Addendum No One.pdf
PDF 2 MB Posted
- Solicitation number
- RFB-785-2500000304-2
- Issued by
- Lincoln County, Kentucky
About this file
This is Addendum No. 1 issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration for campground improvements at Kenlake State Park in Benton, Kentucky (RFB-151-25). The addendum modifies specifications dated November 7, 2024, revising the substantial completion time to 270 calendar days and making several technical modifications including updates to wood patio decking specifications requiring color-matched torque head fasteners and double joists at decking butt-joint locations.
The addendum includes multiple drawing sheet updates affecting wood deck details, slab recess areas, lift station requirements, and electrical power connections to campsites. Key modifications include clarifications that all wood for decks shall be treated except for composite decking, addition of 1" slab recess under sinks, requirements for existing lift station operations during transition, and updates to electrical panel schedules. The document includes detailed foundation plans, electrical site plans, and panel schedules showing power distribution to various campground facilities including RV pedestals, restrooms, cabins, and lift stations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2500000304_1_SO_FORM.PDF | ||
| Final_RFB_785_2500000304_2_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-151-25
FOR: Campground Improvements Kenlake State Park Department of Parks Benton, Kentucky
DATE: December 12, 2024
RFB-785-2500000304
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-151-25 For: Campground Improvements Kenlake State Park Department of Parks Benton, Kentucky
Kristi Sharp, Statewide Procurement Manager Division of Engineering and Contract Administration
Campground Renovation Parks – Campgrounds – Multi Park West Kenlake Campground Engineering File No. 670-CB58-CO54-04 C/S Project No. 2326D
RFB 151-25
2024.12.12
Addendum No. 01 _ The original specifications and drawings dated RTA 11/07/24 for the above referenced project are amended as noted in this Addendum.
Receipt of this Addendum shall be acknowledged by inserting its number in the space provided on the Official Bid Document for RFB 151-25
SPECIFICATIONS
1) Section 10000 – Special Conditions: Revise the Substantial Completion time to 270 calendar days.
2) Section 06 15 33 Wood Patio Decking: Revise paragraph 2.7.2 as follows: For plastic decking used as a top rail on guardrails, use color-matched torque head fasteners.
3) Section 06 15 33 Wood Patio Decking: Add paragraph 3.4.E as follows: Provide double joists at all decking butt-joint locations. Alternate butt-joint location so no two butt-joints are adjacent to each other.
DRAWINGS
4) Sheet C202 – General wood deck details clarification item: All wood for the decks shall be treated wood as noted except the decking, which shall be composite as noted and specified.
5) Sheet C207 – General wood deck details clarification item: All wood for the decks shall be treated wood as noted except the decking, which shall be composite as noted and specified.
6) S201: Added 1” slab recess area under the sinks similar to the other restroom.
7) Sheet UD101 – Existing lift station located on site shall remain operational until new lift station is installed and operational. Upon lift station becoming operational, all existing power connections to existing lift station shall be removed in their entirety. All conduit, wire, boxes, etc. shall be removed back to the source.
8) Sheet U201 – Replace sheet with revised sheet. Add power to campsite as noted.
9) Sheet U203 – Replace sheet with revised sheet. Add power to campsite as noted.
10) Sheet U205 – Replace sheet with revised sheet. Add power to campsite as noted.
11) Sheet U501 – Replace sheet with revised sheet. Update panel schedules as noted.
D
W W
D D
W
B
64'-4 5/8"
/4
15' - 3 5/8"41'-3"
/4
(9 8'
0"
W
F -1
8"
1' - 3"
CIP1
1'
8"5' - 11"
(9 8'
0"
W
F -1
5' - 11"
1'
CIP1
(9 8'
0"
W
F -1
8"
1' - 3"
(98' - 0")WF-1
8"
1'
1' - 3"
7'
/8
ML8A
(98' - 0")WF-1
CMU8
1' - 0 3/8"
5"
(98' - 0")F4.0.12
(99' - 4")P24
C1
6'
/8
ML1
ML1
(9 8'
0"
W
F -1
CMU8
CMU8
1' - 0 3/8"
7'
/8 " (98' - 0")F4.0.12
(99' - 4")P24
C1
ML8AML8A
CMU8
1' - 3"
(98' - 0")WF-1
(9 8'
0"
W
F -1
(98' - 0")WF-1
8"
8"1'
2' -5
/4
2'
-5
/4
ML8A
(9 8'
0"
W
F -1
(9 8'
0"
W
F -1
M L
B
49' - 1" 15' - 3 5/8"
FIN. FL. EL.
100'-0"
FIN. FL. EL.
100'-0"
FIN. FL. EL.
100'-0"
FIN. FL. EL.
100'-0"
F
IN
F
L E
L
RECESS SLAB 1" IN
SHADED AREAS
SHADED AREA REPRESENTS TRENCH
DRAIN - COORDINATE WITH ARCH'L AND
MEP DRAWINGS - TYP.
CMU8
(98' - 0")WF-1
(98' - 0")WF-1
NO SLAB - GRAVEL ONLY
RECESS SLAB 1" IN THESE AREAS
SHADED AREA REPRESENTS TRENCH DRAIN
COORDINATE WITH ARCH'L ADN MEP DRAWINGS - TYP.
A
D
S301
S301
S301
S301
S301
S301
S301
S301
S301
S301
S301
S301
(SIM)
1. See plan legend for slab-on-grade construction. WWF shall be adequately supported by and tied to wire slab bolsters. The use of masonry blocks to support the WWF is prohibited
2. Provide control joints (and construction joints if needed) in the slab-on-grade per the typ. Slab-on-grade joint construction detail.
Control joints shall be located at column centerlines and spaced at 12’-0” maximum in between.
3. The footings have been designed for a net allowable soil bearing pressure of 1500psf. In areas subjected to frost, the footings shall bear a minimum of 24" below finished grade. The bearing stratum of all footings shall be inspected and approved by the geotechnical engineer prior to pouring concrete.
4. The information included in the geotechnical exploration report may be used by the contractor for his general information only.
The architect and structural engineer will not be responsible for the accuracy or applicability of such data therein.
5. For information on soil condition and special soil conditions on excavation, filling, and backfilling see the geotechnical exploration report. For conditions where engineered fill is required, placement and compaction shall be overseen by the testing laboratory.
6. Place footings in the same day excavations are opened. If this is not possible, adequately protect the exposed material in the bases of the footing excavations from any detrimental change in condition such as disturbance from rain or freezing. Prevent surface runoff from entering excavations.
7. Mechanical openings through concrete walls & slabs larger than 8 inches in diameter, not shown on the structural drawings, must be approved by the engineer. Openings 8 inches in diameter or less shall have at least 1 foot clear between openings unless approved by the engineer. Coordinate the installation of sleeves with the construction of formwork & installation of reinforcing steel.
8. All openings through concrete footings, concrete foundation walls, and CMU foundation walls not shown on plan must be coordinated and approved by S.E.O.R. Coordinate the installation of sleeves with the construction formwork and installation of reinforcing steel.
9. All column piers shall be centered beneath columns and poured monolithically with the foundation walls, unless noted otherwise.
10. All spread footings shall be centered beneath the columns. All continuous wall footings shall be centered beneath the walls.
11. All reinforcement anchorages and lap splices shall meet the requirements of ACI 318-11.
12. Field bending of reinforcement is prohibited.
13. All vertical reinforcement dowels in walls and piers shall be tied to the bottom reinforcement mat of the footings. "Floating" the dowels into place during concrete placement will not be permitted.
14. Vertical flush wall pilasters shall be constructed full height in all CMU walls adjacent to all wall openings and wall intersections including corner and tee intersections. Pilasters shall be 1’-4” in length and reinforced with (2)-#5 bars in each cell unless noted otherwise.
15. All ground level, non-loadbearing cmu walls shall bear on a thickened slab whether they are noted on plan or not. See the “thickened slab-on-grade at stair / non-bearing cmu wall” for required construction of the thickened slab.
FOUNDATION NOTESFOUNDATION NOTES
STRUCTURAL WALLS LEGEND
SW1 (X'-X")
MS#
STRUC. WALL & TAG
MS = METAL STUD
RE: SCHEDULE
WS = WOOD STUD
RE: SCHEDULE
# IN TAG IS
REPRESENTATIVE OF
NOMINAL SIZE
SW1 (X'-X")
RED HIDDEN LINE
INDICATES:
• SHEAR WALL WITH
SHEATHING ON ONE
SIDE
• LOCATION OF LINE DOES
NOT INDICATE SPECIFIC
SIDE FOR SHEATHING
• RE: SCHEDULE
RED HIDDEN LINE ON BOTH
SIDES INDICATES:
• SHEAR WALL WITH
SHEATHING ON BOTH
SIDES
• RE: SCHEDULE
SHEAR WALL TYPE & LENGTH
RE: SCHEDULE
RED DOT INDICATES
HOLD-DOWN @ END
OF SHEAR WALL
RE: SCHEDULEHEADER
HEADER OVER WALL
OPENING
RE: SCHEDULE
HEADER
CMU#
LINTEL TYPE
LL = LOOSE LINTEL
RE: SCHEDULE
ML = MASONRY LINTEL
RE: SCHEDULE
SL# = STEEL LINTEL
RE: SCHEDULE
CL# = CONCRETE
LINTEL
RE: SCHEDULE
STRUC. WALL & TAG
# IN TAG IS
REPRESENTATIVE OF
NOMINAL SIZE
RE: SCHEDULE
ICF#
STRUC. WALL & TAG
# IN TAG IS
REPRESENTATIVE OF
NOMINAL SIZE
RE: SCHEDULE
LINTEL
C1
COLUMN & MARK
RE: SCHEDULE
WALL FOOTING
STEM WALL
SLAB EDGE
1'-0"
WALL FOOTING STEP & MARK
DIMENSION REPRESENTS STEP HEIGHT "D"
RE: TYP. STEPPED FOOTING DETAIL
LL
STRUCTURAL WALL
RE: WALL TYPE SCHEDULE
PILASTER
RE: PLAN NOTES & WALL SCHEDULE
LINTEL OVER WALL OPENING
LINTEL TYPE DESIGNATION
LL = LOOSE LINTEL (RE: SCHEDULE)
ML = MASONRY LINTEL (RE: SCHEDULE)
SL# = STEEL LINTEL (RE: SCHEDULE)
WALL TYPE MARK
RE: SCHEDULE
P1
F1
PIER & MARK
RE: SCHEDULE
FOUNDATION & MARK
RE: SCHEDULE
GENERAL PLAN LEGEND SLAB-ON-GRADE CONSTRUCTION
6x6-W2.9xW2.9
CENTERED IN SLAB
(FLAT SHEETS ONLY)
CAST-IN-PLACE
CONCRETE SLAB
PLASTIC VAPOR
RETARDER
COMPACTED POROUS
AGGREGATE
COMPACTED SUBGRADE
4" 4"
WWW.CLOTFELTER-SAMOKAR.COM
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE
DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
DRAWING DATE
PARKS - CAMPGROUND - MULTI PARK WEST
KENLAKE CAMPGROUND
ADDENDUM 1 12/11/24
/1
/2
:1 :1
A
M
TWD
11/7/24
TWD
FOUNDATION PLAN
S201
2326F
RTA
SCALE: 3/8" = 1'-0"1
FOUNDATION PLAN
670-CB58-CO54-04
tdavies G:\PE Stamps\Orders\2024\138336 Davies KY-Eng\138336 Davies KY-Eng Final Model (1)
E PE P
E PE P
EPEP
DP1
EPEP
EPEP
EPEP
EPEP
EPEP
EPEP
EP EP
EP EP
DP3-9,11
UGE
GFI
WP
DP1-17
DP1-1,3
DP1-2,4
DP1-5,7
DP1-6,8
UG
E
UG
E
UG
E
UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGEUG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE UGE UGE UGE UGE
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UG
E
UGE
UGE
UGE
U G
E U
G E
UGE
UGE
UGE
UG
E
UG
E
UG
E
U G
E U
G E
U G
E U
G E
U G
E
EP EP
DP3-14,16
PARTIAL ENLARGED ELECTRICAL SITE PLAN
U201
REVISION HISTORY OF THIS DRAWING
PARKS - CAMPGROUNDS - MULTI PARK WEST
KENLAKE CAMPGROUND
DRAWING NO.10/01/2024
228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE
DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
23629
RTA
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
670-CB58-CO54-06
11/07/2024
ADDENDUM 1.00 12/11/2024
NORTH
PROJECT
SCALE: 1" = 40'-0"
SITE UTILITY PLAN - KENLAKE STATE PARK
IT'S THE LAW
www.kentucky811.com
Kentucky 811 Know what's below.
Call before you dig.
Call 811 or 800-752-6007
BURIED UTILITIES NOTE
BURIED UTILITIES ARE SHOWN AT THEIR APPROXIMATE LOCATION
BASED UPON INFORMATION OBTAINED FROM UTILITY COMPANIES
AND FIELD EVIDENCE. OTHER BURIED UTILITIES MIGHT EXIST ON THE
SUBJECT SITE WHICH ARE NOT SHOWN ON THIS DRAWING. USE
EXTREME CAUTION DURING EXCAVATION PROCEDURES AND
CONTACT KENTUCKY 811 @ 811 OR 1-800-752-6007 FOR EXACT
LOCATION OF BURIED UTILITIES PRIOR TO EXCAVATION OPERATIONS.
NOTICE
SEE CIVIL PLANS FOR SITE GRADING AND ELEVATIONS.
ELECTRICAL
CONSTRUCTION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
INSTALL DISTRIBUTION PANEL ON FREE-STANDING RACK ACCORDING TO 'FREE
STANDING RACK DETAIL'. COORDINATE PLACEMENT OF PANEL WITH EXISTING
CONDITIONS TO AVOID CONFLICT. REFER TO RISER DIAGRAM FOR FURTHER
REQUIREMENTS.
INSTALL RV PEDESTAL EQUAL TO HYPOWER ENERGYMATE ALONGSIDE WATER
AND SANITARY CONNECTIONS. RV PEDESTAL SHALL BE INSTALLED NO CLOSER
THAN SIX (6) FEET FROM NEAREST WATER CONNECTION. REFER TO 'RV
PEDESTAL DETAIL' FOR FURTHER REQUIREMENTS.
ROUTE (1) 3 INCH CONDUIT CONTAINING (3) #250MCM CU CONDUCTORS AND (1) #4
THWN CU GND FROM PANEL BOARD TO RV PEDESTAL TO BE INSTALLED. CONDUIT
SHALL BE ROUTED ALONG EXTERIOR OF CAMPSITES TO AVOID CONFLICT WITHIN
CAMPGROUND. CONTRACTOR SHALL FURNISH AND INSTALL SUITABLE LUGS
WITHIN PEDESTAL FOR TERMINATION OF CABLING. CONDUIT AND WIRE SIZING
INCREASED DUE TO VOLTAGE DROP REQUIREMENTS.
ROUTE (1) 2-1/2 INCH CONDUIT CONTAINING (3) #4/0 THWN CU CONDUCTORS AND
(1) #6 THWN CU GND FROM PANEL BOARD TO RV PEDESTAL TO BE INSTALLED.
CONTRACTOR SHALL FURNISH AND INSTALL SUITABLE LUGS WITHIN PEDESTAL
FOR TERMINATION OF CABLING. CONDUIT SHALL BE ROUTED ALONG EXTERIOR
OF CAMPSITES TO AVOID CONFLICT WITHIN CAMPGROUND. CONDUIT AND WIRE
SIZING INCREASED DUE TO VOLTAGE DROP REQUIREMENTS.
5 RECEPTACLE SHALL BE INSTALLED SURFACE MOUNTED ON FREE STANDING RACK
BELOW PANEL. COORDINATE PLACEMENT OF DEVICE TO AVOID CONFLICT.
ROUTE CONDUIT AND WIRING UNDERGROUND FROM SECONDARY COMPARTMENT
OF TRANSFORMER TO PANEL TO BE INSTALLED. REFER TO RISER DIAGRAM FOR
ALL CONDUIT AND WIRE SIZING REQUIREMENTS.
INSTALL TRANSFORMER PAD ACCORDING TO UTILITY COMPANY STANDARDS AND
'TRANSFORMER PAD' DETAIL. COORDINATE ALL FINAL REQUIREMENTS WITH
LOCAL UTILITY PRIOR TO INSTALLATION.
8 REFER TO DRAWING U203 FOR CONTINUATION.
ROUTE CONDUIT WITH PULL STRING UNDERGROUND BETWEEN TRANSFORMERS
TO BE INSTALLED ON SITE. REFER TO RISER DIAGRAM FOR CONDUIT SIZE
REQUIREMENTS. CONDUIT SHALL BE INSTALLED ACCORDING TO UTILITY
COMPANY STANDARDS.
10 REFER TO DRAWING U202 FOR CONTINUATION.
ROUTE CONDUIT UNDERGROUND FROM DISTRIBUTION PANEL TO EXISTING
GUARD SHACK BUILDING LOCATED ON SITE. COORDINATE ROUTING OF CONDUIT
WITH EXISTING CONDITIONS TO AVOID CONFLICT. REFER TO RISER DIAGRAM FOR
ALL CONDUIT AND WIRING REQUIREMENTS.
12 REFER TO DRAWING U204 FOR CONTINUATION.
MRM
MRM
12/11/2024
N O
PAR
KIN
G
AN
YTIM
E
BATH HOUSE
E PE P
E PE P
EPEP
EPEP
EPEP
EPEP
DP7-10,12
DP1-9,11
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UG
E
U G
E
UG
E
U G
E
U G
E
UG
E
U G
E
UG
E
DP7-1,3
UGE
UGE
UGE
UGE
UGE
UGE
UGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGE
DP1-13,15
BB
EPEP
DP7-13,15
PARTIAL ENLARGED ELECTRICAL SITE PLAN
U203
REVISION HISTORY OF THIS DRAWING
PARKS - CAMPGROUNDS - MULTI PARK WEST
KENLAKE CAMPGROUND
DRAWING NO.10/01/2024
228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE
DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
23629
RTA
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
670-CB58-CO54-06
11/07/2024
ADDENDUM 1.00 12/11/2024
NORTH
PROJECT
SCALE: 1" = 40'-0"
SITE UTILITY PLAN - KENLAKE STATE PARK
IT'S THE LAW
www.kentucky811.com
Kentucky 811 Know what's below.
Call before you dig.
Call 811 or 800-752-6007
BURIED UTILITIES NOTE
BURIED UTILITIES ARE SHOWN AT THEIR APPROXIMATE LOCATION
BASED UPON INFORMATION OBTAINED FROM UTILITY COMPANIES
AND FIELD EVIDENCE. OTHER BURIED UTILITIES MIGHT EXIST ON THE
SUBJECT SITE WHICH ARE NOT SHOWN ON THIS DRAWING. USE
EXTREME CAUTION DURING EXCAVATION PROCEDURES AND
CONTACT KENTUCKY 811 @ 811 OR 1-800-752-6007 FOR EXACT
LOCATION OF BURIED UTILITIES PRIOR TO EXCAVATION OPERATIONS.
NOTICE
SEE CIVIL PLANS FOR SITE GRADING AND ELEVATIONS.
ELECTRICAL
CONSTRUCTION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
ROUTE CONDUIT UNDERGROUND FROM DISTRIBUTION PANEL TO EXISTING
GUARD SHACK BUILDING LOCATED ON SITE. COORDINATE ROUTING OF CONDUIT
WITH EXISTING CONDITIONS TO AVOID CONFLICT. REFER TO RISER DIAGRAM FOR
ALL CONDUIT AND WIRING REQUIREMENTS.
INSTALL RV PEDESTAL EQUAL TO HYPOWER ENERGYMATE ALONGSIDE WATER
AND SANITARY CONNECTIONS. RV PEDESTAL SHALL BE INSTALLED NO CLOSER
THAN SIX (6) FEET FROM NEAREST WATER CONNECTION. REFER TO 'RV
PEDESTAL DETAIL' FOR FURTHER REQUIREMENTS.
ROUTE CONDUIT UNDERGROUND FROM TRANSFORMER TO BATH HOUSE PANEL
TO BE INSTALLED. REFER TO RISER DIAGRAM FOR ALL CONDUIT AND WIRE SIZING
REQUIREMENTS.
ROUTE (1) 2-1/2 INCH CONDUIT CONTAINING (3) #4/0 THWN CU CONDUCTORS AND
(1) #6 THWN CU GND FROM PANEL BOARD TO RV PEDESTAL TO BE INSTALLED.
CONTRACTOR SHALL FURNISH AND INSTALL SUITABLE LUGS WITHIN PEDESTAL
FOR TERMINATION OF CABLING. CONDUIT SHALL BE ROUTED ALONG EXTERIOR
OF CAMPSITES TO AVOID CONFLICT WITHIN CAMPGROUND. CONDUIT AND WIRE
SIZING INCREASED DUE TO VOLTAGE DROP REQUIREMENTS.
CONTRACTOR SHALL INTERCEPT EXISTING CONDUIT ROUTED INTO INTERIOR OF
GUARD SHACK FOR ROUTING OF FEEDERS TO EXISTING PANEL. CONTRACTOR
SHALL FURNISH AND INSTALL ALL NECESSARY COMPONENTS AS REQUIRED TO
SEPERATE EXISTING GROUNDS AND NEUTRALS IN EXISTING PANEL AS REQUIRED
TO MAINTAIN CODE COMPLIANCE.
ROUTE (1) 1 INCH CONDUIT CONTAINING (4) #6 THWN CU CONDUCTORS FROM
PANEL BOARD TO LIGHT POLE TO BE INSTALLED. CONDUIT AND WIRE SIZING
INCREASED DUE TO VOLTAGE DROP REQUIREMENTS.
CONTRACTOR SHALL RECEIVE LIFT STATION CONTROL PANEL FROM RESPECTIVE
CONTRACTOR AND INSTALL ON FREE-STANDING RACK NEAR LIFT STATION TO BE
INSTALLED. CONTROL PANEL SHALL BE INSTALLED OUTSIDE OF CLASSIFIED AREA
AROUND LIFT STATION. REFER TO 'LIFT STATION DETAIL' FOR CLASSIFIED AREA
BOUNDS.
8 REFER TO DRAWING U201 FOR CONTINUATION.
ROUTE CONDUIT WITH PULL STRING UNDERGROUND BETWEEN TRANSFORMER
TO BE INSTALLED ON SITE AND EXISTING UTILITY POLE LOCATED ON SITE.
COORDINATE ALL FINAL CONNECTIONS AS POLE WITH UTILITY PRIOR TO
TERMINATION. REFER TO RISER DIAGRAM FOR ALL CONDUIT SIZE
REQUIREMENTS. CONDUIT SHALL BE INSTALLED ACCORDING TO UTILITY
COMPANY STANDARDS.
10 REFER TO DRAWING U204 FOR CONTINUATION.
ROUTE CONDUIT UNDERGROUND FROM LIFT STATION CONTROL PANEL TO LIFT
STATION FOR INTERCONNECTION. COORDINATE ALL CONDUIT AND WIRING
REQUIREMENTS WITH MANUFACTURER REQUIREMENTS. REFER TO 'LIFT STATION
DETAIL' FOR INSTALLATION REQUIREMENTS.
ROUTE (1) 1 1/4 INCH CONDUIT CONTAINING (4) #4 THWN CU CONDUCTORS
UNDERGROUND FROM PANELBOARD TO LIFT STATION CONTROL PANEL TO BE
INSTALLED. COORDINATE ROUTING OF CONDUIT WITH EXISTING CONDITIONS TO
AVOID CONFLICT. CONDUIT AND WIRE SIZES INCREASED DUE TO VOLTAGE DROP
REQUIREMENTS.
MRM
MRM
ALTERNATE RESTROOM
DP6
U G
E U
G E
U G
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
U G
E U
G E
U G
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
U G
E U
G E
U G
E
UGE
UGE
UGE
UGE
UGE
UG
E
UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
U
G E
U G
E U
G E
DP5
UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UG
E
UG
E
EPEP
EPEP
EPEP
EPEP
EPEP
EPEP
EPEP
EPEP
EPEP
EP EP
EPEPDP5-10,12
DP6-1,3
DP5-5,7
DP5-6,8
DP5-9,11
DP4-1,3
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE UGE UGE UGE UGE
UGE
U G
E U
G
E UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
U G
E U
G E
U G
E U
G E
U G
E U
G E
U G
E U
G E
U G
E U
G E
U G
E
UGEUGEUGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UG
E
UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGEUGE
GFI
WP 5
DP6-17
GFI
WP
DP5-13
EPEP
DP6-2,4
PARTIAL ENLARGED ELECTRICAL SITE PLAN
U205
REVISION HISTORY OF THIS DRAWING
PARKS - CAMPGROUNDS - MULTI PARK WEST
KENLAKE CAMPGROUND
DRAWING NO.10/01/2024
228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE
DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
23629
RTA
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
670-CB58-CO54-06
11/07/2024
ADDENDUM 1.00 12/11/2024
NORTH
PROJECT
SCALE: 1" = 40'-0"
SITE UTILITY PLAN - KENLAKE STATE PARK
IT'S THE LAW
www.kentucky811.com
Kentucky 811 Know what's below.
Call before you dig.
Call 811 or 800-752-6007
BURIED UTILITIES NOTE
BURIED UTILITIES ARE SHOWN AT THEIR APPROXIMATE LOCATION
BASED UPON INFORMATION OBTAINED FROM UTILITY COMPANIES
AND FIELD EVIDENCE. OTHER BURIED UTILITIES MIGHT EXIST ON THE
SUBJECT SITE WHICH ARE NOT SHOWN ON THIS DRAWING. USE
EXTREME CAUTION DURING EXCAVATION PROCEDURES AND
CONTACT KENTUCKY 811 @ 811 OR 1-800-752-6007 FOR EXACT
LOCATION OF BURIED UTILITIES PRIOR TO EXCAVATION OPERATIONS.
NOTICE
SEE CIVIL PLANS FOR SITE GRADING AND ELEVATIONS.
ELECTRICAL
CONSTRUCTION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
INSTALL DISTRIBUTION PANEL ON FREE-STANDING RACK ACCORDING TO 'FREE
STANDING RACK DETAIL'. COORDINATE PLACEMENT OF PANEL WITH EXISTING
CONDITIONS TO AVOID CONFLICT. REFER TO RISER DIAGRAM FOR FURTHER
REQUIREMENTS.
INSTALL RV PEDESTAL EQUAL TO HYPOWER ENERGYMATE ALONGSIDE WATER
AND SANITARY CONNECTIONS. RV PEDESTAL SHALL BE INSTALLED NO CLOSER
THAN SIX (6) FEET FROM NEAREST WATER CONNECTION. REFER TO 'RV
PEDESTAL DETAIL' FOR FURTHER REQUIREMENTS.
ROUTE (1) 3 INCH CONDUIT CONTAINING (3) #250MCM CU CONDUCTORS AND (1) #4
THWN CU GND FROM PANEL BOARD TO RV PEDESTAL TO BE INSTALLED. CONDUIT
SHALL BE ROUTED ALONG EXTERIOR OF CAMPSITES TO AVOID CONFLICT WITHIN
CAMPGROUND. CONTRACTOR SHALL FURNISH AND INSTALL SUITABLE LUGS
WITHIN PEDESTAL FOR TERMINATION OF CABLING. CONDUIT AND WIRE SIZING
INCREASED DUE TO VOLTAGE DROP REQUIREMENTS.
ROUTE (1) 2-1/2 INCH CONDUIT CONTAINING (3) #4/0 THWN CU CONDUCTORS AND
(1) #6 THWN CU GND FROM PANEL BOARD TO RV PEDESTAL TO BE INSTALLED.
CONTRACTOR SHALL FURNISH AND INSTALL SUITABLE LUGS WITHIN PEDESTAL
FOR TERMINATION OF CABLING. CONDUIT SHALL BE ROUTED ALONG EXTERIOR
OF CAMPSITES TO AVOID CONFLICT WITHIN CAMPGROUND. CONDUIT AND WIRE
SIZING INCREASED DUE TO VOLTAGE DROP REQUIREMENTS.
5 RECEPTACLE SHALL BE INSTALLED SURFACE MOUNTED ON FREE STANDING RACK
BELOW PANEL. COORDINATE PLACEMENT OF DEVICE TO AVOID CONFLICT.
ROUTE CONDUIT AND WIRING UNDERGROUND FROM SECONDARY COMPARTMENT
OF TRANSFORMER TO PANEL TO BE INSTALLED. REFER TO RISER DIAGRAM FOR
ALL CONDUIT AND WIRE SIZING REQUIREMENTS.
INSTALL TRANSFORMER PAD ACCORDING TO UTILITY COMPANY STANDARDS AND
'TRANSFORMER PAD' DETAIL. COORDINATE ALL FINAL REQUIREMENTS WITH
LOCAL UTILITY PRIOR TO INSTALLATION.
8 REFER TO DRAWING U204 FOR CONTINUATION.
ROUTE CONDUIT WITH PULL STRING UNDERGROUND BETWEEN TRANSFORMERS
TO BE INSTALLED ON SITE. REFER TO RISER DIAGRAM FOR CONDUIT SIZE
REQUIREMENTS. CONDUIT SHALL BE INSTALLED ACCORDING TO UTILITY
COMPANY STANDARDS.
ROUTE (1) 2 INCH CONDUIT CONTAINING (4) #1 THWN CU CONDUCTORS
UNDERGROUND FROM PANELBOARD TO BRANCH PANEL INSTALLED WITHIN
CABIN. COORDINATE ROUTING OF CONDUIT WITH EXISTING CONDITIONS TO
AVOID CONFLICT. CONDUIT AND WIRE SIZES INCREASED DUE TO VOLTAGE DROP
REQUIREMENTS.
ROUTE (1) 1 1/2 INCH CONDUIT CONTAINING (4) #4 THWN CU CONDUCTORS
UNDERGROUND FROM PANELBOARD TO BRANCH PANEL INSTALLED WITHIN
CABIN. COORDINATE ROUTING OF CONDUIT WITH EXISTING CONDITIONS TO
AVOID CONFLICT. CONDUIT AND WIRE SIZES INCREASED DUE TO VOLTAGE DROP
REQUIREMENTS.
ROUTE (1) 2 INCH CONDUIT CONTAINING (4) #4 THWN CU CONDUCTORS
UNDERGROUND FROM PANELBOARD TO BRANCH PANEL INSTALLED WITHIN
CABIN. COORDINATE ROUTING OF CONDUIT WITH EXISTING CONDITIONS TO
AVOID CONFLICT. CONDUIT AND WIRE SIZES INCREASED DUE TO VOLTAGE DROP
REQUIREMENTS.
CONTRACTOR SHALL RECEIVE LIFT STATION CONTROL PANEL FROM RESPECTIVE
CONTRACTOR AND INSTALL ON FREE-STANDING RACK NEAR LIFT STATION TO BE
INSTALLED. CONTROL PANEL SHALL BE INSTALLED OUTSIDE OF CLASSIFIED AREA
AROUND LIFT STATION. REFER TO 'LIFT STATION DETAIL' FOR CLASSIFIED AREA
BOUNDS.
ROUTE CONDUIT UNDERGROUND FROM LIFT STATION CONTROL PANEL TO LIFT
STATION FOR INTERCONNECTION. COORDINATE ALL CONDUIT AND WIRING
REQUIREMENTS WITH MANUFACTURER REQUIREMENTS. REFER TO 'LIFT STATION
DETAIL' FOR INSTALLATION REQUIREMENTS.
ROUTE (1) 1 1/4 INCH CONDUIT CONTAINING (4) #4 THWN CU CONDUCTORS
UNDERGROUND FROM PANELBOARD TO LIFT STATION CONTROL PANEL TO BE
INSTALLED. COORDINATE ROUTING OF CONDUIT WITH EXISTING CONDITIONS TO
AVOID CONFLICT. CONDUIT AND WIRE SIZES INCREASED DUE TO VOLTAGE DROP
REQUIREMENTS.
ROUTE (1) 2 INCH CONDUIT CONTAINING (3) #1/0 THWN CU CONDUCTORS AND (1)
#6 THWN CU GND UNDERGROUND FROM PANELBOARD TO BRANCH PANEL
INSTALLED WITHIN RESTROOM BUILDING. COORDINATE ROUTING OF CONDUIT
WITH EXISTING CONDITIONS TO AVOID CONFLICT. CONDUIT AND WIRE SIZES
INCREASED DUE TO VOLTAGE DROP REQUIREMENTS.
MRM
MRM
ELECTRICAL SCHEDULES
U501
REVISION HISTORY OF THIS DRAWING
PARKS - CAMPGROUNDS - MULTI PARK WEST
KENLAKE CAMPGROUND
DRAWING NO.10/01/2024
228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE
DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
23629
RTA
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
670-CB58-CO54-06
11/07/2024
ADDENDUM 1.00 12/11/2024
MRM
MRM
Electrical DP1 Schedule
VOLTS/PHASE/WIRE: PANEL SIZE: MAIN TYPE & SIZE: CABINET: MIN SCC: FED FROM:
120/208/3/4 600 A 600 A MCB SURFACE 42000 ----
CIRCUIT NO. AREA SERVED TRIP
AMPS
NO.
POLES
PHASE LOAD VA NO.
POLES
TRIP
AMPS AREA SERVED CIRCUIT NO.
A B C
1,3 CAMPSITE PEDESTAL 200 2 12848 12848 0
2 200 CAMPSITE PEDESTAL 2,412848 12848 0
5,7 CAMPSITE PEDESTAL 200 2 12848 0 12848
2 200 CAMPSITE PEDESTAL 6,812848 0 12848
9,11 CAMPSITE PEDESTAL 200 2 0 12848 12848
2 60 GUARD SHACK PANEL 10,120 4160 4160
13,15 ENTRY LIGHT POLE 20 2 50 50 0
2 20 SPARE 14,160 0 0
17 RACK RECEPTACLE 20 1 0 0 180
1 20 SPARE 180 0 0
19 SPARE 20 1 0 0 0
1 20 SPARE 200 0 0
21 SPARE 20 1 0 0 0
1 20 SPARE 220 0 0
23 SPARE 20 1 0 0 0
1 20 SPARE 240 0 0
25 BLANK 20 1 0 0 0
1 20 BLANK 260 0 0
27 BLANK 20 1 0 0 0
1 20 BLANK 280 0 0
29 BLANK 20 1 0 0 0
1 20 BLANK 300 0 0
CONNECTED LOAD 51442 42754 42884 137.1 KVA
LOAD CATEGORY CONN. LOAD DEMAND FACTOR EST. LOAD
Equipment 136.8 1.00 136.8
Lighting 0.1 1.25 0.1
Receptacles (0 - 10 KVA) 0.2 1.00 0.2
TOTAL 137.1 137.1
Electrical DP2 Schedule
VOLTS/PHASE/WIRE: PANEL SIZE: MAIN TYPE & SIZE: CABINET: MIN SCC: FED FROM:
120/208/3/4 600 A 600 A MCB SURFACE 42000 ----
CIRCUIT NO. AREA SERVED TRIP
AMPS
NO.
POLES
PHASE LOAD VA NO.
POLES
TRIP
AMPS AREA SERVED CIRCUIT NO.
A B C
1,3 CAMPSITE PEDESTAL 200 2 12848 12848 0
2 200 CAMPSITE PEDESTAL 2,412848 12848 0
5,7 CAMPSITE PEDESTAL 200 2 12848 0 12848
2 200 CAMPSITE PEDESTAL 6,812848 0 12848
9,11 CAMPSITE PEDESTAL 200 2 0 12848 12848
1 20 RACK RECEPTACLE 13180 0 0
14 SPARE 20 1 0 0 0
1 20 SPARE 150 0 0
16 SPARE 20 1 0 0 0
1 20 SPARE 170 0 0
18 SPARE 20 1 0 0 0
1 20 SPARE 190 0 0
20 SPARE 20 1 0 0 0
1 20 SPARE 210 0 0
22 SPARE 20 1 0 0 0
1 20 SPARE 230 0 0
24 SPARE 20 1 0 0 0
1 20 BLANK 250 0 0
26 BLANK 20 1 0 0 0
1 20 BLANK 270 0 0
28 BLANK 20 1 0 0 0
1 20 BLANK 290 0 0
30 BLANK 20 1 0 0 0
CONNECTED LOAD 51572 38544 38544 128.7 KVA
LOAD CATEGORY CONN. LOAD DEMAND FACTOR EST. LOAD
Equipment 128.5 1.00 128.5
Receptacles (0 - 10 KVA) 0.2 1.00 0.2
TOTAL 128.7 128.7
Electrical DP4 Schedule
VOLTS/PHASE/WIRE: PANEL SIZE: MAIN TYPE & SIZE: CABINET: MIN SCC: FED FROM:
120/208/3/4 600 A 600 A MCB SURFACE 42000 ----
CIRCUIT NO. AREA SERVED TRIP
AMPS
NO.
POLES
PHASE LOAD VA NO.
POLES
TRIP
AMPS AREA SERVED CIRCUIT NO.
A B C
1,3 CAMPSITE PEDESTAL 200 2 12848 12848 0
2 200 CAMPSITE PEDESTAL 2,412848 12848 0
5,7 CAMPSITE PEDESTAL 200 2 12848 0 12848
2 200 CAMPSITE PEDESTAL 6,812848 0 12848
9,11 CAMPSITE PEDESTAL 200 2 0 12848 12848
2 200 CAMPSITE PEDESTAL 10,120 12848 12848
13 RACK RECEPTACLE 20 1 180 0 0
1 20 SPARE 140 0 0
15 SPARE 20 1 0 0 0
1 20 SPARE 160 0 0
17 SPARE 20 1 0 0 0
1 20 SPARE 180 0 0
19 SPARE 20 1 0 0 0
1 20 SPARE 200 0 0
21 SPARE 20 1 0 0 0
1 20 SPARE 220 0 0
23 SPARE 20 1 0 0 0
1 20 SPARE 240 0 0
25 BLANK 20 1 0 0 0
1 20 BLANK 260 0 0
27 BLANK 20 1 0 0 0
1 20 BLANK 280 0 0
29 BLANK 20 1 0 0 0
1 20 BLANK 300 0 0
CONNECTED LOAD 51572 51392 51392 154.4 KVA
LOAD CATEGORY CONN. LOAD DEMAND FACTOR EST. LOAD
Equipment 154.2 1.00 154.2
Receptacles (0 - 10 KVA) 0.2 1.00 0.2
TOTAL 154.4 154.4
Electrical DP5 Schedule
VOLTS/PHASE/WIRE: PANEL SIZE: MAIN TYPE & SIZE: CABINET: MIN SCC: FED FROM:
120/208/3/4 600 A 600 A MCB SURFACE 42000 ----
CIRCUIT NO. AREA SERVED TRIP
AMPS
NO.
POLES
PHASE LOAD VA NO.
POLES
TRIP
AMPS AREA SERVED CIRCUIT NO.
A B C
1,3 CABIN PANEL 60 2 4160 4160 0
2 60 CABIN PANEL 2,44160 4160 0
5,7 CAMPSITE PEDESTAL 200 2 12848 0 12848
2 200 CAMPSITE PEDESTAL 6,812848 0 12848
9,11 CAMPSITE PEDESTAL 200 2 0 12848 12848
2 30 LIFT STATION 10,120 1825 1825
13 RACK RECEPTACLE 20 1 180 0 0
1 20 SPARE 140 0 0
15 SPARE 20 1 0 0 0
1 20 SPARE 160 0 0
17 SPARE 20 1 0 0 0
1 20 SPARE 180 0 0
19 SPARE 20 1 0 0 0
1 20 SPARE 200 0 0
21 SPARE 20 1 0 0 0
1 20 SPARE 220 0 0
23 SPARE 20 1 0 0 0
1 20 SPARE 240 0 0
25 BLANK 20 1 0 0 0
1 20 BLANK 260 0 0
27 BLANK 20 1 0 0 0
1 20 BLANK 280 0 0
29 BLANK 20 1 0 0 0
1 20 BLANK 300 0 0
CONNECTED LOAD 34196 22993 40369 97.6 KVA
LOAD CATEGORY CONN. LOAD DEMAND FACTOR EST. LOAD
Equipment 93.7 1.00 93.7
Motors 0.0 1.00 0.0
Motors (Largest) 3.6 1.25 4.6
Receptacles (0 - 10 KVA) 0.2 1.00 0.2
TOTAL 97.6 98.5
Electrical DP7 Schedule
VOLTS/PHASE/WIRE: PANEL SIZE: MAIN TYPE & SIZE: CABINET: MIN SCC: FED FROM:
120/208/3/4 600 A 600 A MCB SURFACE 42000 ----
CIRCUIT NO. AREA SERVED TRIP
AMPS
NO.
POLES
PHASE LOAD VA NO.
POLES
TRIP
AMPS AREA SERVED CIRCUIT NO.
A B C
1,3 CAMPSITE PEDESTAL 200 2 12848 12848 0
2 200 CAMPSITE PEDESTAL 2,412848 12848 0
5,7 CAMPSITE PEDESTAL 200 2 12848 0 12848
2 200 CAMPSITE PEDESTAL 6,812848 0 12848
9,11 CAMPSITE PEDESTAL 200 2 0 12848 12848
2 30 LIFT STATION 10,120 1825 1825
13,15 CAMPSITE PEDESTAL 100 2 6424 6424 0
2 60 SPARE 14,160 0 0
17 RACK RECEPTACLE 20 1 0 0 180
1 20 SPARE 180 0 0
19 SPARE 20 1 0 0 0
1 20 SPARE 200 0 0
21 SPARE 20 1 0 0 0
1 20 SPARE 220 0 0
23 SPARE 20 1 0 0 0
1 20 SPARE 240 0 0
25 SPARE 20 1 0 0 0
1 20 SPARE 260 0 0
27 SPARE 20 1 0 0 0
1 20 SPARE 280 0 0
29 SPARE 20 1 0 0 0
1 20 SPARE 300 0 0
CONNECTED LOAD 57816 46793 40549 145.2 KVA
LOAD CATEGORY CONN. LOAD DEMAND FACTOR EST. LOAD
Equipment 141.3 1.00 141.3
Motors 0.0 1.00 0.0
Motors (Largest) 3.6 1.25 4.6
Receptacles (0 - 10 KVA) 0.2 1.00 0.2
TOTAL 145.2 146.1
Electrical DP3 Schedule
VOLTS/PHASE/WIRE: PANEL SIZE: MAIN TYPE & SIZE: CABINET: MIN SCC: FED FROM:
120/208/3/4 600 A 600 A MCB SURFACE 42000 ----
CIRCUIT NO. AREA SERVED TRIP
AMPS
NO.
POLES
PHASE LOAD VA NO.
POLES
TRIP
AMPS AREA SERVED CIRCUIT NO.
A B C
1,3 CAMPSITE PEDESTAL 200 2 12848 12848 0
2 200 CAMPSITE PEDESTAL 2,412848 12848 0
5,7 CAMPSITE PEDESTAL 200 2 12848 0 12848
2 200 CAMPSITE PEDESTAL 6,812848 0 12848
9,11 CAMPSITE PEDESTAL 200 2 0 12848 12848
2 30 LIFT STATION 10,120 1825 1825
13,15 RESTROOM PANEL 60 2 4160 4160 0
2 100 CAMPSITE PEDESTAL 14,166424 6424 0
17 RACK RECEPTACLE 20 1 0 0 180
1 20 SPARE 180 0 0
19 SPARE 20 1 0 0 0
1 20 SPARE 200 0 0
21 SPARE 20 1 0 0 0
1 20 SPARE 220 0 0
23 SPARE 20 1 0 0 0
1 20 SPARE 240 0 0
25 BLANK 20 1 0 0 0
1 20 BLANK 260 0 0
27 BLANK 20 1 0 0 0
1 20 BLANK 280 0 0
29 BLANK 20 1 0 0 0
1 20 BLANK 300 0 0
CONNECTED LOAD 61976 50953 40549 153.5 KVA
LOAD CATEGORY CONN. LOAD DEMAND FACTOR EST. LOAD
Equipment 149.6 1.00 149.6
Motors 0.0 1.00 0.0
Motors (Largest) 3.6 1.25 4.6
Receptacles (0 - 10 KVA) 0.2 1.00 0.2
TOTAL 153.5 154.4
Electrical DP6 Schedule
VOLTS/PHASE/WIRE: PANEL SIZE: MAIN TYPE & SIZE: CABINET: MIN SCC: FED FROM:
120/208/3/4 600 A 600 A MCB SURFACE 42000 ----
CIRCUIT NO. AREA SERVED TRIP
AMPS
NO.
POLES
PHASE LOAD VA NO.
POLES
TRIP
AMPS AREA SERVED CIRCUIT NO.
A B C
1,3 CAMPSITE PEDESTAL 200 2 12848 12848 0
2 100 CAMPSITE PEDESTAL 2,46424 6424 0
5,7 CABIN PANEL 60 2 4160 0 4160
2 60 CABIN PANEL 6,84160 0 4160
9,11 CABIN PANEL 60 2 0 4160 4160
2 60 CABIN PANEL 10,120 4160 4160
13,15 RESTROOM BUILDING PANEL 60 2 4160 4160 0
2 20 SPARE 14,160 0 0
17 RACK RECEPTACLE 20 1 0 0 180
1 20 SPARE 180 0 0
19 SPARE 20 1 0 0 0
1 20 SPARE 200 0 0
21 SPARE 20 1 0 0 0
1 20 SPARE 220 0 0
23 SPARE 20 1 0 0 0
1 20 SPARE 240 0 0
25 BLANK 20 1 0 0 0
1 20 BLANK 260 0 0
27 BLANK 20 1 0 0 0
1 20 BLANK 280 0 0
29 BLANK 20 1 0 0 0
1 20 BLANK 300 0 0
CONNECTED LOAD 31752 31752 16820 80.3 KVA
LOAD CATEGORY CONN. LOAD DEMAND FACTOR EST. LOAD
Equipment 80.1 1.00 80.1
Receptacles (0 - 10 KVA) 0.2 1.00 0.2
TOTAL 80.3 80.3
| Addendum No One.pdf |
| Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings. |
| END OF ADDENDUM |
Addendum 01 RFB-151-25.pdf