This document is Addendum No. 1 for Invitation to Bid No. RFB-238-25, issued by the Commonwealth of Kentucky's Department for Facilities and Support Services, Division of Engineering and Contract Administration for the Department of Juvenile Justice. The project involves flooring and lighting upgrades at the Weber Building located in Madison County, Kentucky. The addendum changes the bid due date to May 19, 2025 at 1:30 PM ET and provides modifications to the project specifications. Key changes include owner selection of switch cover color, contractor provision of ceiling tiles for new configurations, and complete removal of demolished materials from the project site.

The addendum also details specific drawing revisions for the Second Floor Lighting Plan (Drawing E220) and Luminaire Schedule (Drawing E801). These revisions include adjusting lighting layouts in multiple offices (rooms 203-215, 228-231) and adding a new light fixture type (LF-P). The lighting fixtures will be LED troffers with various specifications, including deep steel housing, integral dimmable drivers, occupancy sensors, and warranties from manufacturers like Lithonia. The project appears to be a comprehensive electrical and interior upgrade for the juvenile justice facility, with detailed technical requirements for lighting, wiring, and installation standards.

View the file

Other files

File Type Posted
Final_RFB_785_2500000650_1_SO_FORM.PDF PDF
Final_RFB_785_2500000650_2_SO_FORM.PDF PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-238-25

FOR: DOCJT - Weber Building Flooring and Lighting Upgrades Department for Juvenile Justice Madison County, Kentucky

DATE: May 12, 2025

RFB-785-2500000650

ADDENDUM NO. One (1)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Change bid due date to May 19, 2025 at 1:30 PM ET. All other bid opening information will remain the same.

Item 2: Refer to attachments for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-238-25 For: DOCJT - Weber Building Flooring and Lighting Upgrades Department for Juvenile Justice Madison County, Kentucky

Kristi Sharp, Statewide Procurement Manager Division of Engineering and Contract Administration

RFB-238-25 DOCJT - Weber Building Flooring and Lighting

Addendum Number 1

General Items

1. Owner to choose switch cover color during the shop drawing review.

2. Contractor to provide ceiling tile for new ceiling configuration.

3. Contractor to remove all demolished material from project.

Drawing items:

1. Drawing E220: Second Floor Lighting Plan – Replace with attached, revised sheet E220 drawing.

a. Revise lighting layout in offices 203, 204, 205, 206, 207, 208, 210, 211, 212, 213, 214, 215, 228, 229, 230, and 231.

1. Drawing E801: Luminaire Schedule - Replace with attached, revised sheet E801 drawing.

a. Add new light fixture LF-P.

A

C BDEFGHJKL

R10

R9

R8

R7

R6

R1

R2

R3

R4

R5

228216203

225224223

LF-K LF-K LF-K

LF-KLF-KLF-K

LF-K LF-K LF-K

LF-KLF-KLF-K

LF-K LF-K LF-K

LF-KLF-KLF-K

LF-K

LF-K

LF-KLF-KLF-K

LF-K

LF-K

LF-K

LF-K

LF-K

LF-KLF-KLF-K

LF-K LF-K

LF-B LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-B

LF-E

LF-E

LF-E

LF-E

LF-B LF-B

LF-D LF-D LF-D LF-D

LF-A LF-A LF-A

LF-ALF-ALF-A

LF-A LF-A LF-A

LF-ALF-ALF-A

LF-C

LF-C

LF-C

LF-A

LF-A

LF-A LF-A

LF-A

LF-A

LF-ALF-A

LF-A

LF-ALF-A

LF-A

LF-D

LF-D

LF-A

LF-A LF-A

LF-A

LF-A

LF-A

LF-A

LF-A

LF-A

LF-A

LF-A

LF-A

LF-C LF-C LF-C

LF-D

LF-D LF-D

LF-D

LF-D

LF-H

LF-A LF-A

LF-A LF-A

LF-A

LF-A LF-A

LF-A

LF-ALF-ALF-ALF-A

LF-A LF-A LF-A LF-A

LF-L

LF-L

LF-L

LF-L LF-L

LF-LLF-L

LF-L LF-L

LF-A LF-A LF-A

LF-ALF-ALF-A

a b baa a a a aa a b b b bb bb a b

LF-D

LF-D

4 4

LF-P

LF-P

LF-P

LF-P

LF-P

LF-P LF-P

LF-P

LF-P

LF-P LF-P

LF-P

LF-PLF-P

LF-P LF-P

LF-PLF-P

LF-P LF-P

LF-P

LF-PLF-P

LF-P

LF-P

LF-P LF-P

LF-P

LF-PLF-P

LF-P

LF-P

LF-P

LF-P

LF-P LF-P

LF-P

LF-PLF-P

LF-P

LF-P

LF-P LF-P

LF-P

LF-P

LF-P

LF-P

LF-P

LF-P

LF-P LF-P

LF-P

LF-PLF-P

LF-P LF-P

LF-PLF-P

LF-P LF-P

LF-PLF-P

LF-P

LF-P

NOTE:

IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, AND DUCTS REQUIRED FOR INSTALLATION OF THE WORK. DETAILS AND SECTIONS ARE INCLUDED FOR SOME AREAS TO SHOW INTENDED RELATIONSHIP OF THE WORK OF VARIOUS TRADES.

IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCEAND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.

C E N ENFO

SE

ENOIS AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

2025/03/17

/9

/2

:1

:0

A

M

E220

SECOND FLOOR LIGHTING PLAN

525-CB82-CJ47-00

RECORD DWG. DATE

DOCJT - WEBER BUILDING FLOORING AND LIGHTING UPGRADES

4449 KIT CARSON DRIVE

2025|03|17

22-0751.00

GGC

WTG

C

0 2' 4'1' 3/32" = 1'-0"E220

1 SECOND FLOOR LIGHTING PLAN

CODED NOTES:

1 PROVIDE NEW nLight AIR LINE POWERED SWITCH SERIES RPODL DX ON/OFF + RAISE/LOWER

CONTROL WITH A TWO GANG SINGLE OPENING SWITCH PLATE.

2 PROVIDE TWO NEW nLight AIR LINE POWERED SWITCH SERIES RPODL DX ON/OFF +

RAISE/LOWER CONTROL WITH A THREE GANG DOUBLE OPENING SWITCH PLATE.

3 CONNECT TO EXISTING SWITCH AS REQUIRED.

4 RECONNECT TO EMERGENCY POWER.

2 ADDENDUM 1 05/09/25

C E N ENFO

SE

ENOIS AL

GN

I

E

AT

P R

S

T K

E

CARTER

GREGORY G.

14715

L I S

D RE

Y

EFO K

C

TN

U

REVISION HISTORY OF THIS DRAWING

DECA LOG #

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

DRAWING NO.

ENGR. FILE NO.

2025/03/17

/9

/2

:2

:0

A

M

E801

LUMINAIRE SCHEDULES

525-CB82-CJ47-00

RECORD DWG. DATE

DOCJT - WEBER BUILDING FLOORING AND LIGHTING UPGRADES

4449 KIT CARSON DRIVE

2025|03|17

22-0751.00

GGC

WTG

C

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER CATALOG SERIES

LF-A 2 X 4 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, [INTEGRATED DUAL TECHNOLOGY OCCUPANCY SENSOR], WIRELESS CONTROL, L90 RATED LIFE OF 60,000 HOURS, DLC

QUALIFIED, AND FIVE YEAR LITED FIXTURE WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

WILLIAMS, DAYBRITE

2STAK 2X4 6000LM 80CRI 40K SERIES

LF-B 2 X 4 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, INTEGRATED DUAL TECHNOLOGY OCCUPANCY SENSOR, L90 RATED LIFE OF 60,000 HOURS, DLC QUALIFIED, AND FIVE YEAR

LITED FIXTURE WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

COLUMBIA, METALUX, DAYBRITE

2STAK 2X4 6000LM 80CRI 40K SERIES

LF-C RECESSED 2X4 LED GRID TROFFER WITH DIRECT-LIT TRANSLUCENT ACRYLIC DIFFUSER, DUST PROOF IP5X RATED OPTICS, 8000 DELIVERED LUMENS, 4000K 80 CRI LED ARRAY, L80 LIFE OF 60,000 HOURS, INTERGRATED OCCSENSOR, 100-1% DIMMABLE DRIVER, MADE IN USA, CSA LISTED FOR DAMP LOCATIONS, AND FIVE YEAR WARRANTY.

LITHONIA, OR APPROVE EQUAL BY WILLIAMS,

LEDALITE

CPX 2X4 HRG 4000LM 80CRI SERIES

LF-D RECESSED 6" LED DOWNLIGHT WITH 1500 LUMEN OUTPUT SELF-FLANGED ALZAK LOWER REFLECTOR, 55 DEGREE CUTOFF, GALVENIZED STEEL MOUNTING FRAME, ADJUSTABLE 16-GAUGE GALVANIZED STEEL MOUNTING BARS WITH CONTINUOUS 4" VERTICAL ADJUSTMENT FROM BELOW CEILING, 4000K LED LIGHT ENGINE, THERMALLY PROTECTED SOLID-STATE 0-10V DIMMING DRIVER, RATED SYSTEM LIFE OF 50,000 HOURS AT 70% OUTPUT, MAXIMUM 40 DEGREE CELCIUS OPERATING TEMPERATURE, ENERGY STAR CERTIFIED, AND 5-YEAR LIMITED WARRANTY. INTEGRATED OCCSENSOR.

LITHONIA, OR APPROVED EQUAL OMEGA,

PATHWAY

LDN6 40/15 LO6 AR LSS MVOLT

LF-E UNIVERSAL MOUNTED STENCIL FACE SELF DIAGNOSTIC LED EXIT SIGN WITH DIE-CAST ALUMINUM HOUSING, SINGLE OR DUAL CAST ALUMINUM HINGED FACEPLATE, WHITE FINISHED HOUSING, LOW ENERGY CONSUMPTION LONG-LIFE LED

LAMPS, UL LABEL, AND FIVE YEAR TOTAL FIXTURE WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

SURELITES, DUALITE

LESW 1R OR 2R 120/277

LF-F PENDANT MOUNTED LED WITH 20 GAUGE STEEL HOUSING, STEEL REFLECTORS, HIGH GLOSS BAKED WHITE ENAMEL FINISH, WIDE DIFFUSE ACRYLIC LENS, HIGH OUTPUT LEDS ON TWO LAYER CIRCUIT BOARD, ELECTRONIC LED DRIVER, 3000 DELIVERED LUMENS, 80 CRI, 85% OUTPUT AT 44,000 HOURS, CSA LISTED FOR DAMP LOCATIONS, AND FIVE YEAR LIMITED

WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

WILLIAMS, COLUMBIA

ZL1F L48 5000LM MDD MVOLT 40K 80CRI HC36 SERIES

LF-G 4’-0” LED WALL MOUNTED BRACKET WITH COLD ROLLED STEEL HOUSING, DIE CAST END CAPS, CRESENT SHAPED IMPACT MODIFIED LINEAR FACETED ACRYLIC DIFFUSER, HIGH EFFICIENCY INTEGRAL LED DRIVER, 4000 DELIVERED LUMENS FROM

LED ARRAY, L80 OF 50,000 HOURS, AND FIVE YEAR LIMITED WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

WILLIAMS, PHILIPS

WL4 40L LP840

LF-H SURFACE MOUNTED 2 X 4 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, STEEL SURFACE MOUNTING KIT, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS, DLC QUALIFIED, AND FIVE YEAR LIMITED FIXTURE WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

WILLIAMS, DAYBRITE

2STAK 2X4 6000LM 80CRI 40K SERIES

LF-J 1X4 RECESSED, EDGE-LIT FLAT PANEL, EXTRUDED ALUMINUM AND NARROW FRAME WITH MATTE WHITE FINISH. LITHONIA, OR APPROVED EQUAL BY

COLUMBIA, METALUX, DAYBRITE

EPANL-1X4-3000-80CRI-40K SERIES

LF-K LED HIGHBAY WITH 15” DIAMETER HOUSING, CAST ALUMINUM FINNED DRIVER HOUSING, 18,000 DELIVERED LUMENS, 4000K 80CRI LED ARRAY, IK10 RATED POLYCARBONATE PRISMATIC LENS, 0-10 VOLT 100-10% DIMMABLE LED DRIVER, 55 DEGREE C RATING, LUMEN MAINTENANCE L81 AT 80,000 HOURS, UL LISTING FOR DAMP LOCATION, SUITABLE FOR USE IN AMBIENT

TEMPERATURES FROM -40°C UP TO 55°C, AND 5 YEAR LIMITED WARRANTY.

LITHONIA, OR APPROVED EQUAL BY GE,

HOLOPHANE

CPRB 18000LM MVOLT 40K PM

LF-L 2X2 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 6000 DELIVERED LUMENS, INTEGRATED DUAL TECHNOLOGY OCCUPANCY SENSOR, WIRELESS CONTROL, L90 RATED LIFE OF 60,000 HOURS, DLC

QUALIFIED, AND FIVE YEAR LITED FIXTURE WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

COLUMBIA, METALUX, DAYBRITE

2STAK 2X2 5000LM 80CRI 40K SERIES

LF-M 4'-0" PENDANT MOUNTED INDUSTRIAL WITH IMPACT-RESISTANT FIBERGLASS HOUSING, UL LISTING FOR WET LOCATION, FROSTED ACRYLIC DIFFUSER SECURED TO FULLY GASKETED HOUSING BY STAINLESS STEEL CAPTIVE LATCHES, MULTI VOLT HIGH EFFICIENCY LED DRIVER, INTEGRAL SURGE SUPPRESSION, THERMAL PROTECTION CIRCUIT, 6000 DELIVERED LUMEN LED ARRAY, L80 OF 60,000 HOURS, IP65 RATING, AND FIVE YEAR LIMITED WARRATNY.

LITHONIA, OR APPROVED EQUAL BY KENALL,

DAYBRITE

CVST L48 6000 SERIES

LF-N LED WALL PACK WITH 11.5” WIDE X 7” DEEP X 9” TALL ONE PIECE DIE CAST ALUMINUM HOUSING, REGRESSED LED OPTICAL DELIVERING 2,00 LUMENS, VISUAL COMFORT FORWARD THROW DISTRIBUTION, L91 OF 100,00 HOURS, ELECTRONIC DRIVER, 6KV SURGE PROTECTION, IP66 RATING, CSA LISTED FOR WET LOCATIONS, INTEGRAL PHOTCELL, BI-LEVEL

SWITCHING MOTION SENSOR, AND FIVE YEAR WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

GARGCO, KIM

WDGE1 LED P2 40K 80CRI VF MVOLT PIR1FC3V

LF-P 2 X 2 LED GRID TROFFER WITH 1.9” DEEP STEEL HOUSING, INTEGRAL T-BAR CLIPS, COLD ROLLED STEEL REFLECTOR, POLYESTER POWDER COAT AFTER FABRICATION, IMPACT RESISTANT MODIFIED ACRYLIC PRISMATIC REFRACTOR, INTEGRAL MULTI-VOLT 0-10V 1-100% DIMMABLE DRIVER, 4000 KELVIN LED ARRAY PRODUCING 3000 DELIVERED LUMENS, L90 RATED LIFE OF 60,000 HOURS, DLC QUALIFIED, AND FIVE YEAR LIMITED FIXTURE WARRANTY.

LITHONIA, OR APPROVED EQUAL BY

WILLIAMS, DAYBRITE

2STAK 2X4 3000LM 80CRI 40K COL MIN1 ZT MVOLT SERIES

ELECTRICAL SPECIFICATIONS

SCOPE -- FURNISH AND INSTALL ALL WIRING DEVICES AND EQUIPMENT, ETC., UNLESS OTHERWISE INDICATED, FOR THE COMPLETE ELECTRICAL SYSTEMS. IT IS THE INTENT THAT THE ENTIRE ELECTRICAL WORK AND ALL ELECTRICAL SYSTEMS SHALL BE COMPLETE IN EVERY RESPECT AND THAT ALL OUTLETS, RECEPTACLES, FIXTURES, MOTORS, EQUIPMENT, DEVICES, ETC., SHOWN, NOTED OR REQUIRED SHALL

BE COMPLETELY CONNECTED FROM SOURCE OF POWER TO FINAL CONNECTION, READY FOR

SATISFACTORY OPERATION.

PERMITS, CODES AND APPROVALS

PERMITS -- ALL PERMITS NECESSARY FOR THE COMPLETE ELECTRICAL SYSTEMS SHALL BE OBTAINED BY THE CONTRACTOR FOR DIVISION 26 FROM THE AUTHORITIES GOVERNING SUCH WORK. THE COST OF

ALL PERMITS SHALL BE BORNE BY THIS CONTRACTOR.

CODES AND RULES AND REGULATIONS -- THE MINIMUM STANDARD FOR ALL ELECTRICAL WORK SHALL BE THE LATEST REVISION OF THE NATIONAL ELECTRICAL CODE. WHENEVER AND WHEREVER STATE AND/OR LOCAL LAWS AND/OR REGULATIONS REQUIRE A HIGHER STANDARD THAN THE CURRENT NATIONAL

ELECTRICAL CODE, THEN THESE LAWS AND/OR REGULATIONS SHALL BE FOLLOWED.

APPROVALS

ALL WORK MUST BE APPROVED BY THE ARCHITECT AND THE OWNER BEFORE FINAL PAYMENT WILL BE

MADE.

THE CONTRACTOR FOR DIVISION 26 SHALL FURNISH ELECTRICAL INSPECTION BY THE INSPECTION AGENCY HAVING JURISDICTION. THE ELECTRICAL INSPECTOR SHALL BE NOTIFIED IN WRITING IMMEDIATELY UPON THE START OF THE WORK AND A COPY OF THE NOTICE SHALL BE SENT TO THE ARCHITECT. ALL COSTS INCIDENTAL TO THE ELECTRICAL INSPECTION SHALL BE BORNE BY THE

ELECTRICAL CONTRACTOR.

MATERIALS AND APPLIANCES FOR THE TYPE FOR WHICH THERE ARE UNDERWRITERS' LABORATORIES

STANDARD REQUIREMENTS LISTINGS AND LABELS, SHALL HAVE LISTING OF UNDERWRITERS'

LABORATORIES AND SHALL BE SO LABELLED, OR SHALL CONFORM TO THEIR REQUIREMENTS, IN WHICH CASE CERTIFIED STATEMENTS TO THAT EFFECT SHALL BE FURNISHED BY THE MANUFACTURER WITH A COPY OF AN EXAMINATION REPORT BY A RECOGNIZED TESTING LABORATORY ACCEPTABLE TO THE

ARCHITECT.

DEMOLITION -- IN GENERAL, REMOVE EXISTING WORK INDICATED. THE DRAWINGS SHOW

EXISTING WORK TO THE EXTENT POSSIBLE. HOWEVER, ALL EXISTING WORK MAY NOT BE

SHOWN ON THE DRAWINGS. REMOVE OR RELOCATE EXISTING MECHANICAL AND ELECTRICAL WORK THAT INTERFERES WITH NEW WORK EVEN IF IT IS NOT SHOWN ON THE DRAWINGS. RELOCATE EXISTING

WORK THAT MUST REMAIN IN SERVICE EVEN IF IT IS NOT SHOWN ON THE DRAWINGS.

GROUNDING

ALL METALLIC CONDUIT, CABINETS, EQUIPMENT AND NEUTRAL CONDUCTORS OF THE WIRING SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH THE LATEST ISSUE OF THE NATIONAL ELECTRICAL CODE. IN ADDITION TO THE GROUNDING REQUIRED BY CODE, ALL FEEDERS AND BRANCH CIRCUITS SHALL

CONTAIN A CODE SIZE GROUND WIRE.

CONDUIT AND WIRING

ALL MATERIAL SHALL BE NEW AND SHALL BE LISTED BY THE UNDERWRITERS' LABORATORIES, INC., AS

CONFORMING TO ITS STANDARDS.

FURNISH AND INSTALL ALL OUTLET BOXES, AND JUNCTION BOXES. CEILING OUTLET BOXES SHALL BE CODE GAUGE GALVANIZED STEEL, 4 INCH OCTAGON BOXES, 1-1/2 INCH DEEP MINIMUM, LARGER WHERE REQUIRED. SWITCH AND RECEPTACLE OUTLET BOXES CONCEALED IN WALLS SHALL BE SWITCH UTILITY

OR GANG BOXES.

ALL WIRING SHALL BE INSTALLED IN CONDUIT UNLESS NOTED OTHERWISE. CONDUIT SHALL BE GALVANIZED STEEL ELECTRICAL METALLIC TUBING. SUPPORT CONDUIT PER N.E.C. EMT COUPLING AND

BOX CONNECTORS SHALL BE SET SCREW TYPE AS MANUFACTURED BY STEEL CITY.

FLEXIBLE CONDUIT SHALL BE 1/2" FLEXIBLE METAL CONDUIT IN LENGTHS NOT EXCEEDING SIX FEET FOR CONNECTING LIGHTING FIXTURES. FLEXIBLE CONDUIT MAY ALSO BE USED FOR INSTALLATION OF NEW

DEVICES IN EXISTING PLASTER WALLS.

CONDUCTORS SHALL BE COPPER AND INSULATION SHALL BE THHN. MINIMUM SIZE FOR POWER AND

LIGHTING CIRCUITS SHALL BE #12. MINIMUM INSULATION RATING SHALL BE 600 VOLTS.

WIRING CONNECTORS SHALL BE "WIRE NUT" AS MANUFACTURED BY MINNESOTA MINING AND

MANUFACTURING COMPANY FOR #8 AND SMALLER WIRE.

SECTION 16500 - LIGHTING FIXTURES

GENERAL

THE CONTRACTOR UNDER THIS DIVISION SHALL FURNISH AND INSTALL THE FOLLOWING TYPE LIGHTING

FIXTURES, COMPLETE WITH LAMPS, AS SHOWN ON THE DRAWINGS. FIXTURES OF OTHER

MANUFACTURERS, BUT OF THE SAME STYLE AND OF EQUAL QUALITY, WILL BE ACCEPTABLE UPON

APPROVAL OF THE ARCHITECT/ENGINEER.

THE FOLLOWING INFORMATION SHALL BE FURNISHED TO THE ARCHITECT, WITHIN THIRTY (30) DAYS

AFTER THE DATE OF THE CONTRACT, FOR EACH PROPOSED SUBSTITUTE FIXTURE:

NAME OF MANUFACTURER

CATALOG NUMBER

FIXTURE DRAWINGS SHOWING METAL GAUGES AND FINISH

PHOTOMETRIC DISTRIBUTION CURVES

2 ADDENDUM 1 05/09/25

Addendum No 1.pdf
Item 1: Change bid due date to May 19, 2025 at 1:30 PM ET. All other bid opening information will remain the same.
Item 2: Refer to attachments for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM