This Addendum No. 4 document issued by the Commonwealth of Kentucky Department for Facilities and Support Services Division of Engineering and Contract Administration pertains to Invitation to Bid (RFB-67-27) for interior renovations at the Prestonsburg Readiness Center operated by the Department of Military Affairs in Prestonsburg, Kentucky. The addendum, dated September 15, 2026, provides clarifications and modifications to the original bidding documents across architectural, mechanical, and electrical scopes of work. Key clarifications include: contractors must measure existing door frames for proper hardware sizing; hardware sets for doors 118 and 125 must include surface closers; Atlas Concorde USA porcelain stoneware has been stricken from design specifications; the IT room requires ladder-style cable tray rather than standard cable tray; structured cabling work is included in the general contractor package; existing two-post IT racks may be reused with additional wire management provisions; fiber backbone will be extended by the internet service provider to a new backboard in the IT room with the contractor responsible for connecting to owner's rack-mounted fiber switch; no central fire alarm system exists on the project; outdoor HVAC units require circuits sized to equipment manufacturer specifications; and revised electrical demolition and power/systems plan drawings (ED1.01 and E2.01) are provided as attachments.
The addendum clarifies contractor responsibilities for data rough-in, raceway work, and coordination with multiple trades and owner departments. Contractors must coordinate with the owner's IT department minimum 30 days in advance for equipment removal, coordinate with security for vault system removal, and provide new fully enclosed four-post server racks with patch panels. Surface-mounted raceways are specified for new receptacles and data outlets on existing walls, while devices in new block walls require concealed conduit. Bidders must acknowledge receipt of this addendum in their proposal submissions. The document contains three pages of 8.5x11 inch specifications and two pages of 30x42 inch drawings, incorporating multiple vendor clarifications on equipment selection, circuit sizing, fiber optic installations, and compliance with National Electrical Code requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-67-27
FOR: Interior Renovations Prestonsburg Readiness Center Department of Military Affairs Prestonsburg, Kentucky
DATE: September 15, 2026
RFB-785-2700000085
ADDENDUM NO. Four (4)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-67-27 For: Interior Renovations Prestonsburg Readiness Center Department of Military Affairs Prestonsburg, Kentucky
Janis Wilhoite, Statewide Procurement Analyst II Division of Engineering and Contract Administration
ADDENDUM NO.4
9/14/2026
To: All Planholders
From: alt32 Architecture | Design 310 Old Vine Street, Suite 300 Lexington, KY 40507-1582
Re: RFB-67-27 DMA – Prestonsburg RC Interior Renovation
This addendum is (3) Pages of 8-1/2 x 11 and (2) pages on 30 x 42.
The purpose of this addendum is to clarify further the requirements of the plans. The contractors are governed by the information in the addendum as if included in the plans. The addendum is part of the contract documents. The bidders shall acknowledge receipt of the addendum in their form of proposal.
1) Contractor shall be responsible for measuring existing frames for proper sizing of door leafs and preparations for door hardware.
2) Reference Specification Section 087100: Hardware sets for doors 118 and 125 shall include a surface closer as referenced in other sets.
3) Reference Specification Section 093000: Atlas Concorde USA “Sign” Colored Body Porcelain Stoneware to be stricken from the Design Basis.
See attached MEP items.
End of Addendum.
2265 Harrodsburg Road, Suite 402 • Lexington, KY 40504 Office 859.402.0221 • www.cceky.com Pg. 1
ADDENDUM FOUR – MECHANICAL AND ELECTRICAL
To: All Plan Holders
From: LUKE POWELL, PE Connolly Consulting Engineers, PLLC
Project: DMA Prestonsburg Readiness Center Prestonsburg, Kentucky
Release Date: September 14, 2026
This addendum is issued before award of contract to inform the bidders of revision/clarification to the bidding documents. All requirements contained in the bidding documents shall apply to this addendum, and the general character of the work called for in this addendum shall be the same as originally set forth in the applicable portions of the bidding documents for similar work, unless otherwise specified under this addendum. All incidental work necessitated by this addendum as required to complete the work shall be included in the bids, even though not particularly mentioned in this addendum. This addendum is hereby made a part of the bidding documents and shall be included in the contract and submitted with the proposal or bid. Bidder must acknowledge receipt of this and any other addenda issued related to the project in their proposal or bid.
Contractor Questions
Item No. 1: We are seeking clarification on which rack to use. Page 5 of 271100 scope calls for a CPI #66353- 703 (19" two post relay rack). Drawing E5.01 calls for a 4 post (APC NETSHELTER # SXAR3100 lockable enclosure).
1. It is acceptable to reuse the two existing 2-post racks. Install the existing racks in the new IT room.
Provide additional wire management, cable tray, etc. as required for a complete installation.
Item No. 2: Also need clarification on fiber backbone spec 271300. We do not see a hand off for a provider demarcation point on the drawings. Will the buildings service provider(s) be installing a new circuit into the new IT room #125? OR, Will the structured cabling contractor need to extend fiber optics cable to the existing rack area in the locker room?
1. The internet service provider will repull fiber backbone from building exterior to new new backboard in IT Room, using contractor provided conduit path. The contractor shall extend the fiber backbone from the internet service provider’s equipment at the backboard to the owner’s rack mounted, fiber switch.
2. Contractor shall extend existing conduit from existing rack area and terminate at backboard in new IT Room.
2265 Harrodsburg Road, Suite 402 • Lexington, KY 40504 Office 859.402.0221 • www.cceky.com Pg. 2
Item No. 3: As I was reading thru the "General Notes" on drawing E2.01, Note # 3 "Coordinate Rough in work with Owner", I thought that maybe the structured cabling was not in the GC package.
1. See clarification above.
Item No. 4: Please advise if the structured cabling is a part of the GC scope of work.
1. See clarification above.
Item No. 5: Will there be any fire alarm on this project.
1. There is no central fire alarm system in the building.
Item No. 6: Units CU-1,2,3 notes E11 show 40 amp circuits. Panel C schedule says 15amp 25amp and 15amp.
Unit CU-3 note E10 shows 60amp out of panel D.
1. Contractor shall provide circuit sized for each outdoor unit that meets the equipment manufacturer's
MCA/MAOP requirements.
Item No. 7: Data for rough in/raceway only on the electric scope.
1. Contractor responsible for all data rough-in and new data cabling.
Item No. 8: Please advise if the new IT room receives standard cable tray as specified in the 270536 spec. OR, A ladder style cable runway.
1. Cable tray within the new IT room shall be ladder style cable tray.
General Clarifications
Item No. 9: None.
Drawings Addenda
Item No. 10: Refer to the attached revised Drawing ED1.01 – ELECTRICAL DEMOLITION.
Item No. 11: Refer to the attached revised Drawing E2.01 – POWER AND SYSTEMS PLAN.
End of Addendum
3 3
3 3
SE
C
SEC
1 2 3 4 5 6 7 8 9 10 11
ADMINISTRATIVE OFFICE
COMMANDER
FILES
101A
FACILITY MAINTENANCE
ASSEMBLY HALL
FOOD PREP
SCULLERY
FOOD STORAGE
FLAMMABLE MATERIALS
LOCKER STORAGE
MECHANICAL ROOM
LEARNING CENTER
TRAINING AID STORAGE
LIBRARY & CLASSROOM
CLASSROOM
WOMEN
LOBBY
CORRIDOR
JANITOR
GYM
STORAGE
CLASSROOM
MDP
M
M2
EXIST
F-2
EXIST
F-3
EXIST
UH
EXIST
F-1
EXIST
UH
EXIST
UH
EXIST
UH
EXIST
EXHAUST
HOOD
EXIST
UH
EXIST
UH
D
EXIST
AHU-3
EXIST
AHU-4
EXIST
UH
EXIST
HP-6
EXIST
HP-7
EXIST
HP-4
EXIST
HP-5
EXIST
HP-3
EXIST
HP-2
EXIST
HP-1
EXIST
AHU-1
EXIST
AHU-2
EXIST
UH
C
REMOVE ASSOCIATED LIGHTING
CIRCUIT TO NEAREST J-BOX ABOVE
CEILING AND PREP CONDUCTORS TO
BE REWORKED FOR NEW LIGHTING.
TYPICAL ALL FIXTURES WITHIN
PROJECT AREA.
E13
E12
HDMI
EXIST
RH
EXIST
RH
WAP
WAP
WAP
REMOVE CEILING MOUNTED
WIRELESS ACCESS POINT AND TURN
OVER TO OWNER FOR STORAGE.
REMOVE ASSOCIATED DATA CABLE
BACK TO SOURCE. TYPICAL AT EACH
WAP.
DRILL HALL HIGHBAY
LED LIGHTS ARE
EXIST TO REMAIN.
DISCONNECT GAS HEATER
FROM POWER CIRCUIT.
TYPICAL.
TEMPORARILY REMOVE WALL
MOUNTED SECURITY EQUIPMENT
TO ACCOMMODATE
ARCHITECTURAL WALL FINISH
UPGRADES.
REMOVE EXIST TELECOMM
BACKBOARD, NETWORK
RACKS, ETC. TURN OVER TO
OWNER.
A B
REMOVE EGRESS FROG EYE
LIGHT. CIRCUIT TO REMAIN FOR
REUSE. TYPICAL.
WAP
REMOVE ELECTRIC UNIT
HEATER CIRCUIT &
DISCONNECT. CIRCUIT TO
REMAIN FOR REUSE. TYPICAL,
UON.
E2
EXIST
WH
E1
E1
E1
E1
REMOVE OUTDOOR UNIT
DISCONNECT. CIRCUIT TO
REMAIN FOR REUSE. TYPICAL,
UON.
REMOVE ALL ELECTRICAL
ITEMS WITHIN TEMPORARY
VAULT COMPLETE.
WAPE21
E21
E21
A. THICK DASHED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES
INDICATE EXISTING ITEMS TO REMAIN.
B. MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR
EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE
(OR CIRCUIT) IS INDICATED ON THE DRAWINGS, ENSURE THAT OTHER DEVICES OR
EQUIPMENT 'UPSTREAM' OR 'DOWNSTREAM' ON THE CIRCUITS SHALL REMAIN IN
'PRE-DEMOLITION' WORKING ORDER. 'LEFT-OVER' CIRCUIT BREAKERS SHALL REMAIN,
BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR PANELS BY
CONTRACTOR. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS
AFFECTED BY WORK ON THIS PROJECT.
C. LOCATION OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE
TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT
TO VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT
BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE
WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS
SATISFACTION THAT HE MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH
HE PROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES
AND EQUIPMENT BEING REMOVED BACK TO SOURCE, WHETHER INDICATED OR NOT
(UON).
E. COORDINATE WITH OWNER DISPOSAL OF ALL EQUIPMENT, FIXTURES, DEVICES, ETC.,
WHICH ARE INDICATED FOR DEMOLITION. SALVAGE AND TURN OVER REMOVED
ITEMS TO OWNER AT THEIR OPTION.
F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF
ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED WITH THEIR EQUIPMENT.
G. REMOVE ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS IN
ACCORDANCE WITH NEC REQUIREMENTS.
H. RELOCATE EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH EXISTING OR NEW
WORK OF OTHER TRADES TO PERMIT INSTALLATION OF DEVICES AND EQUIPMENT
SHOWN ON PLANS.
I. UNLESS OTHERWISE NOTED, PATCH SURFACE(S) TO MATCH ADJOINING
CONSTRUCTION AND FINISH FOR ANY ITEMS REMOVED BY THIS CONTRACTOR IN
EXISTING TO REMAIN WALLS, CEILINGS, FLOORS, ETC.
J. CONTRACTOR SHALL TURN OVER TO THE OWNER ALL REMOVED LED LIGHT
FIXTURES AND LED LAMPS.
K. CONTRACTOR SHALL REPLACE ALL EXIST TO REMAIN ELECTRICAL DEVICES (LIGHT
SWITCHES, RECEPTACLES, ETC.). ARCHITECT SHALL SELECT NEW DEVICE &
COVERPLATE COLOR. FIELD VERIFY EXACT QUANTITY AND LOCATIONS.
DEMOLITION GENERAL NOTES
A. REMOVE ALL EXIST DATA SYSTEMS COMPLETE INCLUDING ALL DEVICE OUTLETS,
CONDUIT, RACEWAYS, CABLING, ETC.
B. COORDINATE WITH OWNER'S IT DEPT MINIMUM 30-DAYS IN ADVANCE TO REMOVE ALL
NETWORKING EQUIPMENT AND INTERNET SERVICE EQUIPMENT. THE OWNER WILL
COORDINATE WITH THE INTERNET SERVICE PROVIDER TO REMOVE THE FIBER
INTERNET SERVICE TO THE BUILDING.
C. REMOVE DATA SYSTEMS EQUIPMENT RACKS AND TURN OVER TO OWNER.
D. COORDINATE WITH OWNER'S SECURITY DEPT MINIMUM 30-DAYS IN ADVANCE TO
REMOVE ALL VAULT SECURITY SYSTEM COMPONENTS. THE CONTRACTOR SHALL
MODIFY EXIST LINE VOLTAGE CIRCUITS WITHIN VAULT IN THE PRESENCE OF THE
OWNER.
SYSTEMS DEMOLITION GENERAL NOTES
N 5 5 10 15 20
1/8" = 1'-0"
FEETSCALE
DESCRIPTION OF REVISION
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
DECA LOG #
DRAWING NO.
AS BUILT DATE
DATE
DESCRIPTION OF REVISION DATE
ACCOUNT NO.
REVISION HISTORY OF DRAWINGS
2265 Harrodsburg Road, Suite 402 ▪ Lexington, KY 40504
Office 859.402.0221 ▪ www.cceky.com
A&E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
DRAWING INFORMATION
RTA
095CC7GPR0600
9/
/2
3:
:3
PM
C :\U se rs
\lu ke
\D oc um en ts \C
KY
PR
C -M
EP
_v
_l uk eV
W
BS
K.
rv t
ED1.01
ELECTRICAL DEMOLITION
DMA PRESTONBURG RCCKYPRC
07/26/2026
Author
Checker
1/8" = 1'-0"
ELECTRICAL DEMOLITION
SHEET NOTES
E1 REMOVE EXISTING POWER CIRCUIT COMPLETE BACK TO SOURCE PANEL AND
LABEL BREAKER AS SPARE.
E2 REMOVE ASSOCIATED POWER CIRCUIT BACK TO NEAREST J-BOX AND PREP
CONDUCTORS TO BE REUSED UNDER NEW WORK.
E12 REMOVE EXIST CIRCUITS FOR DISHWASHING ASSEMBLY (DISHWASHER,
BOOSTER HTR, DISPOSAL, DISHWASHER EXHAUST SYSTEM, ETC) COMPLETE
BACK TO SOURCE AND LABEL BREAKERS AS SPARE.
E13 REMOVE COMMERCIAL RANGE, RANGE HOOD, AND ANSUL SYSTEM CIRCUITS
COMPLETE BACK TO SOURCE AND LABEL BREAKERS AS SPARE.
E21 REMOVE EGRESS FROG EYE LIGHT FIXTURE COMPLETE. REMOVE CIRCUIT
BACK TO ABOVE CEILING AND FEED THRU TO DOWNSTREAM FIXTURES.
ADDENDUM NO. 5 09/14/26
R
EF
SE
C
SEC
1 2 3 4 5 6 7 8 9 10 11
ADMINISTRATIVE OFFICE
COMMANDER
FILES
101A
FACILITY MAINTENANCE
ASSEMBLY HALL
FOOD PREP
112SCULLERY
FOOD STORAGE
114FLAMMABLE MATERIALS
LOCKER STORAGE
MECHANICAL ROOM
LEARNING CENTER
TRAINING AID STORAGE
LIBRARY & CLASSROOM
CLASSROOM
MEN
121WOMEN
LOBBY
CORRIDOR
JANITOR
GYM
STORAGE
CLASSROOM
HP-1 HP-2
AHU-1
AHU-2
AHU-3
AHU-4
D
UH-3
UH-4
UH-5
CU-1 CU-2 CU-3CU-IT
WU-IT
GF-3MDP
GF-1
UH-2
M
M2 GF-2
C
A B
E2.01
E5
WH-1
WH-2
RP-1
HP
H P
H P
H P
HP
HP
E5
E5
E5
HP
HP
HP
E11
E11
HP-3
HP-4
UH-1
HP
E5
C -10,12 C -6,8
C -2,4
C -18,20 C -14,16
D -5,7
D -6,8
D -1,3
D -2,4
UH-6
E8
E8
UNIT STORAGE
ARMS VAULT
IT ROOM
OFFICE
HDMI
WAP
WAP
WAP
E11 E11 E10
C -32,34
WAP
E10
E10
E5
E6
E6
REWORK/EXTEND EXIST
208V/1P CIRCUIT FROM
DEMOLISHED CEILING
HEATER TO NEW WALL
HEATER.
RELOCATE EXIST J-BOX
ADJACENT TO AHU TO
ACCOMMODATE NEW
DUCTWORK. COORDINATE
WITH MECHANICAL.
M -1,3
M -2
M -4
M -5
FEED HOOD POWER
FROM KITCHEN
RECEPTACLE CIRCUIT.
EXTEND EXIST INTERNET
SERVICE 2" CONDUIT
CONCEALED ABOVE CEILING
FROM EXIST RACK TO NEW IT
ROOM BACKBOARD
REWORK EXIST DRINKING
FOUNTAIN RECEPTACLE
CONCEALED TO NEW LOCATION.
WAP
FEED NEW RECEPTACLES
FROM ROOM EXIST
RECEPTACLE CIRCUIT,
TYPICAL.
FEED NEW RECEPT FROM
ROOM'S EXIST RECEPT
CIRCUIT, TYPICAL.
PROVIDE NEW 12"X4"
LADDER TYPE CABLE
TRAY AROUND
PERIMETER OF ROOM.
COORDINATE WITH
DUCTWORK LAYOUT.
PROVIDE 48"x96"x3/4" FIRE
RETARDANT PLYWOOD
BACKBOARD FOR NEW FIBER
ENTRANCE. PROVIDE DEDICATED
RECEPTACLE BACKBOARD.
PROVIDE 4" EMT CONDUIT SLEEVES WITH INSULATED
GROUNDING BUSHINGS ON THE COMM CLOSET SIDE
AND NON-GROUNDING INSULATED BUSHINGS ON THE
CORRIDOR SIDE. PROVIDE QTY OF SLEEVES
NECESSARY TO MAINTAIN MAX 40% FILL RATIO (SEE
DATA CABLING SCHEDULE). PROVIDE ONE
ADDITIONAL SPARE 4"C. TERMINATE EACH END OF
CONDUIT ABOVE CABLE TRAY.
FIRESTOP WALL PENETRATION WHERE
REQUIRED. COORDINATE WITH
ARCHITECTURAL DRAWINGS.
PROVIDE WALL MOUNTED COPPER GROUNDING
BUSBAR IAW BUSBAR DETAIL. PROVIDE MINIMUM #4
INSULATED GND CONDUCTOR IN CONDUIT TO THE
BUILDING ELECTRICAL GROUNDING SYSTEM.
PROVIDE NEW FULLY ENCLOUSE 4-POST
SERVER RACK AND PATCH PANELS IAW
DETAIL. OWNER TO INSTALL ALL
NETWORKING EQUIPMENT IN RACK.
WU-IT
E4
E6
PROVIDE (1) DEDICATED QUAD RECEPTACLE ON
BACKBOARD FOR UTILITY DEMARC EQUIPMENT.
PROVIDE (2) DEDICATED QUAD RECEPTACLES AT
RACK ELEVATION FOR POWER TO NETWORKING
EQUIPMENT. COORDINATE RECEPTACLE
LOCATION WITH OWNER PRIOR TO ROUGH-IN.
E6
A. REFER TO ARCHITECTURAL ELEVATIONS AND CASEWORK DRAWINGS FOR
COORDINATION OF DEVICE LOCATIONS PRIOR TO ROUGH-IN.
B. PROVIDE ROUGH-IN J-BOX WITH 1"C TO ACCESSIBLE CEILING SPACE FOR ALL
WIRELESS ACCESS POINTS (WAP). COORDINATE WAP LOCATIONS WITH OWNER IT
REPRESENTATIVE PRIOR TO ROUGH-IN.
C. PROVIDE (2) J-HOOK PATHS AT BOTTOM OF BAR JOISTS FULL LENGTH OF MAIN
BUILDING CORRIDORS TO DATA SWITCH RACK. CONFIRM EXACT LOCATION WITH
OWNER PRIOR TO INSTALLATION.
D. PROVIDE HEAVY DUTY, NON-FUSED (UON), EQUIPMENT DISCONNECT FOR ALL
POWERED HVAC, PLUMBING, AND ELECTRICAL EQUIPMENT. DISCONNECT SHALL
HAVE AMPACITY AND VOLTAGE CHARACTERISTICS TO MEET EQUIPMENT
ELECTRICAL REQUIREMENTS. PROVIDE NEMA 3R OUTDOORS, UON.
E. PROVIDE ROUGH-IN FOR ALL OF OWNER'S SECURITY SYSTEM DEVICES, ACCESS
CONTROL SYSTEMS, DATA/INTERNET SYSTEMS. COORDINATE ALL DEVICE
LOCATIONS AND REQUIREMENTS WITH OWNER IT REPRESENTATIVE PRIOR TO
ROUGH-IN.
F. COORDINATE ALL DATA CONDUIT ROUTES WITH OWNER'S IT REPRESENTATIVE
PRIOR TO ROUGH-IN.
G. PROVIDE VINYL LABEL ON COVER PLATE OF EACH RECEPTACLE IN PROJECT AREA
INDICATING PANEL AND PANEL SPACE NUMBER FEEDING RECEPTACLE.
H. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE
COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE
ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER
TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS
IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT
NAMEPLATES OR ACCESS PANELS OR THROUGH ACCESS/MAINTENANCE
CLEARANCES OF EQUIPMENT BY OTHER TRADES.
I. PROVIDE NEW J-HOOK PATHWAYS FOR ALL EXISTING LOW-VOLTAGE CABLING
SYSTEMS ABOVE CEILING. PROVIDE J-HOOKS FROM EACH INDIVIDUAL ROOM AND IN
CORRIDORS BACK TO IT ROOM. PROVIDE QUANTITY OF J-HOOKS NECESSARY TO
SUPPORT ALL EXISTING CABLING AT A MAXIMUM OF 3-FOOT SPACING INTERVALS.
GENERAL NOTES
N 2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
5 5 10 15 20
1/8" = 1'-0"
FEETSCALE
DESCRIPTION OF REVISION
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
DECA LOG #
DRAWING NO.
AS BUILT DATE
DATE
DESCRIPTION OF REVISION DATE
ACCOUNT NO.
REVISION HISTORY OF DRAWINGS
2265 Harrodsburg Road, Suite 402 ▪ Lexington, KY 40504
Office 859.402.0221 ▪ www.cceky.com
A&E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
DRAWING INFORMATION
RTA
095CC7GPR0600
9/
/2
3:
:5
PM
C :\U se rs
\lu ke
\D oc um en ts \C
KY
PR
C -M
EP
_v
_l uk eV
W
BS
K.
rv t
E2.01
POWER AND SYSTEMS PLAN
DMA PRESTONBURG RCCKYPRC
07/26/2026
Author
Checker
1/8" = 1'-0"
POWER AND SYSTEMS PLAN
SHEET NOTES
E4 INDOOR UNIT POWER FED FROM OUTDOOR UNIT. SEE MECHANICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
E5 PROVIDE NEW HORSE POWER RATED SNAP SWITCH AND CONNECT NEW
MECHANICAL EQUIPMENT TO EXISTING CIRCUIT.
E6 PROVIDE NEW DEDICATED 120V, 20A CIRCUIT FED FROM PANEL C.
E8 REWORK EXISTING RECEPTACLE CIRCUITS TO CONNECT NEW RECEPTACLES.
E10 PROVIDE NEW CIRCUIT, INCLUDING DISCONNECT, 2#6 & #10G AND NEW 60A
BREAKER IN PANEL D.
E11 PROVIDE NEW CIRCUIT, INCLUDING DISCONNECT, 2#8 & #10G AND NEW 40A
BREAKER IN PANEL C.
1/4" = 1'-0"E2.01
ENLARGED IT ROOM POWER AND SYSTEMS PLAN2
ALL NEW RECEPTACLES AND DATA OUTLETS
INSTALLED ON EXIST TO REMAIN BLOCK WALLS
SHALL BE INSTALLED WITH SURFACE MOUNTED
RACEWAYS EQUAL TO WIREMOLD 700 SERIES
(POWER) AND WIREMOLD 2400 SERIES (DATA).
RACEWAY COLORS TO BE SELECTED BY ARCHITECT.
DEVICES INSTALLED IN NEW BLOCK WALLS SHALL BE
INSTALLED WITH CONDUIT & ROUGH-IN
CONCEALED/RECESSED IN WALL.
ADDENDUM NO. 5 09/14/26
| ADDENDUM NO 4.pdf |
| ADDENDUM NO 5.pdf |
| Prestonsburg RC MEP Addendum No5 2026-09-14.pdf |
File details come from the government source that posted it. Updated .