Addendum Two .pdf

PDF 2 MB Posted

Attached to
RFB-157-24 KCTCS Interior Renovation Henderson CC
Solicitation number
RFB-785-2400000371-3
Issued by
Henderson County, Kentucky

About this file

This document is an addendum to an Invitation to Bid (ITB) issued by the Commonwealth of Kentucky Department for Facilities and Support Services Division of Engineering and Contract Administration for the Interior Renovation of the Academic Technical Building at Henderson Community College in the Kentucky Community & Technical College System. The addendum provides updates to the specifications and drawings, including adding stamped ACCUREX drawings, replacing electrical drawings, and modifying the scope of work for the adjacent lab space. The addendum also revises the Alternate Bid No. 1 to include a fireplace and motorized roller shades in lieu of manually operated shades. The bid response date remains February 21, 2024.

The ITB includes an electrical legend, lighting fixture schedule, electrical demolition plans, power and systems plans, a one-line diagram, and detailed drawings for the kitchen exhaust hood, fire suppression system, and utility distribution system. The electrical work involves modifying existing circuits, connecting new lighting and equipment, and integrating the fire suppression system. The kitchen equipment includes an exhaust hood, exhaust fan, controls, and fire suppression system. Pricing, set asides, funding sources, and other salient commercial terms are not provided in the addendum.

View the file

Other files

File Type Posted
Final_RFB_785_2400000371_1_SO_FORM.PDF PDF
Addendum One .pdf PDF
Final_RFB_785_2400000371_3_SO_FORM.PDF PDF
Final_RFB_785_2400000371_2_SO_FORM.PDF PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-157-24

FOR: Interior Renovation Academic Technical Building Henderson Community College Kentucky Community & Technical College System Henderson, Kentucky

DATE: February 21, 2024

RFB-785-2400000371

ADDENDUM NO. Two (2)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-157-24 For: Interior Renovation Academic Technical Building Henderson Community College Kentucky Community & Technical College System Henderson, Kentucky

Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration

P a g e

T000-LASTNAME-

INT

Project: Addendum No.:

Date:

Owner: Project Number:

Contract for:

The original specifications and drawings dated October, 2023 for the project noted above are amended as noted in this Addendum Number 002. Receipt of this addendum and any subsequent addenda must be acknowledged on the final bid documents. This addendum consists of Ten (10) item(s) and Two (2) attachment(s).

2-1 Add stamped ACCUREX drawings attached. Work shown therein becomes part of the contract. Delete Addendum Item 1-1 noting drawings are for reference only.

2-2 Replace the Electrical Drawings in the Construction Documents noted “Not for Construction” with the Stamped Drawings attached.

2-3 Reference Sheet A1.1, Food Service Demolition, Floor & RCP Plans. At the adjacent Lab Space located south of the proposed kitchen, add a Dust Barrier Wall similar to that shown at Room 202 on Sheet A2.1, Cyber Café Demolition Plan & Floor Plan. Additionally add Dust Barrier Walls to the south exterior wall when concrete demolition and piping installation work is underway through the

Lab. Protect existing construction and furnishings.

2-4 Work in the adjacent Lab is restricted to no earlier than May 3 and no later than August 1, 2024.

2-5 Reference attached Sheets M5-1, M5-2, M5-3, M5-4, M5-5 and M5-6.

2-6 Disregard Addendum Item 1-2. Drawings M5-1, M5-2, M5-3, M5-4, M5-5 and M5-6 shall be included in the project. All material and labor associated with hood and fan shall be included.

2-7 Reference attached sheets E1-1, E1-2, E1-3, E1-4, E2-1, E2-2 and E3-1.

2-8 Reference attached sheet E2-1, for modifications for power feed to motorized roller shades.

2-9 Provide five (5) blinds, each +/- 11’-8” wide to cover the entire length of the curtain wall at

Room 202.

2-10 Change Alternate Bid No. 1 to read as follows:

P a g e

Attachments:

By:

CC:

Alternate No. 1

At Room 102, CYBER CAFÉ:

Manually Operated Roller Shades, as specified in Section 122413, Roller Window Shades, shall be installed at the existing curtainwall as part of the Base Bid. Base Bid also includes installation of all required electrical rough-in and wiring for a complete, future motorized installation.

This Alternate Bid is to furnish and install motorized Roller Shades in lieu of Manually Operated Roller Shades as described above.

Aquafire Fireplace (AWA-60-150) at the TV Feature Wall. Work includes creating the wall opening for the fireplace and all required electrical and plumbing rough-in for a complete installation. If this Alternate Bid is not accepted the fireplace will not be installed in the future and the opening and electrical and plumbing rough-in will not be required.

S a,b,c,...

WALL MOUNT JUNCTION BOX.

PHASE

CONDUCTOR

NEUTRAL

GROUND

LC1-1

CEILING OUTLET AND LIGHTING FIXTURE AS SCHEDULED.

SYMBOL DESCRIPTIONDESCRIPTIONSYMBOL

WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE. MOUNT

18 INCHES ABOVE FINISHED FLOOR TO CENTER, UNLESS

NOTED OTHERWISE.

WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE. MOUNT

46 INCHES ABOVE FINISHED FLOOR TO CENTER, OR 8 INCHES

ABOVE COUNTER OR COUNTER BACKSPLASH TO CENTER,

UNLESS NOTED OTHERWISE.

CEILING MOUNT JUNCTION BOX.

SYMBOL INDICATES FIXTURE TYPE WHEN SHOWN ON LIGHTING

PLANS AND SITE ELECTRICAL PLANS ADJACENT TO FIXTURE

SYMBOL. REFER TO LIGHTING FIXTURE SCHEDULE FOR FIXTURE

REQUIREMENTS.

"GFI"

DATA OUTLET. MOUNT OUTLET AT SAME HEIGHT AS THE ASSOCIATED

POWER OUTLET, UNLESS NOTED OTHERWISE. PROVIDE 1 INCH CONDUIT

FROM OUTLET BOX TO NEAREST ACCESSIBLE CEILING CAVITY. BUSH

CONDUIT ENDS. PROVIDE TWO DATA CABLES TO OUTLET. OUTLET BOX

SHALL BE 4" SQUARE BY 2-3/4" DEEP WITH A SINGLE-GANG PLASTER RING,

UNLESS NOTED OTHERWISE. SEE "TYPICAL VOICE/DATA CONDUIT

INSTALLATION DETAIL" AND "TYPICAL VOICE/DATA AND POWER OUTLET

DETAIL" , THIS SHEET, FOR ADDITIONAL REQUIREMENTS.

DESCRIPTIONSYMBOL

OUTLET BOX AND 20A, SINGLE POLE SWITCH. MOUNT AT 46 INCHES

ABOVE FINISHED FLOOR TO CENTER, UNLESS NOTED OTHERWISE.

LOCATE WITHIN 8" OF STRIKE SIDE OF DOOR, UNLESS NOTED

OTHERWISE. LOWER CASE LETTER INDICATES CIRCUIT SWITCHED.

SYMBOL INDICATES GROUND FAULT INTERRUPTER TYPE

RECEPTACLE WHEN SHOWN PLANS ADJACENT TO

SYMBOL.

CEILING OUTLET AND EXIT LIGHT FIXTURE AS SCHEDULED.

ARROWS INDICATE DIRECTION ARROWS REQUIRED

PUSH BUTTON. (EMERGENCY POWER OFF)

LOWER CASE LETTERS INDICATE SWITCHING ARRANGEMENT

WHEN SHOWN NEXT TO OR WITHIN SYMBOL ON PLANS.

CEILING OUTLET AND LIGHTING FIXTURE AS SCHEDULED.

a

MULTI-FUNCTION FLOOR BOX.

ELECTRICAL LEGEND - POWERELECTRICAL LEGEND - LIGHTING ELECTRICAL LEGEND - TECHNOLOGY

TELECOMMUNICATIONS

J

J

EPO

CEILING OUTLET AND LIGHTING FIXTURE AS SCHEDULED.

CEILING MOUNT SMOKE DETECTOR.

DESCRIPTIONSYMBOL

FIRE ALARM SYSTEM

AUDIO-VISUAL ALARM DEVICE. FIRE ALARM SYSTEM. WALL

MOUNT AT SAME HEIGHT AS EXISTING DEVICES, OR 6 INCHES

BELOW CEILING TO TOP, WHICHEVER IS LOWER.

MANUAL PULL STATION. FIRE ALARM SYSTEM. MOUNT AT 46

INCHES A.F.F. TO CENTER, UNLESS NOTED OTHERWISE.

ELECTRICAL LEGEND - SYSTEMS

F

F S

F

WIRELESS NETWORK ACCESS SYSTEM OUTLET.

HOMERUN TO PANEL INDICATED. PREFIX INDICATES PANEL

NOMENCLATURE. NUMBERS INDICATE CIRCUIT NUMBERS.

CIRCUIT. NUMBER OF CROSSBARS INDICATE QUANTITY OF

CONDUCTORS REQUIRED. MINIMUM CONDUIT SIZE SHALL BE

3/4 INCH TRADE SIZE. MINIMUM SIZE CONDUCTORS SHALL BE

12 AWG.

F1

"EX" SYMBOL INDICATES EXISTING DEVICE WHEN SHOWN ON

PLANS ADJACENT TO SYMBOL.

NA

HALF-HATCHING PATTERN SHOWN WITHIN LIGHTING FIXTURE

SYMBOLS INDICATES FIXTURE CONNECTED TO EMERGENCY

BRANCH CIRCUIT.

S 3a

OUTLET BOX AND 20A, THREE-WAY SWITCH. MOUNT AT 46 INCHES

ABOVE FINISHED FLOOR TO CENTER, UNLESS NOTED OTHERWISE.

LOCATE WITHIN 8" OF STRIKE SIDE OF DOOR, UNLESS NOTED

OTHERWISE. LOWER CASE LETTER INDICATES CIRCUIT SWITCHED.

OUTLET BOX AND 20A, DIMMING SWITCH. MOUNT AT 46 INCHES

ABOVE FINISHED FLOOR TO CENTER, UNLESS NOTED OTHERWISE.

LOCATE WITHIN 8" OF STRIKE SIDE OF DOOR, UNLESS NOTED

OTHERWISE. LOWER CASE LETTER INDICATES CIRCUIT

SWITCHED.

a a

OCCUPANCY SENSOR. THE LETTER(S) DESIGNATION NEXT TO

THE SYMBOL (IF SHOWN) INDICATE SWITCHING ZONES TO BE

CONTROLLED VIA THE OCCUPANCY SENSOR. IF A LETTER

DESIGNATION IS NOT SHOWN, THE OCCUPANCY SENSOR SHALL

CONTROL ALL LIGHTING FIXTURES WITHIN THE ROOM. SEE

OCCUPANCY SENSOR CONTROL WIRING DIAGRAMS, AND

DETAILS, THIS SHEET, FOR ADDITIONAL REQUIREMENTS.

GTD

EMERGENCY POWER GENERATOR TRANSFER DEVICE. UL924

AND UL1008 LISTED FOR USE AS A SWITCH BYPASS OR

BRANCH CIRCUIT EMERGENCY LIGHTING TRANSFER SWITCH

AND RATED FOR CONNECTED LOAD AND VOLTAGE. PROVIDE

BODINE GTDU OR APPROVED EQUAL.

VISUAL ALARM DEVICE. FIRE ALARM SYSTEM. WALL

MOUNT AT SAME HEIGHT AS EXISTING DEVICES, OR 6 INCHES

BELOW CEILING TO TOP, WHICHEVER IS LOWER.

F

NOTE: COORDINATE EXACT OUTLET BOX INSTALLATION

LOCATIONS IN FIELD WITH ARCHITECT PRIOR TO ROUGH-IN.

INFORMATION OUTLET

BOXES. VIDEO OUTLET

BOXES, AND ASSOCIATED

POWER OUTLET BOXES

SHALL BE NEATLY GROUPED

TOGETHER AT THE SAME

MOUNTING HEIGHTS.

(TYPICAL, ALL LOCATIONS)

RECEPTACLE

VOICE / DATA

OUTLET BOX

FINISHED FLOOR

TYPICAL INFORMATION OUTLET AND

POWER OUTLET DETAIL

NO SCALE

EXTEND CONDUIT PAST

CEILING AND PROVIDE A

90° BEND IN CONDUIT.

BUSH CONDUIT ENDS.

EXTEND TO NEAREST

ACCESSIBLE CEILING

CAVITY

ACCESSIBLE

CEILING CAVITY

NON-

ACCESSIBLE

CEILING CAVITY

CONDUIT

ROUTED WITHIN

WALL

OUTLET BOX AS

SPECIFIED AND

NOTED

FINISHED FLOOR

TYPICAL INFORMATION OUTLET &

CONDUIT INSTALLATION

NO SCALE

GENERAL LIGHTING CONTROL NOTES:

R e d

W h t

Wht

Blk/Orn Blue

Blue

Relay (if req'd)

Normally Closed

Photocell (if req'd)

Common

Normally Open

Auto Dimming Ctrl (if req'd)

7-Brn

8-Vio

6-Gry

5-Blu

4-Vio w/ Wht stripe

3-Blk

2-Wht

1-Red

SWITCH "a" N

SWITCH "b"

Power Pack

Additional Occupancy

Sensor (qty. as shown on Lighting Plans)

3-WAY

SWITCH

3-WAY

SWITCH

4-WAY

SWITCH

UNSWITCHED HOT CONDUCTOR.

OPERATION & PROGRAMMING NOTE: OCCUPANCY SENSORS SHALL ALLOW

LIGHTING FIXTURES TO BE "TURNED ON" VIA THE LIGHTING CONTROL SWITCHES /

DIMMER SWITCHES WHEN OCCUPANCY HAS BEEN DETECTED. THE LIGHTING

FIXTURES SHALL REMAIN "ON" UNTIL THE AREA HAS BEEN FOUND TO BE

"UNOCCUPIED" FOR THE PROGRAMMED TIME PERIOD (OR WHENEVER THE

LIGHTING CONTROL SWITCH HAS BEEN TURNED "OFF". COORDINATE "ON"

DURATION TIME PERIODS FOR EACH TYPE OF ROOM WITH OWNER PRIOR TO

INSTALLATION OF THE OCCUPANCY SENSORS.

NOTE: CONTROL DIAGRAM IS TYPICAL FOR ALL SPACES WITH ONE OR MORE

SWITCHES AND ONE OR MORE OCCUPANCY SENSORS, UNLESS NOTED OTHERWISE.

SWITCHED HOT CONDUCTOR.

NOTE: SWITCH CONFIGURATIONS SHOWN FOR WIRING

REFERENCE ONLY. SWITCH CONFIGURATION FOR A PARTICULAR

SPACE SHALL BE A COMBINATION OF THE ABOVE TYPES OF

SWITCHES, QUANTITY AS INDICATED ON THE LIGHTING PLANS.

Occupancy

Sensor

LIGHTING CONTROL DIAGRAM - TYPICAL FOR ROOMS WITH SINGLE OR

MULTIPLE CONTROL SWITCHES & OCCUPANCY SENSORS

NO SCALE

7-Brn

8-Vio

6-Gry

5-Blu

4-Vio w/ Wht stripe

3-Blk

2-Wht

1-Red

B lk

Relay (if req'd)

Relay (if req'd)

Relay (if req'd)

Normally Closed

Photocell (if req'd)

Common

Normally Open

Auto Dimming Ctrl (if req'd)

Relay (if req'd)

Relay (if req'd)

A. OCCUPANCY SENSOR DESIGNS ARE BASED ON PRODUCTS BY SENSORSWITCH. CONTRACTOR SHALL BE RESPONSIBLE FOR

ANY DESIGN CHANGES REQUIRED TO USE PRODUCTS BY ANOTHER MANUFACTURER.

B. CEILING MOUNT SENSOR LOCATIONS SHALL BE TYPE AS REQUIRED FOR (AND RATED FOR USE) THE INSTALLED CEILING HEIGHT

AND THE INSTALLED ENVIRONMENT.

C IT IS NOT THE INTENT OF THIS DRAWING TO SHOW, NOR DOES THIS DRAWING SHOW EVERY CONFIGURATION OF LIGHTING CONTROL DIAGRAM REQUIRED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL LIGHTING CONTROL PER THE

LIGHTING CONTROL SYSTEM MANUFACTURER'S REQUIREMENTS.

D. CEILING MOUNT OCCUPANCY SENSORS SHALL BE DUAL TECHNOLOGY (PIR/MICROPHONICS) TYPE WHERE INSTALLED WITHIN

SPACES WHERE OCCUPANTS ARE STATIONARY FOR LONG PERIODS OF TIME.

E. DIMMER SWITCH ADJUSTMENTS. UNLESS NOTED OTHERWISE, ALL DIMMER SWITCHES SHALL BE ADJUSTED / SET TO AUTOMATICALLY TURN ASSOCIATED CONTROLLED LIGHTING FIXTURES "ON" TO THE PREVIOUS DIMMING LEVEL (I.E. AS WAS PRIOR

TO BEING "SHUT-OFF" BY OCCUPANCY SENSORS) WHEN THE ROOM BECOMES OCCUPIED.

F. DIMMER SWITCH ADJUSTMENTS. UNLESS NOTED OTHERWISE, ALL DIMMER SWITCHES SHALL BE ADJUSTED / SET TO AUTOMATICALLY TURN ASSOCIATED CONTROLLED LIGHTING FIXTURES "ON" TO THE PREVIOUS DIMMING LEVEL (I.E. AS WAS PRIOR TO BEING "SHUT-OFF" BY INTERGRAL "ON/OFF" SWITCH) WHEN THE INTEGRAL "ON/OFF" SWITCH IS PLACED IN THE "ON" CONDITION.

DIMMER SWITCH

(0-to-10V Type)

LTG FIXTURE(S) CONTROLLED VIA

DIMMER SWITCH (0-to-10V Type)

LOW VOLTAGE CTRL CKTS

(PER MFGR REQUIREMENTS)

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

CRAIG

34886

AJ SON

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/23

KCTCS - HCC FOOD SERVICE & CYBER CAFE

ELECTRICAL LEGEND

E1.1

ZWS

ZWS

ZWS

ADDENDUM #2 02/20/24

LIGHTING FIXTURE SCHEDULE

---F1D

F2D

MANUFACTURERSYMBOL DESCRIPTION

LOUVER FINISHTYPE

FIXTURE SERIES

LAMP

LENSWATTS REFLECTOR

MOUNTING

LIGHT CONTROL

REMARKS

FIXTURE

VOLTAGEQNTY PER

FIXTURE

F3

6' LENGTH LINEAR LED LIGHTING FIXTURE WITH FLUSH LENS

& WHITE FINISH. PROVIDE FIXTURE WITH CEILING TRIM FOR

INSTALLATION WITHIN T-GRID CEILING.

(FIXTURE DIMENSIONS: 6FT(L) x 4-1/8"(W) x 4"(D)).

[FIXTURE LUMEN OUTPUT ~ 6000 LUMENS]

SATIN

WHITE

120/277

(MULTI-

VOLT)

COOPER LTG

METALUX

QNTY AS

REQUIRED

35W

(NOMINAL

FIXTURE

INPUT

WATTS)

RECESSED,

T-GRID

CEILING

2'x4' LED LOW GLARE FLAT PANEL. CONTRACTOR SHALL

SELECT THE MEDIUM LUMEN OUTPUT POSITION.

(2.2" MAX FIXTURE DEPTH).

[FIXTURE LUMEN OUTPUT ~ 4500 LUMENS]

LEDS 3500K

(60,000 HRS WITH

70% LUMEN

MAINTENANCE)

L70/60

80+ CRI

CPX-2x4-AL08-80CRI-SWW7-SWL-

MVOLT SERIES

22FP3235C-80CRI-35K-NODIM-UNV

SERIES

LITHONIA

AXIS LIGHTING

BBRLED-1000-80-35-FL-6-W-UNV-

NODIM-1-RQD MOUNTING SERIES

LUMENWERX

VIA4R-D-HLO-FH-SW-80-1000-35-6FT-

UNV-D1-1C-XX-W-RQD MOUNTING

SERIES

RECESSED,

T-GRID

120/277

(MULTI-

VOLT)

61.7W

(NOMINAL

FIXTURE

INPUT

WATTS)

LEDS 3500K

(50,000 HRS

WITH 85% LUMEN

MAINTENANCE)

L85/50,000

80+ CRI MIN

QNTY AS

REQUIRED

4' LENGTH LINEAR LED LIGHTING FIXTURE WITH FLUSH LENS

& WHITE FINISH. PROVIDE FIXTURE WITH CEILING TRIM FOR

INSTALLATION WITHIN T-GRID CEILING.

(FIXTURE DIMENSIONS: 4FT(L) x 4-1/8"(W) x 4"(D)).

[FIXTURE LUMEN OUTPUT ~ 3200 LUMENS]

SATIN

WHITE

AXIS LIGHTING

BBRLED-800-80-35-FL-4-W-UNV-NODIM-1-

RQD MOUNTING SERIES

LUMENWERX

VIA4R-D-HLO-FH-SW-80-800-35-4FT-UNV-

D1-1C-XX-W-RQD MOUNTING SERIES

RECESSED,

T-GRID

120/277

(MULTI-

VOLT)

31.5W

(NOMINAL

FIXTURE

INPUT

WATTS)

LEDS 3500K

(50,000 HRS

WITH 85% LUMEN

MAINTENANCE)

L85/50,000

80+ CRI MIN

QNTY AS

REQUIRED

SATIN

WHITE

F5

120/277

(MULTI-

VOLT)

HALO

QNTY AS

REQUIRED

31.6W

(NOMINAL

FIXTURE

INPUT

WATTS)

RECESSED

CLEAR,

SEMI-

SPECULAR

8" APERATURE LED DOWNLIGHT FIXTURE WITH A MAXIMUM

DEPTH OF 8"

[FIXTURE LUMEN OUTPUT ~ 2000 LUMENS]

LEDS 3500K

(60,000 HRS WITH

70% LUMEN

MAINTENANCE)

L70/60

80+ CRI

HC820D010-HM60525835-61MDH

SERIES

LITHONIA

END OF LIGHTING FIXTURE SCHEDULE

F4

120/277

(MULTI-

VOLT)

COOPER LTG

METALUX

QNTY AS

REQUIRED

27.7W

(NOMINAL

FIXTURE

INPUT

WATTS)

RECESSED,

T-GRID

CEILING

2'x2' LED LOW GLARE FLAT PANEL. CONTRACTOR SHALL

SELECT THE MEDIUM LUMEN OUTPUT POSITION.

(2.2" MAX FIXTURE DEPTH).

[FIXTURE LUMEN OUTPUT ~ 3200 LUMENS]

LEDS 3500K

(60,000 HRS WITH

70% LUMEN

MAINTENANCE)

L70/60

80+ CRI

CPX-2x2-AL07-80CRI-SWW7-SWL-

MVOLT SERIES

22FP3235C-80CRI-35K-NODIM-UNV

SERIES

LITHONIA

SATIN

WHITE

EX1

120/277

(MULTI-

VOLT)

QNTY AS

REQUIRED

LESS

THAN 5W

SURFACE,

CEILING

EXIT LIGHTING FIXTURE, WHITE THERMOPLASTIC HOUSING,

SINGLE-FACE WITH RED LETTERS.

LEDS (RED)

LQM QUANTUM SERIESLITHONIA

LBR8-20LM-35K-AR-LSS-MWD-MVOLT

SERIES

F5D

120/277

(MULTI-

VOLT)

HALO

QNTY AS

REQUIRED

31.6W

(NOMINAL

FIXTURE

INPUT

WATTS)

RECESSED

CLEAR,

SEMI-

SPECULAR

SAME FIXTURE AS TYPE "F5" EXCEPT PROVIDE FIXTURE

WITH CAPABILITIES TO DIM TO 10% USING 0-TO-10V

CONTROLS.

LEDS 3500K

(60,000 HRS WITH

70% LUMEN

MAINTENANCE)

L70/60

80+ CRI

HC820D010-HM60525835-61MDH

SERIES

LITHONIA

LBR8-20LM-35K-AR-LSS-MWD-MVOLT

SERIES

1. PROVIDE FIXTURE WITH 0-TO-10V DIMMING CONTROLLER(S) [QNTY AS INDICATED ON LIGHTING

PLAN] FULLY COMPATIBLE WITH THE FIXTURE AND RATED FOR OPERATION WITH THE FIXTURE

AND CONNECTED LOAD. FINISH COLOR OF THE DIMMING CONTROLLER(S) AND DEVICE PLATES

SHALL MATCH THE COLOR OF ALL OTHER WIRING DEVICES / DEVICE PLATES CONNECTED TO

THE ASSOCIATED POWER SOURCE

1. PROVIDE FIXTURE WITH 0-TO-10V DIMMING CONTROLLER(S) [QNTY AS INDICATED ON LIGHTING

PLAN] FULLY COMPATIBLE WITH THE FIXTURE AND RATED FOR OPERATION WITH THE FIXTURE

AND CONNECTED LOAD. FINISH COLOR OF THE DIMMING CONTROLLER(S) AND DEVICE PLATES

SHALL MATCH THE COLOR OF ALL OTHER WIRING DEVICES / DEVICE PLATES CONNECTED TO

THE ASSOCIATED POWER SOURCE

1. PROVIDE FIXTURE WITH 0-TO-10V DIMMING CONTROLLER(S) [QNTY AS INDICATED ON LIGHTING

PLAN] FULLY COMPATIBLE WITH THE FIXTURE AND RATED FOR OPERATION WITH THE FIXTURE

AND CONNECTED LOAD. FINISH COLOR OF THE DIMMING CONTROLLER(S) AND DEVICE PLATES

SHALL MATCH THE COLOR OF ALL OTHER WIRING DEVICES / DEVICE PLATES CONNECTED TO

THE ASSOCIATED POWER SOURCE

1. CONTRACTOR MAY UTILIZE FIXED LUMEN OUTPUT.

1. CONTRACTOR MAY UTILIZE FIXED LUMEN OUTPUT.

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

CRAIG

34886

AJ SON

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/23

KCTCS - HCC FOOD SERVICE & CYBER CAFE

LIGHTING FIXTURE SCHEDULE

E1.2

ZWS

ZWS

ZWS

F

F

F S

F S

F S

F S

F S

NA

GENERAL DEMOLITION NOTES:

GD1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE

BUILDING AND SITE TO BECOME FAMILIAR WITH THE EXISTING

CONDITIONS. THESE REMOVAL DRAWINGS SHALL SERVE TO AID THE

CONTRACTOR IN HIS EVALUATION OF THE EXTENT OF REMOVALS, BUT

SHALL NOT BE HELD TO BE ALL INCLUSIVE.

GD2. FOR FURTHER REQUIREMENTS WITH REGARD TO EXTENT OF

REMOVALS, SEE THE NEW CONSTRUCTION PLANS WHICH ILLUSTRATE

THE ADJACENT NEW CONSTRUCTION.

GD3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS

REQUIRED FOR THE INSTALLATION OF NEW WORK, WHETHER OR NOT

IT IS SPECIFICALLY INDICATED OR NOTED IN THESE DOCUMENTS.

GD4. ALL EQUIPMENT REMOVED FOR RELOCATION SHALL BE

REMOVED IN SUCH A MANNER THAT REUSE IS POSSIBLE.

GD5. ALL CONDUIT RUNS TO REMOVED EQUIPMENT SHALL HAVE ALL

CONDUCTORS REMOVED, UNLESS CONDUCTORS ARE REQUIRED TO

SERVE EXISTING EQUIPMENT TO REMAIN.

GD6. REMOVAL OF EMPTY CONDUIT SHALL BE REQUIRED ONLY IF

SUCH CONDUIT INTERFERES WITH THE NEW CONSTRUCTION AND/OR IF

INDICATED TO BE DISCONNECT AND REMOVED COMPLETE BACK TO

SOURCE OF FEED.

GD7. IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN

MUST BE RELOCATED OR REMOVED DUE TO OTHER DEMOLITION OR

DUE TO INTERFERENCE WITH NEW EQUIPMENT INSTALLATION, THE

CIRCUITS SHALL BE MODIFIED IN A MANNER WHICH SHALL ENSURE

PROPER OPERATION OF THE EQUIPMENT AFTER THE CONSTRUCTION

IS COMPLETE. CONTRACTOR SHALL USE THE SAME GAUGE AND TYPE

OF CONDUCTOR, AND THE SAME CONDUIT SIZE AS EXISTING TO MAKE

ALL REQUIRED CIRCUIT MODIFICATIONS.

GD8. IF WALLS, CEILINGS, FLOORS, OR EQUIPMENT ARE REMOVED, OR

OTHER DEMOLITION OCCURS, WHICH EXPOSES CIRCUITS SERVING

EQUIPMENT TO REMAIN, THE CIRCUITS SHALL BE RELOCATED OR

MODIFIED IN SUCH A MANNER WHICH SHALL ENSURE THE CONTINUED

OPERATION OF THE CIRCUIT. EXISTING CONDUITS EXPOSED DURING

DEMOLITION WHICH REMAIN TO SERVE EQUIPMENT SHALL BE

RESUPPORTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE

NEC.

GD9. EQUIPMENT REMOVED FOR RELOCATION BUT NOT RELOCATED

SHALL BE STORED AT A LOCATION DIRECTED BY THE OWNER.

GD10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER

DISPOSAL OF ALL EQUIPMENT REMOVED.

GD11. OWNER RESERVES THE FIRST RIGHT OF REFUSAL OF REMOVED

EQUIPMENT.

GD12. THE CONTRACTOR SHALL COORDINATE DISRUPTION OF

SERVICES WITH THE OWNER. DISRUPTIONS OF SERVICES SHALL BE

KEPT TO A MINIMUM. DISRUPTIONS SHALL ONLY OCCUR AFTER

RECEIVING OWNER PRIOR APPROVAL.

GD13. THE CONTRACTOR SHALL REFER TO THE MECHANICAL,

PLUMBING, AND ARCHITECTURAL PLANS FOR ADDITIONAL

REQUIREMENTS ON EQUIPMENT AND AREAS REQUIRING

DISCONNECTIONS AND REMOVALS.

GD14. ALL WALL/CEILING MOUNT DEVICES AND FACEPLATES SHALL BE

REMOVED AS REQUIRED FOR WALL FINISH INSTALLATION. PROVIDE ALL

LABOR AND MATERIAL TO INSTALL DEVICES WITHIN EXISTING JUNCTION

BOXES (PROVIDING BOX AND EXTENDERS AS REQUIRED).

GD15. IT IS NOT THE INTENT OF THIS DRAWING TO SHOW ALL EXISTING

ELECTRICAL DEVICES, EQUIPMENT, AND ITEMS TO BE DISCONNECTED

AND REMOVED. THIS DRAWING DOES NOT SHOW ALL ELECTRICAL

DEVICES, EQUIPMENT, AND ITEMS TO BE DISCONNECTED AND

REMOVED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING

THE PROJECT AREAS TO BECOME FAMILIAR WITH THE EXISTING

CONDITIONS AND TO DETERMINE THE AMOUNT OF REMOVALS.

LTG

CONTACTOR

PANEL "L1"

PANEL "M1"

PANEL "E1"

PANEL "C1"

XFMR#3

PANEL "R1"

XFMR#2

GE EST F.A.

CONTROL PANEL

F.A. BOOSTER

PANEL

NOTE D1

NOTE D2

NOTE D2

NOTE D3

NOTE D3

NOTE D3

NOTE D5

NOTE D5

NOTE D5

NOTE D5

NOTE D4

NOTE D6

PANEL "EE"

NOTE D5 NOTE D5 NOTE D5 NOTE D5

NOTE D5

NOTE D5

NOTE D5NOTE D5NOTE D5

NOTE D5

NOTE D5 NOTE D5

NOTE D5

NOTE D2

NOTE D1

R1-6R1-5R1-4R1-3

R1-2

R1-2

R1-2

R1-2R1-2

R1-2

C1-1

C1-1

C1-1

C1-2 C1-2 C1-2 C1-2

R1-31R1-30

NOTE D7,

TYPICAL ALL LOCATIONS.

NOTE D5

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

CRAIG

34886

AJ SON

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/23

KCTCS - HCC FOOD SERVICE & CYBER CAFE

ELECTRICAL DEMO PLAN - SULLIVAN TECHNOLOGY CENTER

E1.3

ZWS

ZWS

ZWS

1/4" = 1'-0"

ELECTRICAL DEMOLITION PLAN - SULLIVAN TECHNOLGY BUILDING - FIRST FLOOR

DEMOLITION NOTES:

D1. DISCONNECT AND REMOVE RECEPTACLE. EXISTING CIRCUIT

SHALL REMAIN AND SHALL BE REWORKED AS REQUIRED FOR REUSE.

D2. DISCONNECT AND REMOVE DATA DEVICE AND ASSOCIATED

CIRCUIT COMPLETE BACK TO SOURCE OF FEED.

D3 DISCONNECT AND REMOVE RECEPTACLE AND ASSOCIATED

CIRCUIT COMPLETE BACK TO SOURCE OF FEED.

D4. DISCONNECT AND REMOVE FIRE ALARM DEVICE AND

ASSOCIATED CIRCUIT COMPLETE BACK TO SOURCE OF FEED.

D5. DISCONNECT AND REMOVE LIGHTING FIXTURE. EXISTING CIRCUIT

SHALL REMAIN AND SHALL BE REWORKED AS REQUIRED FOR REUSE.

D6. DISCONNECT, REMOVE, REWORK AND REINSTALL FIRE ALARM

DEVICE IN SAME GENERAL LOCATION FOR WALL INSTALLATION.

D7. NOMENCLATURE INDICATED PANEL AND CIRCUIT WHICH SERVES

DEVICE PER RECORD DRAWINGS DATED 07-2008.

1'0' 2' 4'

1/4''=1'-0'' North

T

F

F S

S S

S

F

F S

F S

S

F S

NOTE 5

NOTES 2, 3, 4 & 6.

NOTE 7

NOTE 1

NOTE 1

NOTE 8

NOTE 8

NOTE 9

NOTE 10

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

CRAIG

34886

AJ SON

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/23

KCTCS - HCC FOOD SERVICE & CYBER CAFE

ELECTRICAL DEMO PLAN - ACADEMIC TECHNICAL BUILDING

E1.4

ZWS

ZWS

ZWS

1/4" = 1'-0"

ELECTRICAL DEMOLITION PLAN SERVING AREA

DEMOLITION NOTES:

1. DISCONNECT AND REMOVE FIRE ALARM DEVICE COMPLETE

BACK TO SOURCE OF FEED.

2. DISCONNECT AND REMOVE ALL RECEPTACLES WITHIN DASHED

LINE TYPE, UNLESS NOTED OTHERWISE. DISCONNECT AND REMOVE

ALL ASSOCIATED CIRCUITS COMPLETE BACK TO SOURCE OF FEED.

3. DISCONNECT AND REMOVE ALL DATA DEVICES WITHIN DASHED

LINE TYPE, UNLESS NOTED OTHERWISE. DISCONNECT AND REMOVE

ALL ASSOCIATED DATA CABLES COMPLETE BACK TO SOURCE OF

FEED.

4. DISCONNECT AND REMOVE DEVICES WITHIN FLOOR BOX,

WITHIN DASHED LINE TYPE. DISCONNECT AND REMOVE ALL

ASSOCIATED CIRCUITS COMPLETE BACK TO SOURCE OF FEED.

FLOORBOX SHALL BE ABANDONED IN PLACE. CONTRACTOR SHALL

PROVIDE BLANK COVER.

5. DISCONNECT AND REMOVE PANEL "EL" COMPLETE BACK TO

SOURCE OF FEED. DISCONNECT AND REMOVE FEEDER COMPLETE

BACK TO SOURCE OF FEED.

6. DISCONNECT AND REMOVE ALL LIGHTING FIXTURES WITHIN

DASHED LINE TYPE, UNLESS NOTED OTHERWISE. EXISTING CIRCUIT

SHALL REMAIN AND SHALL BE REWORKED AS REQUIRED FOR

REUSE.

7. DISCONNECT AND REMOVE TELEPHONE EQUIPMENT AND

TELEPHONE BACKBOARD COMPLETE BACK TO SOURCE OF FEED.

8. DISCONNECT AND REMOVE FIRE ALARM DEVICE FOR

RELOCATION. EXISTING CIRCUIT SHALL BE REMAIN AND SHALL BE

REWORKED AS REQUIRED TO SERVE DEVICE AT NEW LOCATION.

9. DISCONNECT AND REMOVE LIGHTING FIXTURE FOR

RELOCATION. EXISTING CIRCUIT SHALL REMAIN AND SHALL BE

REWORKED AS REQUIRED FOR REUSE.

10. DISCONNECT AND REMOVE SWITCHES FOR RELOCATION.

SWITCH-LEG CONDUCTORS SHALL BE REWORKED AS REQUIRED

FOR INSTALLATION. CONTRACTOR SHALL FIELD VERIFY EXACT

SWITCH TYPE INSTALLED (I.E. SINGLE POLE, 3WAY, 4WAY, ETC.) FOR

REINSTALLATION. CONTRACTOR SHALL PROVIDE NEW SWITCHES.

1'0' 2' 4'

1/4''=1'-0''

F S

F S

F S

F S

NA

F

F

JJ

JJ

J

S

S

EXEX EXEX EXEX EXEX

EX

EX

NOTE 5

EX

EX

NOTE 2

EX

EX

EX

EX

EX

EX

EX

GFIGFI

GFI

NOTE 4

NOTES 2 & 7.

NOTE 4

NOTE 4

NOTES 2 & 8.

EXISTING LTG

CONTACTOR

EXISTING PANEL "L1"

EXISTING PANEL "M1"

EXISTING PANEL "E1"

EXISTING PANEL "C1"

EXISTING XFMR#3

EXISTING PANEL "R1"

EXISTING XFMR#2

EXISTING GE EST

F.A. CONTROL

PANEL

EXISTING F.A.

BOOSTER PANEL

EXISTING

PANEL "EE"

EX

EX

NOTE 2

NOTE 5

NOTE 3

NOTE 8

NOTE 10

NOTE 8 NOTES 2 & 8.

NOTES 2 & 8.

EX EX EX EX EX EX EX

F1D F1D F1D F1D F1D F1D F1D F1D F1D

F2DF2DF2DF2D

NOTE 6

NOTE 6EX1

EX1

3a

3a

GTD

F5D

F5DF5DF5DF5DF5DF5D

c

GTDGTD

cccccc c b a aaaa bbbbbbbbb

EX1

a a

GTD

NOTE 9 NOTE 9 NOTE 9

NOTE 9

NOTE 1

NOTE 1

NOTE 1

NOTE 11NOTE 11NOTE 11

NOTE 11

F4

F4

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

CRAIG

34886

AJ SON

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/23

KCTCS - HCC FOOD SERVICE & CYBER CAFE

ELECTRICAL PLANS - SULLIVAN TECHNOLOGY CENTER

E2.1

ZWS

ZWS

ZWS

1/4" = 1'-0"

POWER AND SYSTEMS PLAN - STC - FIRST FLOOR

1/4" = 1'-0"

LIGHTING PLAN - STC - FIRST FLOOR

NOTES: CON'T

5. POINT OF CONNECTION TO EXISTING.

6. UTILIZE EXISTING NORMAL CIRCUIT WHICH SERVED LIGHTING IN

AREA TO SERVE NEW FIXTURES. PROVIDE ALL REQUIRED

CONDUCTORS FOR CONTROL OF FIXTURES AS INDICATED.

7. AS PART OF ALTERNATE BLINDS AND FIREPLACE, PROVIDE

RECEPTACLE AND DEDICATED 120V, 20A BRANCH CIRCUIT FOR

WATER VAPOR FIREPLACE. COORDINATE INSTALLATION LOCATION

WITH ARCHITECT AND FIREPLACE MANUFACTURER PRIOR TO

ROUGH-IN.

8. AS PART OF ALTERNATE BLINDS AND FIREPLACE, PROVIDE

RECEPTACLE AND DEDICATED 120V, 20A BRANCH CIRCUIT FOR

ELECTRIC BLIND SYSTEM. PROVIDE FINAL CONNECTION PER

EQUIPMENT MANUFACTURER'S REQUIREMENTS. COORDINATE

INSTALLATION LOCATION WITH EQUIPMENT VENDOR AND ARCHITECT

PRIOR TO START OF ROUGH-IN.

9. CONNECT GENERATOR TRANSFER DEVICE TO EXISTING NORMAL

AND EXISTING EMERGENCY CIRCUIT WHICH SERVES EMERGENCY

AND EGRESS LIGHTING IN AREA. PTOVIDE ALL CONNECTIONS AS

REQUIRED FOR CONTROL AS INDICATED.

10. REINSTALL FIRE ALARM DEVICE REMOVED FOR RELOCATION.

PROVIDE ALL MODIFICATIONS AS REQUIRED FOR RELOCATION.

11. FIXTURE SHALL BE POWERED AND CONTROLLED VIA GTD DEVICE.

1'0' 2' 4'

1/4''=1'-0'' North

1'0' 2' 4'

1/4''=1'-0'' North

NOTES:

1. CONNECT FIXTURE TO EXISTING EMERGENCY CIRCUIT WHICH

SERVES EGRESS AND EMERGENCY FIXTURES WITHIN AREA.

2. UTILIZE CIRCUIT MADE AVAILABLE DURING DEMOLITION TO SERVE

LOAD. CONTRACTOR SHALL DOCUMENT PANEL AND CIRCUIT ON AS-

BUILT DRAWINGS.

3. PROVIDE FIRE ALARM DEVICE COMPATIBLE WITH GE EST FIRE

ALARM CONTROL PANEL AND CONNECT TO EXISTING BUILDING FIRE

ALARM SYSTEM.

4. RECEPTACLE AND DATA DEVICE FOR WALL MOUNT TV.

COORDINATE MOUNTING HEIGHT IN FIELD WITH ARCHITECT PRIOR

TO ROUGH-IN.

J

JJ

J

F

MM

F J

J J

J J

J J

S

S S

S

NOTE 4

NOTE 5

NOTE 6

NOTE 6

NOTE 2

NOTE 1

EX

NOTE 3

NOTE 6

NOTE 6

NOTE 6

NOTE 10

PANEL "K1"

NOTE 12

FOOD SERVICES

CORRIDOR

CLASSROOM

F3F3F3

F3 F3 F3

NL

a a a aa a

NOTE 7

NOTE 8

NOTE 9

NOTE 11

EXEX EX

EXEX EX

EXEX EX

EXEX EX

EXEX EX

F5

F5

NOTE 13

FOOD SERVICES

CORRIDOR

CLASSROOM

PANEL "K1"

EXISTING MAIN

SWITCHGEAR

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

CRAIG

34886

AJ SON

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/23

KCTCS - HCC FOOD SERVICE & CYBER CAFE

ELECTRICAL PLANS - ACADEMIC TECHNICAL BUILDING

E2.2

ZWS

ZWS

ZWS

1/4" = 1'-0"

POWER & SYSTEMS PLAN SERVING AREA

1/4" = 1'-0"

LIGHTING PLAN SERVING AREA

NOTES:

1. PROVIDE MONITORING MODULE FOR MONITORING OF KITCHEN

HOOD FIRE SUPPRESSION SYSTEM. COORDINATE INSTALLATION

WITH KITCHEN EQUIPMENT VENDOR. REFER TO KITCHEN DRAWINGS

FOR ADDITIONAL REQUIREMENTS.

2. PROVIDE 208Y/120V, 200A, 3Ø FEEDER CIRCUIT FROM EXISTING

MAIN SWITCHGEAR TO THE PANELBOARD, WITH SHUNT-TRIP MAIN

BREAKER, PROVIDED WITHIN THE UTILITY DISTRIBUTION SYSTEM

"UDS-1". COORDINATE ALL INSTALLATION REQUIREMENTS WITH

"UDS-1" AND KITCHEN EQUIPMENT PROVIDER PRIOR TO START OF

ROUGH-IN. REFER TO ONE-LINE DIAGRAM, SHEET E3.1, FOR

ADDITIONAL REQUIREMENTS.

3. PROVIDE 120V, 20A BRANCH CIRCUIT TO SERVE UTILITY

DISTRIBUTION SYSTEM POWER FOR CONTROLS/LIGHTS PER

EQUIPMENT MANUFACTURER'S REQUIREMENTS. PROVIDE ALL

REQUIRED CIRCUITS FOR A COMPLETE AND OPERATIONAL SYSTEM.

UTILIZE 2#12, 1#12G AND 3/4"C FROM PANEL "K1" CIRCUIT 2.

4. PROVIDE 120V, 20A, GFI PROTECTED BRANCH CIRCUIT AND

RECEPTACLE FROM PANEL "K1" CIRCUIT 1 TO SERVE

REFRIGERATOR.

5. PROVIDE 120V, 20A, GFI PROTECTED BRANCH CIRCUIT AND

RECEPTACLE FROM PANEL "K1" CIRCUIT 3 TO SERVE FREEZER.

6. PROVIDE JUNCTION BOX MOUNTED AT 18" A.F.F AND 3/4"C

ROUTED TO ACCESSIBLE CEILING FOR FUTURE INSTALLATION OF

KITCHEN EQUIPMENT. PROVIDE BLANK STAINLESS STEEL

COVERPLATE.

7. UTILIZE EXISTING LIGHTING CIRCUITS WHICH SERVED LIGHTING

IN AREA TO SERVE NEW FIXTURES. FIXTURES SHALL BE

CONTROLLED AS INDICATED.

8. UTILIZE CIRCUIT WHICH SERVES CORRIDOR TO SERVE FIXTURE.

FIXTURE SHALL BE CONTROLLED SAME AS CORRIDOR LIGHTING.

9. PROVIDE SWITCHES BASED UPON FIELD VERIFICATION. REWORK

AND EXTEND ALL ASSOCIATED CIRCUITS AS REQUIRED. LIGHTING

CONTROL SWITCHES AND CONNECTED LOAD SHALL OPERATE AS

WAS PRIOR TO START OF DEMOLITION.

10. UTILIZE FIRE ALARM DEVICE REMOVED FOR RELOCATION.

REWORK AND CONNECT TO EXISTING FIRE ALARM CIRCUIT WHICH

SERVED DEVICE PRIOR TO DEMOLITION.

11. UTILIZE LIGHTING FIXTURE REMOVED FOR RELOCATION AND

CONNECT TO EXISTING CIRCUIT WHICH SERVED FIXTURE PRIOR TO

DEMOLITION.

12. PROVIDE 208V, 25A, 1Ø BRANCH CIRCUIT FROM PANEL "K1"

CIRCUIT 13 FOR KITCHEN HOOD EXHAUST FAN. UTILIZE 2#10, 1#10G

AND 3/4"C TO SERVE LOAD. PROVIDE ALL REQUIRED CONTROL

CIRCUITS FROM EXHAUST FAN TO KITCHEN HOOD CONTROL PANEL.

PROVIDE FINAL EQUIPMENT CONNECTIONS PER MANUFACTURER

REQUIREMENTS. REFER TO KITCHEN EQUIPMENT DRAWINGS FOR

ADDITIONAL DETAILS.

13. UTILIZE NEAREST EMERGENCY BRANCH CIRCUIT WHICH SERVED

EGRESS LIGHTING TO SERVE FIXTURE. CONTRACTOR SHALL

DOCUMENT PANEL AND CIRCUIT NUMBER ON AS-BUILT DRAWINGS.

1/16" = 1'-0"

AREA PLAN

1'0' 2' 4'

1/4''=1'-0'' North

1'0' 2' 4'

1/4''=1'-0''

M

1 2 3 5 6 7 8 11 1312 14 159 104 16

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

30 20A

28 20A

SPARE

24 30A

20 30A19

SPARE

SPARE

30A

SPARE

12 20A

8 20A7

SPARE

SPARE

4 40A

2 20A1

SPARE

EXHAUST HOOD SYSTEM

225A, 208Y/120V, 3PH, 4W

RECESSED MOUNT

42 SPACE

22,000 A.I.C.

PROVIDE WITH HINGED COVER ENCLOSURE

PANEL "K1"

20A SPARE

SPARE

20A

GFI

20A

GFI

20ASPARE

25AKITCHEN HOOD EXHAUST FAN

FREEZER

REFRIGERATOR

20A

GFISPARE

20A

GFISPARE

SPACE

SPACE

SPACE

3231SPACE

SPACE

SPACE

3837SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

20ASPARE

20ASPARE

20ASPARE

NO SCALE

ONE-LINE DIAGRAM

EXISTING MAIN SWITCHGEAR

208Y/120V, 3Ø, 4W, 2000A, 65,000 A.I.C.

GE AV-LINE SWITCHBOARD

2000A/3

EXISTING

PANEL

"A1"

EXISTING

PANEL

"A2"

TO D.P.B. #2 UNKNOWN

LOAD

EXISTING

PANEL

"ML"

EXISTING

PANEL

"EL"

TO ATS-7

(EXISTING

PANEL "ATE")

TO VACUUM

PUMP

200A/3 200A/3 600A/3 600A/3 30A/3 100A/3100A/3 60A/3 60A/3

PANEL

"K1"

4#2, 1#8, 1-1/2"C

NOTE 1

NOTE 2

EXISTING

PANEL

"MT"

200A/3

TO CHILLER

FEED #1

600A/3

TO CHILLER

FEED #2

SPACE SPACE

TO D.P.B. #1

400A/3

EXISTING

PANEL

"BS"

200A/3

TO C.W.

PUMP 2

60A/3

CONTINUED BELOW

CONTINUED

FROM ABOVE

60A/3

TO C.W.

PUMP 1

TO BOILER

60A/3

TO AIR

COMPRESSOR

40A/3 40A/3

TO H.W.

PUMP 1

40A/3

TO H.W.

PUMP 2

100A/3

TO AHU#1

100A/3

TO COND.

UNIT #1

60A/3

UNKNOWN

LOAD

400A/3

TO 400A

BUSS DUCT

(OFF)

SPACE

125A/3

TO AHU#2

125A/3

TO

ELEVATOR

(OFF)

200A/3 225A/3

TO ATS-8

(EXISTING

PANEL "EP4")

SPACE SPACE

NOTE 3

UTILITY

DISTRIBUTION

SYSTEM "UDS-1"

(LOCATED WITHIN

KITCHEN HOOD)

4#3/0, 1#6, 2"C

NOTE 2

NOTES 4 & 5.

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

CRAIG

34886

AJ SON

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/23

KCTCS - HCC FOOD SERVICE & CYBER CAFE

ONE-LINE DIAGRAM AND BUSSING DIAGRAM - A/T BUILDING

E3.1

ZWS

ZWS

ZWS

NOTES:

1. DISCONNECT AND REMOVE ALL ELECTRICAL EQUIPMENT WITHIN

HATCHED REGION.

2. POINT OF CONNECTION TO EXISTING EQUIPMENT.

3. PROVIDE NEW DISTRIBUTION LABELS ON EXISTING BREAKERS.

PROVIDE TYPED LAMINATED INDEXCARD WHICH CORRECTLY

IDENTFIES CONNECTED LOADS.

4. UTILITY DISTRIBUTION SYSTEM "UDS-1" PROVIDED WITH

FACTORY INSTALLED MAIN BREAKER WITH SHUNT-TRIP.

5. ALL KITCHEN EQUIPMENT SHALL BE PROVIDED WITH GFCI TYPE

CIRCUIT BREAKERS.

CHROME APPLIANCE DROPS

ROUND LED LIGHT DETAIL

115VAC HOT

115VAC NEUTRAL

GROUND

BLACK

WHITE

GREEN

BLACK

WHITE

GREEN

FIRST LED

HOOD LIGHT

SECOND LED

HOOD LIGHT

LAST LED

HOOD LIGHT

LIGHT QTY

BASED ON

CONFIGURATION

NOTES:

VOLTAGE: 115VAC, 50-60HZ

WATTAGE: 20W EACH

AMPERAGE: 0.167A EACH

LUMENS: 1800

CONDUIT PORTS: 2 EACH

(1/2" - 14 NPT)

COLOR: 3900 - 4100K

DIMMABLE (0-10VDC)

BLACK (115VAC HOT)

WHITE (115VAC NEUTRAL)

GREEN (GROUND)

PURPLE (DIM 0-10VDC +)

GRAY (DIM 0-10VDC -)

8.0

DRAWING NOT TO SCALE

SECURE PANELS

TO WALL STUDS

(HOLES AND FASTENERS

BY OTHERS)

SLIDE

PANEL

BEHIND

HOOD

FLAT

BACKSPLASH

PANEL

FASTEN TO WALL

HARDWARE BY OTHERS

5/16'' BOLTS

PROVIDED BY

MANUFACTURER

CLAMPS

PROVIDED BY MANUFACTURER

HOOD TOP

1" INSULATION

FULL WALL

END FILLER PANEL

PARTIAL WALL

END FILLER PANEL

1" INSULATION

HOOD LENGTH

3.6

TYPICAL

HANGER

BRACKET

3.6

4.0

2.6

THREADED

ROD (1/2")

WASHER

HANGER

BRACKET

1/2" NUT

TEMPERATURE SENSORS

FIELD WIRING TO CONTROLS REQUIRED

USER

INTERFACE:

TOUCH

SCREEN

REMOVABLE GREASE CUP W/

CONCEALED GREASE TROUGH

UL LISTED HIGH EFFICIENCY

'GREASE-X-TRACTOR' FILTERS

UL LISTED LED LIGHT FIXTURE

X K

C

IT

E

M

E

X H

A U

S T

H O

O D

H E

N D

E R

S O

N C

O M

M U

N

IT

Y C

O L L E

G E

A C

C U

R E

X S

O U

T H

O H

K Y

I N

A A R O N

G E A R H A R T

A A

R O

N .G

E A

R H

A R

T

A C

C U

R E

X .C

O M

(5

)5

-5

P R

O J E

C T

M A

R K

/2

/2

2 FP

2W

2 FP

3 FP

3N

2 FP

1 FP

1N

1 FP

1N

48 24

MODEL

LENGTH WIDTH HEIGHT

HOOD DIMENSIONS (IN.)

MARK

WIDTH LENGTH DIA. CFM S.P.

COLLAR(S)

EXHAUST

HOOD INFORMATION

HOOD

NO.

COOKING

LOAD /

DUTY

RATING

HOOD

CONSTR. MUA

CFM

AC

CFM

TOTAL

WEIGHT

LBS.

SECTION

LOCATIONTOTAL

CFM

SUPPLY

HOOD OPTIONS

UL 710 LISTED W/ OUT EXHAUST FIRE DAMPER - UL #R25625

BACK INTEGRAL AIR SPACE - 3 IN WIDE

LEFT NON-INTEGRAL AIR SPACE - 1 IN THICK - ZERO CLEARANCE

4 IN HIGH CEILING ENCLOSURES - FRONT RIGHT - FIELD INSTALLED

FACTORY MOUNTED EXHAUST COLLAR(S)

BACKSPLASH 108.00 IN HIGH 199.00 IN LONG

PERFORMANCE ENHANCING LIP (PEL) TECHNOLOGY

STANDING SEAM CONSTRUCTION FOR SUPERIOR STRENGTH

A N

S U

L R

R E

L E

A S

E O

E M

T A

N K

3" REAR INTEGRAL AIR SPACE

FLAT BACKSPLASH PANEL INST. DETAIL

ENCLOSURE PANEL INSTALLATION DETAIL

ZERO CLEARANCE TO END OF HOOD

NOTES:

TO BE UL LISTED THERE MUST BE

SIDESPLASH PANELS MOUNTED THE FULL

WIDTH OF THE HOOD AGAINST THE

COMBUSTIBLE WALL

VERIFICATION OF HOOD HANGING HEIGHT ABOVE FINISHED FLOOR

(A.F.F.) IS REQUIRED FOR CORRECT PLACEMENT OF FIRE SYSTEM

NOZZLES.

HOOD HANGING HEIGHT FOR FIRE SYSTEMS

RECOMMENDED HANGING HEIGHT = 80" FROM

FINISHED FLOOR TO LOWER FRONT EDGE OF HOOD.

OTHER HANGING HEIGHT = __________" FROM

FINISHED FLOOR TO LOWER EDGE OF HOOD.

ON HOODS OVER 120"

HOOD HANGER BRACKET DETAIL

NOT TO SCALE

REFERENCE SCALED DRAWING FOR ACTUAL LOCATIONS

TYPICAL HOOD

HANGING METHOD

R a n g e

- 4 o r m o re b u rn e rs

F u e l T y p e : E le c tric

" L X

" W

X

" H

F ry e r - F u ll V a t w ith D rip b o a rd

F u e l T y p e : E le c tric

.5 " L

X

" W

X

" H

D u m p

S ta tio n

F u e l T y p e : E le c tric

.5 " L

X

" W

X

" H

G rid d le

F u e l T y p e : E le c tric

" L X

" W

X

" H

C o n v e c tio n O v e n

F u e l T y p e : E le c tric

" L X

" W

X

" H

MARK: Item 1 - Exhaust Hood - SECTION 1

ELEVATION VIEW

MARK: Item 1 - Exhaust Hood - SECTION 1

PLAN VIEW

46 IN. OC

F

IR

E S

Y S

T E

M M

A R

K It e m

C

F ir e S u p p re s s io n

MARK: Item 1 - Exhaust Hood

SECTION VIEW

169.0

FIXTURE TYPE

BULB / LAMP INFO

FOOT

CANDLES

TYPE / MODEL

MATERIAL

SIZE (IN.)

HOOD

NO.

ROUND LED

X-TRACTOR

STAINLESS STEEL

6.5 3.5 3.0

4.0 6.0

26.0

9.0 7.0

78.0 78.0

156.0 12.0 1.0

AIR SPACE

3.0

48.0

4.0

80.0

ABOVE

FINISHED

FLOOR

24.0

4.0

108.0

3.0

199.0 in. LENGTH

BACKSPLASH PANEL

9 26 0.562

26001 156 SINGLEXXEW-156-SITEM 1 - EXHAUST HOOD

4;394.184;MEDIUM

4;430 SS

WHERE

EXPOSED

LIGHTING DETAILS

QTY

L

GREASE FILTRATION DETAILS

QTY

H

LOCATION

UTILITY CABINET(S)

CONTROLS

HOOD INFORMATION

MARK FIRE SYSTEM

MODELTYPE SIZE INTERFACE

67.68

1 ITEM 1 - EXHAUST HOOD RIGHT ANSUL R102 XKC TOUCHSCREEN3

C O N S

TR

U C

TI

O N

C O M P L

IE

S

W

IT

H

N F P A

R R

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

STEINHART

23766

W.

YANR

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/2023

KCTCS - HCC FOOD SERVICE & CYBER CAFE

EXHAUST HOOD DRAWINGS

M5.1 Author

Checker

Designer

STANDARD

FIRE-WRAPPED

18 SQ

12 SQ

DUCT TYPE SIZE

WALL

26.00 SQ ∅ 28.88

51.75

(22.00)

13.25

See Table

22.50

SQ

26.00 SQ

Curb Cap

RECOMMENDED EXHAUST DUCT SIZE

SUGGESTED WALL OPENING

OVERALL HEIGHT MAY BE GREATER DEPENDING ON

MOTOR, ADAPTER, AND/OR HINGE BASE.

DUCT DIMENSIONS ARE LARGEST POSSIBLE DUCT TO FIT THROUGH CURB.

CONSULT SYSTEM DESIGN ENGINEER FOR RECOMMENDED DUCT SIZE.

NOTE: SUGGESTED WALL OPENING WITH ROOF CURB - 26

One piece fully welded windband

Switch, NEMA-3R, Toggle, Shipped with Unit

Hinge, Factory Installed

High Temp Curb Seal Rated for Continuous Duty at 1500 F (Factory Attached)

Grease Pan Kit - Containment Configured for Wall-Mounted Applications (PN:879137)

Grease Trap (PN:475538)

Tapered bushing wheel hub

Breather tube outlet area min. 4.4 sq. in. (sizes 99-480), 2.0 sq. in. (sizes 60-95)

Min. windband material thickness: 0.051" aluminum (060-240), 0.064" aluminum (240HP, 240XP), 0.080" aluminum (sizes 300-480)

Larger Curb Cap Size - 26 Square

Sidewall Mounting - Fan Configured for Wall-Mounted Applications

Curb will be Through Wall, 12 in. Wall Thickness

UL/cUL 705 Listed - Supplement SC - "Power Ventilators for Restaurant Exh. Appliances" (Formerly UL 762)

MODEL

OPERATING

POWER (HP)

V/C/P ENCLOSURE

VOLUME

(CFM)

FAN

RPM

QTY

Direct Drive Upblast Centrifugal Wall Exhaust Fan

MOTORRPMWINDINGS NEC FLA*

MOTOR INFORMATION

SIZE (HP)

WEIGHT

(LB.)

MARK

TOTAL EXTERNAL SP

(IN WG)

MARK INFORMATION FAN INFORMATION

XCUE-160-VG 0.93 208/60/1 TF2,600 1,3521 1725 1 13.22138Item 1A - Exhaust Fan 1.25

Item 1A - Exhaust Fan : SELECTED OPTIONS AND ACCESSORIES

*NEC FLA - Based on table 430. 250 or 430. 248 of National Electrical Code 2020. Actual motor FLA may vary for sizing thermal overload, consult factory"

IT

E

M

A

E X

H A

U S

T F

A N

H E

N D

E R

S O

N C

O M

M U

N

IT

Y C

O L L E

G E

A C

C U

R E

X S

O U

T H

O H

K Y

I N

A A R O N

G E A R H A R T

A A

R O

N .G

E A

R H

A R

T

A C

C U

R E

X .C

O M

(5

)5

-5

P R

O J E

C T

M A

R K

/2

/2

22.00

25.50 25.50

C O N S

TR

U C

TI

O N

C O M P L

IE

S

W

IT

H

N F P A

R R

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

STEINHART

23766

W.

YANR

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/2023

KCTCS - HCC FOOD SERVICE & CYBER CAFE

EXHAUST FAN DRAWINGS

M5.2 Author

Checker

LINE 2

208V / 1PH

POWER FOR E1

MCA: 16.50

MOP: 25

LINE 1

GROUND 208V / 1PH

M

2 HP

13.2 FLA

DS1

6***

VARI-

GREEN

MOTOR

(ECM)

AI

COM

***REMOVE FACTORY

INSTALLED JUMPER

BETWEEN TERMINAL

5 AND 6 IF PRESENT

HOOD

LIGHTS

115VAC

1200W MAX

110V-120V / 1PH

POWER FOR

CONTROLS /

LIGHTS

(NON SHUNTED

15A BREAKER)

C2

NO2

NC2

COMMON

NORMALLY OPEN

NORMALLY CLOSED

FIRE SYSTEM

DRY

CONTACT 2*

UPON FIRE

OR NO POWER TO PANEL:

C TO NO WILL CLOSE

C TO NC WILL OPEN

LTS-H

LTS-N

GND

L

L

BLACK

WHITE

GREEN

DI-2A

DI-2B

DIGITAL IN 2

LIGHT ON/OFF

(DEFAULT)

C NO

DI-1A

DI-1B

DIGITAL IN 1

FAN ON/OFF

(DEFAULT)

C NO

(OPTIONAL ON/OFF INPUTS)

RS-A

RS-B

ROOM SENSOR

(SHIPPED LOOSE) 4.50

2.80

1.10

MOUNTING TYPE

FACTORY MOUNTED:

UTILITY CABINET - RIGHT END OF HOOD

USER INTERFACE CONTROL

FANS AND LIGHTS

INTERFACE CABLE LENGTH

7FT (FACTORY PROVIDED)

(INNER CONTROL BOX: 12 X 20 X 6)

ROOM SENSOR DETAILS

DRAWING NOT TO SCALE

MOUNTING TYPE

SHIP LOOSE:

SURFACE MOUNT

WIRING

BY OTHERS (USE 18/2)

4;CONTROLS

KITCHEN HOOD

NA

JOB NAME: HENDERSON COMMUNITY

COLLEGE

MODEL:

SERIAL NUMBER:

XKC-DCV-SR-10-1-1-0

WIRING DIAGRAM CODE:

MARK: ITEM 1B - CONTROLS

WDSN#

JOB NAME: HENDERSON COMMUNITY

COLLEGE

MODEL:

SERIAL NUMBER:

CAUTION

XKC-DCV-SR-10-1-1-0

THESE DRAWINGS SHALL NOT BE REMOVED FROM

THIS EQUIPMENT. USE COPPER CONDUCTORS

RATED TO 90°C UNLESS SPECIFIED. TORQUE

CONTROL & GROUND BLOCKS TO 8 LBS. IN.

TORQUE POWER LUGS/SCREWS TO COMPONENT

RATINGS LISTED. TORQUE CONTROL BOARD

SCREW TERMINALS TO 3.5 LBS. IN. FIELD CONTROL

WIRING RESISTANCE SHOULD NOT EXCEED 0.75

OHM. SEE IOM FOR ADDITIONAL INFORMATION, OR

CALL FACTORY AT 1-800-371-6858.

WIRING DIAGRAM CODE:

MARK: ITEM 1B - CONTROLS

WDSN#

ATTENTION

UNIT MUST BE GROUNDED IN ACCORDANCE

WITH N.E.C. POWER MUST BE OFF WHILE

SERVICING.

L’APPAREIL DOIT ÊTRE MIS À LA TERRE

CONFORMÉMENT AU CODE C.E. L’ALIMENTATION

DOIT ÊTRE COUPÉE DURANT L’ENTRETIEN.

NE PAS RETIRER CES DESSINS DE CET

ÉQUIPEMENT. SAUF INDICATION CONTRAIRE,

UTILISER DES CONDUCTEURS EN CUIVRE CLASSÉS

90 °C. SERRER LES BORNES DE COMMANDE ET DE

MISE À LA TERRE À 8 LB-PO. SERRER LES

COSSES/VIS D’ALIMENTATION AUX COUPLES

INDIQUÉS POUR LE COMPOSANT. SERRER LES

BORNES À VIS DE LA CARTE DE COMMANDE

À 3,5 LB-PO. LA RÉSISTANCE DU CÂBLAGE DE

COMMANDE LOCAL NE DOIT PAS DÉPASSER

0,75 OHM. POUR PLUS D’INFORMATION, CONSULTER

LE MANUEL OU APPELER 1-800-371-6858PRG VERSION: V4

FIELD WIRED (CÂBLÉ LOCALEMENT)

FACTORY WIRED (CÂBLÉ À L’USINE)

DOC NUMBER: ---- REV: ----

FACTORY SETTINGS

TYPE: VAV

CONFIGURATION: STANDARD

ZONES: 1

HOODS: 1

SUMPS: 0

EXHAUST FANS: 1

SUPPLY FANS: 0

MB ROOM SENSOR: YES

MB TEMP SENSORS: 1

HIGH TEMP FAULT: NO

FREEZE PROTECTION: YES

GAS RESET: NO

FAN PROVING: NO

BMS: NONE

ZONE SETTINGS

SEE ZONE CONFIGURATION IN TABLE ON LEFT

HOOD SETTINGS

SEE HOOD CONFIGURATION IN TABLE ON LEFT

EXHAUST FAN SETTINGS

SEE FAN CONFIGURATION IN TABLE ON LEFT

SUPPLY FAN SETTINGS 4;

SEE FAN CONFIGURATION IN TABLE ON LEFT

SENSOR SETTINGS

SEE HOOD CONFIGURATION IN TABLE ON LEFT

USER INTERFACE SETTINGS (MB) 4;

FAN & LIGHT BUTTONS: SHOW BOTH (SEPERATE)

USER INTERFACE SETTINGS (HCB)

NA

GENERAL SETTINGS 4;

TIME ZONE: CENTRAL DAYLIGHT (DEFAULT)

FIRE/FAULT SETTINGS 4;

EXHAUST DURING FIRE: MAX

SUPPLY DURING FIRE: OFF

LIGHTS DURING FIRE: OFF

BMS SETTINGS

DEFAULT SETTINGS /

PARAMÈTRES PAR DÉFAUT

PRG VERSION: V4

DRAWING NOT TO SCALE

CABINET DETAILS USER INTERFACE DETAILS

MOUNTING LOCATION:

UTILITY CABINET ON HOOD

NOTES:

1) WHEN CONTROLS ARE MOUNTED IN

HOOD-MOUNTED OR WALL-MOUNTED UTILITY

CABINET, FOR HOOD OR WALL CABINET

DIMENSIONS SEE HOOD SUBMITTAL.

2) MINIMUM OF 36" OF CLEARANCE

RECOMMENDED IN FRONT OF CONTROL CABINET

POWER WIRING FOR KITCHEN CONTROLS

43BM

COMMERCIAL APPLIANCE OUTLET CENTER

ELECTRICAL RATINGS: 110-240V,1PHASE, 50 -60HZ,15A

BASE FILE #E200616, ML FILE #E313951

SHUNT TRIP

(BY OTHERS)

WIRING EXAMPLE:

C1

NO1

COMMON

NORMALLY OPEN

APPLIANCE CONTACTORS

(BY OTHERS)

WIRING EXAMPLE:

HOT

NEUTRAL

SHUNT TRIP

BREAKER COIL

C1

NC1

COMMON

NORMALLY CLOSED

HOT

NEUTRAL

APPLIANCE

CONTACTOR COIL

*FIRE SYSTEM DRY CONTACT WIRING EXAMPLES

MAIN

CONTROL PANEL

CONTROL WIRING FOR KITCHEN CONTROLS

MB

(MAIN BOARD)

(WIRING TO BE DONE BY ELECTRICIAN) (WIRING TO BE DONE BY ELECTRICIAN,

IF NO CONTROLS CONTRACTOR.

USE 18-22GA WIRE UNLESS SPECIFIED.)

MAIN

CONTROL PANEL

(CONTINUED)

FS-C

FS-NC

C

NC

NO

FIRE SUPPRESSION

FIRE SYSTEM SWITCH

(REMOVE JUMPER IF USED)**

WILL BE

FACTORY

WIRED IF

MOUNTED

NEXT TO

FIRE SYSTEM

**WHEN FIRE SYSTEM IS

ARMED, FS-C TO FS-NC

SHOULD HAVE CONTINUITY

DOC NUMBER: ---- REV: ----

POWER WIRING FROM BREAKER

PANEL DIRECT TO FANS

BUILDING

BREAKER PANEL

(WIRING TO BE DONE BY ELECTRICIAN)

BUILDING

BREAKER PANEL

MAIN

CONTROL PANEL

H1 N1

GND

HOT

NEUTRAL

GROUND

C1

NO1

NC1

COMMON

NORMALLY OPEN

NORMALLY CLOSED

FIRE SYSTEM

DRY

CONTACT 1*

UPON FIRE

OR NO POWER TO PANEL:

C TO NO WILL CLOSE

C TO NC WILL OPEN

E1-S+ E1-S-

0-10VDC +

0-10VDC -

FAN SPEED

0-10VDC OUT

EXHAUST E1

MARK: ITEM 1A - EXHAUST FAN

EXHAUST E1

MARK:

ITEM 1A - EXHAUST

FAN

TS-1A

TS-1B

HOOD 1

TEMP SENSOR

HOOD MARK:

ITEM 1 - EXHAUST HOOD SECTION 1

WDC#

WDC#

IT

E

M

B

C O

N T

R O

LS

H E

N D

E R

S O

N C

O M

M U

N

IT

Y C

O

LL

E G

E A

C C

U R

E X

S O

U T

H O

H K

Y

IN

A A R O N

G E A R H A R T

A A

R O

N .G

E A

R H

A R

T

A C

C U

R E

X .C

O M

(5

)5

0-

P R

O

JE

C T

M A

R K

/2

/2

1 26001 EXHAUST E1 ITEM 1A - EXHAUST FAN 208 60 NO NO12FULL COLOR

TOUCHSCREEN

CABINET – RIGHT CABINET ON

ITEM 1 - EXHAUST HOODXKC-DCV-SR-10-1-1-0

RIGHT CABINET ON ITEM 1 -

EXHAUST HOODITEM 1B - CONTROLS

1 EXHAUST E1 ITEM 1A - EXHAUST FAN 2600 NO - - 5.0 10.0-1300Z1

1 H1 ITEM 1 - EXHAUST HOOD SECTION 1 Z1 E1 TS1 NO

1 Z1 MB-RS

ZONE CONFIGURATION

ZONE # ZONE ROOM TEMP

HOOD # HOOD HOOD MARK ZONE EXHAUST SUPPLY MB-TEMP SENSORS HCB

HOOD CONFIGURATION

FAN CONFIGURATION

FAN # TYPE FAN FAN MARK MAX CFM MODBUS VFD VFD ADDRESS MIN FREQ. MIN VDC MAX VDCMAX FREQ.MIN CFMZONE

FANS CONTROLLED

ZONE CFMFAN # TYPE FAN FAN MARK MOTOR VOLT CYCLE MOTOR STARTER IN PANEL VFD IN PANELMOTOR PHASEMOTOR HPTYPE

MARK

CONTROL INFORMATION

MODEL LOCATION

USER INTERFACE

LOCATION

ELECTRICAL CONTROL PACKAGE

CONTROL FEATURES

HOOD LIGHT CONTROL

TEMP SENSORS (FACTORY INSTALLED) - QTY. 1

ROOM SENSOR (SHIPPED LOOSE) - QTY. 1

DRY FIRE CONTACTS - QTY. 2

LIGHTS OFF DURING FIRE

EXHAUST MAX DURING FIRE

SUPPLY OFF DURING FIRE

C O N S

TR

U C

TI

O N

C O M P L

IE

S

W

IT

H

N F P A

R R

R E

NI

GNEAN LOIS

ES

F O R P

E

KENTUC

K Y

FO

ETAT

S

DESNE

L I C

STEINHART

23766

W.

YANR

DRAWING INFORMATION

CHECKED BY

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

AS BUILT DATE

MM/DD/YR

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE

RTA DATE

AS BUILT DATE MM/DD/YR

DRAWN BY

A&E FILE NO. 2301-123

DECA LOG #

ACCOUNT NO.

470 CAXV HN 2901

DESCRIPTION OF REVISIONS DATE

DESIGNED BY

10/16/2023

KCTCS - HCC FOOD SERVICE & CYBER CAFE

CONTROLS DRAWINGS

M5.3 Author

Checker

ANSUL R102 (WET CHEMICAL) FIRE PROTECTION SYSTEM - MODEL FSSC

NC

NO

SHUNT TRIP BREAKER

POWER TO

COOKING EQUIPMENT

ELECTRIC GAS VALVE - IF RESET RELAY IS USED

SEE OPTION A OR B AT RIGHT, MECHANICAL

GAS SHUT OFF VALVE DOES NOT REQUIRE

ELECTRICAL CONNECTION.

CONNECTION TO COOKING

EQUIPMENT SHUT DOWN

METHOD OF WIRING, IF PROHIBITED BY LOCAL CODES.

DO NOT SHUT DOWN EXHAUST FANS WITH THIS

NC

NO

FAN(S)

N } INPUT

120 VAC

POWER TO

FAN

STARTER

MANUAL SWITCH

CONNECTION TO FAN SHUT DOWN

N } INPUT

120 VAC

NC

NO

NC

VOLTAGE FREE

BUILDING ALARM(S)

CONTACTS FORINPUT

NO

CONNECTION TO BUILDINGS ALARM

3 4

IT

E

M

C

F

IR

E S

U P

P R

E S

S

IO

N

H E

N D

E R

S O

N C

O M

M U

N

IT

Y C

O L L E

G E

A C

C U

R E

X S

O U

T H

O H

K Y

I N

A A R O N

G E A R H A R T

A A

R O

N .G

E A

R H

A R

T

A C

C U

R E

X .C

O M

(5

)5

-5

P R

O J E

C T

M A

R K

/2

/2

IT

E

M

C

F

IR

E S

U P

P R

E S

S

IO

N

H E

N D

E R

S O

N C

O M

M U

N

IT

Y C

O L L E

G E

A C

C U

R E

X S

O U

T H

O H

K Y

I N

A A R O N

G E A R H A R T

A A

R O

N .G

E A

R H

A R

T

A C

C U

R E

X .C

O M

(5

)5

-5

P R

O J E

C T

M A

R K

/2

/2

SUPPLY

LINE

DETECTION MARK(S) PROTECTED BY FIRE SYSTEM

FIRE SYSTEM OPTIONS AND ACCESSORIES

FULL INSTALLATION (INCLUDES PRE-PIPED HOOD(S) WITH DETECTION AND FACTORY COORDINATED INSTALL)

CHROME SLEEVES FOR FACTORY PROVIDED APPLIANCES DROPS - INCLUDED

METAL BLOW-OFF CAPS - INCLUDED

HOOD SUPPRESSION TANK - INCLUDED - 3 GAL. - [(1) 3.0 TANK(S)]

REMOTE PULL STATION - STANDARD - FIELD INSTALLATION AT SINGLE POINT OF EGRESS

CONTINUOUS FUSIBLE LINK

ANSUL R-102

WET CHEMICAL

11 UTILIZED

11 AVAILABLE

CABINET – RIGHT END OF ITEM 1 -

EXHAUST HOOD

ITEM 1C - FIRE SUPPRESSION

1. STAINLESS STEEL ENCLOSURE

2. AGENT STORAGE TANK

3. EXPELLENT GAS CARTRIDGE

4. ANSUL AUTOMAN RELEASE

5. REGULATOR

6. KNOCKOUT FOR WIRING MICROSWITCH

CONTROL PANEL

WET CHEMICAL FIRE PROTECTION SYSTEM TO BE ANSUL R-102, DESIGNED IN

COMPLIANCE WITH UL 300 REQUIREMENTS.

-VERIFICATION OF ALL COOKING EQUIPMENT MAKE, MODEL AND LOCATION

REQUIRED FOR ALL FIRE PROTECTION SYSTEMS.

-ALL FIRE SYSTEM PIPING IS STANDARDLY TO THE RIGHT END OF THE HOOD

UNLESS A WALL IS LOCATED ON THE RIGHT END.

-ANSUL AUTOMAN RELEASE TO BE LOCATED WITHIN 60" OF HOOD.

THE BASIC FIRE SYSTEM WILL INCLUDE THE FOLLOWING:

-GAS SHUT-OFF VALVE, IF REQUIRED, TO BE SUPPLIED BY MANUFACTURER (UP

TO 2" DIAMETER AS STANDARD), AND INSTALLED BY A LICENSED PLUMBER.

-MICRO SWITCH TO BE SUPPLIED BY MANUFACTURER FOR CONNECTION TO,

BUT NOT LIMITED TO, BUILDING ALARM SYSTEM(S), EXHAUST AND SUPPLY

FANS AND ELECTRICAL POWER SHUT DOWN. FIELD WIRING AND CONNECTIONS

TO BE PERFORMED BY A LICENSED ELECTRICIAN.

THE BASIC FIRE SYSTEM DOES NOT INCLUDE THE FOLLOWING:

-FULL DUMP TEST OTHER THAN WHT IS SPECIFIED PER THE INSTALLATION

MANUAL, OR TO SATISFY A STATE OR LOCAL CODE. PERMIT AND TESTING

FEES ARE NOT INCLUDED UNLESS NOTED UNDER THE EQUIPMENT SCHEDULE

FOR THE FIRE SYSTEM.

-MORE THEN TWO TRIPS TO THE JOBSITE OR SPECIAL TRANSPORTATION, OR

OVERNIGHT LODGING REQUIREMENTS IN REMOTE AREAS. NORMAL TRAVEL

DISTANCE IS FIRST 50 MI. (80.5 KM) FROM OFFICE.

- SPECIAL CLASSES OR ADDITIONAL LABOR FOR ACCESS TO SECURITY

SENSITIVE AREAS.

-INSTALLATION OF GAS SHUT-OFF VALVE.

-SPECIAL DRAWINGS REQUIRED TO SATISFY STATE OR LOCAL CODE. PLAN

EXAMINATION FEES, PE OR FS APPROVAL STAMP.

-UNION LABOR, GOVERNMENT LABOR, OR PREVAILING WAGES REQUIRED FOR

FINAL FIELD HOOK-UP.

-ANY AND ALL ELECTRICAL COMPONENTS/CONNECTIONS REQUIRED TO SHUT

DOWN FANS, SHUT OFF DEVICE FOR ELECTRIC COOKING EQUIPMENT (SHUNT

TRIP BREAKER), OR ACTIVATE AN ALARM SYSTEM, ETC.

-ANY DISMANTLING OR REASSEMBLY REQUIRED TO GAIN ACCESS TO THE FIRE

SUPPRESSION PIPING LOCATED ON THE TOP OF THE HOOD.

-ROUGH-IN HIDDEN CONDUIT FOR REMOTE PULL STATION OR GAS VALVE

(FLUSH MOUNTED PULL STATION).

-INSTALLATION OF MORE THAN (1) REMOTE PULL STATIONS OR DISTANCES

GREATER THAN 20 FT (6.1M.)

-PARTS OR LABOR REQUIRED TO CORRECT PIPING DUE TO COOKING

EQUIPMENT CHANGES OR DEVIATION FROM PLANS. OR ANY CHARGES FOR

MISSING OR ADDITIONAL PARTS OTHER THEN THOSE INDICATED ON THE FIRE

SUPPRESSION DETAIL.

NOTES:

NOT TO SCALE

NOTES:

1.

2.

3. DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN

NORMAL INSTALLATION. BLACK WIRE TO BE USED ONLY

FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.

DPDT SWITCHES PROVIDED BY MANUFACTURER MAY BE

WIRED PER TYPICAL EXAMPLES SHOWN. VERIFY WITH

LOCAL CODES AND EQUIPMENT SUPPLIED AS THE

CONNECTION NEEDED FOR YOUR INSTALLATION.

WIRING…