Addendum Two .pdf
PDF 8 MB Posted
- Attached to
- RFB-131-25 EDU KSD Brady HVAC Project
- Solicitation number
- RFB-785-2500000272-3
- Issued by
- Boyd County, Kentucky
About this file
This is Addendum Two for Brady Hall HVAC Project at Kentucky School for the Deaf in Danville, Kentucky issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration (Invitation to Bid No. RFB-131-25). This addendum primarily provides notification that additional specifications, deletions, and changes will be distributed via Lynn Imaging. The project schedule indicates award by end of 2024, shops for early procurement throughout 2025, student move-out and construction start on May 24, 2026, substantial completion by December 4, 2026, final completion by December 31, 2026, and student move-in on January 4, 2027.
The addendum makes several modifications, including: changes to closed cell spray foam polyurethane requirements in Section 07 20 00; addition of Hardware Set A274 for Opening A274; and updates to mechanical, electrical, plumbing and systems via CMTA narrative and drawings. Additionally, new photocell sensors were added to the dining room area and exit signs were added throughout corridors. Updates were also made to fire alarm, intrusion, and weather notification devices according to the electrical drawings revisions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2500000272_3_SO_FORM.PDF | ||
| Final_RFB_785_2500000272_1_SO_FORM.PDF | ||
| Addendum One .pdf | ||
| Final_RFB_785_2500000272_2_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-131-25
FOR: Brady Hall HVAC Project Kentucky School for the Deaf Department of Education Danville, Kentucky
DATE: November 26, 2024
RFB-785-2500000272
ADDENDUM NO. Two (2)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-131-25 For: Brady Hall HVAC Project Kentucky School for the Deaf Department of Education Danville, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration s t u d i o k r e m e r a r c h i t e c t s
1231 S Shelby St, Louisville, KY 40203
TEL 502.499.1100 FAX 502.499.1101
A D D E N D U M N O . 2
TO: All Plan Holders
FROM: Studio Kremer Architects
PROJECT: Kentucky School for the Deaf
BRADY HALL
ska# 2023-33.5
This Addendum No. 2 supersedes and supplements all portions of the Construction Documents with which it conflicts.
Acknowledgement of this Addendum shall be noted on the Form of Proposal.
Addendum No. 2 makes the following modifications and clarifications to the Construction Drawings and Specifications:
S P E C I F I C A T I O N S .
Item No. 1: Reference Section 07 20 00 – BUILDING INSULATION
1. Reference Section 07 20 00, 2.01: Requirements for Closed Cell Spray Foam Polyurethane products are modified as follows:
A. Closed-cell spray foam polyurethane
1. Manufacturer: Subject to compliance with requirements, provide products of one of the following:
a. BASF (Walltite Low-GWP)
b. Johns Manville (JM Corbond III)
c. Dow Chemical Company
2. Two-Component, spray-applied polyurethane foam with zero-ozone depleting potential that meets the following:
a. Core Density, ASTM D1622: 2.0-2.3 pcf
b. Compressive Strength, ASTM D1621: min. 25 psf
c. Closed-cell content, ASTM D6226: >90
d. Thermal Resistance, ASTM C518: min. 6.4 / inch
e. Water Vapor Permeability, ASTM E96: min. 1.1 perm at 1”
f. Surface Burning Characteristics, ASTM E84: Class 1
g. Provide minimum thickness of 3-1/2 inches.
Spray foam insulation for filling small voids / holes (2.01, B) remains as originally released.
Item No. 2: Reference Section 08 71 00 – Door Hardware
Drawing A-110B
1. Opening A274 on Sheet A-110B did not have a Hardware Set provided. For this opening, provide Hardware Set A274, as follows:
page 2 s t u d i o k r e m e r a r c h i t e c t s
(3) Butt Hinges CH81 x 5.0 x 4.5 652 PBB
(1) Panic Device, Rim, 03 10-03C-CD 94 630 DTX
(2) Rim Cylinder SFIC 7-pin 626 PDQ
(1) Closer, w/Spring Stop / HO D-4550 HCS 689 DTX
(2) Kick Plate KO050 8 x 1LDW x CS x B4E 630 TRI
Note 1: Provide closer drop plate as required by top rail configuration.
Item No. 3:
The attached documents and drawing revisions (3-page narrative and 19 drawings) provided by CMTA describe all changes, corrections, clarifications and updates to the Mechanical, Electrical, Plumbing, and Systems scopes of work and become part of this Addendum.
Item No. 4:
1. Structural sheets were left out of the initial release and re-issued as Addendum No. 1. The attached reduces files may be more useful.
2. The following links to archival drawings of the existing building:
https://drive.google.com/drive/folders/1Adrivaoz39gb3mAN071bS4wWMEaSQ8hR?usp=sharing
Item No. 5:
1. The project schedule shall be as follows:
End of 2024 Award
All of 2025 Shops for early procurement
May 24 2026 Students Move Out
Construction Starts
December 4 2026 Substantial Completion #1 (Construction Complete)
December 31 2026 Final Completion
January 4 2027 Students Move In
END OF ADDENDUM NO.2
(referenced attachments follow)
ENCL:
1. CMTA Addendum Text
2. Electrical attachments (reference CMTA Addendum)
3. Structural sheets re-released (No changes.)
https://drive.google.com/drive/folders/1Adrivaoz39gb3mAN071bS4wWMEaSQ8hR?usp=sharing
Kentucky School for the Deaf - Brady Hall Renovation
Project Number #540CBXLSD6300
Addendum #1
November 25, 2024
CHANGES TO DRAWINGS:
Electrical
Sheet # Sheet Title Noted Update
E001 BRADY HALL – ELECTRICAL LEGEND AND
GENERAL NOTES
Added intrusion and weather notification devices to legend.
E100 BRADY HALL - FIRST FLOOR ELECTRICAL
DEMOLITION - AREA A
Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.
Added exit sign removal scope.
Added removal of FACP.
E101 BRADY HALL - FIRST FLOOR ELECTRICAL
DEMOLITION - AREA B
Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.
Added exit sign removal scope.
E102 BRADY HALL - SECOND FLOOR ELECTRICAL
DEMOLITION - AREA A
Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.
Added exit sign removal scope.
E103 BRADY HALL - SECOND FLOOR ELECTRICAL
DEMOLITION - AREA B
Added fire, intrusion, weather, and smoke detector devices to the drawings that are to be demolished.
Added exit sign removal scope.
E200 BRADY HALL - FIRST FLOOR LIGHTING PLAN
- AREA A
Edited General lighting note ‘I’.
Added exit signs.
E201 BRADY HALL - FIRST FLOOR LIGHTING PLAN
- AREA B
Edited General lighting note ‘I’.
Added exit signs.
E202 BRADY HALL - SECOND FLOOR LIGHTING
PLAN - AREA A
Edited General lighting note ‘I’.
Added photocell sensors to dining room.
Addendum No 2
Added exit signs.
E203 BRADY HALL - SECOND FLOOR LIGHTING
PLAN - AREA B
Edited General lighting note ‘I’.
Added exit signs.
E300 BRADY HALL - FIRST FLOOR
POWER/SYSTEMS PLAN - AREA A
Relocated FACP.
Utility transformer added to drawing.
Added several FA detection and notification devices.
E301 BRADY HALL - FIRST FLOOR
POWER/SYSTEMS PLAN - AREA B
Added several FA detection and notification devices.
E302 BRADY HALL - SECOND FLOOR
POWER/SYSTEMS PLAN - AREA A
Added several FA detection and notification devices.
E303 BRADY HALL - SECOND FLOOR
POWER/SYSTEMS PLAN - AREA B
Added several FA detection and notification devices.
E400 BRADY HALL - ELECTRICAL DEMOLITION
POWER RISER DIAGRAM
Demolished all feeders and pathways.
E401 BRADY HALL - ELECTRICAL POWER RISER
DIAGRAM
Added note ‘E’ to feeder schedule.
Added clarification notes to ‘MSB’ schedule.
E500 BRADY HALL – FIRE ALARM RISER
DIAGRAM
Added detail to sheet.
Added intrusion and weather devices to riser diagram.
E602 BRADY HALL – LIGHT FIXTURE SCHEDULE
AND DETAILS
Added exit sign selections to schedule.
CHANGES TO SPECIFCATIONS:
• 230900 - Instrumentation and Control for HVAC o Revision to Section 1.2.F – JCI to be added as an approved manufacturer.
• 263213 – Diesel Engine Generator Sets o Revision to Section 2.1.A – Generac to be added as an approved manufacturer.
ATTACHMENT(S):
• Electrical Drawings as listed above
• Specifications as listed above.
END OF ADDENDUM
C
SD
I
UON
EM
CFOI
OFOI
CFCI
OFCI
C/S
J
DESCRIPTION
S
S 3
S D
SK
P
SOS
OS
IL
GROUND FAULT PROTECTED DUPLEX WITH WEATHER-
PROOF "WHILE IN USE" TYPE DIE-CAST METAL
COVERPLATE WITH LOCKABLE ENCLOSURE AT
OUTLET - SEE SPECIFICATIONS
WP
ER
ELECTRIC WATER COOLER RECEPTACLE:
COORDINATE EXACT LOCATION WITH PLUMBING
CONTRACTOR TO CONCEAL OUTLET(S) BEHIND
COOLER, PROVIDE MULTIPLE RECEPTACLES WHERE
REQUIRED BY MANUFACTURER, PROVIDE READILY
ACCESSIBLE DEAD FRONT GFCI DEVICE AT 18"
ADJACENT TO WATER COOLER FOR PROTECTION OF
WATER COOLER RECEPTACLE(S)
EWC
W
SS
POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES
SLASH THROUGH ANY DEVICE INDICATES MOUNTING
ABOVE COUNTERTOP 4" ABOVE BACKSPLASH, OR AT 46"
WHERE NO COUNTER IS PRESENT
SVS
VS
LV
ILLUMINATED HANDLE LIGHT SWITCH (ILLUMINATED
WHEN LOAD IS OFF)
EMERGENCY AUTOMATIC TRANSFER SWITCH
FOR LIGHTING CONTROLS (REFER TO DETAIL)
FILLED CENTER BAR INDICATES INTEGRAL GROUND
FAULT PROTECTION (GFCI)
GANG RECEPTACLE IN COMBINATION WITH SWITCH
(PROVIDE DIVIDER IF LIGHTING CIRCUIT IS 277V)
NON-REVERSING MOTOR STARTER SNAP SWITCH
CONTRACTOR FURNISHED OWNER INSTALLED
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
FLUSH MOUNTED REMOTE ALARM INDICATING
STATION/TEST SWITCH
CONNECTION TO SPRINKLER TAMPER
SWITCH WITH ADDRESSABLE MODULE
CONNECTION TO SPRINKLER FLOW
SWITCH WITH ADDRESSABLE MODULE
PHOTO-ELECTRIC SMOKE DETECTOR
MAIN CONTROL PANEL CENTRAL PROCESSING
UNIT (CPU)
LIGHT SWITCH:GENERAL PURPOSE
AS NOTED
AS NOTED
6'-6'' TO
TOP
46" TO
LEVER
PULL STATION : DOUBLE ACTION
AUDIO-ONLY NOTIFICATION APPLIANCE
VISUAL-ONLY NOTIFICATION APPLIANCE
AUDIO/VISUAL NOTIFICATION APPLIANCE
HEAT DETECTOR
CARBON MONOXIDE ALARM: SINGLE STATION
W/SOUNDER BASE
CARBON MONOXIDE AUDIO/VISUAL NOTIFICATION
APPLIANCE
DOOR HOLDER : WALL TYPE
DOOR HOLDER : CLOSURE TYPE
DUCT SMOKE DETECTOR
PRESSURE SWITCH
REMOTE L.C.D. FIRE ALARM ANNUNCIATOR
POST INDICATOR VALVE
ISOLATION MODULE
H.V.A.C. SMOKE DAMPER CONNECTION. REFER TO "SM"
DETAIL FOR ALL REQUIRED EQUIPMENT, DEVICES AND
INSTALLATION REQUIREMENTS INCLUDING TO PROVIDE
DUCT MOUNTED SMOKE DETECTOR AND RELAY.
UNLESS OTHERWISE NOTED
INDICATES EMERGENCY POWER
HD
CM
F
DH
ABV DOOR DH
ABV CLG DD
FS
TS
PS
46"
I
SM
ABBREVIATIONS
DESCRIPTION
STRIP FIXTURE
CROSS-HATCHING INDICATES LIGHT IS POWERED
FROM EMERGENCY POWER
PARALLEL-HATCHING INDICATES LIGHT IS POWERED
FROM THE EMERGENCY-LIFE SAFETY BRANCH POWER
POWER OUTLETS
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE - SAFETY TYPE, TAMPER
RESISTANT.
JUNCTION BOX, CEILING OR WALL
VOLTAGE/1PH RECEPTACLE, AS NOTED
VOLTAGE/3PH RECEPTACLE, AS NOTED
SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)
DIMMER SWITCH
THREE-WAY SWITCH
KEYED SWITCH
OCCUPANCY OR VACANCY SENSOR SWITCH
OCCUPANCY OR VACANCY SENSOR, CEILING MOUNTED
LOW VOLTAGE MOMENTARY SWITCH
PHOTO-CELL AS NOTED
EXIT LIGHT (CEILING, END, WALL MOUNT)
LIGHTING
REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE
SPECIFICATIONS, MOUNTING HEIGHTS, ETC.
WALL, CLG
CLG
CLG
CLG
WALL
54"
46"
46"
46"
46"
46"
46"
46"
1'-6"
1'-6"
1'-6"
46"
1'-6"
1'-6"
2'-2"
CLG
AS NOTED
S
S
S M
D R
A W
IN
G
S Y
M B
O L
SURFACE OR SUSPENDED CEILING FIXTURE (SLASH
INDICATES RECESSED)
POLE MOUNTED AREA LIGHT
EMERGENCY BATTERY WALL-PACK
WALL MOUNT FIXTURE ,
FLOODLIGHT
S
A
F
F
RI
INDICATES VANDAL-PROOF POLYCARBONATE COVER,
VANDAL PROOF COVERS SHALL BE UL LISTED FOR USE
WITH THE SPECIFIC DEVICE THEY ARE PROTECTING
PC
WALL
WALL
7'-6''
FIREMAN'S PHONE JACK FP
ADDRESSABLE RELAY MODULE R
DESCRIPTION
K
DB
DB
WP
DOORBELL PUSHBUTTON STATION, PROVIDE COMPLETE
WITH TRANSFORMER (MOUNT ABOVE CEILING IN
CORRIDOR NEAR PUSH-BUTTON) AND ALL
ACCESSORIES, POWER FROM NEAREST AVAILABLE 120V
NORMAL POWER GENERAL RECEPTACLE CIRCUIT,
NUTONE OR EQUAL
DOORBELL AUDIO/VISUAL STATION, PROVIDE PROVIDE
CONNECTION TO PUSHBUTTON STATION IN AREA.
COORDINATE EXACT AUDIO SOUND (CHIME, BUZZER,
ETC.) DESIRED WITH OwNER/ARCHITECT, NUTONE OR
EQUAL
PLUMBING FIXTURE ELECTRIC EYE TRANSFORMER
CONNECTION. TRANSFORMER SHALL BE 120V-24V.
MOUNT ABOVE SUSPENDED ACCESSIBLE CEILING IN J-
BOX. PROVIDE ADDITIONAL TRANSFORMERS OF SAME
TYPE AS/IF NEEDED
PROVIDE CONNECTION TO HAND DRYER (SEE
ARCHITECTURAL SPECIFICATIONS)
VERIFY WITH
ARCHITECT
C
INDICATES MOUNTING ABOVE COUNTER-TOP,
2" ABOVE BACKSPLASH, NO HIGHER THAN 48''
WG
WIREGUARD - PROVIDE MANUFACTURER'S
SPECIFIC GUARD FOR DEVICE NOTED
BOX ON ANY DEVICE INDICATES SURFACE MOUNTED
BACKBOX/WIREMOLD
CONDUIT CONCEALED IN WALLS OR IN CEILING
SPACE: ARROW(S) INDICATE(S) HOME RUN & #
OF CIRCUITS: HASHMARKS INDICATE # OF
CONDUCTORS. DASHED LINE INDICATES
CONDUIT BELOW FLOOR.
WIREWAY WITH REMOVABLE COVER (SIZE AS NOTED)
PANELBOARD, SURFACE OR FLUSH MOUNTED,
HATCHING INDICATES EMERGENCY
EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE
MECHANICAL EQUIPMENT DESIGNATOR
(SEE MECH. SCHEDULES)
EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)
KITCHEN EQUIPMENT OUTLET COUPLING
CONNECTION (SEE DETAIL)
AS SHOWN
AS SHOWN
AS NOTED
AS SHOWN
MISCELLANEOUS
DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC COMBINATION STARTER
ENCLOSED FLUSH MTD. CIRCUIT BREAKER
WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.
PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR
OUTDOORS.
TRENCH DUCT (SIZE AS NOTED)
PUSHBUTTON STATION
FLEXIBLE CONDUIT
TRANSFORMER
TAGGED NOTE
REVISION TAG
J-HOOK CABLE PATH, SIZE AS NOTED
LOW VOLTAGE CABLE PATH
5'-0"
5'-0"
5'-0"
5'-0"
46"
46"
7'-6''
6'-6'' TO TOP
SURGE PROTECTION DEVICE
GENERATOR ANNUNCIATOR PANEL - SEE
SPECIFICATIONS
46"
THERMOSTAT PROVIDED BY MECHANICAL
CONTRACTOR, ELECTRICAL CONTRACTOR SHALL
PROVIDE BACK-BOX CONDUIT STUB-UP, REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS
SWITCHES
FIRE ALARM
E,EMINDICATES EMERGENCY POWER
GEN-A
SPD
J
J
NAC
PIV
FAA
FACP
T
D R
A W
M B
O L
D R
A W
M B
O L
AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED
AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED
EQUIP-1
PLUMBING FIXTURE SOLENOID VALVE/ELECTRIC EYE
SENSOR CONNECTION. COORDINATE EXACT
CONNECTION REQUIREMENTS WITH MANUFACTURER.
GROUND
NEUTRAL
PHASE
WALL, CLG
WALL, CLG S
A
F
CM
DEVICE USED FOR ELEVATOR CONTROL EL
FIRE ALARM CONTROL EXTENDER EXT
4'-6''
TRANSPONDER CABINET 46" TRAN
DEAD FRONT GFCI DEVICE, LABEL AND INSTALL IN
READILY ACCESSIBLE LOCATION
FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL
USB OUTLETS IN ADDITION TO POWER RECEPTACLES
1'-6"
, J
VARIABLE FREQUENCY DRIVE 5'-0"
CIRCLE ON ANY DEVICE INDICATES DEVICE FED FROM
STUB UP CONDUIT
MOTOR CONNECTION, REFER TO EQUIPMENT
CONNECTION SCHEDULE
DUPLEX RECEPTACLE, CEILING MOUNTED CLG
CONDUIT UP
CONDUIT DOWN
GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''
AS SHOWNBUS DUCT, AMPERAGES AS NOTED
M O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
M O
U N
T
IN
G H
E
IG
C E
N T
E R
O F
B O
X
M O
U N
T
IN
G H
E
IG
C E
N T
E R
O F
B O
X
EMERGENCY SHUTDOWN PUSH BUTTON
ACAREA OF RESCUE ASSISTANCE COMMAND CENTER
ARAREA OF RESCUE ASSISTANCE REMOTE STATION
ET,
OCCUPANCY OR VACANCY SENSOR, WALL MOUNTED OS
DESCRIPTION
P A
T H
W A
Y S
O
F O
I
P A
T H
W A
Y S
O
F C
I
P A
T H
W A
Y S
C
F C
I
IT
E
M U
S E
D O
N P
R O
J E
C T
D E
V
IC
E S
O
F C
I
D E
V
IC
E S
C
F C
I
SYSTEM D
E
V
IC
E S
O
F O
I
SYSTEM
RESPONSIBILITY
MATRIX
FIRE ALARM
DATA PROCESSING
SYSTEM RESPONSIBILITY GENERAL NOTES:
A. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TO VENDOR-
FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGS SHALL BE INCLUDED
BY THE CONTRACTOR.
B. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESS CONTROL
DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.
C. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS. CONTRACTOR
SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT INSTALLATION
LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL SYSTEMS PRIOR TO
CONSTRUCTION.
D. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS, CONTRACTOR SHALL
PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO CABLE PATHS AS REQUIRED BY
SYSTEM VENDORS, TERMINATE CONDUITS AT CABINETS/ON BACKBOARDS AS REQUIRED.
COORDINATE EXACT REQUIREMENTS WITH APPROPRIATE VENDORS PRIOR TO
CONSTRUCTION.
E. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS INCLUDING
CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING, LABELING, ETC.
F. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM COMPLETE,
INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE CONTRACTOR SHALL
CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID. ALL SYSTEMS SHALL MATCH
EXISTING FACILITY STANDARDS AND BE FULLY COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL
SYSTEM VENDORS SHALL COORDINATE EXACT SYSTEM REQUIREMENTS WITH OWNER PRIOR
TO BID. NEW COMPONENTS SHALL BE INTERCONNECTED WITH EXISTING SYSTEMS WHERE
POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BE COORDINATED WITH THE
OWNER PRIOR TO ORDERING. ALL PROGRAMMING SHALL BE INCLUDED AS REQUIRED BY THE
OWNER. PROVIDE 4 HOURS OF TRAINING FOR EACH SYSTEM.
G. MININUM DATA, VOICE AND AUDIO / VISUAL RACEWAY IS 1-1/4" CONDUIT.
SYSTEM
SYMBOLT
E
R M
IN
A
T
IO
N S
O
F O
I
T E
R M
IN
A
T
IO
N S
O
F C
I
T E
R M
IN
A
T
IO
N S
C
F C
I
C A
B L
IN
G
/C O
N D
U C
T O
R S
C
F C
I
C A
B L
IN
G
/C O
N D
U C
T O
R S
O
F O
I
C A
B L
IN
G /C
O N
D U
C T
O R
S
O F
C I
SDSOUNDER BASE SMOKE DETECTOR W/ STROBE SB
WALL
WALL
VISUAL ALARM STROBE ONLY
(BLUE LENS COLOR INTRUDER SYSTEM)
VISUAL ALARM STROBE ONLY
(AMBER LENS COLOR WEATHER SYSTEM)
A. THIS PROJECT INTERFACES EXTENSIVELY WITH EXISTING BUILDING SERVICES. IT SHALL BE
THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND PHASE ALL TIE-INS AND
INTERRUPTIONS OF EXISTING SERVICES TO MINIMIZE OR ELIMINATE DOWNTIME. AS AN
EXAMPLE, MAIN GAS SERVICE, WATER SERVICE, ELECTRICAL SERVICE, HVAC SERVICES,
ETC., WILL BE AFFECTED AND REPLACED OR MOVED DURING THIS PROJECT. THE
CONTRACTOR SHALL INSTALL ALL NEW SERVICES AND EQUIPMENT AND HAVE THEM TESTED
AND FULLY AND RELIABLY FUNCTIONAL PRIOR TO INTERRUPTING, RELOCATING OR
REMOVING ANY EXISTING SERVICES. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
BARE ANY AND ALL COSTS ASSOCIATED WITH THIS PHASING, INCLUDING TEMPORARY
SERVICES, TEMPORARY RELOCATION, PREMIUM TIME WORK, ETC. CONTRACTOR SHALL
COORDINATE ALL SAID WORK WITH THE OWNER AND APPLICABLE UTILITIES PER THE
CONTRACT DOCUMENTS.
ELECTRICAL PHASING NOTES
A. WALL AND FLOOR PATCHING/PAINTING: PATCH/INFILL ALL WALL/FLOOR PENETRATIONS
WHERE EXISTING ELECTRICAL EQUIPMENT/DEVICES/CONDUIT/RACEWAYS ARE REMOVED.
COORDINATE ALL PATCH/INFILL WORK WITH THE GENERAL CONTRACTOR.
B. EXISTING CONDUIT / RACEWAY DEMOLITION: ALL EXISTING CONDUIT / RACEWAY ARE TO BE
REMOVED COMPLETLEY TO BEYOND FINISHED SURFACES. PATCH AND PAINT ALL SURFACES
AS REQUIRED TO MATCH ADJACENT CONDITIONS WHERE CONDUIT / RACEWAY HAVE BEEN
REMOVED.
C. PATCH HOLES IN WALLS, FLOORS, CEILINGS, ROOFS, ETC. TO MATCH ADJACENT SURFACES
AS A RESULT OF REMOVAL OF ELECTRICAL SYSTEMS. PATCHING SHALL BE PERFORMED BY
QUALIFIED TRADESMAN
ELECTRICAL DEMOLITION GENERAL NOTES
A. THE CONTRACTOR IT IS HEREBY ADVISED THAT IS POSSIBLE THAT ASBESTOS AND/OR
OTHER HAZARDOUS MATERIALS ARE OR WERE PRESENT IN THIS BUILDING(S). ANY WORKER,
OCCUPANT, VISITOR, ETC., WHO ENCOUNTERS ANY MATERIAL OF WHOSE CONTENT THEY
ARE NOT CERTAIN SHALL PROMPTLY REPORT THE EXISTENCE AND LOCATION OF THAT
MATERIAL TO THE OWNER. FURTHERMORE, THE CONTRACTOR SHALL INSURE THAT NO ONE
COMES NEAR TO OR IN CONTACT WITH ANY SUCH MATERIAL OR FUMES THEREFROM UNTIL
ITS CONTENT CAN BE ASCERTAINED TO BE NON-HAZARDOUS.
B. CMTA, INC. HAS NO EXPERTISE IN THE DETERMINATION OF THE PRESENCE OF ANY
HAZARDOUS MATERIAL. THEREFORE, NO ATTEMPT HAS BEEN MADE BY CMTA TO IDENTIFY
THE EXISTENCE OR LOCATION OF ANY SUCH HAZARDOUS MATERIAL. FURTHERMORE, CMTA
NOR ANY AFFILIATE HEREOF WILL NOT OFFER OR MAKE ANY RECOMMENDATIONS RELATIVE
TO THE REMOVAL, HANDLING OR DISPOSAL OF SUCH MATERIAL.
C. IF THE WORK WHICH IS TO BE PERFORMED INTERFACES, CONNECTS OR RELATES IN ANY
PHYSICAL WAY WITH OR TO EXISTING COMPONENTS WHICH CONTAIN OR BEAR ANY
HAZARDOUS MATERIAL, ASBESTOS BEING ONE, THEN IT SHALL BE THE CONTRACTOR'S SOLE
RESPONSIBILITY TO CONTACT THE OWNER AND SO ADVISE HIM IMMEDIATELY.
D. THE CONTRACTOR BY EXECUTION OF THE CONTRACT FOR ANY WORK AND/OR BY THE
ACCOMPLISHMENT OF ANY WORK THEREBY AGREE TO BRING NO CLAIM RELATIVE TO
HAZARDOUS MATERIALS FOR NEGLIGENCE, BREACH OF CONTRACT, INDEMNITY, OR ANY
OTHER SUCH ITEM AGAINST CMTA, ITS PRINCIPALS, EMPLOYEES, AGENTS OR
CONSULTANTS. ALSO, THE CONTRACTOR FURTHER AGREES TO DEFEND, INDEMNIFY AND
HOLD CMTA, ITS PRINCIPALS, EMPLOYEES, AGENTS AND CONSULTANTS HARMLESS FROM
ANY SUCH RELATED CLAIMS WHICH MAY BE BROUGHT BY ANY SUBCONTRACTORS,
SUPPLIERS OR ANY OTHER THIRD PARTIES.
E. THE CONTRACTOR IS DIRECTED TO THE SPECIFICATIONS FOR FURTHER INFORMATION.
ELECTRICAL HAZARDOUS MATERIALS NOTES
ALL LOW VOLTAGE, DATA / VOICE, FIRE ALARM, WIRELESS ACCESS POINTS, PROJECTOR / AV
EQUIPMENT, CCTV, AND SECURITY SHALL BE PRE AND POST TESTED. RESULTS SHALL BE
TABULATED AND SENT TO KSD AND THE ENGINEER FOR REVIEW AND COMMENT. THIS SHALL BE
DONE PRIOR TO SUMMER WORK.
CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING THE EXISTING TO REMAIN SYSTEMS AND
SYSTEMS THAT ARE PARTIALLY DEMOLISHED. DOWNSTREAM DEVICES SHALL NOT BE AFFECTED
DURING DEMOLITION AND ANY ISSUES WILL BE REQUIRED TO BE IMMEDIATELY CORRECTED TO
ALLOW PROCEEDING WITH CONSTRUCTION.
PRE AND POST TEST SCOPE
NOTE: ALL NEW LOW-VOLTAGE SYSTEMS CABLING SHALL BE PLENUM RATED.
REVISION HISTORY OF THIS DRAWING
DECA LOG #
ENGR. FILE NO.
DRAWING NO.
DRAWN BY
AS BUILT DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
CHECKED BY
PHASE
RTA DATE
DRAWING DATE
A & E FILE NO.
DRAWING INFORMATION
# 540CBXLSD6300
ACCT# 540CBXLSD6300
10411 Meeting Street Prospect, KY 40059
T: 502 326.3085 F: 502 326.2691
08.20.24
VKYS23
/2
/2
:4
:3
P
M
C
U s e rs \g w e s s lin g \D o c u m e n ts
\V K
Y S
B ra d y H a ll_ g w e s s lin g C
L F
H C
.r v t
P ro je c t
N u m b e r_
O w n e r_ R
T A
E -0
B R
A D
Y H
A L
L
E L
E C
T R
IC
A
L L
E G
E N
D A
N D
G E
N E
R A
L N
O T
E S
E-001
BRADY HALL - ELECTRICAL LEGEND AND GENERAL
NOTES
S 2nd St, Danville, KY 40422
BKB
GTW
RTA
KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL
GENERAL NOTES (LEGEND):
A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH
SHOP DRAWINGS.
B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE UNDERSTANDING OF THE
PROJECT REQUIREMENTS.
C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES. INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC. IN ADDITION, OBSERVE ALL APPLICABLE RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT FROM CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.
D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL
AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOW
CLARIFICATION BY WRITTEN ADDENDUM.
F. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT
SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.
G. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND MUST BE
SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.
H. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS
MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE ENGINEER IN WRITING.
I. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT SHALL APPLY.
J. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO.
MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS
OF THESE DOCUMENTS, AS APPLICABLE.
K. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONED DRAWINGS, OR
DIMENSIONS SUPPLIED TO THE CONTRACTOR.
L. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND FURNITURE, CASEWORK, AND/OR EQUIPMENT. ADDITIONAL OUTLETS MAY BE SHOWN ON ARCHITECTURAL DRAWINGS AND
SHALL BE INCLUDED IN THE CONTRACT.
M. FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONS PROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER PRIOR TO ROUGHING-IN ANY
WORK.
N. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS.
IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER PRIOR TO INSTALLATION FOR
CLARIFICATION.
O. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR
SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.
P. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.
Q. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE
QUALITY OF WORK RESIDES WITH THE ENGINEER
R. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY PERIODS FOR EQUIPMENT ARE
SPECIFIED.
S. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.
T. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS
OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.
U. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL
SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND ARCHITECT.
V. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2' DIMENSION
OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.
W. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE
ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY OF THE PURCHASER.
X. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE- MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TO MAINTAIN
CEILING RATINGS.
Y. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE RATING. NO
INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.
Z. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED
AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE CONTRACTOR(S).
AA. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL
ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.
BB. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THE
COLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.
CC. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.
DD. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES (I.E. VAV
BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.
EE. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN PERMISSION FROM THE ENGINEER AND
CONSENT OF THE OTHER TRADE, IN WRITING.
FF. WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME WALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND TRANSMISSION FROM ROOM TO ROOM.
GG. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH SPECIFICATIONS, WHICHEVER IS MORE
STRINGENT.
HH. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A
PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE ENGINEER.
II. CHECK ALL THREE PHASE MOTORS WITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.
JJ. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO CONSTRUCTION.
KK. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO CONSTRUCTION.
LL. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTING AND
PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.
MM. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).
NN. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL
APPLY.
OO. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGER NOTIFICATION PERIOD, SO
PROVIDE.
PP. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS NEEDED.
QQ. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FOR SEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO MAINTAIN SEQUENCE OF THE WORK FROM PHASE TO PHASE.
PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL TEMPORARY SERVICES AS REQUIRED BY
OWNER TO ACCOMPLISH THE PHASING PLAN.
NO SCALE
ELECTRICAL LEGEND
SHEET LIST - ELECTRICAL
Sheet Number Sheet Name
E-001 BRADY HALL - ELECTRICAL LEGEND AND GENERAL NOTES
E-100 BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION - AREA A
E-101 BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION - AREA B
E-102 BRADY HALL - SECOND FLOOR ELECTRICAL DEMOLITION - AREA A
E-103 BRADY HALL - SECOND FLOOR ELECTRICAL DEMOLITION - AREA B
E-200 BRADY HALL - FIRST FLOOR LIGHTING PLAN - AREA A
E-201 BRADY HALL - FIRST FLOOR LIGHTING PLAN - AREA B
E-202 BRADY HALL - SECOND FLOOR LIGHTING PLAN - AREA A
E-203 BRADY HALL - SECOND FLOOR LIGHTING PLAN - AREA B
E-300 BRADY HALL - FIRST FLOOR POWER/SYSTEMS PLAN - AREA A
E-301 BRADY HALL - FIRST FLOOR POWER/SYSTEMS PLAN - AREA B
E-302 BRADY HALL - SECOND FLOOR POWER/SYSTEMS PLAN - AREA A
E-303 BRADY HALL - SECOND FLOOR POWER/SYSTEMS PLAN - AREA B
E-304 BRADY HALL - POWER/SYSTEMS ROOF PLAN
E-400 BRADY HALL - ELECTRICAL DEMOLITION POWER RISER DIAGRAM
E-401 BRADY HALL - ELECTRICAL POWER RISER DIAGRAM
E-402 BRADY HALL - ELECTRICAL PANELBOARD SCHEDULE
E-403 BRADY HALL - ELECTRICAL PANELBOARD SCHEDULE
E-500 BRADY HALL - FIRE ALARM RISER DIAGRAM
E-600 BRADY HALL - ELECTRICAL DETAILS
E-601 BRADY HALL - ELECTRICAL DETAILS
E-602 BRADY HALL - LIGHT FIXTURE SCHEDULE AND DETAILS
ADDENDUM 01 11/25/24
UP
SD
F
SD
HD
F
HD
HD
SD
SD
SD
SD
SD
HD
HD
HD
F
I W
W I
F
I W
F
F
WI
I W
F
F
WI
F
WI
I W F
F
WI
I W F
F W
I
I W F
F
WI
F F W
I
F W
I
I W
F
F I
W
SD
F W
I
F W
I
I W F
F W
II W
F
BEDROOM
A110
BEDROOM
A111
TOILET
A112
SHOWER
A113
Room
A114
LIVING ROOM
A115
ARTS & CRAFT
A116
PLAY AREA
A117
BEDROOM
A118
BEDROOM
A119
HALL
A120
TOILET
A121
SHOWER
A122
LAUNDRY
A123
TOILET
A145
STAIR
A
Room
A105 Room
A106
LIVING ROOM
A107
PLAY AREA
A108
ARTS AND CRAFTS
A109
CORRIDOR
A100
CONTROL
A103
LOBBY
A102
RAMP
ELEV.
ELEV. MECH.
A124
MECHANICAL
A125
GENERATOR
A146
STORAGE
A126
Room
A127
LIVING Room
A128
PLAY AREA
A129
ARTS AND CRAFTS
A130
BEDROOM
A131
BEDROOM
A132
BEDROOM
A141
BEDROOM
A142
TOILET
A143
SHOWER
A144
TOILET
A133
SHOWER
A134
SENSORY ROOM
A135
TIME OUT
A136
ARTS & CRAFTS
A137
PLAY AREA
A138
Room
A139
LIVING ROOM
A140
CORRIDOR
A104
VESTIBULE
A101
BEDROOM
A110
BEDROOM
A111
TOILET
A112
SHOWER
A113
Room
A114
LIVING ROOM
A115
ARTS & CRAFT
A116
PLAY AREA
A117
BEDROOM
A118
BEDROOM
A119
HALL
A120
TOILET
A121
SHOWER
A122
LAUNDRY
A123
TOILET
A145
STAIR
A
Room
A105 Room
A106
LIVING ROOM
A107
PLAY AREA
A108
ARTS AND CRAFTS
A109
CORRIDOR
A100
CONTROL
A103
LOBBY
A102
RAMP
ELEV.
ELEV. MECH.
A124
MECHANICAL
A125
GENERATOR
A146
STORAGE
A126
Room
A127
LIVING Room
A128
PLAY AREA
A129
ARTS AND CRAFTS
A130
BEDROOM
A131
BEDROOM
A132
BEDROOM
A141
BEDROOM
A142
TOILET
A143
SHOWER
A144
TOILET
A133
SHOWER
A134
SENSORY ROOM
A135
TIME OUT
A136
ARTS & CRAFTS
A137
PLAY AREA
A138
Room
A139
LIVING ROOM
A140
CORRIDOR
A104
VESTIBULE
A101
ED1
ED1
ED2
ED2
ED2
SWBD
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED3
EXISTING
GENERATOR TO
BE REMOVED
FACP
(TYP)
ED4
(TYP)
ED4
(TYP)
ED4
(TYP)
ED4
EXISTING TO REMAIN
KEYPLAN LEGEND
DEVICE TO BE DEMOLISHED
NEW DEVICE
REVISION HISTORY OF THIS DRAWING
DECA LOG #
ENGR. FILE NO.
DRAWING NO.
DRAWN BY
AS BUILT DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
CHECKED BY
PHASE
RTA DATE
DRAWING DATE
A & E FILE NO.
DRAWING INFORMATION
# 540CBXLSD6300
ACCT# 540CBXLSD6300
10411 Meeting Street Prospect, KY 40059
T: 502 326.3085 F: 502 326.2691
08.20.24
VKYS23
/2
/2
:5
:4
P
M
C
U s e rs \g w e s s lin g \D o c u m e n ts
\V K
Y S
B ra d y H a ll_ g w e s s lin g C
L F
H C
.r v t
P ro je c t
N u m b e r_
O w n e r_ R
T A
E -1
B R
A D
Y H
A L
L
F
IR
S T
F L O
O R
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
A
R E
A A
E-100
BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION -
AREA A
S 2nd St, Danville, KY 40422
BKB
GTW
RTA
KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND GRAY SOLID
LINES INDICATE EXISTING ITEMS TO REMAIN.
B. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,
PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK
PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW
LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.
C. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING
CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO
REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS
INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT
OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON
THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.
"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF
POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE
NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
D. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS
DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE
DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING
CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT
ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK
INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS
SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR
THE BID WHICH HE PROPOSES.
E. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS
FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),
WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND
REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES
ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW
FINISHES - SEE ARCHITECTURAL PLANS).
F. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED
FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO
OWNER AT THEIR OPTION.
G. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR
RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED
WITH THEIR EQUIPMENT.
H. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION
BARRIERS AS REQUIRED.
I. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /
CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR
INSTALLED.
J. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE
CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC
REQUIREMENTS.
K. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION
SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND
EQUIPMENT SHOWN ON PLANS.
L. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF
BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND
AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE
RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN
INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS
REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL
AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER
REQUIREMENTS.
M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL
BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND
INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES
OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE
DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL
ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.
UNUSED BREAKERS SHALL BE IN OFF POSITION.
GENERAL NOTES (DEMOLITION):
SCALE: 1/8" = 1'-0"
FIRST FLOOR ELECTRICAL DEMO PLAN - AREA A
KEYNOTES
ED1 REMOVE EXISTING ELECTRICAL CONNECTIONS TO MECHANICAL
EQUIPMENT BEING REMOVED. ALL WIRING SHALL BE REMOVED
BACK TO ELECTRICAL PANEL COMPLETELY. COORDINATE
REMOVAL AND EXACT EQUIPMENT LOCATIONS WITH MECHANICAL
WORK (TYPICAL).
ED2 EXISTING LED LIGHT FIXTURES TO REMAIN (TYPICAL).
ED3 EXISTING 750kVA , 120/208V, THREE PHASE, OIL FILLED UTILITY
TRANSFORMER TO REMAIN.
ED4 DEMOLISH ALL EXIT SIGNS IN CORRIDORS.
F
HD
F
SD
SD
HD
SD
SD
SD
SD
SD
SD
SD
SD
F
A
F
I W
F
I W F
F
WI
F
WI
I W
F
I W
F
F W I
F W I
FWI
I W
F
F
I W
I W
F
I W
F
SD
HDI W
F
I W F
I W
F
I W
F
LF6
LF6 LF6
LF6
LF25
LF25
LF25
LF25
LF25
LF25
LF25
LF25 LF25 LF25 LF25 LF25 LF25
LF6 LF6 LF6 LF6
LF6LF6LF6LF6
LF6 LF6 LF6 LF6
LF3
LF7
LF9 LF9
LF9 LF9
LF9 LF9
LF31 LF31
LF31
LF31
LF31 LF31
LF37 LF31
LF9
LF18
LF20
LF9
LF31
LF7
LF7
LF7
LF31
LF9
LF20
LF20
LF18
LF18
LF9
LF31
LF31
LF31
LF31
LF31
LF31
LF31
LF31
LF37
CORRIDOR
A104
CORRIDOR
B100
MULTI -
PURPOSE
B101
STORAGE
B102
STORAGE
B103
TOILET
B104
TOILET
B105
PHYSCIAL
THERAPY
B106
LIVING RM.
B108
KITCHEN
B109
BEDROOM
B110
BATH
B113
BEDROOM
B114
BATH
B117
MECH.
B143
STORAGE
B120
LAUNDRY
B121
BEDROOM
B141
BATH
B138
BATH
B137
BEDROOM
B135
LIVING ROOM
B130
STAIR
B
ELEC. RM.
B122
JAN.
B123
BEDROOM
B126
BATH
B127
HALL
B119
ED2
ED1
ED1
ED2
ED2
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
(TYP)
ED4
(TYP)
ED4
(TYP)
ED4
EXISTING TO REMAIN
KEYPLAN LEGEND
DEVICE TO BE DEMOLISHED
NEW DEVICE
REVISION HISTORY OF THIS DRAWING
DECA LOG #
ENGR. FILE NO.
DRAWING NO.
DRAWN BY
AS BUILT DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
CHECKED BY
PHASE
RTA DATE
DRAWING DATE
A & E FILE NO.
DRAWING INFORMATION
# 540CBXLSD6300
ACCT# 540CBXLSD6300
10411 Meeting Street Prospect, KY 40059
T: 502 326.3085 F: 502 326.2691
08.20.24
VKYS23
/2
/2
:5
:5
P
M
C
U s e rs \g w e s s lin g \D o c u m e n ts
\V K
Y S
B ra d y H a ll_ g w e s s lin g C
L F
H C
.r v t
P ro je c t
N u m b e r_
O w n e r_ R
T A
E -1
B R
A D
Y H
A L L
F
IR
S
T F
L O
O R
E L E
C T
R
IC
A L
D E
M O
L
IT
IO
N
A
R E
A B
E-101
BRADY HALL - FIRST FLOOR ELECTRICAL DEMOLITION -
AREA B
S 2nd St, Danville, KY 40422
BKB
GTW
RTA
KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND GRAY SOLID
LINES INDICATE EXISTING ITEMS TO REMAIN.
B. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,
PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK
PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW
LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.
C. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING
CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO
REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS
INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT
OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON
THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.
"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF
POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE
NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
D. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS
DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE
DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING
CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT
ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK
INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS
SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR
THE BID WHICH HE PROPOSES.
E. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS
FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),
WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND
REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES
ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW
FINISHES - SEE ARCHITECTURAL PLANS).
F. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED
FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO
OWNER AT THEIR OPTION.
G. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR
RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED
WITH THEIR EQUIPMENT.
H. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION
BARRIERS AS REQUIRED.
I. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /
CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR
INSTALLED.
J. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE
CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC
REQUIREMENTS.
K. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION
SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND
EQUIPMENT SHOWN ON PLANS.
L. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF
BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND
AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE
RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN
INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS
REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL
AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER
REQUIREMENTS.
M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL
BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND
INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES
OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE
DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL
ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.
UNUSED BREAKERS SHALL BE IN OFF POSITION.
GENERAL NOTES (DEMOLITION):
SCALE: 1/8" = 1'-0"
FIRST FLOOR ELECTRICAL DEMO PLAN - AREA B
KEYNOTES
ED1 REMOVE EXISTING ELECTRICAL CONNECTIONS TO
MECHANICAL EQUIPMENT BEING REMOVED. ALL WIRING SHALL
BE REMOVED BACK TO ELECTRICAL PANEL COMPLETELY.
COORDINATE REMOVAL AND EXACT EQUIPMENT LOCATIONS
WITH MECHANICAL WORK (TYPICAL).
ED2 EXISTING LED LIGHT FIXTURES TO REMAIN (TYPICAL).
ED4 DEMOLISH ALL EXIT SIGNS IN CORRIDORS.
DN
F
SD
F
HD
SD
SD
SD
SD
HD
SD
SD
SD
SD
SD
SD
SD
HD
F
HD
HD
F S
SD
SD
SD
HD
SD
SD
SD
F
SD
F
I W
F
F
WI
F W
I
I W F
I W
F
HD
I W F
I W F
F W
I
F W
I
F
WI
F
I W
F W
I
F
FWI
F
FWI
FWI
FWI
I W
I W
F
I W
F
F
HDSD
I W
F
W I
F
W F
I
W F
I
F
F W
I F W
I
SD I W
F
F W
I
F
WI
F
WI
F
WI
I W F
I W
F
I W
F
HD
I W F
I W
F
HD
F W
I
F
I W
ED1
CORRIDOR
A200
Room
A212
LOBBY
A201
CLASSROOM
A203
TOILET
A204
CLASSROOM
A205
TOILET
A206
JAN.
A207
COMM.
SKILLS
A208
DIAGNOSTIC
A209
MEDIA
A210
TOILET
A211
Room
A213
CLASSROOM
A214
TOILET
A216
Room
A217
Room
A218
Room
A219
Room
A220
Room
A221
Room
A222
Room
A223
CORRIDOR
A224
DRY STOR.
A225
HALL
A226
DISH WASH
A229
FREEZER
A230
FREEZER
A231
OFFICE
A232 JAN.
A233
Room
A234
LINEN
A238
DINING ROOM
A240
ELEC.
A274
JAN.
NURSES
LOUNGE
TLT.
WARD #1
A249
SHOWER
A252
TLT.
A254
HEAD NURSE
A247
STORAGE
A248
STORAGE
A246
Room
A275
TLT.
A259 DENTIST
A260
EXAM
A261CORRIDOR
A241
LOUNGE
A264
OFFICE
A265
TREATMENT
A262
TOILET
A271
WARD #2
A270
RAMP
CLASSROOM
A215
TLT.
A253
ELEV.
OFFICE
A255
WAITING RM.
A263
SHOWER
A272
TLT.
A266
DIRECTORS
OFFICE
A273
RECEPTION
B203
OFFICE
A258
WALK IN
REFG.
A235
COOKING
AREA
A239
CORRIDOR
A202
M-306
ED1ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1 ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
ED1
(TYP)
ED4
(TYP)
ED4
(TYP)
ED4
(TYP)
ED4
(TYP)
ED4
(TYP)
ED4
EXISTING TO REMAIN
KEYPLAN LEGEND
DEVICE TO BE DEMOLISHED
NEW DEVICE
REVISION HISTORY OF THIS DRAWING
DECA LOG #
ENGR. FILE NO.
DRAWING NO.
DRAWN BY
AS BUILT DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
CHECKED BY
PHASE
RTA DATE
DRAWING DATE
A & E FILE NO.
DRAWING INFORMATION
# 540CBXLSD6300
ACCT# 540CBXLSD6300
10411 Meeting Street Prospect, KY 40059
T: 502 326.3085 F: 502 326.2691
08.20.24
VKYS23
/2
/2
:5
:5
P
M
C
U s e rs \g w e s s lin g \D o c u m e n ts
\V K
Y S
B ra d y H a ll_ g w e s s lin g C
L F
H C
.r v t
P ro je c t
N u m b e r_
O w n e r_ R
T A
E -1
B R
A D
Y H
A L L
S
E C
O N
D F
L O
O R
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
A
R E
A A
E-102
BRADY HALL - SECOND FLOOR ELECTRICAL DEMOLITION
- AREA A
S 2nd St, Danville, KY 40422
BKB
GTW
RTA
KENTUCKY SCHOOL FOR THE DEAF - BRADY HALL
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND GRAY SOLID
LINES INDICATE EXISTING ITEMS TO REMAIN.
B. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE,
PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK
PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW
LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.
C. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING
CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO
REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS
INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT
OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON
THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.
"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF
POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE
NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
D. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS
DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE
DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING
CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT
ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK
INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS
SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR
THE BID WHICH HE PROPOSES.
E. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS
FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),
WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND
REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES
ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW
FINISHES - SEE ARCHITECTURAL PLANS).
F. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED
FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO
OWNER AT THEIR OPTION.
G. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR
RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED
WITH THEIR EQUIPMENT.
H. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION
BARRIERS AS REQUIRED.
I. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /
CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR
INSTALLED.
J. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE
CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC
REQUIREMENTS.
K. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION
SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND
EQUIPMENT SHOWN ON PLANS.
L. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF
BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND
AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE
RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN
INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS
REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL
AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER
REQUIREMENTS.
M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL
BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND
INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES
OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE
DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL
ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.
UNUSED BREAKERS SHALL BE IN OFF POSITION.
GENERAL NOTES (DEMOLITION):
SCALE: 1/8" = 1'-0"
SECOND FLOOR ELECTRICAL DEMO PLAN - AREA A
KEYNOTES
ED1 REMOVE EXISTING ELECTRICAL CONNECTIONS TO
MECHANICAL EQUIPMENT BEING REMOVED. ALL WIRING SHALL
BE REMOVED BACK TO ELECTRICAL PANEL COMPLETELY.
COORDINATE REMOVAL AND EXACT EQUIPMENT LOCATIONS
WITH MECHANICAL WORK (TYPICAL).
ED4 DEMOLISH ALL EXIT SIGNS IN CORRIDORS.
HD
SD SD
SD
SDSD
SD
SD
SD
SD
S D
SD
SD
F
F
SD
SD
SD
I W
F
F F W
I
F
F
I W
F
WI F
I W
FWI
F W
I
F W
I
F W
I
SD
FWI
FWI
FWI
I W F
I W F
F
F
F
I W F
F W
I
WI
I W
F
FWI
F
WI
FWI
W I
F
W I
F
FWIFWI
I W
F I
W F
LOBBY
B201
WAITING
LOUNGE
B204
OFFICE
B205
RECEPTION
B207
CLERICAL
B211
CONFERENCE
B208
CLERICAL
B212
DIRECTOR
B213
COUNSELOR
B215
SOCIAL WK.
B216
AUDIOLOGIST
B217
TESTING
B219
OBS.
B221
AUDIO
TESTING #1
AUDIO
TESTING #2
ENGINEER
B223
SOCIAL WK.
B227
PARENT
EDUC.
B228
PARENT
EDUC.
B229
FISCAL
OFFICE
B230
STOR.
B231
WAITING
B232
OPTHAMOLOGY
B233
OTOLOGY
B234
STOR.
B235
CORRIDOR
B210
STAFF
LOUNGE
B240
Room
B241 VEST.
B242
VEST.
B243
JAN.
B244
MENS
B245
BEDROOM
B248
BEDROOM
B251