This is Addendum One to Invitation to Bid No. RFB-77-27, issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, on behalf of the Kentucky Transportation Cabinet for the Loadometer Station Renovation project located at Boone County I-71 Southbound, Mile 75 in Walton, Kentucky. The project involves upgrading the existing southbound rest area pump station with equipment modifications and electrical system improvements. The addendum was issued on September 23, 2026, and establishes binding changes to the specifications and drawings that bidders must acknowledge on their proposals.
The addendum clarifies and modifies six key items within the project scope. Specifications for packaged lift stations are revised to reflect the pump station upgrade work, and alternative grinder pump manufacturers meeting equivalent performance standards are now acceptable, specifically Zoeller Engineered Products 71 Series from Louisville, Kentucky, subject to submittal review. Electrical work modifications include deletion of coded sheet notes 8 and 9 from Sheet E201, clarification that existing panelboards M, I, R, and OL will remain in place with all breakers and circuits replaced with new conductors in compression EMT conduit, addition of a manual throw transfer switch generator disconnect on the building's rear, and relocation of the data rack to the mechanical room with existing conduits intercepted and routed with new conduits of equal size and quantity while replacing existing conductors with new cables. Bidders are required to acknowledge receipt of this addendum on the Form of Proposal.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum Two.pdf | ||
| Final_RFB_785_2700000115_2_SO_FORM.PDF | ||
| Final_RFB_785_2700000115_3_SO_FORM.PDF | ||
| Final_RFB_785_2700000115_1_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-77-27
FOR: Loadometer Station Renovation Boone County I-71 Southbound, Mile 75 Kentucky Transportation Cabinet Walton, Kentucky
DATE: September 24, 2026
RFB-785-2700000115
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-77-27 For: Loadometer Station Renovation Boone County I-71 Southbound, Mile 75 Kentucky Transportation Cabinet Walton, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
Addendum One 1
ADDENDUM ONE 9/23/2026
KYTC - Boone Co I-71 Loadometer Station Renovation Gallagher Office of Architecture, LLC I-71 Southbound, Mile 75, Walton, KY 41094 227 Miller Street Account # 625-CC95-Z001-56 Lexington, Kentucky 40507
The Bidding and General Documents, Technical Specifications, and Drawings are clarified or changed in accordance with the following. Bidders shall acknowledge receipt of this Addendum on the Form of Proposal in the space provided.
Item 1.: Refer to Specifications, Section 333213, “Packaged Lift Stations”, Paragraph 1, “General”, revise the first sentence to read.
“The contractor shall furnish and install the necessary equipment to upgrade the existing South Bound rest area pump station in Boone County.”
Item 2.: Refer to Specifications, Section 333213, “Packaged Lift Stations”, Paragraph 2, “Grinder Pumps”:
Based on representation by the Bidder that the function, performance, fabrication, appearance, finish including exterior color, quality and warranty are equivalent or superior to the specified product, the following manufacturer and product that may be incorporated into the Work is acceptable subject to Submittal review during Construction:
Manufacturer: Zoeller Engineered Products, 71 Series, Louisville, KY
Item 3.: Refer to Drawings, Sheet E201, “Electrical New Work Plans”, Delete coded sheet notes 8 and 9 from this drawing.
Item 4: Refer to Drawings, Sheet E201, “Electrical New Work Plans”, clarify that Panelboard M, I, R, and OL are existing to remain in their current locations. Existing feeders to these panels will also remain. All breakers in all panels are to be replaced. All circuits from all panels are to be replaced with new conductors in new compression EMT conduit.
Item 5.: Refer to Drawings, Sheet E201, “Electrical New Work Plans”, clarify that new generator disconnect on back of building is included in the project scope and is to be a manual throw transfer switch, service entrance rated with disconnect for connection to future generator.
Item 6.: Refer to Drawings, Sheet E201, “Electrical New Work Plans”, clarify that coded sheet note #3 refers to the relocated data rack being moved to its new location in the Mechanical Room. The existing conduits are to be intercepted and routed with new conduits of equal size and quantity, to the new wall and rack on the exterior wall.
The existing conductors are to be replaced with new cables, equal to existing.