN THE STATE THE PROJECT IS TO BE LOCATED.
4. DELEGATED DESIGN: THE BUILDING SHALL BE DESIGNED BY THE MANUFACTURER‘S LICENSED PROFESSIONAL ENGINEER AND SHALL
WITHSTAND THE EFFECTS OF ALL CODE REQUIRED LOADING AS INDICATED PLUS THE FOLLOWING LOADS:
5. PEMB SHALL MEET THE FOLLOWING DEFLECTION CRITERIA UNDER LOADS INDICATED:
A. LATERAL DRIFT: EAVE HEIGHT (INCHES) /60
D. VERTICAL DEFLECTION: AS INDICATED IN MBC TABLE 1604.3
COLLATERAL LOADS: 5 PSF
ROOF TOP EQUIPMENT: REFER TO PLAN & MECHANICAL
COLD-FORMED METAL FRAMING
1. ALL MATERIALS AND WORKMANSHIP SHALL BE IN COMPLIANCE WITH AMERICAN IRON AND STEEL INSTITUTE (AISI) DESIGN OF COLD
FORMED STEEL STRUCTURAL MEMBERS AND AMERICAN WELDING SOCIETY (AWS) STRUCTURAL WELDING CODE - SHEET STEEL. THIS
SPECIFICATION APPLIES TO ALL COLD FORMED STRUCTURAL LOAD BEARING MEMBERS.
2. ENGAGE QUALIFIED PROFESSIONAL ENGINEER TO DESIGN COLD-FORMED METAL FRAMING. FRAMING INDICATED REPRESENTS THE
MINIMUM SIZE, GAGE, AND SPACING REQUIRED. IF DELEGATED DESIGN REQUIREMENTS ARE DIFFERENT, PROVIDE THE MORE
STRINGENT REQUIREMENTS.
3. FOR 16 GAGE AND HEAVIER UNITS, USE FY=50 KSI PER ASTM A653 UNO. FOR 18 GAGE AND LIGHTER UNITS, USE FY=33 KSI UNO.
4. PROVIDE GALVANIZED FINISH TO METAL FRAMING COMPONENTS COMPLYING WITH ASTM A 525 FOR MINIMUM G60 COATING.
5. AXIALLY LOADED STUDS SHALL HAVE FULL BEARING AGAINST INSIDE TRACK WEB. SPLICES IN STUDS AND JOISTS ARE NOT PERMITTED.
6. FASTEN ALL COMPONENTS WITH EITHER SELF-TAPPING SCREWS OR WELDING OF SUFFICIENT SIZE TO ENSURE STRENGTH OF
CONNECTION AND AS SPECIFICALLY INDICATED ON THE DRAWINGS. ALL WELDS SHALL BE TOUCHED UP WITH ZINC ENRICHED PRIMER.
7. ALL BEARING WALL STUDS SHALL BE ALIGNED AND SECURELY ATTACHED TO THE FLANGE OR WEB OF BOTH UPPER AND LOWER
TRACKS. ALL ABUTTING TRACK JOINTS SHALL BE SECURELY ANCHORED TO A COMMON STRUCTURAL ELEMENT OR SHALL BE BUTT
WELDED OR SPLICED TOGETHER.
8. JACK STUDS OR CRIPPLES SHALL BE INSTALLED BELOW ALL OPENINGS FOR HEADER SUPPORT AND SHALL BE FIRMLY ATTACHED TO
SUPPORTING MEMBERS.
9. PROVIDE CONTINUOUS U-CHANNEL STUD BRIDGING IN ALL LOAD BEARING WALLS AT A SPACING NOT EXCEEDING 48" ON CENTER.
WALL STUD U-CHANNELS SHALL BE ATTACHED IN A MANNER TO PREVENT STUD ROTATION.
10. JOISTS SHALL BE LOCATED DIRECTLY OVER BEARING STUDS. PROVIDE WEB STIFFENERS AT THE JOIST REACTION POINTS WHERE
INDICATED ON PLANS OR AS REQUIRED BY DELEGATED DESIGN.
11. PROVIDE JOIST BRIDGING AT MID-SPAN UNO ON PLANS. PROVIDE END BLOCKING WHERE JOISTS ARE NOT OTHERWISE RESTRAINED.
12. PROVIDE VERTICAL SLIP CONNECTIONS WHERE NON-LOAD BEARING WALLS SPAN BETWEEN TWO OR MORE LEVELS OF THE BUILDING, OR WHERE SPECIFICALLY NOTED ON THE DRAWINGS, TO ALLOW VERTICAL DEFLECTION OF THE BUILDING FRAME WITHOUT LOADING
THE STUDS.
13. COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ALL COLD-FORMED METAL FRAMING LOCATIONS AND
REQUIREMENTS. COORDINATE LOCATIONS AND DESIGN FOR ALL WALL HUNG EQUIPMENT.
REQUIRED SPECIAL INSPECTIONS OF LOAD-BEARING COLD-FORMED METAL FRAMING
SPECIAL INSPECTION TASK
CONTINUOUS SPECIAL
INSPECTION
PERIODIC SPECIAL
INSPECTION
1. VERIFY STUD, TRACK, AND JOIST SIZES AND GAUGES ARE IN COMPLIANCE WITH THE
SHOP DRAWINGS AND INSTALLATION DRAWINGS
2. VERIFY PROPER SEATING OF STUDS IN TRACK
3. VERIFY HEADER SIZES, GAUGES, AND CONNECTION DETAILS ARE IN COMPLIANCE WITH
THE SHOP DRAWINGS AND INSTALLATION DRAWINGS
4. VERIFY SCREW ATTACHMENTS, BOLTING, ANCHORING AND OTHER FASTENING OF
COMPONENTS ARE IN COMPLIANCE WITH THE SHOP DRAWINGS AND INSTALLATION
DRAWINGS
5. VERIFY WELDING OF ELEMENTS IS IN COMPLIANCE WITH THE SHOP DRAWINGS AND
INSTALLATION DRAWINGS
6. VERIFY STUD AND JOIST BRIDGING DETAILS AND SPACING ARE IN COMPLIANCE WITH THE
SHOP DRAWINGS AND INSTALLATION DRAWINGS
7. WHERE COLD-FORMED STEEL TRUSS SPAN IS 60 FEET OR GREATER, VERIFY THAT THE
TEMPORARY INSTALLATION RESTRAINT/BRACING AND THE PERMANENT INDIVIDUAL
TRUSS MEMBER RESTRAINT/BRACING ARE INSTALLED IN ACCORDANCE WITH THE
APPROVED TRUSS SUBMITTAL PACKAGE
X
X
X
X
X
X
X
NOTE: LOAD-BEARING COLD-FORMED METAL FRAMING INCLUDES BOTH VERTICAL- AND LATERAL- LOAD-BEARING ELEMENTS. VERTICAL LOAD-
BEARING ELEMENTS ARE THOSE WHICH CARRY VERTICAL LOADS OTHER THAN THEIR SELF-WEIGHT AND THE WEIGHT OF APPLIED SHEATHING
MATERIALS. LATERAL LOAD-BEARING ELEMENTS INCLUDE ELEMENTS OF THE LATERAL FORCE-RESISTING SYSTEM SUCH AS SHEAR WALLS, STRAP-
BRACED WALLS, AND DIAPHRAGMS; AND INCLUDE ALL EXTERIOR WALL AND SOFFIT FRAMING.
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION
SPECIAL INSPECTION TASK
CONTINUOUS SPECIAL
INSPECTION
PERIODIC SPECIAL
INSPECTION
1. INSPECT REINFORCEMENT AND VERIFY PLACEMENT.
2. REINFORCMENT BAR WELDING (PERMITTED ONLY WHEN SPECIFICALLY SHOWN IN THE
DETAILS OR WITH PERMISSION IN WRITING BY THE ENGINEER):
A. VERIFY WELDABILITY OF REINFORCMENT BARS OTHER THAN ASTM A706
B. INSPECT SINGLE-PASS FILLET WELDS UP TO AND INCLUDING 5/16"
C. INSPECT ALL OTHER WELDS
3. INSPECT ANCHORS CAST IN CONCRETE
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS
B. ALL OTHER ANCHORS POST-INSTALLED IN HARDENED CONCRETE
5. VERIFY USE OF REQUIRED DESIGN MIX.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS,
PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF THE
CONCRETE.
7. INSPECT CONCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES.
9. INSPECT PRESTRESSED CONCRETE FOR APPLICATION OF PRESTRESSING FORCES.
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
11. VERIFY IN-SITU CONCRETE STRENGTH PRIOR TO REMOVAL OF SHORES AND FORMS FROM
BEAMS AND STRUCTURAL SLABS.
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF CONCRETE MEMBER
BEING FORMED.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
EXCEPTIONS - THE ABOVE SPECIAL INSPECTIONS AND TESTS SHALL NOT BE REQUIRED FOR THE FOLLOWING BUILDING ELEMENTS:
1. ISOLATED SPREAD FOOTINGS OF BUILDINGS THREE STORIES OR LESS ABOVE GRADE THAT ARE FULLY SUPPORTED ON EARTH OR ROCK.
2.…