Addendum One.pdf
PDF 2 MB Posted
- Attached to
- RFB-203-26 EDU KSD Middleton Exterior Repairs
- Solicitation number
- RFB 785 2600000405 3
- Issued by
- Boyd County, Kentucky
About this file
This is an Addendum One to an Invitation to Bid (RFB-203-26) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for exterior repairs to Middleton Hall Dormitory at the Kentucky School for the Deaf in Danville, Kentucky. The addendum, dated March 10, 2026, modifies the original bid documents dated January 29, 2026, and introduces changes to specifications and drawings that become binding upon contract issuance. Key modifications include a complete replacement of Specification 072100 (Spray-In-Place Thermal Insulation), additions to the Metal Wall Panel manufacturer list to include Classic Green Color and IMETCO Latitude Metal Wall Panel, and clarifications on structural steel and welding requirements per ASTM A572 and AWS D1.1 standards. The addendum references a site visit conducted on February 24, 2026, at 10 a.m., for which a sign-in sheet is attached.
The thermal insulation specification details require batt insulation with R-21 value and sprayed-in-place polyurethane foam systems at 2 lb. and 1/2 lb. densities for exterior cavity walls and openings. The specification mandates Air Barrier Association of America (ABAA) accreditation and certification for subcontractors and installers, with quality assurance inspections at 50 percent completion and mock-up wall construction requirements. Approved manufacturers for spray-applied systems include NCFI Polyurethanes, BASF, Carlisle, Huntsman, Gaco, Henry Company, JohnsManville, SWD Urethane, and Xcelus Building Systems. A preinstallation meeting is required to coordinate spray foam installation with masonry work, and all defective work must be promptly removed and replaced at no additional cost to the owner.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2600000405_3_SO_FORM.PDF | ||
| Final_RFB_785_2600000405_2_SO_FORM.PDF | ||
| Addendum Two.pdf | ||
| Final_RFB_785_2600000405_1_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-203-26
FOR: Exterior Repairs Middleton Hall Dormitory Kentucky School for the Deaf Danville, Kentucky
DATE: March 10, 2026
RFB-785-2600000405
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-203-26 For: Exterior Repairs Middleton Hall Dormitory Kentucky School for the Deaf Danville, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
ADDENDUM No. 1 PAGE 1
ADDENDUM NO. 1
TO THE DRAWINGS AND SPECIFICATIONS
FOR THE
KSD Middleton Hall Dormitory Envelope Danville, Kentucky
Account No. 540-CC6C-SD67-00
RTA 23025
March 09, 2026
To All Plan Holders of Record:
This Addendum modifies bid documents dated 01/29/2026 for the above project and shall become part of said documents in the preparation of proposals and execution of work of the subject project.
General:
1. Refer to the attached sign-in sheet from the site visit on 02/24/26 at 10 am.
Specifications:
1. Refer to Specification 072100 – Spray-In-Place Thermal Insulation.
a) Replace Specification 072100 in its entirety with the attached revised specification 072100.
2. Refer to Specification 074213 – Metal Wall Panel
a) Refer to Part 2 Products, 2.01 Manufacturers,
i) B.2.a. Add Classic Green Color
ii) C. Add IMETCO Latitude Metal Wall Panel to the manufacturer list.
Drawings:
1. Clarification on the structural drawings:
a) Where products are not otherwise listed in structural specifications, clarify products as follows:
i) Steel plate: ASTM A572. 50 ksi. Steel to be new, unused and perfect stock, free from millscale, rust, flake, pitting, and imperfections, without bends, kinks, and distortions. Provide holes required for securing other work to structural steel framing, and for attaching connections and embeds to other work. Clean surfaces to be painted. Remove dirt, loose rust, loose mill scale, and spatter, slag, or flux deposits. Wipe steel surfaces with solvent to remove rolling oils that impair primer bond.
Prepare surfaces according to SSPC specifications per SSPC-SP 2 “Hand Tool Cleaning.” Shop prime with fabricator’s standard lead- and chromate-free, non-asphaltic, rust-inhibiting primer.
ii) Welding: Qualify procedures and personnel in accordance with applicable provisions of AWS D1.1 “Structural Welding Code – Steel” and AISC 360. All field welding shall be performed by personnel qualified by AWS procedure and who have engaged in the necessary processes of welding during each six-month period since the latest qualification. Comply with AWS D1.1 for procedures, appearance and quality of welds, and methods used in correcting welding work. Remove all cracks, pores, slag inclusions, incomplete fusions, and incomplete penetrations over ½” long in any weld and reweld.
RTA 23025
Account No. 540-CALK-SD19-00
THERMAL INSULATION 072100 - 1
SECTION 072100 - THERMAL INSULATION
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Batt insulation in exterior wall construction.
B. Sprayed-in-place thermal insulation (2 lb.) air barrier system at all exterior cavity wall construction.
C. Sprayed-in-place thermal insulation (1/2 lb.) at all exterior cavity wall openings with metal stud box/beam constructed headers, jambs, and sills.
1.02 RELATED REQUIREMENTS
A. Section 042000 - Unit Masonry: Supporting construction for insulation..
B. Section 054100 - Cold-Formed Exterior Steel Stud Framing: Supporting construction for sprayed-in-place and batt insulation.
C. Section 061000 - Rough Carpentry: Supporting construction for batt insulation.
D. Section 075200 - Modified Bituminous Membrane Roofing: Installation requirements for board insulation over low slope roof deck.
E. Section 075400 - Thermoplastic Membrane Roofing: Installation requirements for board insulation over low slope roof deck.
F. Section 092116 - Gypsum Board Assemblies: Acoustic insulation inside walls and partitions.
1.03 REFERENCE STANDARDS
A. ASTM C665 - Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame
Construction and Manufactured Housing; 2012.
B. ASTM E136 - Standard Test Method for Behavior of Materials in a Vertical Tube Furnace At 750
Degrees C; 2012.
C. ASTM E2357 - Standard Test Method for Determining Air Leakage of Air Barrier Assemblies.
1.04 SUBMITTALS
A. Product Data: Provide data on product characteristics, performance criteria, and product limitations.
B. Sprayed-in-Place Thermal Insulation:
1. Provide data on product characteristics, product testing, product performance criteria, and product limitations.
a. Provide specific data that product is approved for direct application on cmu substrate as part of cmu/masonry veneer cavity wall and/or exterior sheathing as part of the metal stud/sheathing/masonry veneer cavity wall construction.
b. Provide product data on all auxiliary components; primer, seam tape and transition strip materials.
c. Provide specific data that product has been tested and is approved for use as an air barrier.
d. Provide hydrostatic water resistance pressure test results.
e. Shop Drawings: Indicate locations and extent of sprayed-in-place thermal insulation air barrier system assemblies and details of all typical conditions, intersections with other envelope assemblies and materials, membrane counter-flashings, and details showing how gaps in construction will be bridged, how inside and outside corners are negotiated, how materials that cover the insulation are secured, how air-tight conditions are maintained, and how miscellaneous penetrations such as conduits, pipes, electric boxes and similar items are sealed.
THERMAL INSULATION 072100 - 2
2. Quality Assurance Program: Provide evidence of current accreditation of the subcontractor and certification of installers under the Air Barrier Association of America's (ABAA)
Quality Assurance Program. Provide accreditation and certification information on the form included in the Form of Proposal.
C. Manufacturer certificate, located at the end of this section, to be submitted within 24 hours of the bid, for the proposed sprayed-in-place thermal insulation system confirming that the sprayed-in-place thermal insulation system installer is approved to install the proposed sprayed-in-place thermal insulation system.
1.05 FIELD CONDITIONS
A. Do not install insulation adhesives when temperature or weather conditions are detrimental to successful installation.
1.06 QUALITY ASSURANCE
A. Source Limitations: Obtain each type of building insulation through one source.
B. Fire-Test-Response Characteristics: Provide insulation and related materials with the fire-test-response characteristics indicated, as determined by testing identical products per test method indicated below by UL or another testing and inspecting agency acceptable to authorities having jurisdiction. Identify materials with appropriate markings of applicable testing and inspecting agency.
1. Surface - Burning Characteristics: ASTM E 84.
2. Fire - Resistance Ratings: ASTM E 119.
3. Combustion Characteristics: ASTM E 136.
C. Sprayed-In-Place Thermal Insulation: Current accreditation of the subcontractor and certification of installers in accordance with the Air Barrier Association of America's (ABAA) Quality Assurance
Program.
1. Install in accordance with ABAA and training requirements outlined in ULC S705.2-05
Installation Standard.
D. Sprayed-In-Place Thermal Insulation Field Quality Control:
1. ABAA Site Inspections: ABAA to verify conformance with the manufacturers instructions, the ULC S705.2 Installation Standard, the ABAA Quality Assurance Program and requirements of this specification.
a. Inspections and testing shall be carried out at 50 percent of sprayed-in-place thermal insulation completion. Forward written inspection reports to the Architect within 10 working days of the inspection and test being performed.
b. If the tests reveal any defects, promptly remove and replace defective work at no additional expense to the Owner.
1) If the preliminary or final written inspection report indicates the system will not or has not passed then an additional ABAA inspection shall be conducted to ensure defects and deficiencies have been corrected and a passing ABAA report can be obtained.
1.07 PRE-INSTALLATION MEETING
A. Preinstallation Meeting: Per Section 042000 - Unit Masonry the general contractor/construction manager will conduct a preinstallation conference prior to the masonry installation occuring. The sprayed-in-place thermal insulation installer is to attend this preinstallation conference too coordinate the installation of the sprayed-in-place insulation with the masonry subcontractor.
1. Review foreseeable methods and procedures related to sprayed-in-place thermal insulation installation, including but not necessarily limited to the following:
a. Protection of through wall flashing.
b. Spray around horizontal reinforcing eyes.
c. Hot and cold weather protection.
THERMAL INSULATION 072100 - 3
d. Protection of work in process and installed.
e. Sequencing of work with masonry installation.
f. Review percentages of completion when ABAA testing will be conducted.
g. Has the project been registered with the ABAA for testing?
1) If registered has the ABAA testing agent been notified?
1.08 MOCK-UP
A. Sprayed-in-place thermal insulation to be included in the mock-up wall construction.
PART 2 PRODUCTS
2.01 BATT INSULATION MATERIALS
A. Glass Fiber Batt Insulation: Flexible preformed batt or blanket, complying with ASTM C665;
friction fit.
1. Surface Burning Characteristics: Flame spread index of 25 or less; smoke developed index of 450 or less, when tested in accordance with ASTM E 84.
2. Combustibility: Non-combustible, when tested in accordance with ASTM E136, except for facing, if any.
3. Formaldehyde Content: Zero.
4. Thermal Resistance: R-value of 21.
5. Thickness: 5-1/2 inch.
6. Facing: Unfaced.
7. Recycled Content: Give preference to products having recycled content.
8. Manufacturers: Subject to compliance with requirements, manufacturers offering the following products that may be incorporated into the work include;
a. Johns Manville: www.jm.com.
b. Knauf Insulation GmbH: www.knaufinsulation.us.
c. Owens Corning Corp: www.owenscorning.com.
2.02 SPRAYED-IN-PLACE THERMAL INSULATION
A. Manufacturers: Subject to compliance with requirements, manufacturers offering the following products that may be incorporated into the work include, but are not limited to the following:
1. Basis of Design: Design concept and the drawings indicate the size, profiles, dimensional requirements and aesthetics of the following:
a. NCFI Polyurethanes, Division of BMC: InsulBloc 2 lb. Spray Foam System 11-017.
b. NCFI Polyurethanes, Division of BMC: InsulStar Light 1/2 lb. Spray Foam System.
2. Products by other manufacturers (listed below) may be considered, provided deviations in dimensions, profiles, and formulations are minor and do not change the design concept as judged by the Architect.
a. NCFI Polyurethanes, Division of BMC: InsulBloc 2 lb. Spray Foam System 11-017:
www.ncfi.com
b. BASF Polyurethane Foam Enterprises, LLC: Walltite 2 lb.Air Barrier System:
www.basf-pfe.com
c. Carlisle Spray Foam Insulation: SealTite Pro Closed Cell: www.carlislefi.com
d. Huntsman Building Solutions/ formerly Demilec USA, LLC: Heatlok Soya HFO:
www.demilecusa.com
e. Gaco (Holcim): Gaco WallFoam 183M 2 lb.: www.gaco.com
f. Henry Company: Permax 2.0: www.henry.com
g. Huntsman Building Solutions/ formerly Icynene-Lapolla Inc.: ProSeal LE 2 lb.
Spray Foam Insulation: www.icynene.com
h. JohnsManville Insulation Systems: JM Corbond III 2 lb.: www.jm.com
i. SWD Urethane: Quik-Shield 112-XC: www.swdurethane.com
j. Xcelus Building Systems, Inc.: Xcelus XLS 2000: www.xcelusbuildingsystems.com
THERMAL INSULATION 072100 - 4
3. Products by other manufacturers (listed below) may be considered, provided deviations in dimensions, profiles, and formulations are minor and do not change the design concept as judged by the Architect.
a. NCFI Polyurethanes, Division of BMC: InsulStarLight 1/2 lb. Spray Foam System
11-017: www.ncfi.com
b. BASF Polyurethane Foam Enterprises, LLC: Enertite 1/2 lb.Air Barrier System:
www.basf-pfe.com
c. Huntsman Building Solutions/ formerly Demilec APX 1.2: www.demilecusa.com
d. Gaco (Holcim): Gaco WallFoam Open Cell Foam 052N 1/2 lb.:
www.gacowallfoam.com
e. Huntsman Building Solutions/ formerly Icynene-Lapolla Inc.: LD-R-50 1/2 lb.
Spray Foam Insulation: www.icynene.com
f. JohnsManville Insulation Systems: JM ocSPF 1/2 lb.: www.jm.com
B. Spray applied closed cell, 2 lb. polyurethane foam insulation, air seal and water repellent treatment for
CMU cavity wall and cold formed metal stud framed walls throughout the project.
1. Physical material properties shall be:
2. Core Density 1.9-2.2 lb/ft per ASTM D-1622
3. Water Vapor Transmission <1.0 @ 2" thick /perms per ASTM E-96
4. R-Value 6.7 minimum at 1inch thick per ASTM C-518
5. R-Value Aged: 6.4 minimum at 1 inch thick per ASTM C-1029
6. Compressive Strength 25 (min) psi per ASTM D-1621
7. Flame Spread <25 per ASTM E-84
8. Smoke Developed <450 per ASTM E-84
9. Air Leakage - Infiltration: 0.00 @ 1.57 psf/cfm/ft2 per ASTM E-283
10. Air Leakage - Exfiltration: 0.00 @ 1.57 psf/cfm/ft2 per ASTM E-283
11. Air Barrier System Test: ASTM E 2357 and NFPA 285
12. Tensile Bond Strength >45 for masonry psi per ASTM D-1623
13. Hydrostatic Water Pressure Resistance Test: No failure at 56.5 feet head pressure per
AATCC 127-1998.
C. Spray applied open cell, 1/2 lb. polyurethane foam insulation, air seal and water repellent treatment for boxed/beam headers, jambs, and sills at openings in exterior metal stud framed walls throughout the project.
1. Physical material properties shall be:
2. Core Density 0.5 lb/ft per ASTM D-1622
3. Water Vapor Transmission 15 /perms at 1 inch per ASTM E-96
4. R-Value 4.1 minimum at 1 inch thick per ASTM C-518
5. Flame Spread <25 per ASTM E-84
6. Smoke Developed <450 per ASTM E-84
7. Air Leakage - Infiltration: 0.00 @ 1.57 psf/cfm/ft2 per ASTM E-283
8. Air Leakage - Exfiltration: 0.00 @ 1.57 psf/cfm/ft2 per ASTM E-283
9. Air Barrier System Test: ASTM E 2357 and NFPA 285
D. Refer to the wall types on the A0.1 drawing sheet for thickness of spray polyurethane material required.
E. Apply spray polyurethane foam directly to the masonry block or exterior sheathing in accordance with the manufacturers installation instructions. All surfaces to be sprayed with foam must be free of moisture and ice.
F. Do not apply spray polyurethane foam during inclement weather or when ambient temperatures and humidity are outside the ranges prescribed by the manufacturer.
1. Optimum Adhesion: Sprayed-In-Place Thermal Insulation Installer to determine appropriate grade of adhesive material to be used on project based on; project type, substrate type, time of year of installation, average daily temperatures forecasted during installation, and other factors, as determined by the sprayed-in-place thermal insulation manufacturer to maintain
THERMAL INSULATION 072100 - 5
the specified requirements. No additional compensation will be considered, or due, the sprayed-in-place thermal insulation contractor if the sprayed-in-place thermal insulation manufacturer requires a tack coat, or the type or grade of adhesive, originally bid, to be changed due to project type, environmental and/or temperature factors, to maintain the specified requirements and construction schedule.
G. Materials:
1. Transition Strip and Seam Tape Primer:
a. Primer to facilitate adhesion of flashings to fiberglass faced sheathing, concrete and masonry substrates.
1) Manufacturers: Subject to compliance with requirements, manufacturers offering the following products that may be incorporated into the work include, but are not limited to the following:
(a) Grace Construction Products: Perm-A-Barrier WB Primer
(b) W. R. Meadows, Inc.: Mel-Prime
(c) Product approved for use by sprayed-in-place thermal insulation manufacturer.
2. Seam Tape:
a. Self-adhered flashing with cross-laminated, high density polyethylene sheet backed with pressure-sensitive rubberized asphalt adhesive.
1) Manufacturers: Subject to compliance with requirements, manufacturers offering the following products that may be incorporated into the work include, but are not limited to the following:
(a) Grace Construction Products: Vycor Plus
(b) W. R. Meadows, Inc.: Air-Shield 25 mil Flashing Tape
(c) Product approved for use by sprayed-in-place thermal insulation manufacturer.
3. Transition Strip Materials:
a. Contractor option to use self-adhered sheet product or fluid applied product for the transition strip materials.
b. Self-adhered Transition Strip Material: Minimum 1 mm self-adhered flashing sheet with cross-laminated, high density polyethylene sheet backed with pressure-sensitive rubberized asphalt adhesive. Install transition strip materials at all wall openings, transitions in substrate and connections to adjacent elements:
1) Manufacturers: Subject to compliance with requirements, manufacturers offering the following products that may be incorporated into the work include, but are not limited to the following:
(a) Carlisle Coatings and Waterproofing: CCW-705 TWF
(b) Grace Construction Products: Perm-A-Barrier Flashing
(c) Henry: Blueskin SA
(d) Protective Coatings Technology, Inc.: Poly-Wall Crack Guard
(e) Tremco, Inc.; ExoAir 110
(f) W. R. Meadows, Inc.: Air Shield
c. Fluid-applied Transition Strip Material System: One component rubberized air barrier material. Suitable for spray, roller or brush application direct to substrate.
Install by roller/brush in two minimum 13 mil wet thickness applications, or one 26 mil wet thickness application by spray. Provide all additional auxiliary materials necessary to complete the entire system: Reinforced, nonwoven, polyester sheathing joint fabric with preformed corners, polyester-faced 30-mil thick, self-sealing, rubberized asphalt membrane, and water-based primer.
1) Manufacturers: Subject to compliance with requirements, manufacturers offering the following products that may be incorporated into the work include, but are not limited to the following:
(a) BASF: Enershield-1, Quick Corner 6, TF Membrane, WS
Flashing Primer: www.enershield.basf.com
THERMAL INSULATION 072100 - 6
(b) Prosoco - R-Guard Fast Flash
(c) W. R. Meadows, Inc.: Air Shield LM
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that substrate, adjacent materials, and insulation materials are dry and that substrates are ready to receive insulation.
B. Verify substrate surfaces are flat, free of honeycomb, fins, irregularities, or materials or substances that may impede adhesive bond.
3.02 BATT INSTALLATION
A. Install insulation in accordance with manufacturer's instructions.
B. Install in exterior wall spaces without gaps or voids. Do not compress insulation.
C. Trim insulation neatly to fit spaces. Insulate miscellaneous gaps and voids.
D. Fit insulation tightly in cavities and tightly to exterior side of mechanical and electrical services within the plane of the insulation.
3.03 SPRAYED-IN-PLACE THERMAL INSULATION AIR BARRIER SYSTEM
A. Equipment used to spray insulation shall comply with ABAA ULC S705.2 and the manufacturer's recommendations.
B. Record equipment settings daily as required by the ABAA ULC S705.2 installation standard.
C. Apply in consecutive passes as recommended by manufacturer and thickness indicated on drawings.
Passes shall not be less than 1/2 inch and not greater than 2 inches.
D. Install within manufacturer's tolerances, but not more than minus 1/4 inch or plus 1/2 inch.
1. The total average thickness, tested and provided on the final ABAA Audit Report, for the sprayed insulation installed on the wall in the field shall be the minimum thickness indicated, for the various wall types, as shown on the drawings.
E. Surface of foam insulation to be free of voids and embedded foreign objects.
F. Remove masking materials and overspray from adjacent areas immediately after foam surface has hardened. Ensure cleaning methods do not damage work performed by other sections.
G. Trim as required, any excess thickness that would interfere with the application of cladding/covering system by other trades.
H. Complete connections to other components and repair any gaps, holes or other damage using material which conforms to ABAA ULC S710.1 or ABAA ULC S711.1 and installed in accordance with
ABAA ULC S710.2 or ABAA ULC S711.2 as applicable.
I. Fill exterior metal stud boxed/beam headers, jambs, and sills at all openings completely with 0.5 lb.
spray insulation.
J. Transition Strip and/or Fluid-Applied Material Installation: Install transition strip/fluid-applied materials to provide continuity throughout the building envelope. Install materials in accordance with manufacturer's recommendations and the following:
1. Priming, seam tape/fluid-applied material, and transition strips are required by RossTarrant whether or not they are required by a manufacturer to meet the ABAA air leakage requirements of ASTM E2357.
2. Apply primer for seam tape and transition strips. Allow primer to dry completely before transition strip application. Apply as many coats as necessary for proper adhesion.
THERMAL INSULATION 072100 - 7
3. Position subsequent sheets of transition strips applied above so that membrane overlaps the membrane sheet below by a minimum of 2 inches, unless greater overlap is required by manufacturer. Roll into place with roller.
4. Overlap horizontally adjacent pieces of transition strips a minimum of 2 inches, unless greater overlap is required. Roll seams with roller.
5. Seal around all penetrations with a transition strip or other procedure.
6. At changes in substrate plane, provide transition material to make a smooth transition from one place to another.
7. Provide mechanically fastened non-corrosive metal sheet to span gaps in substrate plane and to make a smooth transition from one plane to another. Membrane shall be continuously supported by substrate.
8. At through-wall flashings, provide an additional 6 inch wide strip of membrane counterflashing to seal top of through-wall flashing to membrane. Seal exposed top edge of strip with bead of mastic.
9. At deflection and control joints, provide backup for the membrane to accommodate anticipated movement.
10. At expansion and seismic joints provide transition to the joint assemblies.
11. At the top of parapet walls, provide transition material over top of parapet to transition with roof membrane.
12. Do not allow materials to come into contact with chemically incompatible materials.
13. Do not expose transition membrane to sunlight longer than recommended by manufacturer.
14. Inspect installation prior to enclosing assembly and repair damaged areas with sprayed-in-place thermal insulation air barrier system.
3.04 PROTECTION
A. Do not permit installed insulation to be damaged prior to its concealment.
END OF SECTION 072100
SPRAYED-IN-PLACE THERMAL INSULATION (072100)
INSTALLER'S CERTIFICATION
072100.01 - 1
SECTION 072100.01 - SPRAYED-IN-PLACE THERMAL INSULATION (072100) INSTALLER'S
CERTIFICATION
SPRAYED-IN-PLACE THERMAL INSULATION (072100) INSTALLER'S CERTIFICATION
This certification must be completed and submitted as outlined in the Supplemental Instructions to Bidders. Failure to submit this completed certification may be cause for rejection of the bidder's proposal. Upon submittal of this form RossTarrant will verify from the ABAA website (www.airbarrier.org) the listed installers current and valid certification, at the time of bid, with the ABAA. Installers listed without current and valid ABAA certification will be rejected.
This certification must be completed and submitted within 24 hours after bids are received.
Date Submitted:________________________
Name & Address of Sprayed-In-Place Thermal Insulation Installer:
I certify that _____________________________ (Name of Sprayed-In-Place Thermal Insulation Installer) has achieved ABAA Accreditation for sprayed-in-place thermal insulation installation, and is a member with current and valid ABAA Certification.
ABAA Accreditation Number___________________________________________
I certify that _____________________________ (Name of Sprayed-In-Place Thermal Insulation Subcontractor) installers have achieved ABAA Certification for sprayed-in-place thermal insulation installation, and is a member with current and valid ABAA Certification.
ABAA Certification Numbers___________________________________________
Signed:_________________________________Title: ___________________
UP
B D F G H L N S W Y Z
KJ M
PEC
TQ R
U V X
A
D4.2 I
D4.2 F
D4.2 E D4.2
G
D4.2 N
D4.2 O
D4.2 P
D4.2 S
D4.2 T
D4.2 H
D4.2 K
D4.2 L
D4.2 U
D4.2 Y
D4.2 X
D4.2 V
D4.2 W
D4.1 A
D4.1 B
D4.1 C
D4.1 D
W-2 W-2W-1 W-1 W-1
W-1
W-1 W-1 W-1
W-1 W-1
W-1
W-2
W-2 W-2 W-2
W-2
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-2
W-1
W-1
W-1
W-1
W-1
W-1
W-1
P-3
M-2
M-8
M-3
M-3
W-1
W-1
D-1
D-1
M-5
A4.2 Q
A4.2 R
A4.2 M
D4.2 M
D4.2 R
M-7
D-1
D-1
M-6
R-2 R-2 R-2
R-2 R-2
R-2 R-2
M-8
M-8
B D F G H L N S W Y Z
KJ
PEC
TQ R
U V X
A
D4.2 I
D4.2 F
D4.2 E D4.2
G
D4.2 H
D4.2 J
D4.1 A
D4.1 B
W-1 W-1 W-1 W-1 W-1 W-1
W-1
W-1 W-1
W-1
W-2
D-1
M-8
LIVING
ROOM
BATH
134A
BED/STUDY
134C
BED/STUDY
134D
BED/STUDY
133E
BED/STUDY
133D
BED/STUDY
132C
BED/STUDY
132D
LIVING
ROOM
VENDING
MECH.
104A
LAUNDRY
OFFICE
105A
MECH.
133B
BATH
133A
TOILET
133C
TOILET
132B
BATH
132A
LIVING
ROOM
LIVING
ROOM
BED/STUDY
135D
BED/STUDY
135C
BED/STUDY
136D
BED/STUDY
136E
LIVING
ROOM
LIVING
ROOM
BED/STUDY
137D
BED/STUDY
137C
BED/STUDY
138D
BED/STUDY
138E
BATH
137A
TOILET
137B
WOMENS
MECH.
138B
ALCOVE
MONITOR
BATH
135A
TOILET
135B TOILET
136C
MECH.
136B
BATH
136A
STAIR
NO. 2
S2
CORRIDOR
117A
LINEN
102A
HOUSEKEEPING
101A
JANITOR
COAT
ROOM
107 CONVERSATION
LOBBY
LIVING
ROOM
TOILET
138C
BATH
138A
COAT
ROOM
MULTI-PURPOSE
ROOM
WAREWASHING
123LAUNDRY
VENDING
CORRIDOR
LIVING
ROOM
MECH.
MEN'S
TOILET
BED/STUDY
127D
BED/STUDY
127C
BED/STUDY
128D
BATH
127A
TOILET
127B
MECH
128B
OFFICE
105B
BED/STUDY
128E
LIVING
ROOM
BATH
128A TOILET
128C
LIVING
ROOM
BED/STUDY
129D
BED/STUDY
129C
CLOSET
129B
BATH
129A
MECH
104B
LINEN
STORAGE
102B
STAIR
NO. 3
S3
LIVING
ROOM
BED/STUDY
131E
BED/STUDY
131D
BED/STUDY
130C
BED/STUDY
130D
MECH
131B
TOILET
131C BATH
131A
LIVING
ROOM
BATH
130A
TOILET
130B
CORRIDOR
117B
HOUSEKEEPING
101B
STAIR
NO. 1
S1
CLOSET
134B
ALCOVE
STORAGE
HOLDING
BED/STUDY
011D
BED/STUDY
011C
BED/STUDY
010D
BED/STUDY
010E
STAIR
NO. 2
S2
LIVING
ROOM
BATH
011A
TOILET
011B
MECH.
010B
BATH
010A
TOILET
010C
LIVING
ROOM
LINEN
STORAGE
LIVING
ROOM
BED/STUDY
009E
LAUNDRY
BED/STUDY
009D
BED/STUDY
008C
BED/STUDY
008D
MECH.
009B
BATH
009A
TOILET
009C
LIVING
ROOM
JANITOR
BATH
008A
TOILET
008B
HOUSEKEEPING
CORRIDOR
RECREATION
ROOM
PASSAGE
STAIR
NO. 1
S1
STORAGE
MECH.
ALCOVE
HOLDING
REMOVE EXISTING WINDOW ASSEMBLY,
INCLUDING SOLID SURFACE SILL, BRICK
VENEER, AND 4" CMU BLOCK BELOW
WINDOW SILL, AS REQUIRED FOR NEW
WORK. REFER TO ARCHITECTURAL DETAILS.
GENERAL DEMOLITION NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
THESE DEMOLITION PLANS ARE MEANT TO BE A
CONVENIENCE TO THE CONTRACTOR.
CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION
NECESSARY FOR INSTALLATION OF NEW WORK
WHETHER SHOWN HERE OR NOT.
REFER TO SECTIONS AND DETAILS FOR ADDITIONAL
DEMOLITION WORK REQUIRED IN SPECIFIC AREAS
OF WORK.
CONTRACTOR SHALL VERIFY LOAD BEARING
CONDITIONS OF WALLS PRIOR TO THEIR
DEMOLITION. ANY WALL FOUND TO BE LOAD
BEARING WHICH IS NOT SO NOTED SHALL PROMPTLY
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT
PRIOR TO ITS DEMOLITION.
WHERE WALLS OR OTHER ITEMS ARE REMOVED,
CLEAN AND REPAIR FLOORS TO FLUSH CONDITION
SUITABLE TO RECEIVE FLOOR FINISH. WHERE
MASONRY WALLS EXTEND THROUGH SLAB AND REST
ON FOOTING, REMOVE BLOCK TO MINIMUM OF 4"
BELOW FINISH FLOOR. FILL FLUSH WITH CONCRETE.
PROVIDE MIN. 4" CONCRETE FILL AT ABANDONED
PIPES OR OTHER OPENINGS IN THE FLOOR SLABS
WHICH ARE EXPOSED OR CREATED BY OTHER
DEMOLITION. GRIND TO FLUSH AS RQD.
ALL CONCRETE BLOCK, AND/OR BRICK VENEER
INFILL OR PATCHES IN EXISTING MASONRY SHALL BE
TOOTHED INTO ADJACENT SOUND MASONRY IN
FULL UNITS U.N.O. PARTIAL MASONRY UNITS
ADJACENT TO OPENINGS SHALL BE REMOVED AS
RQD. TO ALLOW TOOTHING. WHERE NEW MASONRY
CONSTRUCTION JOINS EXISTING MASONRY WALLS,
REMOVE MASONRY UNITS AT CONNECTIONS AS
NECESSARY TO PERMIT TOOTHING OF NEW
CONSTRUCTION WHETHER OR NOT SUCH
DEMOLITION IS SPECIFICALLY SHOWN ON
DEMOLITION PLANS. OVER-DEMOLISH EXISTING
MASONRY UNITS TO PROVIDE FINISHED OPENING.
PROVIDE NEW MASONRY TIES AND HORIZONTAL
JOINT REINFORCING PER SPECIFICATIONS. NEW
MASONRY CONSTRUCTION SHALL PRECISELY
MATCH ADJACENT EXISTING MASONRY IN COLOR,
TEXTURE, PATTERN AND FINISH, U.N.O.
ALL HVAC GRILLES, LOUVERS, AND OTHER
MECHANICAL, ELECTRICAL, AND PLUMBING
EQUIPMENT WHICH ARE ABANDONED AND/OR
CALLED OUT TO BE REMOVED SHALL BE
COMPLETELY REMOVED. OPENINGS SHALL BE
INFILLED WITH NEW CONSTRUCTION MATCHING
EXISTING ADJACENT CONSTRUCTION. REFER TO
NOTE '1' ABOVE AND MEP DRAWINGS OF RELATED
ITEMS.
EXISTING DOORS AND FRAMES SHOWN IN WALL TO
BE DEMOLISHED SHALL BE REMOVED. PATCH AS
NOTED. REMOVE ALL OTHER MATERIALS
ASSOCIATED WITH DOOR THAT WILL NOT BE USED.
REMOVE ALL WALL MOUNTED ITEMS WHICH ARE
NOT SPECIFICALLY INDICATED TO BE REMOVED BUT
WHICH INTERFERE WITH, OR ARE NOT PART OF
FINISHED CONSTRUCTION. OTHER SALVAGED ITEMS
WHICH ARE NOT INDICATED TO BE REUSED IN THE
RENOVATION OR RETURNED TO THE OWNER MAY BE
SALVAGED BY THE CONTRACTOR AND REMOVED
FROM THE SITE.
SEE NEW WORK PLANS FOR NEW WORK TO BE
INSTALLED.
1/8" = 1'-0" D1.1
BGROUND FLOOR DEMOLITION PLAN
E G I S
DEE R
No.
T
R
COMMONWEALTH
E
K OF Y
KCUTN
CR
A
H I T E C
T
SA
RAH J. LAMERE
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SERVICES SUPPORT
DIVISION OF ENGINEERING AND CONTRACT
ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
DECA LOG #
DECA REVIEWED
FOR INTENT ONLY
DRAWING NO.
COMMONWEALTH OF KENTUCKY
101 old lafayette avenue lexington, kentucky 40502 p 859.254.4018 Copyright 2026
PHASE
DESCRIPTION OF REVISIONS
DATE1
RTA
REVISION HISTORY OF THIS DRAWING
DESCRIPTION OF REVISIONS
DATE
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
RTA DATE
DRAWING INFORMATION
D1.1
MIDDLETON HALL EXTERIOR REPAIRS
GROUND & FIRST FLOOR DEMOLITION PLANS
KENTUCKY SCHOOL FOR THE DEAF
Addendum #1 03/09/26
540-CC6C-SD67-00
540-CC6C-SD67-00
SJL, FB
HRR
01/29/2026
23025
01/14/2026
DEMOLITION NOTES
DOOR DEMOLITION NOTES:
D-1 REMOVE EXISTING DOORS, METAL FRAME AND
HARDWARE IN ITS ENTIRETY. REFER TO PLANS FOR NEW
WORK.
MISCELLANEOUS DEMOLITION:
M-1 REMOVE EXISTING BRICK VENEER, RIGID INSULATION,
AND ALL MASONRY ANCHORS IN THEIR ENTIRETY.
PREPARE EXISTING CMU SURFACE TO BE CLEAN AND
READY TO RECEIVE NEW SPRAY FOAM. EXISTING FASCIA
TO REMAIN IN PLACE.
M-2 EXISITING HANDRAIL TO REMAIN. REFER TO NEW WORK
FOR MORE INFORMATION.
M-3 EXISTING METAL PANEL SOFFIT TO REMAIN.
M-4 REMOVE EXISTING METAL PANEL AND ASSOCIATED
FRAMING IN ITS ENTIRETY.
M-5 EXISTING GUARDRAIL AND RAMP TO REAMIN.
M-6 EXISTING BRICK VENEER TO REAMIN. REFER TO NEW
WORK FOR MORE INFORMATION.
M-7 REMOVE EXISTING GUARDRAIL ITS ENTIRETY.
M-8 DEMOLISH EXISTING METAL CEILING SYSTEM, INCLUDING
PANELS AND SUPPORT FRAMING. COORDINATE WITH
NEW WORK AND ADJACENT FINISHES.
PARTITION DEMOLITION NOTES:
P-1 REMOVE PORTION OF EXISITING CMU WALL AS
REQUIRED TO ACCOMODATE NEW WINDOW OPENING.
COORDINATE WITH NEW WINDOW SIZE.
P-2 REMOVE A PORTION OF THE EXISTING CMU WALL
BETWEEN STEEL BEAMS, AS INDICATED IN THE
DRAWINGS. COORDINATE WITH NEW WORK. THIS MAY
BE A BEARING WALL; PROVIDE SHORING AND BRACING
AS REQUIRED PRIOR TO DEMOLITION.
P-3 REMOVE EXISTING MASONRY WALL IN ITS ENTIRETY.
ROOF DEMOLITION CATEGORY:
R-1 REMOVE EXISITING GUTTER AND EDGE TRIM IN ENTIRETY.
R-2 REMOVE EXISITING DOWNSPOUT IN ENTIRETY.
R-3 REMOVE PORTION OF EXISTING COPING AND
ASSOCIATED WOOD BLOCKING AS REQUIRED FOR NEW
WORK. REFER TO NEW WORK FOR ADDITIONAL
INFORMATION.
R-4 REMOVE EXISTING RAKE BOARD AND/OR METAL EDGE
TRIM IN ITS ENTIRETY.
R-5 REMOVE PORTION OF THE EXISTING PVC ROOF ASSEMBL
AS REQUIRED FOR INSTALLATION OF NEW EXTERIOR
FRAMING. COORDINATE NEW WORK WITH
ARCHITECTURAL DETAILS AND STRUCTURAL DRAWINGS.
R-6 REMOVE A PORTION OF THE EXISTING SBS ROOF
ASSEMBLY DOWN TO THE DECK AS REQUIRED FOR
INSTALLATION OF KICKERS. COORDINATE WITH
ARCHITECTURAL DETAILS AND STRUCTURAL DRAWINGS.
R-7 REMOVE EXISTING PVC ROOF MEMBRANE AS REQUIRED
TO FACILITATE REMOVAL OF EXISTING GUTTER AND
RAKE.
WINDOW DEMOLITION NOTES:
W-1 REMOVE EXISTING WINDOW/STOREFRONT AND DOOR,
INCLUDING FRAMES, GLAZING, HARDWARE, AND TRIM,
IN ITS ENTIRETY. PREPARE OPENING FOR INSTALLATION
OF NEW WINDOW/STOREFRONT SYSTEM AS SHOWN.
W-2 REMOVE EXISITING WINDOW IN ENTIRETY. MODIFY
OPENING AS REQUIRED FOR INSTALLATION OF NEW
WINDOW. COORDINATE WITH NEW WINDOW SIZE.
1/8" = 1'-0" D1.1
AFIRST FLOOR DEMOLITION PLAN
KEY PLAN
SCALE: NTS
N
A4.1 D
A4.1 C
B
G
A4.2 K
WY
A4.2 F
V
N
P
T
O
U
A4.2 L
I
A4.2 J
A4.2 E
A4.1
A4.1 A
A4.2 A4.2
A4.1 H
A4.2
A4.2
A4.2
A4.2
A4.2
A4.2 A4.2
S A4.2
X A4.2A4.2
A4.2 Q
R A4.2
M A4.2
1 1/2" = 1'-0" D1.1
CWINDOW SILL DEMOLITION DETAIL
REVISIONS
# DATE DESCRIPTION
1 03/09/26 ADDENDUM#1
UP
W D
UPUP
W D W/D W/D W/D
D W
DW DW
D W
UP
B D F G H L N S W Y Z
KJ M
PEC
TQ R
U V X
A4.1 B
RESTROOM
LINEN
STORAGE
HOUSEKEEPING
OFFICE
LAUNDRY
TOILET
105C
TOILET
102C
BATH
102D
BATH
105D
JANITOR
CLOSET
MECH.
BATH
108C
BED/STUDY
108A
BED/STUDY
108B
BATH
110D
TOILET
110C
TOILET
109C
BATH
109D
MECH.
110D-1
STAIR
SC
STAIR
SB
BED/STUDY
128A
BED/STUDY
128B
BATH
128C
MECH.
LINEN
STORAGE
OFFICE
BATH
129D
MECH.
130C-1
BATH
130C
TOILET
129C
HOUSEKEEPING
RESTROOM
MECH.
124A
BATH
121D
BATH
125D
TOILET
125C
TOILET
121C
BED/STUDY
121A
BED/STUDY
121B
MECH.
MULTI-PURPOSE
ROOM
CUST./STORAGE
118A
COMMUNITY
KITCHEN
BATHROOM
113C
MECH.
CORRIDOR
CD1-A
CORRIDOR
CD1-B LIVING
ROOM
MECH.
105D-1
BREAK
ROOM
116A
SENSORY
116B
BED/STUDY
113B
BED/STUDY
110B
BED/STUDY
109B
BED/STUDY
109A
LIVING
ROOM
BED/STUDY
113A
BED/STUDY
110A
LIVING
ROOM
LIVING
ROOM
LIVING
ROOM
BED/STUDY
105B
BED/STUDY
105A
BED/STUDY
102B
BED/STUDY
102A
LIVING
ROOM
LIVING
ROOM
LIVING
ROOM
BED/STUDY
130A
BED/STUDY
130B
BED/STUDY
129B
BED/STUDY
129A
LIVING
ROOM
LIVING
ROOM
BED/STUDY
125A
BED/STUDY
125B
LIVING
ROOM
COMMON
SPACE
CONVERSATION
117A
COAT
ROOM
COMMONS
VENDING
LOBBY
LA
ALCOVE
VESTIBULE
VA
CORRIDOR
CD1-C
STAIR
SA
A
ELEVATOR
EL
A4.1 D
B A5.1
AC
AABA
B
AAAB
B B
A
A
A
B
J
A
A
E
L
B
A4.1 C
G
B
A4.2 I
A4.2 F
A4.2 E
A4.2 G
A4.2 N
A4.2 O
A4.2 P
A4.2 S
A4.2 T
A4.2 H
A4.2 K
A4.2 L
A4.2 U
A4.2 Y
A4.2 X
A4.2 V
A4.2 W
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A1
WALL
TYPE
A1
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
B
A
A
A
A
A
A
K
B
F.
V
4'
3/ 4"
F.V
G
F
F
H
9.
A4.1 A
A A5.1
WALL
TYPE
D
099000.A
A1.1 C
A1.1 C
SIM.1
A1.1 C
SIM.
A1.1 C
SIM.
F.V.
4' - 3 1/2"
A1.2 D
A1.2 D
V A
.2
V A
.1
V A
.4
V A
.3
P
Q
A4.2 Q
A4.2 R
A4.2 M
1 1
6' - 0 5/8"
F.V.
1' - 8"
F.V.
5' - 4"
F.V.
4' - 5 7/8"
L LWALL
TYPE
B
WALL
TYPE
B
WALL
TYPE
B
WALL
TYPE
B
WALL
TYPE
B
WALL
TYPE
B
WALL
TYPE
B
WALL
TYPE
B
WALL
TYPE
B
F.V.
11 3/8"
A1.2 D
SIM
42' - 5 5/8" 13' - 2 5/8" 42' - 5 3/8" 13' - 4 3/8" 25' - 5 3/4" 50' - 2 7/8"
/8
/4
/8
/8
/4
9'
GENERAL PLAN NOTES
1.
2.
3.
4.
5.
6.
7.
8.
DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS
TAKE PRECEDENCE.
ALL DIMENSIONS ARE TO FACE OF STUDS, MASONRY
OR TO CENTERLINE OF STRUCT'L STEEL UNLESS
OTHERWISE NOTED. CONTACT ARCHITECT WITH ANY
QUESTIONS REGARDING DIMENSIONS.
MASONRY DIMENSIONS ARE ACTUAL. EXTERIOR
WALL DIMENSIONS ARE TO EXTERIOR FACE OF
VENEER.
ALL EXTERIOR WALLS ARE WALL TYPE 'A' U.N.O.
PROVIDE BULLNOSE UNITS AT ALL VERTICAL OUTSIDE
CONCRETE BLOCK CORNERS U.N.O.
REFER TO STRUCTURAL DRAWINGS FOR TYPES, SIZES,
LOCATIONS, CONNECTIONS, REINFORCEMENT AND
OTHER REQ. PERTAINING TO STRUCTURAL
COMPONENTS INDICATED.
REFER TO STRUCTURAL DRAWINGS FOR LINTEL
SCHEDULE. ALL EXTERIOR LINTELS ARE TO BE
GALVANIZED AND PAINTED.
MASONRY OPENINGS IN CMU WALLS FOR DOORS
ARE TYPICALLY LOCATED 8" FROM THE JAMB
OPENING TO THE ADJACENT WALL U.N.O.
B D F G H L N S W Y Z
KJ M
PEC
TQ R
U V X
A4.1 A
MECH.
010D-1
BATH
011D
BATH
010D
TOILET
010C
TOILET
011C
STORAGE
MECH.
007C-1
BATH
007C
TOILET
004C
BATH
004D
JANITOR
CLOSET
TRUNK
STORAGE
011A
MECHANICAL
ROOM
RECREATION
ROOM
PASSAGE
HOUSEKEEPING
BULK
STORAGE
LINEN
STORAGE
CORRIDOR
CA-001
BED/STUDY
004B
LIVING
ROOM
BED/STUDY
004A
LIVING
ROOM
BED/STUDY
010A
BED/STUDY
010B
BED/STUDY
011B
LIVING
ROOM
LIVING
ROOM
BED/STUDY
007B
ALCOVE
BED/STUDY
011A
STAIR
SC
STAIR
SA
CORRIDOR
CA-002
ELEVATOR
EL
A
BED/STUDY
007A
A4.1 D
B A5.1
A AAAA
AA
AAA
A
A4.2 I
A4.2 F
A4.2 E
A4.2 G
A4.2 H
A4.2 J
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
WALL
TYPE
A
SA
099000.A099000.A
F.
V
4'
3/ 8"
099000.A
WALL
TYPE
B
WALL
TYPE
B
J
A4.1 B
WALL
TYPE
A
074213.C
WALL
TYPE
A1
1/
2"
E G I S
DEE R
No.
T
R
COMMONWEALTH
E
K OF Y
KCUTN
CR
A
H I T E C
T
SA
RAH J. LAMERE
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SERVICES SUPPORT
DIVISION OF ENGINEERING AND CONTRACT
ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
DECA LOG #
DECA REVIEWED
FOR INTENT ONLY
DRAWING NO.
COMMONWEALTH OF KENTUCKY
101 old lafayette avenue lexington, kentucky 40502 p 859.254.4018 Copyright 2026
PHASE
DESCRIPTION OF REVISIONS
DATE1
RTA
REVISION HISTORY OF THIS DRAWING
DESCRIPTION OF REVISIONS
DATE
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
RTA DATE
DRAWING INFORMATION
A1.1
MIDDLETON HALL EXTERIOR REPAIRS
GROUND & FIRST FLOOR PLAN
KENTUCKY SCHOOL FOR THE DEAF
Addendum#1 03/09/26
540-CC6C-SD67-00
540-CALK-SD19-00
SJL, FB
HRR
01/29/2026
23025
01/14/2026
1/8" = 1'-0" A1.1
BGROUND FLOOR PLAN
1/8" = 1'-0" A1.1
AFIRST FLOOR PLAN
MATERIAL REFERENCE
074213.C Metal Wrap & Trim 099000.A Paint
KEY PLAN
SCALE: NTS
N
A4.1 D
A4.1 C
B
G
A4.2 K
WY
A4.2 F
V
N
P
T
O
U
A4.2 L
I
A4.2 J
A4.2 E
A4.1
A4.1 A
A4.2 A4.2
A4.1 H
A4.2
A4.2
A4.2
A4.2
A4.2
A4.2 A4.2
S A4.2
X A4.2A4.2
A4.2 Q
R A4.2
M A4.2
PLAN NOTES
1 INFILL EXISTING CMU WALL OPENING WITH METAL STUD
FRAMING AND GYPSUM BOARD. PAINT TO MATCH
ADJACENT WALL.
2 EXISTING HOLLOW METAL DOOR AND FRAME TO BE
PATCHED, REPAIRED, AND PAINTED. PREPARE SURFACES TO
RECEIVE NEW FINISH.
3 EXISTING STEEL ANGLES, STEP STRIPS, AND GUARDRAIL AT
LOADING DOCK TO BE CLEANED, PREPPED, AND PAINTED.
4 EXISTING EXPOSED MASONRY TO BE CLEANED, PREPPED,
AND PAINTED.
5 REPLACE ALL CRACKED, DAMAGED, OR LOOSE CMU
BELOW AND AROUND WINDOW OPENING TO ACHIEVE A
UNIFORM CMU WALL FINISH.
6 REMOVE EXISTING SOFFIT AS REQUIRED AND PROVIDE NEW
METAL SOFFIT. NEW SOFFIT TO MATCH EXISTING HEIGHT AND
ALIGN WITH ADJACENT CONDITIONS. SEE SECTION
074213.B.
1 1/2" = 1'-0" A1.1
CEXPANSION JOINT DETAIL
REVISIONS
# DATE DESCRIPTION
1 03/09/26 ADDENDUM#1
| Addendum One |
| Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings. |
| END OF ADDENDUM |
| Addendum-1 -23025 |
| 072100 -Thermal Insulation--ADD |
| 072100_01 Sprayed-In-Place Thermal Insulation _072100_ Installer's Certification- |
| 23025 - Addendum#1 drawings |
| D1.1 - GROUND & FIRST FLOOR DEMOLITION PLANS |
| A1.1 - GROUND & FIRST FLOOR PLAN |
File details come from the government source that posted it. Updated .