This is Addendum Two for Brady Hall HVAC Project at Kentucky School for the Deaf in Danville, Kentucky issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration (Invitation to Bid No. RFB-131-25). This addendum primarily provides notification that additional specifications, deletions, and changes will be distributed via Lynn Imaging. The project schedule indicates award by end of 2024, shops for early procurement throughout 2025, student move-out and construction start on May 24, 2026, substantial completion by December 4, 2026, final completion by December 31, 2026, and student move-in on January 4, 2027.

The addendum makes several modifications, including: changes to closed cell spray foam polyurethane requirements in Section 07 20 00; addition of Hardware Set A274 for Opening A274; and updates to mechanical, electrical, plumbing and systems via CMTA narrative and drawings. Additionally, new photocell sensors were added to the dining room area and exit signs were added throughout corridors. Updates were also made to fire alarm, intrusion, and weather notification devices according to the electrical drawings revisions.

View the file

Other files

File Type Posted
Final_RFB_785_2500000272_3_SO_FORM.PDF PDF
Final_RFB_785_2500000272_1_SO_FORM.PDF PDF
Addendum One .pdf PDF
Final_RFB_785_2500000272_2_SO_FORM.PDF PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-131-25

FOR: Brady Hall HVAC Project Kentucky School for the Deaf Department of Education Danville, Kentucky

DATE: November 26, 2024

RFB-785-2500000272

ADDENDUM NO. Two (2)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-131-25 For: Brady Hall HVAC Project Kentucky School for the Deaf Department of Education Danville, Kentucky

Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration s t u d i o k r e m e r a r c h i t e c t s

1231 S Shelby St, Louisville, KY 40203

TEL 502.499.1100 FAX 502.499.1101

A D D E N D U M N O . 2

TO: All Plan Holders

FROM: Studio Kremer Architects

PROJECT: Kentucky School for the Deaf

BRADY HALL

ska# 2023-33.5

This Addendum No. 2 supersedes and supplements all portions of the Construction Documents with which it conflicts.

Acknowledgement of this Addendum shall be noted on the Form of Proposal.

Addendum No. 2 makes the following modifications and clarifications to the Construction Drawings and Specifications:

S P E C I F I C A T I O N S .

Item No. 1: Reference Section 07 20 00 – BUILDING INSULATION

1. Reference Section 07 20 00, 2.01: Requirements for Closed Cell Spray Foam Polyurethane products are modified as follows:

A. Closed-cell spray foam polyurethane

1. Manufacturer: Subject to compliance with requirements, provide products of one of the following:

a. BASF (Walltite Low-GWP)

b. Johns Manville (JM Corbond III)

c. Dow Chemical Company

2. Two-Component, spray-applied polyurethane foam with zero-ozone depleting potential that meets the following:

a. Core Density, ASTM D1622: 2.0-2.3 pcf

b. Compressive Strength, ASTM D1621: min. 25 psf

c. Closed-cell content, ASTM D6226: >90

d. Thermal Resistance, ASTM C518: min. 6.4 / inch

e. Water Vapor Permeability, ASTM E96: min. 1.1 perm at 1”

f. Surface Burning Characteristics, ASTM E84: Class 1

g. Provide minimum thickness of 3-1/2 inches.

Spray foam insulation for filling small voids / holes (2.01, B) remains as originally released.

Item No. 2: Reference Section 08 71 00 – Door Hardware

Drawing A-110B

1. Opening A274 on Sheet A-110B did not have a Hardware Set provided. For this opening, provide Hardware Set A274, as follows:

page 2 s t u d i o k r e m e r a r c h i t e c t s

(3) Butt Hinges CH81 x 5.0 x 4.5 652 PBB

(1) Panic Device, Rim, 03 10-03C-CD 94 630 DTX

(2) Rim Cylinder SFIC 7-pin 626 PDQ

(1) Closer, w/Spring Stop / HO D-4550 HCS 689 DTX

(2) Kick Plate KO050 8 x 1LDW x CS x B4E 630 TRI

Note 1: Provide closer drop plate as required by top rail configuration.

Item No. 3:

The attached documents and drawing revisions (3-page narrative and 19 drawings) provided by CMTA describe all changes, corrections, clarifications and updates to the Mechanical, Electrical, Plumbing, and Systems scopes of work and become part of this Addendum.

Item No. 4:

1. Structural sheets were left out of the initial release and re-issued as Addendum No. 1. The attached reduces files may be more useful.

2. The following links to archival drawings of the existing building:

https://drive.google.com/drive/folders/1Adrivaoz39gb3mAN071bS4wWMEaSQ8hR?usp=sharing

Item No. 5:

1. The project schedule shall be as follows:

End of 2024 Award

All of 2025 Shops for early procurement

May 24 2026 Students Move Out

Construction Starts

December 4 2026 Substantial Completion #1 (Construction Complete)

December 31 2026 Final Completion

January 4 2027 Students Move In

END OF ADDENDUM NO.2

(referenced attachments follow)

ENCL:

1. CMTA Addendum Text

2. Electrical attachments (reference CMTA Addendum)

3. Structural sheets re-released (No changes.)

https://drive.google.com/drive/folders/1Adrivaoz39gb3mAN071bS4wWMEaSQ8hR?usp=sharing

Kentucky School for the Deaf - Brady Hall Renovation

Project Number #540CBXLSD6300

Addendum #1

November 25, 2024

CHANGES TO DRAWINGS:

Electrical

Sheet # Sheet Title Noted Update

E001 BRADY HALL – ELECTRICAL LEGEND AND

GENERAL NOTES

Added intrusion and weather notification devices to legend.

E100 BRADY HALL - FIRST FLOOR ELECTRICAL

DEMOLITION - AREA A

Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.

Added exit sign removal scope.

Added removal of FACP.

E101 BRADY HALL - FIRST FLOOR ELECTRICAL

DEMOLITION - AREA B

Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.

Added exit sign removal scope.

E102 BRADY HALL - SECOND FLOOR ELECTRICAL

DEMOLITION - AREA A

Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.

Added exit sign removal scope.

E103 BRADY HALL - SECOND FLOOR ELECTRICAL

DEMOLITION - AREA B

Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.

Added exit sign removal scope.

E200 BRADY HALL - FIRST FLOOR LIGHTING PLAN

- AREA A

Edited General lighting note ‘I’.

Added exit signs.

E201 BRADY HALL - FIRST FLOOR LIGHTING PLAN

- AREA B

Edited General lighting note ‘I’.

Added exit signs.

E202 BRADY HALL - SECOND FLOOR LIGHTING

PLAN - AREA A

Edited General lighting note ‘I’.

Added photocell sensors to dining room.

Addendum No 2

Added exit signs.

E203 BRADY HALL - SECOND FLOOR LIGHTING

PLAN - AREA B

Edited General lighting note ‘I’.

Added exit signs.

E300 BRADY HALL - FIRST FLOOR

POWER/SYSTEMS PLAN - AREA A

Relocated FACP.

Utility transformer added to drawing.

Added several FA detection and notification devices.

E301 BRADY HALL - FIRST FLOOR

POWER/SYSTEMS PLAN - AREA B

Added several FA detection and notification devices.

E302 BRADY HALL - SECOND FLOOR

POWER/SYSTEMS PLAN - AREA A

Added several FA detection and notification devices.

E303 BRADY HALL - SECOND FLOOR

POWER/SYSTEMS PLAN - AREA B

Added several FA detection and notification devices.

E400 BRADY HALL - ELECTRICAL DEMOLITION

POWER RISER DIAGRAM

Demolished all feeders and pathways.

E401 BRADY HALL - ELECTRICAL POWER RISER

DIAGRAM

Added note ‘E’ to feeder schedule.

Added clarification notes to ‘MSB’ schedule.

E500 BRADY HALL – FIRE ALARM RISER

DIAGRAM

Added detail to sheet.

Added intrusion and weather devices to riser diagram.

E602 BRADY HALL – LIGHT FIXTURE SCHEDULE

AND DETAILS

Added exit sign selections to schedule.

CHANGES TO SPECIFCATIONS:

• 230900 - Instrumentation and Control for HVAC o Revision to Section 1.2.F – JCI to be added as an approved manufacturer.

• 263213 – Diesel Engine Generator Sets o Revision to Section 2.1.A – Generac to be added as an approved manufacturer.

ATTACHMENT(S):

• Electrical Drawings as listed above

• Specifications as listed above.

END OF ADDENDUM

C

SD

I

UON

EM

CFOI

OFOI

CFCI

OFCI

C/S

J

DESCRIPTION

S

S 3

S D

SK

P

SOS

OS

IL

GROUND FAULT PROTECTED DUPLEX WITH WEATHER-

PROOF "WHILE IN USE" TYPE DIE-CAST METAL

COVERPLATE WITH LOCKABLE ENCLOSURE AT

OUTLET - SEE SPECIFICATIONS

WP

ER

ELECTRIC WATER COOLER RECEPTACLE:

COORDINATE EXACT LOCATION WITH PLUMBING

CONTRACTOR TO CONCEAL OUTLET(S) BEHIND

COOLER, PROVIDE MULTIPLE RECEPTACLES WHERE

REQUIRED BY MANUFACTURER, PROVIDE READILY

ACCESSIBLE DEAD FRONT GFCI DEVICE AT 18"

ADJACENT TO WATER COOLER FOR PROTECTION OF

WATER COOLER RECEPTACLE(S)

EWC

W

SS

POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES

SLASH THROUGH ANY DEVICE INDICATES MOUNTING

ABOVE COUNTERTOP 4" ABOVE BACKSPLASH, OR AT 46"

WHERE NO COUNTER IS PRESENT

SVS

VS

LV

ILLUMINATED HANDLE LIGHT SWITCH (ILLUMINATED

WHEN LOAD IS OFF)

EMERGENCY AUTOMATIC TRANSFER SWITCH

FOR LIGHTING CONTROLS (REFER TO DETAIL)

FILLED CENTER BAR INDICATES INTEGRAL GROUND

FAULT PROTECTION (GFCI)

GANG RECEPTACLE IN COMBINATION WITH SWITCH

(PROVIDE DIVIDER IF LIGHTING CIRCUIT IS 277V)

NON-REVERSING MOTOR STARTER SNAP SWITCH

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

FLUSH MOUNTED REMOTE ALARM INDICATING

STATION/TEST SWITCH

CONNECTION TO SPRINKLER TAMPER

SWITCH WITH ADDRESSABLE MODULE

CONNECTION TO SPRINKLER FLOW

SWITCH WITH ADDRESSABLE MODULE

PHOTO-ELECTRIC SMOKE DETECTOR

MAIN CONTROL PANEL CENTRAL PROCESSING

UNIT (CPU)

LIGHT SWITCH:GENERAL PURPOSE

AS NOTED

AS NOTED

6'-6'' TO

TOP

46" TO

LEVER

PULL STATION : DOUBLE ACTION

AUDIO-ONLY NOTIFICATION APPLIANCE

VISUAL-ONLY NOTIFICATION APPLIANCE

AUDIO/VISUAL NOTIFICATION APPLIANCE

HEAT DETECTOR

CARBON MONOXIDE ALARM: SINGLE STATION

W/SOUNDER BASE

CARBON MONOXIDE AUDIO/VISUAL NOTIFICATION

APPLIANCE

DOOR HOLDER : WALL TYPE

DOOR HOLDER : CLOSURE TYPE

DUCT SMOKE DETECTOR

PRESSURE SWITCH

REMOTE L.C.D. FIRE ALARM ANNUNCIATOR

POST INDICATOR VALVE

ISOLATION MODULE

H.V.A.C. SMOKE DAMPER CONNECTION. REFER TO "SM"

DETAIL FOR ALL REQUIRED EQUIPMENT, DEVICES AND

INSTALLATION REQUIREMENTS INCLUDING TO PROVIDE

DUCT MOUNTED SMOKE DETECTOR AND RELAY.

UNLESS OTHERWISE NOTED

INDICATES EMERGENCY POWER

HD

CM

F

DH

ABV DOOR DH

ABV CLG DD

FS

TS

PS

46"

I

SM

ABBREVIATIONS

DESCRIPTION

STRIP FIXTURE

CROSS-HATCHING INDICATES LIGHT IS POWERED

FROM EMERGENCY POWER

PARALLEL-HATCHING INDICATES LIGHT IS POWERED

FROM THE EMERGENCY-LIFE SAFETY BRANCH POWER

POWER OUTLETS

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE - SAFETY TYPE, TAMPER

RESISTANT.

JUNCTION BOX, CEILING OR WALL

VOLTAGE/1PH RECEPTACLE, AS NOTED

VOLTAGE/3PH RECEPTACLE, AS NOTED

SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)

DIMMER SWITCH

THREE-WAY SWITCH

KEYED SWITCH

OCCUPANCY OR VACANCY SENSOR SWITCH

OCCUPANCY OR VACANCY SENSOR, CEILING MOUNTED

LOW VOLTAGE MOMENTARY SWITCH

PHOTO-CELL AS NOTED

EXIT LIGHT (CEILING, END, WALL MOUNT)

LIGHTING

REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE

SPECIFICATIONS, MOUNTING HEIGHTS, ETC.

WALL, CLG

CLG

CLG

CLG

WALL

54"

46"

46"

46"

46"

46"

46"

46"

1'-6"

1'-6"

1'-6"

46"

1'-6"

1'-6"

2'-2"

CLG

AS NOTED

S

S

S M

D R

A W

IN

G

S Y

M B

O L

SURFACE OR SUSPENDED CEILING FIXTURE (SLASH

INDICATES RECESSED)

POLE MOUNTED AREA LIGHT

EMERGENCY BATTERY WALL-PACK

WALL MOUNT FIXTURE ,

FLOODLIGHT

S

A

F

F

RI

INDICATES VANDAL-PROOF POLYCARBONATE COVER,

VANDAL PROOF COVERS SHALL BE UL LISTED FOR USE

WITH THE SPECIFIC DEVICE THEY ARE PROTECTING

PC

WALL

WALL

7'-6''

FIREMAN'S PHONE JACK FP

ADDRESSABLE RELAY MODULE R

DESCRIPTION

K

DB

DB

WP

DOORBELL PUSHBUTTON STATION, PROVIDE COMPLETE

WITH TRANSFORMER (MOUNT ABOVE CEILING IN

CORRIDOR NEAR PUSH-BUTTON) AND ALL

ACCESSORIES, POWER FROM NEAREST AVAILABLE 120V

NORMAL POWER GENERAL RECEPTACLE CIRCUIT,

NUTONE OR EQUAL

DOORBELL AUDIO/VISUAL STATION, PROVIDE PROVIDE

CONNECTION TO PUSHBUTTON STATION IN AREA.

COORDINATE EXACT AUDIO SOUND (CHIME, BUZZER,

ETC.) DESIRED WITH OwNER/ARCHITECT, NUTONE OR

EQUAL

PLUMBING FIXTURE ELECTRIC EYE TRANSFORMER

CONNECTION. TRANSFORMER SHALL BE 120V-24V.

MOUNT ABOVE SUSPENDED ACCESSIBLE CEILING IN J-

BOX. PROVIDE ADDITIONAL TRANSFORMERS OF SAME

TYPE AS/IF NEEDED

PROVIDE CONNECTION TO HAND DRYER (SEE

ARCHITECTURAL SPECIFICATIONS)

VERIFY WITH

ARCHITECT

C

INDICATES MOUNTING ABOVE COUNTER-TOP,

2" ABOVE BACKSPLASH, NO HIGHER THAN 48''

WG

WIREGUARD - PROVIDE MANUFACTURER'S

SPECIFIC GUARD FOR DEVICE NOTED

BOX ON ANY DEVICE INDICATES SURFACE MOUNTED

BACKBOX/WIREMOLD

CONDUIT CONCEALED IN WALLS OR IN CEILING

SPACE: ARROW(S) INDICATE(S) HOME RUN & #

OF CIRCUITS: HASHMARKS INDICATE # OF

CONDUCTORS. DASHED LINE INDICATES

CONDUIT BELOW FLOOR.

WIREWAY WITH REMOVABLE COVER (SIZE AS NOTED)

PANELBOARD, SURFACE OR FLUSH MOUNTED,

HATCHING INDICATES EMERGENCY

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

MECHANICAL EQUIPMENT DESIGNATOR

(SEE MECH. SCHEDULES)

EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)

KITCHEN EQUIPMENT OUTLET COUPLING

CONNECTION (SEE DETAIL)

AS SHOWN

AS SHOWN

AS NOTED

AS SHOWN

MISCELLANEOUS

DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC COMBINATION STARTER

ENCLOSED FLUSH MTD. CIRCUIT BREAKER

WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.

PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR

OUTDOORS.

TRENCH DUCT (SIZE AS NOTED)

PUSHBUTTON STATION

FLEXIBLE CONDUIT

TRANSFORMER

TAGGED NOTE

REVISION TAG

J-HOOK CABLE PATH, SIZE AS NOTED

LOW VOLTAGE CABLE PATH

5'-0"

5'-0"

5'-0"

5'-0"

46"

46"

7'-6''

6'-6'' TO TOP

SURGE PROTECTION DEVICE

GENERATOR ANNUNCIATOR PANEL - SEE

SPECIFICATIONS

46"

THERMOSTAT PROVIDED BY MECHANICAL

CONTRACTOR, ELECTRICAL CONTRACTOR SHALL

PROVIDE BACK-BOX CONDUIT STUB-UP, REFER TO

MECHANICAL DRAWINGS FOR LOCATIONS

SWITCHES

FIRE ALARM

E,EMINDICATES EMERGENCY POWER

GEN-A

SPD

J

J

NAC

PIV

FAA

FACP

T

D R

A W

M B

O L

D R

A W

M B

O L

AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED

AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED

EQUIP-1

PLUMBING FIXTURE SOLENOID VALVE/ELECTRIC EYE

SENSOR CONNECTION. COORDINATE EXACT

CONNECTION REQUIREMENTS WITH MANUFACTURER.

GROUND

NEUTRAL

PHASE

WALL, CLG

WALL, CLG S

A

F

CM

DEVICE USED FOR ELEVATOR CONTROL EL

FIRE ALARM CONTROL EXTENDER EXT

4'-6''

TRANSPONDER CABINET 46" TRAN

DEAD FRONT GFCI DEVICE, LABEL AND INSTALL IN

READILY ACCESSIBLE LOCATION

FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL

USB OUTLETS IN ADDITION TO POWER RECEPTACLES

1'-6"

, J

VARIABLE FREQUENCY DRIVE 5'-0"

CIRCLE ON ANY DEVICE INDICATES DEVICE FED FROM

STUB UP CONDUIT

MOTOR CONNECTION, REFER TO EQUIPMENT

CONNECTION SCHEDULE

DUPLEX RECEPTACLE, CEILING MOUNTED CLG

CONDUIT UP

CONDUIT DOWN

GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''

AS SHOWNBUS DUCT, AMPERAGES AS NOTED

M O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

M O

U N

T

IN

G H

E

IG

C E

N T

E R

O F

B O

X

M O

U N

T

IN

G H

E

IG

C E

N T

E R

O F

B O

X

EMERGENCY SHUTDOWN PUSH BUTTON

ACAREA OF RESCUE ASSISTANCE COMMAND CENTER

ARAREA OF RESCUE ASSISTANCE REMOTE STATION

ET,

OCCUPANCY OR VACANCY SENSOR, WALL MOUNTED OS

DESCRIPTION

P A

T H

W A

Y S

O

F O

I

P A

T H

W A

Y S

O

F C

I

P A

T H

W A

Y S

C

F C

I

IT

E

M U

S E

D O

N P

R O

J E

C T

D E

V

IC

E S

O

F C

I

D E

V

IC

E S

C

F C

I

SYSTEM D

E

V

IC

E S

O

F O

I

SYSTEM

RESPONSIBILITY

MATRIX

FIRE ALARM

DATA PROCESSING

SYSTEM RESPONSIBILITY GENERAL NOTES:

A. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TO VENDOR-

FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGS SHALL BE INCLUDED

BY THE CONTRACTOR.

B. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESS CONTROL

DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.

C. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS. CONTRACTOR

SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT INSTALLATION

LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL SYSTEMS PRIOR TO

CONSTRUCTION.

D. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS, CONTRACTOR SHALL

PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO CABLE PATHS AS REQUIRED BY

SYSTEM VENDORS, TERMINATE CONDUITS AT CABINETS/ON BACKBOARDS AS REQUIRED.

COORDINATE EXACT REQUIREMENTS WITH APPROPRIATE VENDORS PRIOR TO

CONSTRUCTION.

E. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS INCLUDING

CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING, LABELING, ETC.

F. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM COMPLETE,

INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE CONTRACTOR SHALL

CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID. ALL SYSTEMS SHALL MATCH

EXISTING FACILITY STANDARDS AND BE FULLY COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL

SYSTEM VENDORS SHALL COORDINATE EXACT SYSTEM REQUIREMENTS WITH OWNER PRIOR

TO BID. NEW COMPONENTS SHALL BE INTERCONNECTED WITH EXISTING SYSTEMS WHERE

POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BE COORDINATED WITH THE

OWNER PRIOR TO ORDERING. ALL PROGRAMMING SHALL BE INCLUDED AS REQUIRED BY THE

OWNER. PROVIDE 4 HOURS OF TRAINING FOR EACH SYSTEM.

G. MININUM DATA, VOICE AND AUDIO / VISUAL RACEWAY IS 1-1/4" CONDUIT.

SYSTEM

SYMBOLT

E

R M

IN

A

T

IO

N S

O

F O

I

T E

R M

IN

A

T

IO

N S

O

F C

I

T E

R M

IN

A

T

IO

N S

C

F C

I

C A

B L

IN

G

/C O

N D

U C

T O

R S

C

F C

I

C A

B L

IN

G

/C O

N D

U C

T O

R S

O

F O

I

C A

B L

IN

G /C

O N

D U

C T

O R

S

O F

C I

SDSOUNDER BASE SMOKE DETECTOR W/ STROBE SB

WALL

WALL

VISUAL ALARM STROBE ONLY

(BLUE LENS COLOR INTRUDER SYSTEM)

VISUAL ALARM STROBE ONLY

(AMBER LENS COLOR WEATHER SYSTEM)

A. THIS PROJECT INTERFACES EXTENSIVELY WITH EXISTING BUILDING SERVICES. IT SHALL BE

THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND PHASE ALL TIE-INS AND

INTERRUPTIONS OF EXISTING SERVICES TO MINIMIZE OR ELIMINATE DOWNTIME. AS AN

EXAMPLE, MAIN GAS SERVICE, WATER SERVICE, ELECTRICAL SERVICE, HVAC SERVICES,

ETC., WILL BE AFFECTED AND REPLACED OR MOVED DURING THIS PROJECT. THE

CONTRACTOR SHALL INSTALL ALL NEW SERVICES AND EQUIPMENT AND HAVE THEM TESTED

AND FULLY AND RELIABLY FUNCTIONAL PRIOR TO INTERRUPTING, RELOCATING OR

REMOVING ANY EXISTING SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO

BARE ANY AND ALL COSTS ASSOCIATED WITH THIS PHASING, INCLUDING TEMPORARY

SERVICES, TEMPORARY RELOCATION, PREMIUM TIME WORK, ETC. CONTRACTOR SHALL

COORDINATE ALL SAID WORK WITH THE OWNER AND APPLICABLE UTILITIES PER THE

CONTRACT DOCUMENTS.

ELECTRICAL PHASING NOTES

A. WALL AND FLOOR PATCHING/PAINTING: PATCH/INFILL ALL WALL/FLOOR PENETRATIONS

WHERE EXISTING ELECTRICAL EQUIPMENT/DEVICES/CONDUIT/RACEWAYS ARE REMOVED.

COORDINATE ALL PATCH/INFILL WORK WITH THE GENERAL CONTRACTOR.

B. EXISTING CONDUIT / RACEWAY DEMOLITION: ALL EXISTING CONDUIT / RACEWAY ARE TO BE

REMOVED COMPLETLEY TO BEYOND FINISHED SURFACES. PATCH AND PAINT ALL SURFACES

AS REQUIRED TO MATCH ADJACENT CONDITIONS WHERE CONDUIT / RACEWAY HAVE BEEN

REMOVED.

C. PATCH HOLES IN WALLS, FLOORS, CEILINGS, ROOFS, ETC. TO MATCH ADJACENT SURFACES

AS A RESULT OF REMOVAL OF ELECTRICAL SYSTEMS. PATCHING SHALL BE PERFORMED BY

QUALIFIED TRADESMAN

ELECTRICAL DEMOLITION GENERAL NOTES

A. THE CONTRACTOR IT IS HEREBY ADVISED THAT IS POSSIBLE THAT ASBESTOS AND/OR

OTHER HAZARDOUS MATERIALS ARE OR WERE PRESENT IN THIS BUILDING(S). ANY WORKER,

OCCUPANT, VISITOR, ETC., WHO ENCOUNTERS ANY MATERIAL OF WHOSE CONTENT THEY

ARE NOT CERTAIN SHALL PROMPTLY REPORT THE EXISTENCE AND LOCATION OF THAT

MATERIAL TO THE OWNER. FURTHERMORE, THE CONTRACTOR SHALL INSURE THAT NO ONE

COMES NEAR TO OR IN CONTACT WITH ANY SUCH MATERIAL OR FUMES THEREFROM UNTIL

ITS CONTENT CAN BE ASCERTAINED TO BE NON-HAZARDOUS.

B. CMTA, INC. HAS NO EXPERTISE IN THE DETERMINATION OF THE PRESENCE OF ANY

HAZARDOUS MATERIAL. THEREFORE, NO ATTEMPT HAS BEEN MADE BY CMTA TO IDENTIFY

THE EXISTENCE OR LOCATION OF ANY SUCH HAZARDOUS MATERIAL. FURTHERMORE, CMTA

NOR ANY AFFILIATE HEREOF WILL NOT OFFER OR MAKE ANY RECOMMENDATIONS RELATIVE

TO THE REMOVAL, HANDLING OR DISPOSAL OF SUCH MATERIAL.

C. IF THE WORK WHICH IS TO BE PERFORMED INTERFACES, CONNECTS OR RELATES IN ANY

PHYSICAL WAY WITH OR TO EXISTING COMPONENTS WHICH CONTAIN OR BEAR ANY

HAZARDOUS MATERIAL, ASBESTOS BEING ONE, THEN IT SHALL BE THE CONTRACTOR'S SOLE

RESPONSIBILITY TO CONTACT THE OWNER AND SO ADVISE HIM IMMEDIATELY.

D. THE CONTRACTOR BY EXECUTION OF THE CONTRACT FOR ANY WORK AND/OR BY THE

ACCOMPLISHMENT OF ANY WORK THEREBY AGREE TO BRING NO CLAIM RELATIVE TO

HAZARDOUS MATERIALS FOR NEGLIGENCE, BREACH OF CONTRACT, INDEMNITY, OR ANY

OTHER SUCH ITEM AGAINST CMTA, ITS PRINCIPALS, EMPLOYEES, AGENTS OR

CONSULTANTS. ALSO, THE CONTRACTOR FURTHER AGREES TO DEFEND, INDEMNIFY AND

HOLD CMTA, ITS PRINCIPALS, EMPLOYEES, AGENTS AND CONSULTANTS HARMLESS FROM

ANY SUCH RELATED CLAIMS WHICH MAY BE BROUGHT BY ANY SUBCONTRACTORS,

SUPPLIERS OR ANY OTHER THIRD PARTIES.

E. THE CONTRACTOR IS DIRECTED TO THE SPECIFICATIONS FOR FURTHER INFORMATION.

ELECTRICAL HAZARDOUS MATERIALS NOTES

ALL LOW VOLTAGE, DATA / VOICE, FIRE ALARM, WIRELESS ACCESS POINTS, PROJECTOR / AV

EQUIPMENT, CCTV, AND SECURITY SHALL BE PRE AND POST TESTED. RESULTS SHALL BE

TABULATED AND SENT TO KSD AND THE ENGINEER FOR REVIEW AND COMMENT. THIS SHALL BE

DONE PRIOR TO SUMMER WORK.

CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING THE EXISTING TO REMAIN SYSTEMS AND

SYSTEMS THAT ARE PARTIALLY DEMOLISHED. DOWNSTREAM DEVICES SHALL NOT BE AFFECTED

DURING DEMOLITION AND ANY ISSUES WILL BE REQUIRED TO BE IMMEDIATELY CORRECTED TO

ALLOW PROCEEDING WITH CONSTRUCTION.

PRE AND POST TEST SCOPE

NOTE: ALL NEW LOW-VOLTAGE SYSTEMS CABLING SHALL BE PLENUM RATED.

REVISION HISTORY OF THIS DRAWING

DECA LOG #

ENGR. FILE NO.

DRAWING NO.

DRAWN BY

AS BUILT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

# 540CBXLSD6300

ACCT# 540CBXLSD6300

10411 Meeting Street Prospect, KY 40059

T: 502 326.3085 F: 502 326.2691

08.20.24

VKYS23

/2

/2

:4

:3

P

M

C

U s e rs \g w e s s lin g \D o c u m e n ts

\V K

Y S

B ra d y H a ll_ g w e s s lin g C

L F

H C

.r v t

P ro je c t

N u m b e r_

O w n e r_ R

T A

E -0

B R

A D

Y H

A L

L

E L

E C

T R

IC

A

L L

E G

E N

D A

N D

G E

N E

R A

L N

O T

E S

E-001

BRADY HALL - ELECTRICAL LEGEND AND GENERAL

NOTES

S 2nd St, Danville, KY 40422

BKB

GTW

RTA

KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL

GENERAL NOTES (LEGEND):

A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH

SHOP DRAWINGS.

B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE UNDERSTANDING OF THE

PROJECT REQUIREMENTS.

C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES. INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC. IN ADDITION, OBSERVE ALL APPLICABLE RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT FROM CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.

D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL

AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOW

CLARIFICATION BY WRITTEN ADDENDUM.

F. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT

SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.

G. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND MUST BE

SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.

H. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS

MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE ENGINEER IN WRITING.

I. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT SHALL APPLY.

J. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO.

MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS

OF THESE DOCUMENTS, AS APPLICABLE.

K. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONED DRAWINGS, OR

DIMENSIONS SUPPLIED TO THE CONTRACTOR.

L. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND FURNITURE, CASEWORK, AND/OR EQUIPMENT. ADDITIONAL OUTLETS MAY BE SHOWN ON ARCHITECTURAL DRAWINGS AND

SHALL BE INCLUDED IN THE CONTRACT.

M. FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONS PROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER PRIOR TO ROUGHING-IN ANY

WORK.

N. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS.

IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER PRIOR TO INSTALLATION FOR

CLARIFICATION.

O. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR

SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.

P. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.

Q. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE

QUALITY OF WORK RESIDES WITH THE ENGINEER

R. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY PERIODS FOR EQUIPMENT ARE

SPECIFIED.

S. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.

T. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS

OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.

U. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL

SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND ARCHITECT.

V. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2' DIMENSION

OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.

W. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE

ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY OF THE PURCHASER.

X. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE- MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TO MAINTAIN

CEILING RATINGS.

Y. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE RATING. NO

INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.

Z. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED

AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE CONTRACTOR(S).

AA. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL

ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.

BB. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THE

COLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.

CC. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.

DD. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES (I.E. VAV

BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.

EE. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN PERMISSION FROM THE ENGINEER AND

CONSENT OF THE OTHER TRADE, IN WRITING.

FF. WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME WALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND TRANSMISSION FROM ROOM TO ROOM.

GG. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH SPECIFICATIONS, WHICHEVER IS MORE

STRINGENT.

HH. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A

PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE ENGINEER.

II. CHECK ALL THREE PHASE MOTORS WITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.

JJ. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO CONSTRUCTION.

KK. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO CONSTRUCTION.

LL. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTING AND

PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.

MM. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).

NN. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL

APPLY.

OO. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGER NOTIFICATION PERIOD, SO

PROVIDE.

PP. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS NEEDED.

QQ. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FOR SEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO MAINTAIN SEQUENCE OF THE WORK FROM PHASE TO PHASE.

PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL TEMPORARY SERVICES AS REQUIRED BY

OWNER TO ACCOMPLISH THE PHASING PLAN.

NO SCALE

ELECTRICAL LEGEND

SHEET LIST - ELECTRICAL

Sheet Number Sheet Name

E-001 BRADY HALL - ELECTRICAL LEGEND AND GENERAL NOTES

E-100 BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION - AREA A

E-101 BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION - AREA B

E-102 BRADY HALL - SECOND FLOOR ELECTRICAL DEMOLITION - AREA A

E-103 BRADY HALL - SECOND FLOOR ELECTRICAL DEMOLITION - AREA B

E-200 BRADY HALL - FIRST FLOOR LIGHTING PLAN - AREA A

E-201 BRADY HALL - FIRST FLOOR LIGHTING PLAN - AREA B

E-202 BRADY HALL - SECOND FLOOR LIGHTING PLAN - AREA A

E-203 BRADY HALL - SECOND FLOOR LIGHTING PLAN - AREA B

E-300 BRADY HALL - FIRST FLOOR POWER/SYSTEMS PLAN - AREA A

E-301 BRADY HALL - FIRST FLOOR POWER/SYSTEMS PLAN - AREA B

E-302 BRADY HALL - SECOND FLOOR POWER/SYSTEMS PLAN - AREA A

E-303 BRADY HALL - SECOND FLOOR POWER/SYSTEMS PLAN - AREA B

E-304 BRADY HALL - POWER/SYSTEMS ROOF PLAN

E-400 BRADY HALL - ELECTRICAL DEMOLITION POWER RISER DIAGRAM

E-401 BRADY HALL - ELECTRICAL POWER RISER DIAGRAM

E-402 BRADY HALL - ELECTRICAL PANELBOARD SCHEDULE

E-403 BRADY HALL - ELECTRICAL PANELBOARD SCHEDULE

E-500 BRADY HALL - FIRE ALARM RISER DIAGRAM

E-600 BRADY HALL - ELECTRICAL DETAILS

E-601 BRADY HALL - ELECTRICAL DETAILS

E-602 BRADY HALL - LIGHT FIXTURE SCHEDULE AND DETAILS

ADDENDUM 01 11/25/24

UP

SD

F

SD

HD

F

HD

HD

SD

SD

SD

SD

SD

HD

HD

HD

F

I W

W I

F

I W

F

F

WI

I W

F

F

WI

F

WI

I W F

F

WI

I W F

F W

I

I W F

F

WI

F F W

I

F W

I

I W

F

F I

W

SD

F W

I

F W

I

I W F

F W

II W

F

BEDROOM

A110

BEDROOM

A111

TOILET

A112

SHOWER

A113

Room

A114

LIVING ROOM

A115

ARTS & CRAFT

A116

PLAY AREA

A117

BEDROOM

A118

BEDROOM

A119

HALL

A120

TOILET

A121

SHOWER

A122

LAUNDRY

A123

TOILET

A145

STAIR

A

Room

A105 Room

A106

LIVING ROOM

A107

PLAY AREA

A108

ARTS AND CRAFTS

A109

CORRIDOR

A100

CONTROL

A103

LOBBY

A102

RAMP

ELEV.

ELEV. MECH.

A124

MECHANICAL

A125

GENERATOR

A146

STORAGE

A126

Room

A127

LIVING Room

A128

PLAY AREA

A129

ARTS AND CRAFTS

A130

BEDROOM

A131

BEDROOM

A132

BEDROOM

A141

BEDROOM

A142

TOILET

A143

SHOWER

A144

TOILET

A133

SHOWER

A134

SENSORY ROOM

A135

TIME OUT

A136

ARTS & CRAFTS

A137

PLAY AREA

A138

Room

A139

LIVING ROOM

A140

CORRIDOR

A104

VESTIBULE

A101

BEDROOM

A110

BEDROOM

A111

TOILET

A112

SHOWER

A113

Room

A114

LIVING ROOM

A115

ARTS & CRAFT

A116

PLAY AREA

A117

BEDROOM

A118

BEDROOM

A119

HALL

A120

TOILET

A121

SHOWER

A122

LAUNDRY

A123

TOILET

A145

STAIR

A

Room

A105 Room

A106

LIVING ROOM

A107

PLAY AREA

A108

ARTS AND CRAFTS

A109

CORRIDOR

A100

CONTROL

A103

LOBBY

A102

RAMP

ELEV.

ELEV. MECH.

A124

MECHANICAL

A125

GENERATOR

A146

STORAGE

A126

Room

A127

LIVING Room

A128

PLAY AREA

A129

ARTS AND CRAFTS

A130

BEDROOM

A131

BEDROOM

A132

BEDROOM

A141

BEDROOM

A142

TOILET

A143

SHOWER

A144

TOILET

A133

SHOWER

A134

SENSORY ROOM

A135

TIME OUT

A136

ARTS & CRAFTS

A137

PLAY AREA

A138

Room

A139

LIVING ROOM

A140

CORRIDOR

A104

VESTIBULE

A101

ED1

ED1

ED2

ED2

ED2

SWBD

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED3

EXISTING

GENERATOR TO

BE REMOVED

FACP

(TYP)

ED4

(TYP)

ED4

(TYP)

ED4

(TYP)

ED4

EXISTING TO REMAIN

KEYPLAN LEGEND

DEVICE TO BE DEMOLISHED

NEW DEVICE

REVISION HISTORY OF THIS DRAWING

DECA LOG #

ENGR. FILE NO.

DRAWING NO.

DRAWN BY

AS BUILT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

# 540CBXLSD6300

ACCT# 540CBXLSD6300

10411 Meeting Street Prospect, KY 40059

T: 502 326.3085 F: 502 326.2691

08.20.24

VKYS23

/2

/2

:5

:4

P

M

C

U s e rs \g w e s s lin g \D o c u m e n ts

\V K

Y S

B ra d y H a ll_ g w e s s lin g C

L F

H C

.r v t

P ro je c t

N u m b e r_

O w n e r_ R

T A

E -1

B R

A D

Y H

A L

L

F

IR

S T

F L O

O R

E L E

C T

R

IC

A L D

E M

O L

IT

IO

N

A

R E

A A

E-100

BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION -

AREA A

S 2nd St, Danville, KY 40422

BKB

GTW

RTA

KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND GRAY SOLID

LINES INDICATE EXISTING ITEMS TO REMAIN.

B. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,

PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK

PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW

LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.

C. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING

CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO

REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS

INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT

OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON

THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.

"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF

POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE

NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

D. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS

DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE

DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING

CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT

ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK

INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS

SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR

THE BID WHICH HE PROPOSES.

E. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS

FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),

WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND

REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES

ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW

FINISHES - SEE ARCHITECTURAL PLANS).

F. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED

FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO

OWNER AT THEIR OPTION.

G. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR

RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED

WITH THEIR EQUIPMENT.

H. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION

BARRIERS AS REQUIRED.

I. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /

CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR

INSTALLED.

J. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE

CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC

REQUIREMENTS.

K. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION

SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND

EQUIPMENT SHOWN ON PLANS.

L. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF

BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND

AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE

RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN

INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS

REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL

AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER

REQUIREMENTS.

M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL

BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND

INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES

OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE

DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL

ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.

UNUSED BREAKERS SHALL BE IN OFF POSITION.

GENERAL NOTES (DEMOLITION):

SCALE: 1/8" = 1'-0"

FIRST FLOOR ELECTRICAL DEMO PLAN - AREA A

KEYNOTES

ED1 REMOVE EXISTING ELECTRICAL CONNECTIONS TO MECHANICAL

EQUIPMENT BEING REMOVED. ALL WIRING SHALL BE REMOVED

BACK TO ELECTRICAL PANEL COMPLETELY. COORDINATE

REMOVAL AND EXACT EQUIPMENT LOCATIONS WITH MECHANICAL

WORK (TYPICAL).

ED2 EXISTING LED LIGHT FIXTURES TO REMAIN (TYPICAL).

ED3 EXISTING 750kVA , 120/208V, THREE PHASE, OIL FILLED UTILITY

TRANSFORMER TO REMAIN.

ED4 DEMOLISH ALL EXIT SIGNS IN CORRIDORS.

F

HD

F

SD

SD

HD

SD

SD

SD

SD

SD

SD

SD

SD

F

A

F

I W

F

I W F

F

WI

F

WI

I W

F

I W

F

F W I

F W I

FWI

I W

F

F

I W

I W

F

I W

F

SD

HDI W

F

I W F

I W

F

I W

F

LF6

LF6 LF6

LF6

LF25

LF25

LF25

LF25

LF25

LF25

LF25

LF25 LF25 LF25 LF25 LF25 LF25

LF6 LF6 LF6 LF6

LF6LF6LF6LF6

LF6 LF6 LF6 LF6

LF3

LF7

LF9 LF9

LF9 LF9

LF9 LF9

LF31 LF31

LF31

LF31

LF31 LF31

LF37 LF31

LF9

LF18

LF20

LF9

LF31

LF7

LF7

LF7

LF31

LF9

LF20

LF20

LF18

LF18

LF9

LF31

LF31

LF31

LF31

LF31

LF31

LF31

LF31

LF37

CORRIDOR

A104

CORRIDOR

B100

MULTI -

PURPOSE

B101

STORAGE

B102

STORAGE

B103

TOILET

B104

TOILET

B105

PHYSCIAL

THERAPY

B106

LIVING RM.

B108

KITCHEN

B109

BEDROOM

B110

BATH

B113

BEDROOM

B114

BATH

B117

MECH.

B143

STORAGE

B120

LAUNDRY

B121

BEDROOM

B141

BATH

B138

BATH

B137

BEDROOM

B135

LIVING ROOM

B130

STAIR

B

ELEC. RM.

B122

JAN.

B123

BEDROOM

B126

BATH

B127

HALL

B119

ED2

ED1

ED1

ED2

ED2

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

(TYP)

ED4

(TYP)

ED4

(TYP)

ED4

EXISTING TO REMAIN

KEYPLAN LEGEND

DEVICE TO BE DEMOLISHED

NEW DEVICE

REVISION HISTORY OF THIS DRAWING

DECA LOG #

ENGR. FILE NO.

DRAWING NO.

DRAWN BY

AS BUILT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

# 540CBXLSD6300

ACCT# 540CBXLSD6300

10411 Meeting Street Prospect, KY 40059

T: 502 326.3085 F: 502 326.2691

08.20.24

VKYS23

/2

/2

:5

:5

P

M

C

U s e rs \g w e s s lin g \D o c u m e n ts

\V K

Y S

B ra d y H a ll_ g w e s s lin g C

L F

H C

.r v t

P ro je c t

N u m b e r_

O w n e r_ R

T A

E -1

B R

A D

Y H

A L L

F

IR

S

T F

L O

O R

E L E

C T

R

IC

A L

D E

M O

L

IT

IO

N

A

R E

A B

E-101

BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION -

AREA B

S 2nd St, Danville, KY 40422

BKB

GTW

RTA

KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND GRAY SOLID

LINES INDICATE EXISTING ITEMS TO REMAIN.

B. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,

PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK

PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW

LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.

C. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING

CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO

REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS

INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT

OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON

THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.

"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF

POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE

NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

D. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS

DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE

DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING

CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT

ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK

INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS

SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR

THE BID WHICH HE PROPOSES.

E. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS

FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),

WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND

REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES

ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW

FINISHES - SEE ARCHITECTURAL PLANS).

F. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED

FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO

OWNER AT THEIR OPTION.

G. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR

RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED

WITH THEIR EQUIPMENT.

H. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION

BARRIERS AS REQUIRED.

I. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /

CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR

INSTALLED.

J. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE

CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC

REQUIREMENTS.

K. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION

SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND

EQUIPMENT SHOWN ON PLANS.

L. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF

BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND

AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE

RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN

INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS

REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL

AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER

REQUIREMENTS.

M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL

BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND

INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES

OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE

DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL

ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.

UNUSED BREAKERS SHALL BE IN OFF POSITION.

GENERAL NOTES (DEMOLITION):

SCALE: 1/8" = 1'-0"

FIRST FLOOR ELECTRICAL DEMO PLAN - AREA B

KEYNOTES

ED1 REMOVE EXISTING ELECTRICAL CONNECTIONS TO

MECHANICAL EQUIPMENT BEING REMOVED. ALL WIRING SHALL

BE REMOVED BACK TO ELECTRICAL PANEL COMPLETELY.

COORDINATE REMOVAL AND EXACT EQUIPMENT LOCATIONS

WITH MECHANICAL WORK (TYPICAL).

ED2 EXISTING LED LIGHT FIXTURES TO REMAIN (TYPICAL).

ED4 DEMOLISH ALL EXIT SIGNS IN CORRIDORS.

DN

F

SD

F

HD

SD

SD

SD

SD

HD

SD

SD

SD

SD

SD

SD

SD

HD

F

HD

HD

F S

SD

SD

SD

HD

SD

SD

SD

F

SD

F

I W

F

F

WI

F W

I

I W F

I W

F

HD

I W F

I W F

F W

I

F W

I

F

WI

F

I W

F W

I

F

FWI

F

FWI

FWI

FWI

I W

I W

F

I W

F

F

HDSD

I W

F

W I

F

W F

I

W F

I

F

F W

I F W

I

SD I W

F

F W

I

F

WI

F

WI

F

WI

I W F

I W

F

I W

F

HD

I W F

I W

F

HD

F W

I

F

I W

ED1

CORRIDOR

A200

Room

A212

LOBBY

A201

CLASSROOM

A203

TOILET

A204

CLASSROOM

A205

TOILET

A206

JAN.

A207

COMM.

SKILLS

A208

DIAGNOSTIC

A209

MEDIA

A210

TOILET

A211

Room

A213

CLASSROOM

A214

TOILET

A216

Room

A217

Room

A218

Room

A219

Room

A220

Room

A221

Room

A222

Room

A223

CORRIDOR

A224

DRY STOR.

A225

HALL

A226

DISH WASH

A229

FREEZER

A230

FREEZER

A231

OFFICE

A232 JAN.

A233

Room

A234

LINEN

A238

DINING ROOM

A240

ELEC.

A274

JAN.

NURSES

LOUNGE

TLT.

WARD #1

A249

SHOWER

A252

TLT.

A254

HEAD NURSE

A247

STORAGE

A248

STORAGE

A246

Room

A275

TLT.

A259 DENTIST

A260

EXAM

A261CORRIDOR

A241

LOUNGE

A264

OFFICE

A265

TREATMENT

A262

TOILET

A271

WARD #2

A270

RAMP

CLASSROOM

A215

TLT.

A253

ELEV.

OFFICE

A255

WAITING RM.

A263

SHOWER

A272

TLT.

A266

DIRECTORS

OFFICE

A273

RECEPTION

B203

OFFICE

A258

WALK IN

REFG.

A235

COOKING

AREA

A239

CORRIDOR

A202

M-306

ED1ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1 ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

ED1

(TYP)

ED4

(TYP)

ED4

(TYP)

ED4

(TYP)

ED4

(TYP)

ED4

(TYP)

ED4

EXISTING TO REMAIN

KEYPLAN LEGEND

DEVICE TO BE DEMOLISHED

NEW DEVICE

REVISION HISTORY OF THIS DRAWING

DECA LOG #

ENGR. FILE NO.

DRAWING NO.

DRAWN BY

AS BUILT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

# 540CBXLSD6300

ACCT# 540CBXLSD6300

10411 Meeting Street Prospect, KY 40059

T: 502 326.3085 F: 502 326.2691

08.20.24

VKYS23

/2

/2

:5

:5

P

M

C

U s e rs \g w e s s lin g \D o c u m e n ts

\V K

Y S

B ra d y H a ll_ g w e s s lin g C

L F

H C

.r v t

P ro je c t

N u m b e r_

O w n e r_ R

T A

E -1

B R

A D

Y H

A L L

S

E C

O N

D F

L O

O R

E L E

C T

R

IC

A L D

E M

O L

IT

IO

N

A

R E

A A

E-102

BRADY HALL - SECOND FLOOR ELECTRICAL DEMOLITION

- AREA A

S 2nd St, Danville, KY 40422

BKB

GTW

RTA

KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND GRAY SOLID

LINES INDICATE EXISTING ITEMS TO REMAIN.

B. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,

PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK

PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW

LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.

C. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING

CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO

REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS

INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT

OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON

THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.

"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF

POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE

NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

D. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS

DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE

DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING

CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT

ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK

INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS

SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR

THE BID WHICH HE PROPOSES.

E. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS

FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),

WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND

REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES

ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW

FINISHES - SEE ARCHITECTURAL PLANS).

F. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED

FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO

OWNER AT THEIR OPTION.

G. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR

RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED

WITH THEIR EQUIPMENT.

H. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION

BARRIERS AS REQUIRED.

I. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /

CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR

INSTALLED.

J. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE

CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC

REQUIREMENTS.

K. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION

SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND

EQUIPMENT SHOWN ON PLANS.

L. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF

BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND

AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE

RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN

INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS

REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL

AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER

REQUIREMENTS.

M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL

BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND

INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES

OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE

DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL

ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.

UNUSED BREAKERS SHALL BE IN OFF POSITION.

GENERAL NOTES (DEMOLITION):

SCALE: 1/8" = 1'-0"

SECOND FLOOR ELECTRICAL DEMO PLAN - AREA A

KEYNOTES

ED1 REMOVE EXISTING ELECTRICAL CONNECTIONS TO

MECHANICAL EQUIPMENT BEING REMOVED. ALL WIRING SHALL

BE REMOVED BACK TO ELECTRICAL PANEL COMPLETELY.

COORDINATE REMOVAL AND EXACT EQUIPMENT LOCATIONS

WITH MECHANICAL WORK (TYPICAL).

ED4 DEMOLISH ALL EXIT SIGNS IN CORRIDORS.

HD

SD SD

SD

SDSD

SD

SD

SD

SD

S D

SD

SD

F

F

SD

SD

SD

I W

F

F F W

I

F

F

I W

F

WI F

I W

FWI

F W

I

F W

I

F W

I

SD

FWI

FWI

FWI

I W F

I W F

F

F

F

I W F

F W

I

WI

I W

F

FWI

F

WI

FWI

W I

F

W I

F

FWIFWI

I W

F I

W F

LOBBY

B201

WAITING

LOUNGE

B204

OFFICE

B205

RECEPTION

B207

CLERICAL

B211

CONFERENCE

B208

CLERICAL

B212

DIRECTOR

B213

COUNSELOR

B215

SOCIAL WK.

B216

AUDIOLOGIST

B217

TESTING

B219

OBS.

B221

AUDIO

TESTING #1

AUDIO

TESTING #2

ENGINEER

B223

SOCIAL WK.

B227

PARENT

EDUC.

B228

PARENT

EDUC.

B229

FISCAL

OFFICE

B230

STOR.

B231

WAITING

B232

OPTHAMOLOGY

B233

OTOLOGY

B234

STOR.

B235

CORRIDOR

B210

STAFF

LOUNGE

B240

Room

B241 VEST.

B242

VEST.

B243

JAN.

B244

MENS

B245

BEDROOM

B248

BEDROOM

B251