Addendum #6 for the New Mexico State University (NMSU) Aggie Innovation Space project at the Engineering Complex 1 (EC1) in Las Cruces, New Mexico, provides comprehensive updates and modifications to the original bid documents. The addendum covers detailed revisions to specifications, drawings, and technical requirements for a new approximately 4,000 square foot two-story addition. Key changes include eliminating certain specifications like fibrous concrete reinforcing, replacing entire sections of technical specifications for structural steel framing and door hardware, and making specific modifications to architectural and mechanical drawings. The document provides precise instructions for construction techniques, material specifications, and installation requirements across multiple disciplines including concrete placement, structural framing, mechanical systems, electrical infrastructure, and signage.
The addendum includes specific technical adjustments such as modifying floor finish options, updating room signage requirements, relocating mechanical equipment, and providing detailed electrical and access control specifications. Notable changes involve adjusting concrete finishing techniques, specifying new structural steel framing methods, revising door hardware configurations, and detailing compressed air and mechanical system installations. The document references NMSU's campus wayfinding and signage policy, includes specifications for building plaques, and provides comprehensive guidance for contractors on installation, testing, and coordination requirements. The project appears to be funded through NMSU and involves creating a specialized innovation space with advanced manufacturing and printing capabilities, requiring precise technical specifications and interdisciplinary coordination.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1268224-event.pdf | ||
| Addendum 8.pdf | ||
| Subcontractor Listing.pdf | ||
| Addendum 1 Site Visit.pdf | ||
| Drawings.pdf | ||
| Wage Rates Eng Complex.pdf | ||
| ADDENDUM 3.pdf | ||
| ADDENDUM 5.pdf | ||
| ADDENDUM 7.pdf | ||
| ADDENDUM 2.pdf | ||
| Specs.pdf | ||
| BID Form rev 2.1.2024.pdf | ||
| ADDENDUM 4.pdf | ||
| NMSU Construction TC 3-19-24 UGC -- Clean Copy.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
so ut h m ai n, s tu di o d l as c ru ce s, n m p
.5
.3 f
.5
.3 w w w
.s tu di o-d.
bi z studio d architects architecture planning LEED services
ADDENDUM #6
NMSU Aggie Innovation Space @ EC1 1025 Stewart St.
Las Cruces, New Mexico November 18, 2024
NOTICE TO BIDDERS: The following revisions, additions, and clarifications shall be incorporated in the Bidding Documents for this project. All other provisions of the Contract Documents shall remain unchanged. This Addendum is hereby made part of the Contract Documents to the same extent as though contained in the original documents and itemized listings thereof.
The following revisions to the permitted construction documents cover the addition of an area separation Firewall between suites C and D. The revised drawing sheets provided with this addendum are pending review from the City of Las Cruces Community Development Department and may be subject to changes.
SPECIFICATIONS
Item 1: Section 01 1112: A SWPPP is not required for this project.
Item 2: Section 01 1116, Paragraph 1.15: Project is not LEED Certified.
Item 3: Section 03 0240, Fibrous Concrete Reinforcing: Eliminate this section from the Project Specifications.
Item 4: Section 03 0313, Paragraph 3.5, Subsection A-1: Eliminate requirement for control joint sealant from project.
Item 5: Section 03 0313: Replace entire section with revised, attached specification.
Item 6: Section 03 3500: Add entire section to Project Specifications.
Item 7: Section 05 1200: Replace entire section with revised, attached specification.
Item 8: Section 08 7100, Door Hardware: Replace entire section with revised, attached specification.
Item 9: Section 08 7120, Door Access Control System: Replace entire section with revised, attached specification.
Item 10: Section 09 9100, User Painting, Section 2.02: Eliminate section 2.02 from specification.
Item 11: Section 10 1400, Signage: Replace entire section with revised, attached specification.
Item 12: Listing Threshold: Listing Threshold to be $12,500.
DRAWINGS
Item 13: Sheet AS100: Broom finish is acceptable on new site concrete that is to match existing.
Item 14: Sheet A100: Revise Additive Alternate #2 to read “MILLWORK WITHIN PROJECT ROOM 164.
SHELVING WITHIN OPEN WORK AREA 163.”
Item 15: Sheet A100, Keyed Note #9: ADA door opener button to be relocated to opposite side of new concrete walk. When facing door 160, the opener shall be placed on the right side of the walk. Opener to be so ut h m ai n, s tu di o d l as c ru ce s, p
.5
.3 f
.5
.3 w w w
.s tu di o-d.
mounted to 6x6 Steel tube w/ cap- embed 18” min., T.O. tube to be 48” a.f.f., prime and paint. See attached, revised electrical sheets.
Item 16: Sheet A101: Add attached A101 sheet to the drawing set.
Item 17: Sheet A101, Room Signs: See attached sheet A101 for room sign locations. See attached sections from NMSU Campus Wayfinding and Signage Policy (Updated 2019). Refer to entire policy for complete listing of all signage requirements. See revised, attached specification section.
Item 18: Sheet A101, Building Plaque: See attached sheet A101 for building plaque location and size. See attached specifications for additional requirements.
Item 19: Sheet A200, Floor Finish: Base Bid floor finish throughout space to be sealed concrete (Ashford Formula or equal). Additive Alternate #1 to provide Epoxy Floor Finish throughout space. Note: no sealer to be applied if Additive Alternate #1 is accepted.
Item 20: Sheet A200, Floor Finish (F1): Revise Floor Finish (F1) to refer to rooms 161 Powder Printers, 162 Metal Printers and 168 Storage.
Item 21: Sheet A200 and A700: Tile wall finish only occurs behind drinking fountains, refer to 5/A700.
Item 22: Sheet A400: Revise Keyed Notes 7 to read “80-MIL. FULLY ADHERED SINGLE-PLY ROOF SYSTEM
ON R-30 (MIN.) RIGID INSULATION ON METAL DECK (SEE STRUCTURAL). PROVIDE 60-MIL
MEMBRANE AT PARAPET WALLS.”
Item 23: Sheet A400: Revise Keyed Note 14 to read “60-MIL. FULLY ADHERED SINGLE-PLY ROOF SYSTEM
ON SLOPED RIGID INSULATION ON METAL DECK (SEE STRUCTURAL).”
Item 24: Detail 5/A401: EIFS starter track at top of wall(s) may be eliminated if system manufacturer does not require starter track to be installed. EIFS system must be installed per manufacturer’s requirements.
Item 25: Detail 5/A402: GC to provided notch in EIFS to serve as a drip edge.
Item 26: Detail 13/S6.0 and Detail 3/A402: Steel beams for the entry canopy to all have the same bottom of steel elevation. See attached, revised structural sheets S3.0 and S6.0.
Item 27: Detail 1/A402 and 3/A402: Provide 3-5/8” metal stud joists at 24” O.C. between all canopy steel beams as additional support/backing for Densglass sheathing and STO DEFS soffit system. See revised, attached sheet A402.
Item 28: Detail 2/A600: Both sides of wall to have ½” Densglass sheathing.
Item 29: Sheet S1.0, Foundation General Notes: Base course material is not required underneath concrete slab.
Item 30: Soil and Concrete Testing; Structural Inspections and Testing: Testing to be conducted by labs contracted through NMSU.
Item 31: Building Perimeter Footing Insulation: 1” rigid insulation exceeds the IECC requirements for unheated slab on grade construction for other than R occupancies within Zone 3. 2” is therefore not required. Refer to Table C402.1.3.
Item 32: Sheet P101: Replace entire sheet with attached, revised sheet.
Item 33: Sheet P700: Replace entire sheet with attached, revised sheet.
Item 34: Sheet P700, Keyed Note 1: The current air compressor is located in outside the existing workshop in the courtyard. Compressor to be relocated at start of project by NMSU. Contractor to move and install compressor in its final location once the rest of the compressed air system is completed and ready to be made operational. Coordinate relocation of components with NMSU.
Item 35: Sheet P700, Keyed Note 4: The current air dryer is located inside the existing workshop. The plumbing contractor will be relocating the air dryer to its new location. Coordinate with NMSU whether they will want to keep the dryer system operational during construction.
Item 36: Sheet M100: NMSU will contract with third party test and balance (TAB) contractor directly. Mechanical contractor will not need to include a TAB allowance in the bid.
Item 37: Sheet M200: Replace entire sheet with attached, revised sheet.
Item 38: Sheet M200, Hood Duct Sizing: Exhaust fan duct size to be 10” diameter.
mellujan Cross-Out so ut h m ai n, s tu di o d l as c ru ce s, p
.5
.3 f
.5
.3 w w w
.s tu di o-d.
Item 39: Sheet M300: Replace entire sheet with attached, revised sheet.
Item 40: Sheet M500: Add attached A500 sheet to the drawing set Item 41: Sheet M501: Add attached A501 sheet to the drawing set Item 42: Sheet M502: Add attached A502 sheet to the drawing set Item 43: Sheet M503: Add attached A503 sheet to the drawing set Item 44: Sheet M504: Add attached A504 sheet to the drawing set Item 45: Sheet E300: Replace entire sheet with attached, revised sheet.
Item 46: Sheet E400: Replace entire sheet with attached, revised sheet.
Item 47: Sheet E600: Replace entire sheet with attached, revised sheet.
Item 48: Sheet E800: Replace entire sheet with attached, revised sheet.
ADDITIONAL DOCUMENTS
Item 49: Geotech Report: See attached Geotechnical Report Item 50: NMSU Terms and Conditions, Section 13, Overhead and Profit: Allowances for Overhead and Profit may be made only on Change Orders resulting in net increases to the Contract Sum. Per NMSU Terms and Conditions the allowed mark-up percentages are:
A. Contractor / Sub-Contractor O/H and Profit for Work by Own Forces: Less than $20,000 = 12%;
$20,001 or Greater = 7%.
B. Contractor O/H & Profit for Work by Subcontractor(s): Less than $20,000 = 8%; $20,001 or Greater
= 5%.
END OF ADDENDUM NO. 6
4842 Aggie Innovation Space Concrete Placing, Finishing & Curing
EC1 Addition 030313 - 1 23.16
SECTION 03 0313
CONCRETE PLACING, FINISHING & CURING
PART 1. GENERAL
1.1 DESCRIPTION
A. Scope of Work: The extent of concrete placing, finishing and curing work is shown on the Contract
Drawings.
B. In the event that certain features of the construction are not fully shown on the drawings, or called for in the structural notes or in the specifications, then such construction shall be in the same character for similar conditions that are shown or called for.
C. Related Work specified in other Sections: Documents affecting work of this Section include, but are not limited to, General Conditions, Supplementary Conditions and Sections in Division 1 and the following sections of these Specifications.
1. Concrete General Section 03 0000
2. Concrete Formwork Section 03 0100
3. Concrete Reinforcing Steel Section 03 0200
4. Fibrous Concrete Reinforcing Section 03 0240
1.2 SUBMITTALS
A. See Section 03 00 00.
1.3 QUALITY ASSURANCE
A. The Contractor shall comply with the provisions of the codes, specifications and standards shown in detail in Section 03 00 00. All codes can be obtained from their respective issuers. ASTM Specifications as referenced are made a part of the project. However, if they are in conflict with Uniform Building Code, the building code shall govern.
PART 2. PRODUCTS
A. See Section 03 0000.
PART 3. EXECUTION
3.1 PREPARATION FOR PLACEMENT
A. General: Assure that all reinforcing is properly and securely positioned and tied. Verify that all required sleeves, anchors, slots, inserts, conduit boxes and similar items have been properly located and secured to prevent displacement during concrete placement. Determine that all expansion joints, felt strips, construction and control joints are properly located and formed.
Assure that equipment is clean and that all debris is removed from the forms, or other places receiving concrete. Reinforcing to be free of ice and snow. Assure that forms are lined, oiled or wetted as specified for the particular usage. During freezing weather the use of water to wet forms is prohibited. Immediately prior to pour, dampen sub-grade for slabs on grade.
Remove water from places of deposit. Remove latence and unsound material from the surface of hardened concrete and moisten surfaces before new concrete is placed.
3.2 REVIEWS BY THE ARCHITECT
A. Notify the Architect 24 hours in advance of all concrete placement. The site must be reviewed by
Architect or field representative. Review by the Architect of the concrete placement shall not relieve the Contractor to produce the finished concrete required by the provisions of the Drawings and Specifications.
B. Immediately in advance of placing concrete, excavations, forms, reinforcements, inserts, etc. may be reviewed by the Architect and if any part of the work is determined to be unsatisfactory, the concrete work shall not proceed until after all defects have been remedied and the approval of the Architect has been obtained.
3.3 PLACING CONCRETE
A. Conveying: Convey concrete from the mixer to place of deposit using wheeled vehicles, chutes, tremies, pumping equipment or other equipment. Assure as nearly as possible a continuous flow
EC1 Addition 030313 - 2 of concrete at the delivery end. Concrete shall be delivered without segregation of material during the conveying operations. Provide runways for wheeled conveying equipment. Do not wheel conveying equipment over reinforcement and do not support runways on reinforcement.
Assure that screeds are accurately set and rigidly secured to withstand pouring operations.
B. Placing: Deposit concrete as near as possible to final position. Excessive "pushing" of material from one position to another is prohibited. Place concrete in a condition that it is plastic and "flows" between reinforcing, mixes well with previous layers. To prevent loss of excessive concrete volume as the placed material is drying it is recommended the Contractor plan on using "ASTM C-494, type A superplasticizer admixture" for increasing and providing the free movement of concrete during placement. Add the superplasticizer at the concrete placement site in quantities recommended by the manufacturer of the product for the desired slump values. Slumps up to 10" are possible without any decrease in concrete strength. If drops greater than five (5') feet are required, use a tremie or other method approved by the Architect. Complete all panels, sections, etc., before cessation of concrete placement.
C. When placing new concrete adjacent or over "old" concrete use a concrete bonding agent similar to Dewey & Almy "Daraweld", Larson Products "Weldcrete" or approved equal mixed and applied per the manufacturer's directions.
D. Compaction: Consolidate all concrete with suitable vibrating equipment. Contractor shall have on hand or an immediate source of spare vibrating equipment. Do not use the vibrating equipment in fresh concrete excessively, to transport material or for mixing fresh material with previously set concrete.
3.4 CONCRETE FINISHING
A. General: Form tie holes, voids, gravel pockets, and finish of exposed surfaces shall have all fins and loose materials removed to a smooth surface and voids filled with a dry cement mortar and rammed in place to provide a solid uniform surface matching the existing concrete surface. Use a Carborundum stone and leave the surface clean and smooth.
B. Slabs, sidewalks and exterior paving:
1. Slab surfaces shall be finished by screeding to the required finish level and when free of all tool marks, the surface shall be given the specified finish. Tamping is not recommended by ACI. Finish slabs shall be level and in a true plane with a tolerance for deviation of not more than 1/8" in ten (10') feet. Note! Addition of water to increase slump will cause depressions in the slab which exceed this tolerance causing final slab grinding.
2. Joints in sidewalks shall be grooved at right angles to the sidewalks at intervals equal to the width or a maximum of 5' o.c, unless otherwise shown on the Drawings. Grooves shall be 1" deep.
3. Slope across width for drainage: 1/8" per foot slope all walks, etc.
4. All interior floors shall have a second troweling to produce a smooth "hard" troweled, burnished finish. All exposed interior slabs, reinforced with fibers, shall be finished in such a manner that there are NO EXPOSED FIBERS remaining after final troweling.
5. Where slabs abut curbing or other concrete construction install a continuous 1/2" preformed bituminous expansion material. Similar joints shall be installed in straight runs of walks at not over 20' o.c. Joint material shall extend from finish level to 1/4" below beginning level of concrete.
6. Exposed Aggregate finish slabs (where noted on the drawings), shall be of local brown rock approved by the Architect. Size shall be from ¼” to ¾” maximum dimension. Clean and wet thoroughly (drain off excess water) before applying.
7. Placing and embedding aggregate: Immediately after the slab has been screeded and darbied, the selected aggregate should be scattered by hand-evenly distributed so that the entire surface is completely covered with a single layer. Special care should be taken in covering the edge to ensure a uniform appearance.
8. The initial embedding of the aggregate is usually done by patting with the darby or the flat side of the strike-off rod. After the aggregate is embedded and as soon as the concrete will support the weight of mason on kneeboards, the surface should be hand-floated with a
EC1 Addition 030313 - 3 magnesium float or darby. This operation should be performed thoroughly so that all aggregate is completely embedded just beneath the surface. The grout should completely surround and slightly cover all aggregate with no holes or openings left in the surface.
Following this floating, a reliable retarder shall be spayed or brushed on the surface according to the manufacturer’s recommendation.
9. Exposing the aggregate: Proper timing is quite critical in exposing aggregate, a test panel should be made and tested to determine the best time to begin. Exposing should be done as soon as the grout can be removed by simultaneously brushing and flushing with water without overexposing operations, kneeboards must be used with special care. If possible, this should be avoided because of risk of breaking aggregate bond.
10. Curing: Exposed aggregate slabs should be cured thoroughly. Care must be taken that the method of curing does not stain the surface. Straw, earth, and some types of building paper may cause staining.
11. Provide two test panels 24’ x 24’ for Architect’s approval.
C. Walls and beams:
1. Formed concrete basic finish: After removal of forms, remove loose material and fins from concrete surface. Grout fill honeycombs, tie holes and other pockets or voids in concrete surface. At areas to be grouted, remove unsound concrete, clean away any debris, thoroughly wet surfaces, brush coat with neat cement and fill with mortar packed solidly into void. Completely fill all holes passing through walls. Use mortar consisting of one part white and normal cement, two parts sand passing a No. 16 screen, and as little water as necessary for handling and placing. Blend cements in proportions as to secure a color match in unpainted areas when dry. Finish exposed patchwork flush with and matching adjoining surfaces. Damp cure patchwork for 72 hours.
2. Smooth finish: Use for all exterior vertical and overhead concrete surfaces that will be exposed as finish work, except where otherwise specified. Use steel forms or line forms with 3/16" pressed wood or 1/4" plywood. Install sheets as large as possible. All joints shall have smooth, even, closed edges. Grind marks and fins, prominent grain indentations, bulges and/or depressions. Finish surfaces shall be uniformly smooth and washed clean.
3. Rubbed finish (where called for and for all interior exposed concrete): Fins and other projections shall be carefully removed, offsets leveled, and damaged places repaired.
Surfaces shall be rubbed with cement or abrasive bricks and water. Do not use mortar or grout in this rubbing process. After all form marks and other blemishes are removed, prepare an area where the finish is uniformly clean and smooth, a 48" square required to be inspected and approved by the Architect for all surfaces of this type.
4. Curbs and gutters: Joints shall be grooved at 10' o.c. perpendicular to the sides with contraction joints not over 10' o.c. and expansion joints not over 40' o.c. All concrete sidewalk abutments shall have a 1/2" expansion joint installed.
5. Concrete Columns: All exterior poured-in-place round concrete columns to have a sandblasted finish. Prepare surfaces to be sandblasted same as “Rubbed Finish” surfaces.
Lightly sandblast prepared surfaces to produce a uniform sand texture without exposing concrete aggregate. Prepare a sample area for approval by the Architect
3.5 CONCRETE JOINTS
A. Joints: Form or construct all joints in concrete work true-to-line and accurately placed.
1. Control, Contraction or Construction Joints: All slabs shall be saw-cut immediately after final finish troweling is complete. Saw joints, 1/4 the depth of the slab and not over 12 feet o.c. unless shown otherwise on Drawings. During hot weather conditions, joints shall be cut 1/4 the depth of the slab at a maximum of 10 feet o.c. Immediately after saw cutting, the joint shall be cleaned. Use metal-keyed, 22 gage, control joints only when authorized by the Architect. If locations are not indicated on Drawings, locate to least impair strength of the structural elements.
2. Beams, girders, brackets, column capitals, haunches and similar parts shall be considered as part of the floor systems and placed monolithically therewith. Locate construction joints
EC1 Addition 030313 - 4 in floors near the middle of the spans of slabs, beams, or girders unless another member of the joint shall be offset a distance equal to twice the width of the beam. Where a joint is made, the hardened surface shall be thoroughly cleaned and all latence removed. Vertical joints shall be thoroughly wetted and slushed with a coat of neat cement grout before placing new concrete. At least two hours shall elapse after depositing concrete in columns and walls before placing concrete in members supported thereon.
3. Expansion Joints: Locate wall expansion joints where all exterior slabs abut building surfaces as shown on the Drawings. Unless otherwise detailed, make joints in slabs 1/2" thick, using premolded asphalt impregnated fiberboard, full thickness of the slab. Finish the edges of slabs at expansion joints with slightly rounded edging tool. In no case shall the reinforcement or other fixed metal items which are embedded in or bonded to the concrete be run continuous through an expansion joint. Locate other slab expansion joints where indicated on the Drawings. If not otherwise shown, divide slab-on grade surfaces into areas not exceeding 900 square feet by locating joints where exterior slabs abut rigid vertical surfaces and along column center lines. Interior slabs on grade and topping slabs shall contain shrinkage compensating cement as specified and shall be poured without expansion joints.
4. Bond-Barrier Joints: Form such joints with 15-lb asphalt saturated felt, full thickness of the slab where interior slabs abut rigid vertical surfaces, wrapped around pipe and conduit penetrations, and elsewhere as shown on Drawings.
3.6 EMBEDDED ITEMS
A. Anchor Slots: Use only approved type galvanized metal with wood or fiber insert, set in true vertical position and anchored securely in place. Provide for masonry abutting concrete and for masonry veneer and furring, one slot for each abutment, not more than 18" o.c. for veneer and furring.
B. Work of Other Trades: Allow other trades time and facilities to install necessary embedded items.
3.7 WEATHER RESTRICTIONS
A. Cold weather placement: Place concrete only if the air temperature is above 40 degrees F.
and rising. Concrete may be placed, after approval by the Architect, if the materials are preheated. Concrete after placement shall be maintained at 50 degrees or higher for 4 days (normal cement) or 3 days (high early strength cement). Leave protection in place one day after heating is discontinued. Concrete shall not be placed when snow, rain, or blowing sand are expected.
B. Hot weather placement: During low humidity, high temperature or wind take suitable precaution to avoid premature drying of fresh concrete during finishing and curing. Concrete shall be protected from "flash" set, loss of slump, cold joints, shrinkage surface cracks, etc.
3.8 CURING
A. Base Bid: Sealing of exposed to view concrete floors. All floors which are scheduled in the Room
Finish Schedule as “Concrete with Sealer” are to receive the “Ashford Formula” system as manufactured by Concrete Chemical Company, Springville, Utah. System is to be applied in accordance with manufacturer’s printed instructions.
B. Additive Alternate #1: If Additive Alternate #1 (Epoxy Flooring) is accepted, all floors shall be protected against moisture loss by moist curing. The Contractor shall instigate the process immediately after final troweling, or floating of concrete section placed.
1. Apply two (2) coats of membrane-curing compound at right angles to each other.
2. After concrete placement, all surfaces shall be protected against construction loads, marring by equipment and personnel movements.
3.9 CLEAN-UP
A. General: At the completion of each concrete installation, all forms, debris and other material resulting from the concrete installation shall be removed from the site at the Contractor's expense and his location.
EC1 Addition 030313 - 5
END OF SECTION
4842 Aggie Innovation Space Concrete Finishing EC1 Addition 033500 - 1
SECTION 03 35 00
CONCRETE FINISHING
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes:
1. Single application cure-densifier-hardener for new and existing concrete floors.
2. Precautions for avoiding staining concrete before and after application.
B. Related Section:
1. Cast-In-Place Concrete: Division 03 Cast-In-Place Concrete sections.
1.2 REFERENCES
A. American National Standards Institute (ANSI):
1. ANSI B101.1 Test Method for Measuring Wet SCOF of Common Hard-Surface Floors.
2. ANSI B101.3 Test Method for Measuring Wet DCOF of Common Hard-Surface Floors.
B. ASTM International (ASTM):
1. ASTM C779 Standard Test Method for Abrasion Resistance of Horizontal Concrete Surfaces.
2. ASTM C805 Standard Test Method for Rebound Number of Hardened Concrete.
3. ASTM D3359 Standard Test Methods for Measuring Adhesion by Tape Test.
4. ASTM F150-06(2018) Standard Test Method for Electrical Resistance of Conductive and Static Dissipative Resilient
Flooring.
5. ASTM G23 Practice for Operating Light-Exposure Apparatus (Carbon-Arc Type) With and Without Water for Exposure of
Nonmetallic Materials (Withdrawn 2000).
C. National Floor Safety Institute (NFSI):
1. Certified as High Traction by the National Floor Safety Institute (NFSI), Phase 2 testing.
D. USGBC LEED Version 4
1. Indoor VOC Emission Test; California Department of Public Health CDPH/EHLB/Standard Method Version 1.2, 2017.
E. Health Product Declaration Collaborative (HPD)
1. HPD v1.0.
2. HPD v2.1.
1.3 SUBMITTALS
A. General: Submit listed submittals in accordance with Conditions of the Contract.
B. Product Data: Submit product data, including manufacturer’s Spec-Data® sheet, installation instructions and technical bulletins for specified products.
C. Certificates: Manufacturer’s certification that the installer is acceptable.
D. Maintenance Data: Maintenance instructions, including precautions for avoiding staining after application.
1.4 QUALITY ASSURANCE
A. Installer Qualifications: Acceptable to the manufacturer.
B. Regulatory Requirements: In accordance with Conditions of the Contract (if applicable).
1.5 DELIVERY, STORAGE & HANDLING
A. General: Comply with Division 01 Product Requirements section.
B. Delivery: Deliver materials in manufacturer’s original, unopened, undamaged containers with identification labels intact.
EC1 Addition 033500 - 2
C. Storage and Protection: Store materials protected from exposure to harmful environmental conditions and at temperature and humidity conditions recommended by the manufacturer.
D. Handling: Protect materials from dirt, corrosion, oil, grease and other contaminants.
PART 2 PRODUCTS
2.1 MATERIAL
A. Manufacturer: Curecrete Distribution, Inc.
1. Contact: 1203 Spring Creek Place, Springville, UT 84663-0551; Telephone: (800) 998-5664, (801) 489-5663; Fax: (801)
489-3307; Email: info@ashfordformula.com; Website: www.ashfordformula.com.
B. Cure-Densifier-Hardener: Ashford Formula is a transparent, chemically reactive, water-based treatment that penetrates into the concrete surface, forming a chemical reaction of crystalline growth that fills in the natural pores and voids in the concrete surface.
1. Abrasion Resistance to Revolving Disks: At least a 32.5% improvement over untreated samples when tested in accordance with ASTM C779.
2. Surface Adhesion: At least a 22% increase in adhesion for epoxy when tested in accordance with ASTM D3359.
3. Hardening: As follows when tested in accordance with ASTM C39:
a. After 7 Days: An increase of at least 40% over untreated samples.
b. After 28 Days: An increase of at least 38% over untreated samples.
4. Rebound Number: An increase of at least 13.3% over untreated samples when tested in accordance with ASTM C805.
5. Electrical Resistance: To ASTM F150.
6. Light Exposure Degradation: No evidence of adverse effects on treated samples when tested in accordance with ASTM
G23.
7. Test Method for Measuring Wet SCOF of Common Hard-Surface Floors in accordance with ANSI B101.1.
8. Test Method for Measuring Wet DCOF of Common Hard-Surface Floors in accordance with ANSI B101.3.
9. Certified as High Traction by the National Floor Safety Institute (NFSI), Phase 2 testing.
10. Certified Compliant according to California Department of Public Health CDPH/EHLB/Standard Method Version 1.2, 2017.
2.2 PRODUCT SUBSTITUTIONS
A. Substitutions: Substitutions in accordance with Conditions of the Contract.
PART 3 EXECUTION
3.1 MANUFACTURER’S INSTRUCTIONS
A. Compliance: Comply with manufacturer’s product data, including product technical bulletins, product catalog installation instructions and product carton instructions for installation.
3.2 EXAMINATION
A. Do not begin installation until substrates have been properly prepared and are suitable for application of product.
B. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
3.3 PREPARATION
A. Clean surfaces thoroughly prior to installation.
B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.
C. Do not use frozen material. Thaw and agitate prior to use.
D. If construction equipment must be used for application, diaper all components that might drip oil, hydraulic fluid or other liquids.
3.4 INSTALLATION
A. New Concrete: Apply cure-densifier hardener to new concrete as soon as the concrete is firm enough to work on after troweling;
EC1 Addition 033500 - 3 with colored concrete, wait a minimum of 30 days before application.
1. Spray on at rate of 200 ft2/gal (5 m2/L).
2. Keep surface wet with cure-densifier-hardener for a minimum soak-in period of 30 minutes without allowing it to dry or become slippery. If slipperiness occurs before the 30 minute time period has elapsed, apply additional cure-densifier-hardener, as needed, to keep the entire surface in a non-slippery state for the first 15 minutes; for the remaining 15 minutes, mist the surface as needed with water to keep the material in a non-slippery state. In hot weather conditions, follow manufacturer’s special application procedures.
3. When the treated surface becomes slippery after this period, lightly mist with water until slipperiness disappears.
4. Wait for surface to become slippery again, and then flush entire surface with water to remove all cure-densifier-hardener residue.
5. Squeegee surface completely dry, flushing any remaining slippery areas until no residue remains.
6. Wet vacuum or scrubbing machines can be used in accordance with manufacturer’s instructions to remove residue.
B. Existing Concrete: Apply cure-densifier-hardener only to clean, bare concrete.
1. Thoroughly remove previous treatments, laitance, oil and other contaminants.
2. Saturate surface with cure-densifier-hardener; respray or broom excess onto dry spots.
3. Keep surface wet with cure-densifier-hardener for a minimum soak-in period of 30–40 minutes.
4. If most of the material has been absorbed after the 30 minute soak-in period, remove all excess material, especially from low spots, using broom or squeegee.
5. If most of the material remains on the surface after the 30 minute soak-in period, wait until the surface becomes slippery and then flush with water, removing all cure-densifier-hardener residue. Squeegee completely dry, flushing any remaining slippery areas until no residue remains.
6. If water is not available, remove residue using squeegee.
3.5 PROTECTION
A. Protect installed floors for at least 3 months until chemical reaction process is complete.
1. Do not allow traffic on floors for 3 hours after application.
2. Do not allow parking of vehicles on concrete slab.
3. If vehicles must be temporarily parked on slab, place drop cloths under vehicles during entire time parked.
4. Do not allow pipe cutting using pipe cutting machinery on concrete slab.
5. Do not allow temporary placement and storage of steel members on concrete slabs.
6. Clean up spills immediately and spot-treat stains with degreaser or oil emulsifier.
7. Clean floor regularly in accordance with manufacturer’s recommendations.
4842 Aggie Innovation Space Structural Steel Framing EC1 Addition 051200 - 1
SECTION 051200 - STRUCTURAL STEEL FRAMING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Structural shapes.
2. Channels and angles.
3. Hollow structural sections.
4. Structural pipe.
5. Structural plates and bars.
6. Floor plates.
7. Bolts, connectors, and anchors.
8. Grout.
1.2 SUBMITTALS
A. Shop Drawings:
1. Indicate profiles, sizes, spacing, locations of structural members, openings, attachments, and bolts.
2. Erection Drawings: Indication location and configuration of all steel members coordinate with erection sequence, means and method.
3. Connections: Connections have been designed in accordance with the AISC Code of Standard Practice Section 3.1.2, Option (2). The Steel Detailer shall select, and complete connection based on information in the construction documents. The fabrication is not required to hire a professional engineer for the connection design.
4. Cambers: Indicate camber on all structural members to be camber in accordance with the AISC Code of Standard Practice.
5. Indicate welded connections with AWS A2.4 welding symbols, and indicate net weld lengths.
B. Manufacturer's Certificate: Certify that products and materials meet or exceed specified requirements.
C. Mill Test Reports: Submit reports indicating structural strength, destructive and non-destructive test analysis, and chemical makeup.
1.3 QUALITY ASSURANCE
A. Perform Work according to following:
1. Structural Steel: AISC 303 and AISC 360.
2. High-Strength Bolted Connections: RCSC - Specification for Structural Joints
Using ASTM A325 (A325M) or ASTM A490 (A490M) Bolts.
3. Steel Cable Structures: ASCE 19.
B. Fabricator:
1. Company specializing in fabricating products specified in this Section with minimum five years' documented experience our have the following current AISC Certification:
a. Standard Steel Building Structures (STD).
b. Conventional Steel Building Structures (SBD).
c. Complex Steel Building Structures (CBD).
C. Erector:
1. Company specializing in performing Work of this Section with minimum five years' documented experience or have the following current AISC Certification:
a. Certified Steel Erector (CSE).
b. Advanced Certified Steel Erector (ACSE).
D. Shop Painter:
EC1 Addition 051200 - 2
1. Company specializing in performing Work of this Section with minimum three years' documented experience with following current AISC Certification:
a. Sophisticated Paint Endorsement - Enclosed (P1).
b. Sophisticated Paint Endorsement - Covered (P2).
c. Sophisticated Paint Endorsement - Outside (P3).
E. Welders and Welding Procedures: AWS D1.1 (D1.1M) qualified within previous 12 months.
PART 2 - PRODUCTS
2.1 STRUCTURAL STEEL
A. Structural W Shapes: As indicated in Structural Notes B. Structural M Shapes: As indicated in Structural Notes C. Structural S Shapes: As indicated in Structural Notes D. Channels and Angles: As indicated in Structural Notes E. Steel Pipe: As indicated in Structural Notes F. Square & Rectangular Tube: As indicated in Structural Notes G. Round Tube: As indicated in Structural Notes
2.2 BOLTS, CONNECTORS, AND ANCHORS
A. Bolts: As indicated in Structural Notes B. Nuts: ASTM A563 C. Washers: ASTM F436 D. Headed Anchor Studs: As indicated in Structural Notes E. Anchor Rods: As indicated in Structural Notes F. Threaded Rods: ASTM A36 or as indicated in Drawings.
2.3 WELDING MATERIALS
A. Welding Materials:
B. AWS D1.1 (D1.1M).
C. Type required for materials being welded.
2.4 FINISHES - Structural Steel that will not receive fire proofing and will are not indicated as Architectural Exposed shall be prepared as follows:
A. Prepare structural component surfaces according to SSPC SP 3.
B. Primer shall be applied in the shop prior to transportation of material to the job site.
The shop primer shall be a fast curing, universal modified alkyd, rust inhibiting shop coat with good resistance to normal atmospheric corrosion. Primer shall comply with all federal standards for VOC, lead and chromate levels. Shop primer shall be applied per manufacturer’s recommendations.
C. All exposed steel shall be touch up painted prior to applying top coat with primer to match shop primer.
2.5 SOURCE QUALITY CONTROL
A. Testing: Test bolted and welded connections as specified in PART 3 for field quality control tests.
B. Certificate of Compliance: When fabricator is approved by authorities having jurisdiction, submit certificate of compliance indicating Work performed at fabricator's facility conforms to Contract Documents.
C. Specified shop tests are not required for Work performed by approved fabricator.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verify that bearing surfaces are at correct elevation.
B. Verify that anchor rods are set in correct locations and arrangements, with correct exposure for steel attachment.
3.2 PREPARATION
A. Furnish templates for installation of anchor rods and embedments in concrete and masonry work.
3.3 ERECTION
EC1 Addition 051200 - 3
A. Allow for erection loads and for sufficient temporary bracing to maintain structure safe, plumb, and in alignment until completion of erection and installation of permanent bracing.
B. Field-weld components and shear connectors as indicated on Drawings.
C. Field-connect members with threaded fasteners; torque to required resistance and snug-tighten for bearing-type connections.
D. Do not field-cut or alter structural members without approval of Architect/Engineer.
E. After erection, touch up welds and abrasions to match shop finishes.
3.4 GROUT INSTALLATION
A. Shim bearing plates and equipment supports to proper elevation, and snug-tighten anchor bolts.
B. Fill void under bearing surface with grout; install and pack grout to remove air pockets.
C. Moist-cure grout.
D. Remove forms after grout is set; trim grout edges to form smooth surface, splayed 45 degrees.
E. Tighten anchor bolts after grout has cured for a minimum of three days.
3.5 TOLERANCES
A. Maximum Variation from Plumb: ¼-inch per story, noncumulative.
B. Maximum Offset from Alignment: ¼-inch.
3.6 FIELD QUALITY CONTROL
A. Bolted Connections: Inspect according to AISC 303.
1. Visually inspect all bolted connections.
2. Direct Tension Indicators: Comply with requirements of ASTM F959.
B. Welding: Inspect welds according to AWS D1.1.
1. Use certified welders, and conduct inspections and tests as required. Record types and locations of defects found in Work. Record work required and performed to correct deficiencies.
2. Visually inspect all welds.
3. Ultrasonic Inspection: ASTM E164; perform on each full-penetration weld.
4. Liquid Penetrant Inspection: ASTM E165.
5. Magnetic Particle Inspection: ASTM E709
6. Radiographic Inspection: ASTM E94.
C. Correct defective bolted connections and welds.
4842 Aggie Innovation Space EC1 Addition Door Hardware
23.16 08 7100 - 1
SECTION 08 71 00
DOOR HARDWARE
PART I - GENERAL
1.01 DESCRIPTION
A. Related Work:
1. Cabinet Hardware: Interior Architectural Woodwork.
2. Threshold Caulking: Joint Sealants.
3. Connecting Electrical Hardware: Electrical
1.02 QUALITY ASSURANCE
A. Design Criteria: Provide Underwriter’s Laboratory listed hardware for fire or accident hazard where scheduled or required to maintain rating of openings. Comply with requirements of door and door frame labels. Comply with NFPA No. 80 and local codes that are in effect in the area of the project.
1.03 SUBMITTALS
A. Hardware Schedule: Within 10 days after receipt of a contract for the finish hardware, prepare a complete schedule and submit 8 copies of the hardware schedule with 3 copies of catalogue cuts, highlighted to show each different hardware item to the Architect for review.
B. Do not order hardware until an approved copy of the schedule is returned to the supplier bearing the approval of the Architect.
This schedule shall indicate the following details:
Door numbers Frame materials Location Hand of door Size and thickness of door Degree of opening Door material Type of attachment Door Number / Heading Index
C. Templates: After receipt of the approved corrected hardware schedule, upon request the hardware supplier shall send 4 sets of all templates and corrected hardware schedule to the general contractor for distribution to the wood door, metal door, and frame manufacturers/suppliers.
D. Maintenance Manuals: Furnish 1 copy of maintenance manual covering the finish hardware for this project. The manual shall consist of printed sheets from the hardware manufacturer bound in a three-ring binder and properly indexed.
Include the following information in the maintenance manuals:
1. Address and telephone number of the hardware supplier.
2. Address and telephone number of each hardware manufacturer.
3. Maintenance instructions and parts list for each type of operating hardware including:
a. Locks.
b. Exit Devices.
c. Closers.
4. Warranty for closers and all other hardware.
23.16 08 7100 - 2
1.04 DELIVERY, STORAGE, AND HANDLING
A. Deliver hardware to the jobsite only after proper provision for storage has been made.
NO DIRECT SHIPMENTS WILL BE ALLOWED.
B. Properly package and clearly identify each item relative to the hardware schedule.
C. The hardware supplier shall authorize his representative to be present when all finish hardware is delivered to the jobsite and shall check-in each item and turn over to the General Trades Contractor for storage in a secure place under lock and key.
1.05 WARRANTY
A. Furnish 3 copies of the following written warranty to be included in the Maintenance Manuals:
1. Warranty against mechanical failure of door closers for a 10 year period.
2. Warranty against failure of parts of all hardware except door closers for a period 1 year.
3. Warranty shall include cylinder locks.
4. Starting date for all warranty periods to be the date of substantial completion of building by owner.
PART 2 - PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A. Butts: Ives, Bommer, Hager, Stanley IVE B. Exit Devices : Von Duprin – 99 SERIES*** VON C. Door Closers: LCN - 4010 SERIES *** LCN D. Cylindrical Locksets: Yale – 5400 SERIES*** YAL E. Thresholds & Weatherstrip: Pemko, National Guard, Reese, Zero ZER F. Stops & Door Trim: Ives, Trimco, Rockwood, Glynn Johnson IVE G. O/H Stops: Glynn Johnson GLY H. Coordinators: Ives, Glynn Johnson, DCI IVE I. Auto Flush Bolts: Ives, Glynn Johnson, DCI IVE J. Door Operators: Horton Operators – 4100 Heavy duty, 7100 standard duty K. Mortise Locks: Preferred Schlage, Schlage L9000 Series, Levon or Rhodes Trim Yale 8600 or 8700 Series, Augusta Trim;
*** - NMSU’s Standard – NO SUBSTITUTES
2.02 SCHEDULED HARDWARE
A. Requirements for design: grade, function, finish, size, and other distinctive qualities of each type of Builder’s Hardware is indicated in the Hardware Schedule at the end of this section. Products are identified by using manufacturer’s hardware product numbers.
B. Manufacturer’s Product Designation: One or more manufacturers are listed for each hardware type required. The initial after the manufacturer’s name indicates whose product designation is used in the Hardware Schedule for purposes of establishing minimum requirements. Provide the product designated, or where more than one manufacturer is listed, the comparable product of one of the other manufacturers which comply with requirements including those specified elsewhere in the section.
2.03 MATERIALS AND FABRICATION
23.16 08 7100 - 3
A. Hand of Door: The drawings show the direction of slide, swing, or hand of each door leaf. Furnish each item of hardware for proper installation and operation of the door movement as shown.
B. Base Metals: Produce hardware units of the basic metal and forming method indicated using the manufacturer’s standard metal alloy, composition, temper, and hardness. Do not furnish “Optional” materials or forming methods for those indicated, except as otherwise specified.
C. Fasteners: Manufacture hardware to conform to published templates generally prepared for machine screw installation. Do not provide hardware that has been prepared for self-tapping screws except as specifically indicated.
1. Furnish screws for installation with each hardware item. Provide Phillips flat-head screws except as otherwise indicated. Finish exposed (exposed under any condition) screws to match the hardware finish or if exposed in surfaces of other work to match the finish of such other work as closely as possible including “prepared for paint” in surfaces to receive painted finish.
a. Sex Bolts: Install door closer, door holders, and exit devices on wood doors by means of thru bolts and sex nuts.
2. Provide concealed fasteners for hardware units which are exposed when the door is closed except to the extent no standard units of the type specified are available with concealed fasteners. Do not use thru bolts for installation where the bolt head or the nut on the opposite face is exposed in other work except where it is not feasible to adequately reinforce the work.
2.04 BUTTS, HINGES, AND PIVOTS
A. Templates: Provide only template produced units.
B. Screws: Furnish Phillips flat-head all purpose or machine screws for installation of units except furnish
Phillips flat-head all purpose wood screws for installation of units into wood. Finish screw heads to match surface of hinges or pivots.
C. Hinge Pins: Except as otherwise indicated provide hinge pins as follows:
1. Steel Hinges: Steel pins
2. Non-ferrous Hinges: Stainless steel pins
3. Exterior Doors: Non-removable pins (NRP)
4. Interior doors: Non-rising pins
5. Tips. Flat button and matching plug finished to match leaves
D. Number of hinges: Provide number of hinges indicated but not less than 3 hinges per door leaf for doors 90” or less in height and 1 additional hinge for each 30” of additional height.
E. Size of hinge leaves: 4.5” high, except 5” for doors 3’6” wide and wider.
F. Width of hinges: Shall be sufficient to clear trim projection when door swings 180 degrees.
G. Fire rated doors over 8’0” shall have heavy weight hinges.
H. All hinges SHALL be made of steel and have steel ball bearings.
2.05 KEYING
23.16 08 7100 - 4
A. All final cylinders and keying by owner.
B. Material supplier shall supply 0-bit cylinders for all doors with two keys per cylinder.
Contact NMSU OFS Lockshop for keyway. (575) 646-2209.
2.06 CYLINDRICAL TYPE LOCKSETS
A. All locksets and latch sets shall have steel cylindrical cases with interior parts made of steel or brass.
No plastic, die cast, or aluminum mechanisms will be allowed.
B. Chassis: Cylindrical design, corrosion - resistant plated cold-rolled steel.
C. Latch Retractors: Forged steel. Balance of inner parts: Corrosion-resistant plated steel, or stainless steel.
D. Lever Trim: Accessible design, independent operation, spring-cage supported, minimum 2" clearance from lever mid-point to door face.
E. Locks shall be of such construction that when locked, the door may be opened from within by using lever and without the use of a key or special knowledge.
F. Rosettes: Minimum 3-7/16" diameter for coverage of ANSI/DHI A115.18, 1994 door preparation, through-bolt lugs on both spring cages to fully engage this pattern.
G. Springs: Full compression type.
H. Strikes: 16 gage curved steel, bronze or brass with 1" deep box construction, lips of sufficient length to clear trim and protect clothing.
2.07 CLOSER AND DOOR CONTROL DEVICES
A. Surface type door closers shall be fully hydraulic, full rack and pinion action with a one piece forge steel piston. Barrier-free where designated.
B. Separate adjusting valves shall be provided for closing speed, latching speed and back-check.
C. Adjusting valves shall be made of a metal material, concealed, adjustable only with special wrench and shall be seated with “O” type rings.
D. Closers shall NOT be supplied with “Pressure Relief Valves”.
2.08 EXIT DEVICES
A. Exit devices: Von Duprin as scheduled with push-through pad design, no exposed touch bar fasteners, no exposed cavities when operated.
1. Provide certification by independent testing laboratory that specified devices have completed over 1,000,000 cycles and still perform in accordance to ANSI/BHMA A156.3 - 1997.
2. All internal parts shall be of cold-rolled steel with zinc dichromate coating.
3. Mechanism case shall have an average thickness of .140" Compression spring engineering.
4. Non-handled basic device design with center case interchangeable with all functions.
5. All devices shall have quiet return fluid dampeners.
6. All latchbolts for wide stile devices shall be deadlocking with 3/4" throw and have a self-lubricating coating to reduce friction and wear.
23.16 08 7100 - 5
7. Device push bar must release when a force of 32 pounds, or less, of pressure is applied when a force of 250 pounds is applied to the door.
8. Device shall bear UL label for fire and or panic as may be required.
9. All surface strikes shall be roller type and utilize a plate underneath to prevent movement.
B. Lever Trim: "Breakaway" design, forged brass or bronze escutcheon with a minimum of .130" thickness, match lockset lever design.
C. Removable Mullions: Removable with single turn of building key, securely reinstalled without need for key.
D. Furnish glass bead kits for vision lites where required. Devices for flush doors must fit flat on the door.
E. Exit devices shall be able to have latch-bolt monitoring switches, request to exit switches, electric latch-retraction, alarm kits, electric outside trim, or cylinder dogging added to the existing unit as the need arises for future electrified openings without replacing the original exit device.
2.09 MISCELLANEOUS DOOR TRIM UNITS
A. Material shall be brass, bronze or stainless steel as appropriate for required finish. Brass bronze material to be 0.050” minimum thickness, and stainless steel to be 0.050” minimum thickness. Edges of plates to be beveled and polished except lower edge can be square.
B. Width of plates shall be 2” less than door width.
C. Push Plates: Plate shall be 4” x 16”.
D. Pull Plates: Plate shall be 4” x 16”. Grip shall be extruded or cast bronze or stainless steel located on center of plate.
E. Smoke Seal shall be a self-adhesive SILICONE material measuring 3/8” x 1/4”.
2.10 TOOLS FOR MAINTENANCE
A. Furnish a complete set of specialized tools as needed for Owner’s continued adjustment, maintenance and removal or replacement of finish hardware.
PART 3 - EXECUTION
3.01 INSTALLATION
A. General: All finish hardware shall be installed by General Contractor.
B. Furnish all items of hardware with attachment screws, bolts, nuts, etc., as required to attach hardware to type of material involved and…