Addendum 4.pdf

PDF 781 KB Posted

Attached to
RFB-67-27 DMA - Prestonsburg RC Interior Renovations
Solicitation number
RFB 785 2700000085 5
Issued by
Elliott County, Kentucky

About this file

This Addendum No. 4 document issued by the Commonwealth of Kentucky Department for Facilities and Support Services Division of Engineering and Contract Administration pertains to Invitation to Bid (RFB-67-27) for interior renovations at the Prestonsburg Readiness Center operated by the Department of Military Affairs in Prestonsburg, Kentucky. The addendum, dated September 15, 2026, provides clarifications and modifications to the original bidding documents across architectural, mechanical, and electrical scopes of work. Key clarifications include: contractors must measure existing door frames for proper hardware sizing; hardware sets for doors 118 and 125 must include surface closers; Atlas Concorde USA porcelain stoneware has been stricken from design specifications; the IT room requires ladder-style cable tray rather than standard cable tray; structured cabling work is included in the general contractor package; existing two-post IT racks may be reused with additional wire management provisions; fiber backbone will be extended by the internet service provider to a new backboard in the IT room with the contractor responsible for connecting to owner's rack-mounted fiber switch; no central fire alarm system exists on the project; outdoor HVAC units require circuits sized to equipment manufacturer specifications; and revised electrical demolition and power/systems plan drawings (ED1.01 and E2.01) are provided as attachments.

The addendum clarifies contractor responsibilities for data rough-in, raceway work, and coordination with multiple trades and owner departments. Contractors must coordinate with the owner's IT department minimum 30 days in advance for equipment removal, coordinate with security for vault system removal, and provide new fully enclosed four-post server racks with patch panels. Surface-mounted raceways are specified for new receptacles and data outlets on existing walls, while devices in new block walls require concealed conduit. Bidders must acknowledge receipt of this addendum in their proposal submissions. The document contains three pages of 8.5x11 inch specifications and two pages of 30x42 inch drawings, incorporating multiple vendor clarifications on equipment selection, circuit sizing, fiber optic installations, and compliance with National Electrical Code requirements.

View the file

Other files

File Type Posted
Addendum 3.pdf PDF
Final_RFB_785_2700000085_3_SO_FORM.PDF PDF
Final_RFB_785_2700000085_1_SO_FORM.PDF PDF
Final_RFB_785_2700000085_4_SO_FORM.PDF PDF
Final_RFB_785_2700000085_2_SO_FORM.PDF PDF
Final_RFB_785_2700000085_5_SO_FORM.PDF PDF
Addendum 2.pdf PDF
Addendum 1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-67-27

FOR: Interior Renovations Prestonsburg Readiness Center Department of Military Affairs Prestonsburg, Kentucky

DATE: September 15, 2026

RFB-785-2700000085

ADDENDUM NO. Four (4)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-67-27 For: Interior Renovations Prestonsburg Readiness Center Department of Military Affairs Prestonsburg, Kentucky

Janis Wilhoite, Statewide Procurement Analyst II Division of Engineering and Contract Administration

ADDENDUM NO.4

9/14/2026

To: All Planholders

From: alt32 Architecture | Design 310 Old Vine Street, Suite 300 Lexington, KY 40507-1582

Re: RFB-67-27 DMA – Prestonsburg RC Interior Renovation

This addendum is (3) Pages of 8-1/2 x 11 and (2) pages on 30 x 42.

The purpose of this addendum is to clarify further the requirements of the plans. The contractors are governed by the information in the addendum as if included in the plans. The addendum is part of the contract documents. The bidders shall acknowledge receipt of the addendum in their form of proposal.

1) Contractor shall be responsible for measuring existing frames for proper sizing of door leafs and preparations for door hardware.

2) Reference Specification Section 087100: Hardware sets for doors 118 and 125 shall include a surface closer as referenced in other sets.

3) Reference Specification Section 093000: Atlas Concorde USA “Sign” Colored Body Porcelain Stoneware to be stricken from the Design Basis.

See attached MEP items.

End of Addendum.

2265 Harrodsburg Road, Suite 402 • Lexington, KY 40504 Office 859.402.0221 • www.cceky.com Pg. 1

ADDENDUM FOUR – MECHANICAL AND ELECTRICAL

To: All Plan Holders

From: LUKE POWELL, PE Connolly Consulting Engineers, PLLC

Project: DMA Prestonsburg Readiness Center Prestonsburg, Kentucky

Release Date: September 14, 2026

This addendum is issued before award of contract to inform the bidders of revision/clarification to the bidding documents. All requirements contained in the bidding documents shall apply to this addendum, and the general character of the work called for in this addendum shall be the same as originally set forth in the applicable portions of the bidding documents for similar work, unless otherwise specified under this addendum. All incidental work necessitated by this addendum as required to complete the work shall be included in the bids, even though not particularly mentioned in this addendum. This addendum is hereby made a part of the bidding documents and shall be included in the contract and submitted with the proposal or bid. Bidder must acknowledge receipt of this and any other addenda issued related to the project in their proposal or bid.

Contractor Questions

Item No. 1: We are seeking clarification on which rack to use. Page 5 of 271100 scope calls for a CPI #66353- 703 (19" two post relay rack). Drawing E5.01 calls for a 4 post (APC NETSHELTER # SXAR3100 lockable enclosure).

1. It is acceptable to reuse the two existing 2-post racks. Install the existing racks in the new IT room.

Provide additional wire management, cable tray, etc. as required for a complete installation.

Item No. 2: Also need clarification on fiber backbone spec 271300. We do not see a hand off for a provider demarcation point on the drawings. Will the buildings service provider(s) be installing a new circuit into the new IT room #125? OR, Will the structured cabling contractor need to extend fiber optics cable to the existing rack area in the locker room?

1. The internet service provider will repull fiber backbone from building exterior to new new backboard in IT Room, using contractor provided conduit path. The contractor shall extend the fiber backbone from the internet service provider’s equipment at the backboard to the owner’s rack mounted, fiber switch.

2. Contractor shall extend existing conduit from existing rack area and terminate at backboard in new IT Room.

2265 Harrodsburg Road, Suite 402 • Lexington, KY 40504 Office 859.402.0221 • www.cceky.com Pg. 2

Item No. 3: As I was reading thru the "General Notes" on drawing E2.01, Note # 3 "Coordinate Rough in work with Owner", I thought that maybe the structured cabling was not in the GC package.

1. See clarification above.

Item No. 4: Please advise if the structured cabling is a part of the GC scope of work.

1. See clarification above.

Item No. 5: Will there be any fire alarm on this project.

1. There is no central fire alarm system in the building.

Item No. 6: Units CU-1,2,3 notes E11 show 40 amp circuits. Panel C schedule says 15amp 25amp and 15amp.

Unit CU-3 note E10 shows 60amp out of panel D.

1. Contractor shall provide circuit sized for each outdoor unit that meets the equipment manufacturer's

MCA/MAOP requirements.

Item No. 7: Data for rough in/raceway only on the electric scope.

1. Contractor responsible for all data rough-in and new data cabling.

Item No. 8: Please advise if the new IT room receives standard cable tray as specified in the 270536 spec. OR, A ladder style cable runway.

1. Cable tray within the new IT room shall be ladder style cable tray.

General Clarifications

Item No. 9: None.

Drawings Addenda

Item No. 10: Refer to the attached revised Drawing ED1.01 – ELECTRICAL DEMOLITION.

Item No. 11: Refer to the attached revised Drawing E2.01 – POWER AND SYSTEMS PLAN.

End of Addendum

3 3

3 3

SE

C

SEC

1 2 3 4 5 6 7 8 9 10 11

ADMINISTRATIVE OFFICE

COMMANDER

FILES

101A

FACILITY MAINTENANCE

ASSEMBLY HALL

FOOD PREP

SCULLERY

FOOD STORAGE

FLAMMABLE MATERIALS

LOCKER STORAGE

MECHANICAL ROOM

LEARNING CENTER

TRAINING AID STORAGE

LIBRARY & CLASSROOM

CLASSROOM

WOMEN

LOBBY

CORRIDOR

JANITOR

GYM

STORAGE

CLASSROOM

MDP

M

M2

EXIST

F-2

EXIST

F-3

EXIST

UH

EXIST

F-1

EXIST

UH

EXIST

UH

EXIST

UH

EXIST

EXHAUST

HOOD

EXIST

UH

EXIST

UH

D

EXIST

AHU-3

EXIST

AHU-4

EXIST

UH

EXIST

HP-6

EXIST

HP-7

EXIST

HP-4

EXIST

HP-5

EXIST

HP-3

EXIST

HP-2

EXIST

HP-1

EXIST

AHU-1

EXIST

AHU-2

EXIST

UH

C

REMOVE ASSOCIATED LIGHTING

CIRCUIT TO NEAREST J-BOX ABOVE

CEILING AND PREP CONDUCTORS TO

BE REWORKED FOR NEW LIGHTING.

TYPICAL ALL FIXTURES WITHIN

PROJECT AREA.

E13

E12

HDMI

EXIST

RH

EXIST

RH

WAP

WAP

WAP

REMOVE CEILING MOUNTED

WIRELESS ACCESS POINT AND TURN

OVER TO OWNER FOR STORAGE.

REMOVE ASSOCIATED DATA CABLE

BACK TO SOURCE. TYPICAL AT EACH

WAP.

DRILL HALL HIGHBAY

LED LIGHTS ARE

EXIST TO REMAIN.

DISCONNECT GAS HEATER

FROM POWER CIRCUIT.

TYPICAL.

TEMPORARILY REMOVE WALL

MOUNTED SECURITY EQUIPMENT

TO ACCOMMODATE

ARCHITECTURAL WALL FINISH

UPGRADES.

REMOVE EXIST TELECOMM

BACKBOARD, NETWORK

RACKS, ETC. TURN OVER TO

OWNER.

A B

REMOVE EGRESS FROG EYE

LIGHT. CIRCUIT TO REMAIN FOR

REUSE. TYPICAL.

WAP

REMOVE ELECTRIC UNIT

HEATER CIRCUIT &

DISCONNECT. CIRCUIT TO

REMAIN FOR REUSE. TYPICAL,

UON.

E2

EXIST

WH

E1

E1

E1

E1

REMOVE OUTDOOR UNIT

DISCONNECT. CIRCUIT TO

REMAIN FOR REUSE. TYPICAL,

UON.

REMOVE ALL ELECTRICAL

ITEMS WITHIN TEMPORARY

VAULT COMPLETE.

WAPE21

E21

E21

A. THICK DASHED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES

INDICATE EXISTING ITEMS TO REMAIN.

B. MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR

EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE

(OR CIRCUIT) IS INDICATED ON THE DRAWINGS, ENSURE THAT OTHER DEVICES OR

EQUIPMENT 'UPSTREAM' OR 'DOWNSTREAM' ON THE CIRCUITS SHALL REMAIN IN

'PRE-DEMOLITION' WORKING ORDER. 'LEFT-OVER' CIRCUIT BREAKERS SHALL REMAIN,

BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR PANELS BY

CONTRACTOR. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS

AFFECTED BY WORK ON THIS PROJECT.

C. LOCATION OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE

TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT

TO VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT

BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE

WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS

SATISFACTION THAT HE MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH

HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES

AND EQUIPMENT BEING REMOVED BACK TO SOURCE, WHETHER INDICATED OR NOT

(UON).

E. COORDINATE WITH OWNER DISPOSAL OF ALL EQUIPMENT, FIXTURES, DEVICES, ETC.,

WHICH ARE INDICATED FOR DEMOLITION. SALVAGE AND TURN OVER REMOVED

ITEMS TO OWNER AT THEIR OPTION.

F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF

ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED WITH THEIR EQUIPMENT.

G. REMOVE ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS IN

ACCORDANCE WITH NEC REQUIREMENTS.

H. RELOCATE EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH EXISTING OR NEW

WORK OF OTHER TRADES TO PERMIT INSTALLATION OF DEVICES AND EQUIPMENT

SHOWN ON PLANS.

I. UNLESS OTHERWISE NOTED, PATCH SURFACE(S) TO MATCH ADJOINING

CONSTRUCTION AND FINISH FOR ANY ITEMS REMOVED BY THIS CONTRACTOR IN

EXISTING TO REMAIN WALLS, CEILINGS, FLOORS, ETC.

J. CONTRACTOR SHALL TURN OVER TO THE OWNER ALL REMOVED LED LIGHT

FIXTURES AND LED LAMPS.

K. CONTRACTOR SHALL REPLACE ALL EXIST TO REMAIN ELECTRICAL DEVICES (LIGHT

SWITCHES, RECEPTACLES, ETC.). ARCHITECT SHALL SELECT NEW DEVICE &

COVERPLATE COLOR. FIELD VERIFY EXACT QUANTITY AND LOCATIONS.

DEMOLITION GENERAL NOTES

A. REMOVE ALL EXIST DATA SYSTEMS COMPLETE INCLUDING ALL DEVICE OUTLETS,

CONDUIT, RACEWAYS, CABLING, ETC.

B. COORDINATE WITH OWNER'S IT DEPT MINIMUM 30-DAYS IN ADVANCE TO REMOVE ALL

NETWORKING EQUIPMENT AND INTERNET SERVICE EQUIPMENT. THE OWNER WILL

COORDINATE WITH THE INTERNET SERVICE PROVIDER TO REMOVE THE FIBER

INTERNET SERVICE TO THE BUILDING.

C. REMOVE DATA SYSTEMS EQUIPMENT RACKS AND TURN OVER TO OWNER.

D. COORDINATE WITH OWNER'S SECURITY DEPT MINIMUM 30-DAYS IN ADVANCE TO

REMOVE ALL VAULT SECURITY SYSTEM COMPONENTS. THE CONTRACTOR SHALL

MODIFY EXIST LINE VOLTAGE CIRCUITS WITHIN VAULT IN THE PRESENCE OF THE

OWNER.

SYSTEMS DEMOLITION GENERAL NOTES

N 5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

DESCRIPTION OF REVISION

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

DECA LOG #

DRAWING NO.

AS BUILT DATE

DATE

DESCRIPTION OF REVISION DATE

ACCOUNT NO.

REVISION HISTORY OF DRAWINGS

2265 Harrodsburg Road, Suite 402 ▪ Lexington, KY 40504

Office 859.402.0221 ▪ www.cceky.com

A&E FILE NO.

DRAWING DATE

DRAWN BY

CHECKED BY

PHASE

RTA DATE

DRAWING INFORMATION

RTA

095CC7GPR0600

9/

/2

3:

:3

PM

C :\U se rs

\lu ke

\D oc um en ts \C

KY

PR

C -M

EP

_v

_l uk eV

W

BS

K.

rv t

ED1.01

ELECTRICAL DEMOLITION

DMA PRESTONBURG RCCKYPRC

07/26/2026

Author

Checker

1/8" = 1'-0"

ELECTRICAL DEMOLITION

SHEET NOTES

E1 REMOVE EXISTING POWER CIRCUIT COMPLETE BACK TO SOURCE PANEL AND

LABEL BREAKER AS SPARE.

E2 REMOVE ASSOCIATED POWER CIRCUIT BACK TO NEAREST J-BOX AND PREP

CONDUCTORS TO BE REUSED UNDER NEW WORK.

E12 REMOVE EXIST CIRCUITS FOR DISHWASHING ASSEMBLY (DISHWASHER,

BOOSTER HTR, DISPOSAL, DISHWASHER EXHAUST SYSTEM, ETC) COMPLETE

BACK TO SOURCE AND LABEL BREAKERS AS SPARE.

E13 REMOVE COMMERCIAL RANGE, RANGE HOOD, AND ANSUL SYSTEM CIRCUITS

COMPLETE BACK TO SOURCE AND LABEL BREAKERS AS SPARE.

E21 REMOVE EGRESS FROG EYE LIGHT FIXTURE COMPLETE. REMOVE CIRCUIT

BACK TO ABOVE CEILING AND FEED THRU TO DOWNSTREAM FIXTURES.

ADDENDUM NO. 5 09/14/26

R

EF

SE

C

SEC

1 2 3 4 5 6 7 8 9 10 11

ADMINISTRATIVE OFFICE

COMMANDER

FILES

101A

FACILITY MAINTENANCE

ASSEMBLY HALL

FOOD PREP

112SCULLERY

FOOD STORAGE

114FLAMMABLE MATERIALS

LOCKER STORAGE

MECHANICAL ROOM

LEARNING CENTER

TRAINING AID STORAGE

LIBRARY & CLASSROOM

CLASSROOM

MEN

121WOMEN

LOBBY

CORRIDOR

JANITOR

GYM

STORAGE

CLASSROOM

HP-1 HP-2

AHU-1

AHU-2

AHU-3

AHU-4

D

UH-3

UH-4

UH-5

CU-1 CU-2 CU-3CU-IT

WU-IT

GF-3MDP

GF-1

UH-2

M

M2 GF-2

C

A B

E2.01

E5

WH-1

WH-2

RP-1

HP

H P

H P

H P

HP

HP

E5

E5

E5

HP

HP

HP

E11

E11

HP-3

HP-4

UH-1

HP

E5

C -10,12 C -6,8

C -2,4

C -18,20 C -14,16

D -5,7

D -6,8

D -1,3

D -2,4

UH-6

E8

E8

UNIT STORAGE

ARMS VAULT

IT ROOM

OFFICE

HDMI

WAP

WAP

WAP

E11 E11 E10

C -32,34

WAP

E10

E10

E5

E6

E6

REWORK/EXTEND EXIST

208V/1P CIRCUIT FROM

DEMOLISHED CEILING

HEATER TO NEW WALL

HEATER.

RELOCATE EXIST J-BOX

ADJACENT TO AHU TO

ACCOMMODATE NEW

DUCTWORK. COORDINATE

WITH MECHANICAL.

M -1,3

M -2

M -4

M -5

FEED HOOD POWER

FROM KITCHEN

RECEPTACLE CIRCUIT.

EXTEND EXIST INTERNET

SERVICE 2" CONDUIT

CONCEALED ABOVE CEILING

FROM EXIST RACK TO NEW IT

ROOM BACKBOARD

REWORK EXIST DRINKING

FOUNTAIN RECEPTACLE

CONCEALED TO NEW LOCATION.

WAP

FEED NEW RECEPTACLES

FROM ROOM EXIST

RECEPTACLE CIRCUIT,

TYPICAL.

FEED NEW RECEPT FROM

ROOM'S EXIST RECEPT

CIRCUIT, TYPICAL.

PROVIDE NEW 12"X4"

LADDER TYPE CABLE

TRAY AROUND

PERIMETER OF ROOM.

COORDINATE WITH

DUCTWORK LAYOUT.

PROVIDE 48"x96"x3/4" FIRE

RETARDANT PLYWOOD

BACKBOARD FOR NEW FIBER

ENTRANCE. PROVIDE DEDICATED

RECEPTACLE BACKBOARD.

PROVIDE 4" EMT CONDUIT SLEEVES WITH INSULATED

GROUNDING BUSHINGS ON THE COMM CLOSET SIDE

AND NON-GROUNDING INSULATED BUSHINGS ON THE

CORRIDOR SIDE. PROVIDE QTY OF SLEEVES

NECESSARY TO MAINTAIN MAX 40% FILL RATIO (SEE

DATA CABLING SCHEDULE). PROVIDE ONE

ADDITIONAL SPARE 4"C. TERMINATE EACH END OF

CONDUIT ABOVE CABLE TRAY.

FIRESTOP WALL PENETRATION WHERE

REQUIRED. COORDINATE WITH

ARCHITECTURAL DRAWINGS.

PROVIDE WALL MOUNTED COPPER GROUNDING

BUSBAR IAW BUSBAR DETAIL. PROVIDE MINIMUM #4

INSULATED GND CONDUCTOR IN CONDUIT TO THE

BUILDING ELECTRICAL GROUNDING SYSTEM.

PROVIDE NEW FULLY ENCLOUSE 4-POST

SERVER RACK AND PATCH PANELS IAW

DETAIL. OWNER TO INSTALL ALL

NETWORKING EQUIPMENT IN RACK.

WU-IT

E4

E6

PROVIDE (1) DEDICATED QUAD RECEPTACLE ON

BACKBOARD FOR UTILITY DEMARC EQUIPMENT.

PROVIDE (2) DEDICATED QUAD RECEPTACLES AT

RACK ELEVATION FOR POWER TO NETWORKING

EQUIPMENT. COORDINATE RECEPTACLE

LOCATION WITH OWNER PRIOR TO ROUGH-IN.

E6

A. REFER TO ARCHITECTURAL ELEVATIONS AND CASEWORK DRAWINGS FOR

COORDINATION OF DEVICE LOCATIONS PRIOR TO ROUGH-IN.

B. PROVIDE ROUGH-IN J-BOX WITH 1"C TO ACCESSIBLE CEILING SPACE FOR ALL

WIRELESS ACCESS POINTS (WAP). COORDINATE WAP LOCATIONS WITH OWNER IT

REPRESENTATIVE PRIOR TO ROUGH-IN.

C. PROVIDE (2) J-HOOK PATHS AT BOTTOM OF BAR JOISTS FULL LENGTH OF MAIN

BUILDING CORRIDORS TO DATA SWITCH RACK. CONFIRM EXACT LOCATION WITH

OWNER PRIOR TO INSTALLATION.

D. PROVIDE HEAVY DUTY, NON-FUSED (UON), EQUIPMENT DISCONNECT FOR ALL

POWERED HVAC, PLUMBING, AND ELECTRICAL EQUIPMENT. DISCONNECT SHALL

HAVE AMPACITY AND VOLTAGE CHARACTERISTICS TO MEET EQUIPMENT

ELECTRICAL REQUIREMENTS. PROVIDE NEMA 3R OUTDOORS, UON.

E. PROVIDE ROUGH-IN FOR ALL OF OWNER'S SECURITY SYSTEM DEVICES, ACCESS

CONTROL SYSTEMS, DATA/INTERNET SYSTEMS. COORDINATE ALL DEVICE

LOCATIONS AND REQUIREMENTS WITH OWNER IT REPRESENTATIVE PRIOR TO

ROUGH-IN.

F. COORDINATE ALL DATA CONDUIT ROUTES WITH OWNER'S IT REPRESENTATIVE

PRIOR TO ROUGH-IN.

G. PROVIDE VINYL LABEL ON COVER PLATE OF EACH RECEPTACLE IN PROJECT AREA

INDICATING PANEL AND PANEL SPACE NUMBER FEEDING RECEPTACLE.

H. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE

COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE

ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER

TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS

IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT

NAMEPLATES OR ACCESS PANELS OR THROUGH ACCESS/MAINTENANCE

CLEARANCES OF EQUIPMENT BY OTHER TRADES.

I. PROVIDE NEW J-HOOK PATHWAYS FOR ALL EXISTING LOW-VOLTAGE CABLING

SYSTEMS ABOVE CEILING. PROVIDE J-HOOKS FROM EACH INDIVIDUAL ROOM AND IN

CORRIDORS BACK TO IT ROOM. PROVIDE QUANTITY OF J-HOOKS NECESSARY TO

SUPPORT ALL EXISTING CABLING AT A MAXIMUM OF 3-FOOT SPACING INTERVALS.

GENERAL NOTES

N 2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

DESCRIPTION OF REVISION

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

DECA LOG #

DRAWING NO.

AS BUILT DATE

DATE

DESCRIPTION OF REVISION DATE

ACCOUNT NO.

REVISION HISTORY OF DRAWINGS

2265 Harrodsburg Road, Suite 402 ▪ Lexington, KY 40504

Office 859.402.0221 ▪ www.cceky.com

A&E FILE NO.

DRAWING DATE

DRAWN BY

CHECKED BY

PHASE

RTA DATE

DRAWING INFORMATION

RTA

095CC7GPR0600

9/

/2

3:

:5

PM

C :\U se rs

\lu ke

\D oc um en ts \C

KY

PR

C -M

EP

_v

_l uk eV

W

BS

K.

rv t

E2.01

POWER AND SYSTEMS PLAN

DMA PRESTONBURG RCCKYPRC

07/26/2026

Author

Checker

1/8" = 1'-0"

POWER AND SYSTEMS PLAN

SHEET NOTES

E4 INDOOR UNIT POWER FED FROM OUTDOOR UNIT. SEE MECHANICAL

DRAWINGS FOR ADDITIONAL INFORMATION.

E5 PROVIDE NEW HORSE POWER RATED SNAP SWITCH AND CONNECT NEW

MECHANICAL EQUIPMENT TO EXISTING CIRCUIT.

E6 PROVIDE NEW DEDICATED 120V, 20A CIRCUIT FED FROM PANEL C.

E8 REWORK EXISTING RECEPTACLE CIRCUITS TO CONNECT NEW RECEPTACLES.

E10 PROVIDE NEW CIRCUIT, INCLUDING DISCONNECT, 2#6 & #10G AND NEW 60A

BREAKER IN PANEL D.

E11 PROVIDE NEW CIRCUIT, INCLUDING DISCONNECT, 2#8 & #10G AND NEW 40A

BREAKER IN PANEL C.

1/4" = 1'-0"E2.01

ENLARGED IT ROOM POWER AND SYSTEMS PLAN2

ALL NEW RECEPTACLES AND DATA OUTLETS

INSTALLED ON EXIST TO REMAIN BLOCK WALLS

SHALL BE INSTALLED WITH SURFACE MOUNTED

RACEWAYS EQUAL TO WIREMOLD 700 SERIES

(POWER) AND WIREMOLD 2400 SERIES (DATA).

RACEWAY COLORS TO BE SELECTED BY ARCHITECT.

DEVICES INSTALLED IN NEW BLOCK WALLS SHALL BE

INSTALLED WITH CONDUIT & ROUGH-IN

CONCEALED/RECESSED IN WALL.

ADDENDUM NO. 5 09/14/26

ADDENDUM NO 4.pdf
ADDENDUM NO 5.pdf
Prestonsburg RC MEP Addendum No5 2026-09-14.pdf

File details come from the government source that posted it. Updated .