Addendum No 1.pdf
PDF 476 KB Posted
- Solicitation number
- RFB 785 2500000650 2
- Issued by
- Lincoln County, Kentucky
About this file
This Addendum No. 1 is issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, pertaining to Invitation to Bid No. RFB-238-25 for flooring and lighting upgrades at the Weber Building, a Department for Juvenile Justice facility located in Madison County, Kentucky. The project involves furnishing and installing comprehensive electrical and lighting work, including LED lighting fixtures of various types (grid troffers, downlights, exit signs, wall packs, and high-bay fixtures), new air-powered switch controls, wiring devices, conduit systems, and associated electrical infrastructure. The addendum revises the bid due date to May 19, 2025 at 1:30 PM ET and includes substantial modifications to the lighting design, specifically revising the Second Floor Lighting Plan (Drawing E220) with updated lighting layouts for sixteen offices and introducing a new light fixture type (LF-P) to the Luminaire Schedule (Drawing E801). The contractor is responsible for providing ceiling tiles for the new ceiling configuration and removing all demolished material from the project site.
The specifications require all materials to meet Underwriters' Laboratories standards and comply with the National Electrical Code and applicable state and local regulations. All permits and inspection costs are the contractor's responsibility. Lighting fixtures specified include products from manufacturers such as Lithonia with approved equals from Williams, Daybrite, Columbia, Metalux, and other suppliers, all featuring LED technology with 4000 Kelvin color temperature, dimmable drivers, occupancy sensors where noted, and warranties ranging from five to ten years. The contractor must coordinate with subcontractors to resolve any installation conflicts between trades, with no additional compensation provided for such corrections. Shop drawing review by the owner will determine final switch cover color selection.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2500000650_1_SO_FORM.PDF | ||
| Final_RFB_785_2500000650_2_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-238-25
FOR: DOCJT - Weber Building Flooring and Lighting Upgrades Department for Juvenile Justice Madison County, Kentucky
DATE: May 12, 2025
RFB-785-2500000650
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Change bid due date to May 19, 2025 at 1:30 PM ET. All other bid opening information will remain the same.
Item 2: Refer to attachments for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-238-25 For: DOCJT - Weber Building Flooring and Lighting Upgrades Department for Juvenile Justice Madison County, Kentucky
Kristi Sharp, Statewide Procurement Manager Division of Engineering and Contract Administration
RFB-238-25 DOCJT - Weber Building Flooring and Lighting
Addendum Number 1
General Items
1. Owner to choose switch cover color during the shop drawing review.
2. Contractor to provide ceiling tile for new ceiling configuration.
3. Contractor to remove all demolished material from project.
Drawing items:
1. Drawing E220: Second Floor Lighting Plan – Replace with attached, revised sheet E220 drawing.
a. Revise lighting layout in offices 203, 204, 205, 206, 207, 208, 210, 211, 212, 213, 214, 215, 228, 229, 230, and 231.
1. Drawing E801: Luminaire Schedule - Replace with attached, revised sheet E801 drawing.
a. Add new light fixture LF-P.
A
C BDEFGHJKL
R10
R9
R8
R7
R6
R1
R2
R3
R4
R5
228216203
225224223
LF-K LF-K LF-K
LF-KLF-KLF-K
LF-K LF-K LF-K
LF-KLF-KLF-K
LF-K LF-K LF-K
LF-KLF-KLF-K
LF-K
LF-K
LF-KLF-KLF-K
LF-K
LF-K
LF-K
LF-K
LF-K
LF-KLF-KLF-K
LF-K LF-K
LF-B LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-B
LF-E
LF-E
LF-E
LF-E
LF-B LF-B
LF-D LF-D LF-D LF-D
LF-A LF-A LF-A
LF-ALF-ALF-A
LF-A LF-A LF-A
LF-ALF-ALF-A
LF-C
LF-C
LF-C
LF-A
LF-A
LF-A LF-A
LF-A
LF-A
LF-ALF-A
LF-A
LF-ALF-A
LF-A
LF-D
LF-D
LF-A
LF-A LF-A
LF-A
LF-A
LF-A
LF-A
LF-A
LF-A
LF-A
LF-A
LF-A
LF-C LF-C LF-C
LF-D
LF-D LF-D
LF-D
LF-D
LF-H
LF-A LF-A
LF-A LF-A
LF-A
LF-A LF-A
LF-A
LF-ALF-ALF-ALF-A
LF-A LF-A LF-A LF-A
LF-L
LF-L
LF-L
LF-L LF-L
LF-LLF-L
LF-L LF-L
LF-A LF-A LF-A
LF-ALF-ALF-A
a b baa a a a aa a b b b bb bb a b
LF-D
LF-D
4 4
LF-P
LF-P
LF-P
LF-P
LF-P
LF-P LF-P
LF-P
LF-P
LF-P LF-P
LF-P
LF-PLF-P
LF-P LF-P
LF-PLF-P
LF-P LF-P
LF-P
LF-PLF-P
LF-P
LF-P
LF-P LF-P
LF-P
LF-PLF-P
LF-P
LF-P
LF-P
LF-P
LF-P LF-P
LF-P
LF-PLF-P
LF-P
LF-P
LF-P LF-P
LF-P
LF-P
LF-P
LF-P
LF-P
LF-P
LF-P LF-P
LF-P
LF-PLF-P
LF-P LF-P
LF-PLF-P
LF-P LF-P
LF-PLF-P
LF-P
LF-P
NOTE:
IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES.
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCEAND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.
C E N ENFO
SE
ENOIS AL
GN
I
E
AT
P R
S
T K
E
CARTER
GREGORY G.
14715
L I S
D RE
Y
EFO K
C
TN
U
REVISION HISTORY OF THIS DRAWING
DECA LOG #
DRAWN BY
AS BULT DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
CHECKED BY
PHASE
RTA DATE
DRAWING DATE
A & E FILE NO.
DRAWING INFORMATION
DRAWING NO.
ENGR. FILE NO.
2025/03/17
/9
/2
:1
:0
A
M
E220
SECOND FLOOR LIGHTING PLAN
525-CB82-CJ47-00
RECORD DWG. DATE
DOCJT - WEBER BUILDING FLOORING AND LIGHTING UPGRADES
4449 KIT CARSON DRIVE
2025|03|17
22-0751.00
GGC
WTG
C
0 2' 4'1' 3/32" = 1'-0"E220
1 SECOND FLOOR LIGHTING PLAN
CODED NOTES:
1 PROVIDE NEW nLight AIR LINE POWERED SWITCH SERIES RPODL DX ON/OFF + RAISE/LOWER
CONTROL WITH A TWO GANG SINGLE OPENING SWITCH PLATE.
2 PROVIDE TWO NEW nLight AIR LINE POWERED SWITCH SERIES RPODL DX ON/OFF +
RAISE/LOWER CONTROL WITH A THREE GANG DOUBLE OPENING SWITCH PLATE.
3 CONNECT TO EXISTING SWITCH AS REQUIRED.
4 RECONNECT TO EMERGENCY POWER.
2 ADDENDUM 1 05/09/25
C E N ENFO
SE
ENOIS AL
GN
I
E
AT
P R
S
T K
E
CARTER
GREGORY G.
14715
L I S
D RE
Y
EFO K
C
TN
U
REVISION HISTORY OF THIS DRAWING
DECA LOG #
DRAWN BY
AS BULT DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
CHECKED BY
PHASE
RTA DATE
DRAWING DATE
A & E FILE NO.
DRAWING INFORMATION
DRAWING NO.
ENGR. FILE NO.
2025/03/17
/9
/2
:2
:0
A
M
E801
LUMINAIRE SCHEDULES
525-CB82-CJ47-00
RECORD DWG. DATE
DOCJT - WEBER BUILDING FLOORING AND LIGHTING UPGRADES
4449 KIT CARSON DRIVE
2025|03|17
22-0751.00
GGC
WTG
C
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER CATALOG SERIES
LF-A 2 X 4 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, [INTEGRATED DUAL TECHNOLOGY OCCUPANCY SENSOR], WIRELESS CONTROL, L90 RATED LIFE OF 60,000 HOURS, DLC
QUALIFIED, AND FIVE YEAR LITED FIXTURE WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
WILLIAMS, DAYBRITE
2STAK 2X4 6000LM 80CRI 40K SERIES
LF-B 2 X 4 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, INTEGRATED DUAL TECHNOLOGY OCCUPANCY SENSOR, L90 RATED LIFE OF 60,000 HOURS, DLC QUALIFIED, AND FIVE YEAR
LITED FIXTURE WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
COLUMBIA, METALUX, DAYBRITE
2STAK 2X4 6000LM 80CRI 40K SERIES
LF-C RECESSED 2X4 LED GRID TROFFER WITH DIRECT-LIT TRANSLUCENT ACRYLIC DIFFUSER, DUST PROOF IP5X RATED OPTICS, 8000 DELIVERED LUMENS, 4000K 80 CRI LED ARRAY, L80 LIFE OF 60,000 HOURS, INTERGRATED OCCSENSOR, 100-1% DIMMABLE DRIVER, MADE IN USA, CSA LISTED FOR DAMP LOCATIONS, AND FIVE YEAR WARRANTY.
LITHONIA, OR APPROVE EQUAL BY WILLIAMS,
LEDALITE
CPX 2X4 HRG 4000LM 80CRI SERIES
LF-D RECESSED 6" LED DOWNLIGHT WITH 1500 LUMEN OUTPUT SELF-FLANGED ALZAK LOWER REFLECTOR, 55 DEGREE CUTOFF, GALVENIZED STEEL MOUNTING FRAME, ADJUSTABLE 16-GAUGE GALVANIZED STEEL MOUNTING BARS WITH CONTINUOUS 4" VERTICAL ADJUSTMENT FROM BELOW CEILING, 4000K LED LIGHT ENGINE, THERMALLY PROTECTED SOLID-STATE 0-10V DIMMING DRIVER, RATED SYSTEM LIFE OF 50,000 HOURS AT 70% OUTPUT, MAXIMUM 40 DEGREE CELCIUS OPERATING TEMPERATURE, ENERGY STAR CERTIFIED, AND 5-YEAR LIMITED WARRANTY. INTEGRATED OCCSENSOR.
LITHONIA, OR APPROVED EQUAL OMEGA,
PATHWAY
LDN6 40/15 LO6 AR LSS MVOLT
LF-E UNIVERSAL MOUNTED STENCIL FACE SELF DIAGNOSTIC LED EXIT SIGN WITH DIE-CAST ALUMINUM HOUSING, SINGLE OR DUAL CAST ALUMINUM HINGED FACEPLATE, WHITE FINISHED HOUSING, LOW ENERGY CONSUMPTION LONG-LIFE LED
LAMPS, UL LABEL, AND FIVE YEAR TOTAL FIXTURE WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
SURELITES, DUALITE
LESW 1R OR 2R 120/277
LF-F PENDANT MOUNTED LED WITH 20 GAUGE STEEL HOUSING, STEEL REFLECTORS, HIGH GLOSS BAKED WHITE ENAMEL FINISH, WIDE DIFFUSE ACRYLIC LENS, HIGH OUTPUT LEDS ON TWO LAYER CIRCUIT BOARD, ELECTRONIC LED DRIVER, 3000 DELIVERED LUMENS, 80 CRI, 85% OUTPUT AT 44,000 HOURS, CSA LISTED FOR DAMP LOCATIONS, AND FIVE YEAR LIMITED
WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
WILLIAMS, COLUMBIA
ZL1F L48 5000LM MDD MVOLT 40K 80CRI HC36 SERIES
LF-G 4’-0” LED WALL MOUNTED BRACKET WITH COLD ROLLED STEEL HOUSING, DIE CAST END CAPS, CRESENT SHAPED IMPACT MODIFIED LINEAR FACETED ACRYLIC DIFFUSER, HIGH EFFICIENCY INTEGRAL LED DRIVER, 4000 DELIVERED LUMENS FROM
LED ARRAY, L80 OF 50,000 HOURS, AND FIVE YEAR LIMITED WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
WILLIAMS, PHILIPS
WL4 40L LP840
LF-H SURFACE MOUNTED 2 X 4 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, STEEL SURFACE MOUNTING KIT, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS, DLC QUALIFIED, AND FIVE YEAR LIMITED FIXTURE WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
WILLIAMS, DAYBRITE
2STAK 2X4 6000LM 80CRI 40K SERIES
LF-J 1X4 RECESSED, EDGE-LIT FLAT PANEL, EXTRUDED ALUMINUM AND NARROW FRAME WITH MATTE WHITE FINISH. LITHONIA, OR APPROVED EQUAL BY
COLUMBIA, METALUX, DAYBRITE
EPANL-1X4-3000-80CRI-40K SERIES
LF-K LED HIGHBAY WITH 15” DIAMETER HOUSING, CAST ALUMINUM FINNED DRIVER HOUSING, 18,000 DELIVERED LUMENS, 4000K 80CRI LED ARRAY, IK10 RATED POLYCARBONATE PRISMATIC LENS, 0-10 VOLT 100-10% DIMMABLE LED DRIVER, 55 DEGREE C RATING, LUMEN MAINTENANCE L81 AT 80,000 HOURS, UL LISTING FOR DAMP LOCATION, SUITABLE FOR USE IN AMBIENT
TEMPERATURES FROM -40°C UP TO 55°C, AND 5 YEAR LIMITED WARRANTY.
LITHONIA, OR APPROVED EQUAL BY GE,
HOLOPHANE
CPRB 18000LM MVOLT 40K PM
LF-L 2X2 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, INTEGRATED DUAL TECHNOLOGY OCCUPANCY SENSOR, WIRELESS CONTROL, L90 RATED LIFE OF 60,000 HOURS, DLC
QUALIFIED, AND FIVE YEAR LITED FIXTURE WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
COLUMBIA, METALUX, DAYBRITE
2STAK 2X2 5000LM 80CRI 40K SERIES
LF-M 4'-0" PENDANT MOUNTED INDUSTRIAL WITH IMPACT-RESISTANT FIBERGLASS HOUSING, UL LISTING FOR WET LOCATION, FROSTED ACRYLIC DIFFUSER SECURED TO FULLY GASKETED HOUSING BY STAINLESS STEEL CAPTIVE LATCHES, MULTI VOLT HIGH EFFICIENCY LED DRIVER, INTEGRAL SURGE SUPPRESSION, THERMAL PROTECTION CIRCUIT, 6000 DELIVERED LUMEN LED ARRAY, L80 OF 60,000 HOURS, IP65 RATING, AND FIVE YEAR LIMITED WARRATNY.
LITHONIA, OR APPROVED EQUAL BY KENALL,
DAYBRITE
CVST L48 6000 SERIES
LF-N LED WALL PACK WITH 11.5” WIDE X 7” DEEP X 9” TALL ONE PIECE DIE CAST ALUMINUM HOUSING, REGRESSED LED OPTICAL DELIVERING 2,00 LUMENS, VISUAL COMFORT FORWARD THROW DISTRIBUTION, L91 OF 100,00 HOURS, ELECTRONIC DRIVER, 6KV SURGE PROTECTION, IP66 RATING, CSA LISTED FOR WET LOCATIONS, INTEGRAL PHOTCELL, BI-LEVEL
SWITCHING MOTION SENSOR, AND FIVE YEAR WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
GARGCO, KIM
WDGE1 LED P2 40K 80CRI VF MVOLT PIR1FC3V
LF-P 2 X 2 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 3000 DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS, DLC QUALIFIED, AND FIVE YEAR LIMITED FIXTURE WARRANTY.
LITHONIA, OR APPROVED EQUAL BY
WILLIAMS, DAYBRITE
2STAK 2X4 3000LM 80CRI 40K COL MIN1 ZT MVOLT SERIES
ELECTRICAL SPECIFICATIONS
SCOPE -- FURNISH AND INSTALL ALL WIRING DEVICES AND EQUIPMENT, ETC., UNLESS OTHERWISE INDICATED, FOR THE COMPLETE ELECTRICAL SYSTEMS. IT IS THE INTENT THAT THE ENTIRE ELECTRICAL WORK AND ALL ELECTRICAL SYSTEMS SHALL BE COMPLETE IN EVERY RESPECT AND THAT ALL OUTLETS, RECEPTACLES, FIXTURES, MOTORS, EQUIPMENT, DEVICES, ETC., SHOWN, NOTED OR REQUIRED SHALL
BE COMPLETELY CONNECTED FROM SOURCE OF POWER TO FINAL CONNECTION, READY FOR
SATISFACTORY OPERATION.
PERMITS, CODES AND APPROVALS
PERMITS -- ALL PERMITS NECESSARY FOR THE COMPLETE ELECTRICAL SYSTEMS SHALL BE OBTAINED BY THE CONTRACTOR FOR DIVISION 26 FROM THE AUTHORITIES GOVERNING SUCH WORK. THE COST OF
ALL PERMITS SHALL BE BORNE BY THIS CONTRACTOR.
CODES AND RULES AND REGULATIONS -- THE MINIMUM STANDARD FOR ALL ELECTRICAL WORK SHALL BE THE LATEST REVISION OF THE NATIONAL ELECTRICAL CODE. WHENEVER AND WHEREVER STATE AND/OR LOCAL LAWS AND/OR REGULATIONS REQUIRE A HIGHER STANDARD THAN THE CURRENT NATIONAL
ELECTRICAL CODE, THEN THESE LAWS AND/OR REGULATIONS SHALL BE FOLLOWED.
APPROVALS
ALL WORK MUST BE APPROVED BY THE ARCHITECT AND THE OWNER BEFORE FINAL PAYMENT WILL BE
MADE.
THE CONTRACTOR FOR DIVISION 26 SHALL FURNISH ELECTRICAL INSPECTION BY THE INSPECTION AGENCY HAVING JURISDICTION. THE ELECTRICAL INSPECTOR SHALL BE NOTIFIED IN WRITING IMMEDIATELY UPON THE START OF THE WORK AND A COPY OF THE NOTICE SHALL BE SENT TO THE ARCHITECT. ALL COSTS INCIDENTAL TO THE ELECTRICAL INSPECTION SHALL BE BORNE BY THE
ELECTRICAL CONTRACTOR.
MATERIALS AND APPLIANCES FOR THE TYPE FOR WHICH THERE ARE UNDERWRITERS' LABORATORIES
STANDARD REQUIREMENTS LISTINGS AND LABELS, SHALL HAVE LISTING OF UNDERWRITERS'
LABORATORIES AND SHALL BE SO LABELLED, OR SHALL CONFORM TO THEIR REQUIREMENTS, IN WHICH CASE CERTIFIED STATEMENTS TO THAT EFFECT SHALL BE FURNISHED BY THE MANUFACTURER WITH A COPY OF AN EXAMINATION REPORT BY A RECOGNIZED TESTING LABORATORY ACCEPTABLE TO THE
ARCHITECT.
DEMOLITION -- IN GENERAL, REMOVE EXISTING WORK INDICATED. THE DRAWINGS SHOW
EXISTING WORK TO THE EXTENT POSSIBLE. HOWEVER, ALL EXISTING WORK MAY NOT BE
SHOWN ON THE DRAWINGS. REMOVE OR RELOCATE EXISTING MECHANICAL AND ELECTRICAL WORK THAT INTERFERES WITH NEW WORK EVEN IF IT IS NOT SHOWN ON THE DRAWINGS. RELOCATE EXISTING
WORK THAT MUST REMAIN IN SERVICE EVEN IF IT IS NOT SHOWN ON THE DRAWINGS.
GROUNDING
ALL METALLIC CONDUIT, CABINETS, EQUIPMENT AND NEUTRAL CONDUCTORS OF THE WIRING SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH THE LATEST ISSUE OF THE NATIONAL ELECTRICAL CODE. IN ADDITION TO THE GROUNDING REQUIRED BY CODE, ALL FEEDERS AND BRANCH CIRCUITS SHALL
CONTAIN A CODE SIZE GROUND WIRE.
CONDUIT AND WIRING
ALL MATERIAL SHALL BE NEW AND SHALL BE LISTED BY THE UNDERWRITERS' LABORATORIES, INC., AS
CONFORMING TO ITS STANDARDS.
FURNISH AND INSTALL ALL OUTLET BOXES, AND JUNCTION BOXES. CEILING OUTLET BOXES SHALL BE CODE GAUGE GALVANIZED STEEL, 4 INCH OCTAGON BOXES, 1-1/2 INCH DEEP MINIMUM, LARGER WHERE REQUIRED. SWITCH AND RECEPTACLE OUTLET BOXES CONCEALED IN WALLS SHALL BE SWITCH UTILITY
OR GANG BOXES.
ALL WIRING SHALL BE INSTALLED IN CONDUIT UNLESS NOTED OTHERWISE. CONDUIT SHALL BE GALVANIZED STEEL ELECTRICAL METALLIC TUBING. SUPPORT CONDUIT PER N.E.C. EMT COUPLING AND
BOX CONNECTORS SHALL BE SET SCREW TYPE AS MANUFACTURED BY STEEL CITY.
FLEXIBLE CONDUIT SHALL BE 1/2" FLEXIBLE METAL CONDUIT IN LENGTHS NOT EXCEEDING SIX FEET FOR CONNECTING LIGHTING FIXTURES. FLEXIBLE CONDUIT MAY ALSO BE USED FOR INSTALLATION OF NEW
DEVICES IN EXISTING PLASTER WALLS.
CONDUCTORS SHALL BE COPPER AND INSULATION SHALL BE THHN. MINIMUM SIZE FOR POWER AND
LIGHTING CIRCUITS SHALL BE #12. MINIMUM INSULATION RATING SHALL BE 600 VOLTS.
WIRING CONNECTORS SHALL BE "WIRE NUT" AS MANUFACTURED BY MINNESOTA MINING AND
MANUFACTURING COMPANY FOR #8 AND SMALLER WIRE.
SECTION 16500 - LIGHTING FIXTURES
GENERAL
THE CONTRACTOR UNDER THIS DIVISION SHALL FURNISH AND INSTALL THE FOLLOWING TYPE LIGHTING
FIXTURES, COMPLETE WITH LAMPS, AS SHOWN ON THE DRAWINGS. FIXTURES OF OTHER
MANUFACTURERS, BUT OF THE SAME STYLE AND OF EQUAL QUALITY, WILL BE ACCEPTABLE UPON
APPROVAL OF THE ARCHITECT/ENGINEER.
THE FOLLOWING INFORMATION SHALL BE FURNISHED TO THE ARCHITECT, WITHIN THIRTY (30) DAYS
AFTER THE DATE OF THE CONTRACT, FOR EACH PROPOSED SUBSTITUTE FIXTURE:
NAME OF MANUFACTURER
CATALOG NUMBER
FIXTURE DRAWINGS SHOWING METAL GAUGES AND FINISH
PHOTOMETRIC DISTRIBUTION CURVES
2 ADDENDUM 1 05/09/25
| Addendum No 1.pdf |
| Item 1: Change bid due date to May 19, 2025 at 1:30 PM ET. All other bid opening information will remain the same. |
| Item 2: Refer to attachments for all additions, deletions, and/or changes to specifications and/or drawings. |
| END OF ADDENDUM |
Addendum 1 (6).pdf