Addendum 2.pdf
PDF 1 MB Posted
- Solicitation number
- RFB 785 2700000128 4
- Issued by
- Kentucky
About this file
This is Addendum No. 2 to Invitation to Bid (RFB-83-27) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for controls upgrades at Campbell Regional Juvenile Detention Center operated by the Department of Juvenile Justice in Newport, Kentucky. The project, identified as KFI Project Number 25-1309.00, involves upgrading the building automation system controls for a multizone air handling unit (AHU) and related HVAC equipment at the detention center. The addendum modifies the original bid specifications and drawings to clarify temperature sensor requirements and valve information. The official bid opening date has been moved to October 22, 2026, at 1:30 P.M. Eastern Time. Key technical changes include the requirement to furnish and install nine zone discharge air temperature sensors (one for each zone) and five return duct temperature sensors for zones 1, 2, 3, 5, and 7, as well as corrections to plan sheets IC200, IC600, and IC700 to clarify sensor locations and specifications.
The addendum provides detailed specifications for hardware and software points related to the multizone AHU system, including temperature sensors, control damper actuators, control valves, smoke detectors, and related instrumentation. All work must comply with the contract documents and subsequent addenda. The existing valve schedule indicates that three control valves—a multizone AHU hot water valve (3-inch, 206 GPM), a chilled water valve (2.5-inch, 94.2 GPM), and a boiler/hot water system valve (2.5-inch, 101 GPM)—are to be replaced in accordance with original bid documents as like-type, size, and performance characteristics that comply with specification sections 250000 and 250500 for integrated automation and HVAC instrumentation and control.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-83-27
FOR: Controls Upgrades Campbell Regional Juvenile Detention Center Department of Juvenile Justice Newport, Kentucky
DATE: October 12, 2026
RFB-2700000128
ADDENDUM NO. Two (2)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
Item 2: Official Bid opening date has been moved to October 22, 2026, at 1:30 P.M. Eastern Time. All other bidding information will remain the same.
END OF ADDENDUM
Invitation to Bid No. RFB-83-27 For: Controls Upgrades Campbell Regional Juvenile Detention Center Department of Juvenile Justice Newport, Kentucky
Janis Wilhoite, Statewide Procurement Analyst II Division of Engineering and Contract Administration
ADDENDUM
Page 1 of 1 Find a way.
Date: 10/8/2026 Project: DJJ – Campbell Controls Upgrades
KFI Project Number: 25-1309.00
Addendum Number: 02
THIS ADDENDUM IS A CONTRACT DOCUMENT AND MAY APPLY TO ANY OR ALL CONTRACTS AND SUBCONTRACTS UNLESS OTHERWISE SPECIFIED HEREIN OR SHOWN ON THE ATTACHED DRAWINGS (IF ANY). ALL WORK REQUIRED BY THIS ADDENDUM SHALL BE IN COMPLETE ACCORD WITH THE CONTRACT DOCUMENTS AND SUBSEQUENT ADDENDA THERETO. THE ITEMS LISTED IN THIS ADDENDUM ARE NOT IN ANY ORDER IN REGARD TO THE DRAWINGS OR THE SPECIFICATIONS. ALL CONTRACTORS ARE CAUTIONED TO EXAMINE EACH AND EVERY ITEM OF THIS ADDENDUM.
THE FOLLOWING CHANGES OR CLARIFICATIONS TO THE PLANS & SPECIFICATIONS SHALL BE INCLUDED AS PART OF THE CONTRACT DOCUMENT
CONTROL CHANGES
1. There are nine zones for the Multi-zone AHU. The current IC600 diagram shows to provide four discharge air temperature sensors and four wall space zone sensors. The AHU points list on IC601 shows only one discharge air temperature sensor. Nine zone discharge air temperature sensors shall be furnished and installed, one for each zone. In addition, five return duct temperature sensors shall be installed for zones 1, 2, 3, 5, and 7.
SPECIFICATION CHANGES:
1. NONE
PLAN SHEET CHANGES:
1. IC200 – Corrected keynotes to better clarify temperature sensors that are a return duct temperature senor and wall zone sensor for the Multizone AHU.
2. IC600 – Added clarifying information for discharge air, return air, and wall temperature sensors.
3. IC600 – Added additional temperature sensors per the Controls Change described in Controls Changes above.
4. IC700 – Added existing valve information to sheet. Valve information is based on Owner-provided As-
Built drawings. Valves are to be replaced per original bid drawings.
END OF ADDENDUM
SALLY PORT
JANITOR
INTAKE
INTERVIEW
STORAGE
HOLDING
HOLDING
DR. OFFICE
122B STORAGE
122C
COMM. CLOSET
RECEIVING
FREEZERCOOLERSTORAGE
115C
KITCHEN
JAN.
115A
OFFICE
115B
TOILET
LIBRARY
MULTIUSE
CLASSROOM
MULTIUSE
OFFICE
137A
TEACHERJAN/STOR
COUNSELOR
206G
CELL
206H
CELL
206I
CELL
206J
CELL
206K
CELL
206L
CELL
206M
CELL
206F
CELL
206E
CELL
206D
CELL
206C
CELL
206B
DAYROOM
CELL
205F
CELL
205E
CELL
205D
CELL
205C
CELL
205B
CELL
205A
COUNSELOR
205G
CELL
205H
CELL
205I
CELL
205J
CELL
205K
CELL
205L
CELL
203I
CELL
203H
CELL
203G
CELL
203F
SPACE
203E
MULTIUSE
DAYROOM
CELL
203D
CELL
203C
CELL
203B
SHOWER
203A
ELEC
MECH/
SHOWER
201Q
CELL
201P
CELL
201O
CELL
201N
CELL
201M
DAYROOM
CELL
201L
CELL
201K
CELL
201J
SPACE
201I
MULTIUSE
CELL
201H
CELL
201G
CELL
201F
CELL
201E
CELL
201D
CELL
201C
CELL
201B
SPACE
MULTIUSE
SHOWER
201A
CONTROL
TOILET
204A
SHOWER
205M
SHOWER
206A
TOILET
HOLDING
208 STAFF
TOILET
STOR.
111A
ROOM
MULTIUSE
TOILET
100A
LOCKERS
100B
LOBBY
100 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CASEWORKERS
TOILET
TOILET
PROPERTY ROOM
ISSUE &
RECORDS
MEDICALMEDICAL
EXAM
122D CORRIDOR
123TOILET
122A
LAUNDRY
VISITING
CONTACT
NON
VEST.
CORRIDOR
VEST.
RECEPTION
102 WORKROOM
TOILET
CORRIDOR
STOR.
GENERAL
DAYROOM
SHOWER
CLASSROOM
CLASSROOM
CORRIDOR
CLASSROOM
CLASSROOM
OFFICE
VEST.
OFFICE
MECH./ELEC.
CORRIDOR
STORAGE
109 STORAGE VESTIBULE
BREAKROOM
T
CP-MECH-BAS
UNIT HEATER 2
AHU
(EXISTING)
CHILLER
(EXISTING)
B1
B2
T
T
TT
TT
T
TT
TT
T
T
UNIT HEATER 1
T
T
KITCHEN HOOD
(EXISTING)
EXISTING FIRE ALARM
PANEL
IC200A
AC-1
AC-2
TT
FLOOR PLAN LEGEND
BAS CONTROL PANEL
UNITARY CONTROLLER
MECHANICAL EQUIPMENT
2021 KFI Engineers©
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
2343 Alexandria Drive Suite 200 Lexington, KY 40504 Tel: 859-271-3246 Email: kfi@kfi-eng.com
523CB9ZCA0800
09/02/2026
Au to de sk
D oc s:
//2
5-
D
JJ
C am pb el l C o.
V en til at io n
U pg ra de s /M
P2 5_
D
JJ
-C am pb el
C o.
Ve nt ila tio n U pg ra de s.
rv t
/8
/2
2:
:2
PM
RTS
25-1309.00
09/02/2026
TCC
CONTROLS OVERALL PLAN - LEVEL 01
IC200
RTA
DJJ - CAMPBELL CONTROLS UPGRADES
1/8" = 1'-0"IC200
1 CONTROLS OVERALL PLAN - LEVEL 01
KEYNOTES:
# KEYNOTE
01 REPLACE EXISTING RETURN DUCT TEMPERATURE SENSOR WITH NEW. LOCATION IS APPROXIMATE.
02 REPLACE EXISTING THERMOSTAT FOR MECHANICAL ROOM SUPPLY FAN WITH NEW TEMPERATURE
SENSOR.
03 REUSE EXISTING CONTROL PANEL. PROVIDE NEW CONTROLS FOR EXISTING AHU. DEMOLISHED
CONTROLLERS TO BE RETURNED TO OWNER.
04 RELOCATE EXISTING MICROZONE CONTROLLER, MZ-4, OUTSIDE OF EXISTING CONTROL PANEL.
INTEGRATE MZ-4 MICROZONE CONTROLLER INTO NEW CP-MECH-WATER CONTROL PANEL.
05 REPLACE EXISTING KITCHEN EXHAUST HOOD OVERRIDE SWITCH AND MAKE-UP AIR UNIT SENSORS
CONTROLS WITH NEW. INTEGRATE NEW MAU SENSORS AND KITCHEN HOOD EXHAUST FAN
CONTROLS INTO BAS.
06 REPLACE EXISTING THERMOSTAT WITH NEW BACNET MSTP WALL CONTROLLER. INTEGRATE
THERMOSTAT CONTROLS WITH AIR CONDITIONING LOCATED IN MECHANICAL ROOM 101. INTEGRATE
BACNET COMMUNICATIONS INTO NEW BAS.
07 PROVIDE NEW UNITARY CONTROLLER FOR CONTROLLING EXISTING UNIT HEATER. INTEGRATE NEW
UNITARY CONTROLLER INTO NEW BAS.
08 INTEGRATE EXISTING FIRE ALARM PANEL INTO NEW BAS.
09 REPLACE EXISTING THERMOSTAT WITH NEW TEMPERATURE SENSOR. INTEGRATE NEW
TEMPERATURE SENSOR INTO NEW BAS CONTROLLER.
10 REPLACE EXISTING WALL SPACE SENSOR WITH NEW. LOCATION IS APPROXIMATE.
No: Date: Revision:
1 10.08.26 Addendum 02
1 10.08.26 Addendum 02
C E N ENFO
SE
ENOIS AL GN I
E
AT
PR
S
T K
E
S.
JOSHUA
KRACK
L I S
D RE
Y
EFO K
CTN U
29466
2021 KFI Engineers©
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
2343 Alexandria Drive Suite 200 Lexington, KY 40504 Tel: 859-271-3246 Email: kfi@kfi-eng.com
523CB9ZCA0800
09/02/2026
Au to de sk
D oc s:
//2
5-
D
JJ
C am pb el l C o.
V en til at io n
U pg ra de s /M
P2 5_
D
JJ
-C am pb el
C o.
Ve nt ila tio n U pg ra de s.
rv t
/8
/2
2:
:2
PM
RTS
25-1309.00
09/02/2026
TCC
MULTIZONE AIR HANDLING UNIT
IC600
RTA
DJJ - CAMPBELL CONTROLS UPGRADES
FLOW DIAGRAM - MULTIZONE AHU SEQUENCE
The system is constant static pressure, constant air volume with return/exhaust fan tracking. Supply and return/exhaust fans are driven by constant speed drives. The air handling unit consists of supply fan, economizer dampers, a cold deck with cooling coil, a hot deck with a heating coil, nine (9) individual zone mixing dampers. Systems operate 24 hours per day. An operator override to OFF is available through software.
When the supply fan motor starter H-O-A switch is in the AUTO position, the DDC will close the control system start/stop relay to energize the system and the AHU supply fan will start. The return fans 1 and 2 will start via hard-wire interlock after the supply fan starts. The DDC will then start exhaust fans EF-1,2,3,4,6,7,8,9.
When the supply and return fans are operating, the control dampers are either positioned for full recirculation of air, positioned to introduce minimum outside air, or modulated to maintain mixed air temperature.
The outdoor air conditions that will allow economizer use in lieu of chilled water will be determined through the BAS. When the outside air temperature is less than 65°F (adj.), the unit shall be able to economize. While the unit is in economizing mode, the outside air damper shall be able to modulate between the minimum outside air damper position and 100% open. When the outside air temperature has risen above the economizer setpoint, plus 4°F (adj.), economizer mode shall be disabled. The outside air, return air, and relief air dampers are modulated by the mixed air temperature control between minimum position and fully open to maintain a mixed air temperature of 55°F.
A CO2 sensor, located in the mixed air stream will monitor CO2 concentration to control the damper position between “Normal Minimum Outside Air Quantity” and “Absolute Minimum Outside Air Quantity”. When the sensor detects a rise in CO2 concentration, the outside air damper will open to its “Normal Minimum” position. On a decrease in CO2 concentration the outside air damper will close to a point which satisfies the sensor or to its “Absolute Minimum” position (5%). Should the CO2 level, at the sensor location, rise to an unacceptable level for a period greater than two minutes, an alarm will be sent to the BAS, providing time and date of alarm.
Filter condition is monitored by a pressure gauge and a differential pressure sensor. When the pressure drop across the filter exceeds a predetermined setpoint, an alarm indication will be sent to the BAS providing time and date of the alarm indicating a filter change is needed.
A cold deck temperature controller with its temperature transmitter in the cold deck discharge modulates the cooling coil valve to maintain its setpoint temperature during AHU operation.
A hot deck temperature controller with its temperature transmitter in the heating coil discharge modulates the heating coil valve to maintain its temperature setpoint. Outside air temperature controllers lower the setpoint of the hot deck controller as outside air temperature rises. On a fall in outside air temperature, the reverse occurs. The reset schedule is as follows: When outside air temperature is 0°F, hot deck setpoint will be 100°F; when outside air is 60°F, the hot deck setpoint will be reset to 70°F.
Each zone space sensor/thermostat or duct-mounted remote duct sensor modulates its respective zone mixing dampers between hot deck and cold deck to maintain space or remote duct temperature.
Unit Protection: Safety shutdowns shall be accomplished via hard-wired shutdown circuits. At a minimum, the unit shall shut down for the following reasons:
Freezestat Alarm (Requires Manual Reset) When the freezestat low temperature switch is activated, a freezestat alarm shall be sent to the BAS.
The outside air and exhaust air dampers shall close. The return air damper shall open.
The supply and return fans shall be disabled.
The hot water pump shall be enabled. The hot water control valve shall modulate to maintain a heating coil discharge temperature of 55°F (adj.).
Fire Alarm System Shutdown (Reset by Fire Alarm System) Fire alarm control modules shall be provided, by Others, for the outside air dampers, exhaust air dampers, and return air dampers. Control modules shall be hardwired to the dampers so that when a fire alarm signal is initiated the dampers fail to their fail safe position.
Fire alarm control modules shall be provided, by Others, for the supply and return fans. Control modules shall be hardwired to the fans so that when a fire alarm signal is initiated, the fans shall be disabled.
The unit shall be disabled when smoke is detected by either the supply or return air smoke duct detectors.
No: Date: Revision:
1 10.08.26 Addendum 02
1 10.08.26 Addendum 02
C E N ENFO
SE
ENOIS AL GN I
E
AT
PR
S
T K
E
S.
JOSHUA
KRACK
L I S
D RE
Y
EFO K
CTN U
29466
Qty Device Tag Description Furnished By Installed By Wired and Terminated By
4 ZNT ZONE TEMPERATURE SENSOR
CONTRACTOR CONTRACTOR CONTRACTOR
10 TT DISCHARGE AIR TEMPERATURE SENSOR
5 TT RETURN AIR TEMPERATURE SENSOR
1 TT OUTSIDE AIR TEMPERATURE SENSOR
3 AT AVERAGING TEMPERATURE SENSOR
1 MT RETURN AIR HUMIDITY SENSOR
1 AQ AIR QUALITY SENSOR
17 CD CONTROL DAMPER ACTUATOR
2 CV CONTROL VALVE
3 ASH DUCT SMOKE DETECTOR
4 ISL CURRENT SENSING RELAY
1 TSL FREEZESTAT
4 CMD GENERAL PURPOSE RELAY - FAN / PUMP COMMAND
HARDWARE POINTS SOFTWARE POINTS Show on Graphic
CEMCS
Integration Tag Point Name Full Point Name Point Description Wiring Type AI AO BI BO AV BV Loop Sched Trend Alarm
ZNT ZN4_T Archibus#_01_XXX_IC_AHU_ZN4_T ZONE 4 WALL SPACE TEMPERATURE TEMP SENSOR X X X X X ZNT ZN6_T Archibus#_01_XXX_IC_AHU_ZN6_T ZONE 6 WALL SPACE TEMPERATURE TEMP SENSOR X X X X X ZNT ZN8_T Archibus#_01_XXX_IC_AHU_ZN8_T ZONE 8 WALL SPACE TEMPERATURE TEMP SENSOR X X X X X ZNT ZN9_T Archibus#_01_XXX_IC_AHU_ZN9_T ZONE 9 WALL SPACE TEMPERATURE TEMP SENSOR X X X X X SPT ZN4_T_SPT Archibus#_01_XXX_IC_AHU_ZN4_T_SPT ZONE 4 TEMPERATURE SETPOINT TEMP SENSOR X X X X X SPT ZN6_T_SPT Archibus#_01_XXX_IC_AHU_ZN6_T_SPT ZONE 6 TEMPERATURE SETPOINT TEMP SENSOR X X X X X SPT ZN8_T_SPT Archibus#_01_XXX_IC_AHU_ZN8_T_SPT ZONE 8 TEMPERATURE SETPOINT TEMP SENSOR X X X X X SPT ZN9_T_SPT Archibus#_01_XXX_IC_AHU_ZN9_T_SPT ZONE 9 TEMPERATURE SETPOINT TEMP SENSOR X X X X X TT RA1_T Archibus#_01_XXX_IC_AHU_RA1_T ZONE 1 RETURN AIR TEMPERATURE TEMP SENSOR X X X X X TT RA2_T Archibus#_01_XXX_IC_AHU_RA2_T ZONE 2 RETURN AIR TEMPERATURE TEMP SENSOR X X X X X TT RA3_T Archibus#_01_XXX_IC_AHU_RA3_T ZONE 3 RETURN AIR TEMPERATURE TEMP SENSOR X X X X X TT RA5_T Archibus#_01_XXX_IC_AHU_RA5_T ZONE 5 RETURN AIR TEMPERATURE TEMP SENSOR X X X X X TT RA7_T Archibus#_01_XXX_IC_AHU_RA7_T ZONE 7 RETURN AIR TEMPERATURE TEMP SENSOR X X X X X TT DA_T Archibus#_01_XXX_IC_AHU_DA_T DISCHARGE AIR TEMPERATURE SENSOR TEMP SENSOR X X X X X TT DA1_T Archibus#_01_XXX_IC_AHU_DA1_T ZONE 1 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA2_T Archibus#_01_XXX_IC_AHU_DA2_T ZONE 2 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA3_T Archibus#_01_XXX_IC_AHU_DA3_T ZONE 3 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA4_T Archibus#_01_XXX_IC_AHU_DA4_T ZONE 4 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA5_T Archibus#_01_XXX_IC_AHU_DA5_T ZONE 5 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA6_T Archibus#_01_XXX_IC_AHU_DA6_T ZONE 6 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA7_T Archibus#_01_XXX_IC_AHU_DA7_T ZONE 7 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA8_T Archibus#_01_XXX_IC_AHU_DA8_T ZONE 8 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT DA9_T Archibus#_01_XXX_IC_AHU_DA9_T ZONE 9 DISCHARGE AIR TEMPERATURE TEMP SENSOR X X X X X TT OA_T Archibus#_01_XXX_IC_AHU_OA_T OUTSIDE AIR TEMPERATURE SENSOR TEMP SENSOR X X X X AT MA_T Archibus#_01_XXX_IC_AHU_MA_T MIXED AIR TEMPERATURE TEMP SENSOR X X X X X AT HC_T Archibus#_01_XXX_IC_AHU_HC_T HOT WATER COIL TEMPERATURE TEMP SENSOR X X X X AT CC_T Archibus#_01_XXX_IC_AHU_CC_T COLD WATER COIL TEMPERATURE TEMP SENSOR X X X X
DPT PFLTR_DP_S Archibus#_01_XXX_IC_AHU_PFLTR_DP_S PREFILTER STATUS DIFFERENTIAL PRESSURE SENSOR X X X X MT RA_H Archibus#_01_XXX_IC_AHU_RA_H RETURN AIR HUMIDITY HUMIDITY SENSOR X X X X X AQ MA_Q Archibus#_01_XXX_IC_AHU_MA_Q MIXED AIR QUALITY AIR QUALITY SENSOR X X X X X CD EA_DPR_C2 Archibus#_01_XXX_IC_AHU_EA_DPR_C2 EXHAUST AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD EA_DPR_C1 Archibus#_01_XXX_IC_AHU_EA_DPR_C1 EXHAUST AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CV CHW_VLV_C Archibus#_01_XXX_IC_AHU_CHW_VLV_C COOLING VALVE DC VOLTAGE OUTPUT X X X X CV HW_VLV_C Archibus#_01_XXX_IC_AHU_HW_VLV_C HEATING VALVE DC VOLTAGE OUTPUT X X X X CD DA_DPR1_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR2_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR3_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR4_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR5_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR6_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR7_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR8_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD DA_DPR9_C Archibus#_01_XXX_IC_AHU_DA_DPR_C DISCHARGE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD OA_DPR_C Archibus#_01_XXX_IC_AHU_OA_DPR_C OUTSIDE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD OA_DPR_C Archibus#_01_XXX_IC_AHU_OA_DPR_C OUTSIDE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD OA_DPR_C Archibus#_01_XXX_IC_AHU_OA_DPR_C OUTSIDE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD OA_DPR_C Archibus#_01_XXX_IC_AHU_OA_DPR_C OUTSIDE AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD RA_DPR_C Archibus#_01_XXX_IC_AHU_RA_DPR_C RETURN AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X CD RA_DPR_C Archibus#_01_XXX_IC_AHU_RA_DPR_C RETURN AIR DAMPER COMMAND DC VOLTAGE OUTPUT X X X X
ASH RA_SD_S2 Archibus#_01_XXX_IC_AHU_RA_SD_S2 RETURN AIR SMOKE DETECTOR DRY CONTACT X X X X X ASH RA_SD_S1 Archibus#_01_XXX_IC_AHU_RA_SD_S1 RETURN AIR SMOKE DETECTOR DRY CONTACT X X X X X ASH SA_SD_S Archibus#_01_XXX_IC_AHU_SA_SD_S SUPPLY AIR SMOKE DETECTOR DRY CONTACT X X X X X ISL RFAN1_RUN_S Archibus#_01_XXX_IC_AHU_RFAN_RUN_S RETURN FAN STATUS DRY CONTACT X X X X X ISL RFAN2_RUN_S Archibus#_01_XXX_IC_AHU_RFAN_RUN_S RETURN FAN STATUS DRY CONTACT X X X X X ISL SFAN_RUN_S Archibus#_01_XXX_IC_AHU_SFAN_RUN_S SUPPLY FAN STATUS DRY CONTACT X X X X X ISL HW_P_RUN_S Archibus#_01_XXX_IC_AHU_HW_P_RUN_S HOT WATER PUMP STATUS DRY CONTACT X X X X X TSL FZ_S Archibus#_01_XXX_IC_AHU_FZ_S FREEZESTAT DRY CONTACT X X X X X
FIRE_ALM FIRE_ALM Archibus#_01_XXX_IC_AHU_FIRE_ALM FIRE ALARM PANEL STATUS DRY CONTACT X X X X SMK SMOKE_PURGE Archibus#_01_XXX_IC_AHU_SMOKE_PURGE SMOKE PURGE STATUS DRY CONTACT X X X X CMD SFAN_RUN_C Archibus#_01_XXX_IC_AHU_SFAN_RUN_C SUPPLY FAN COMMAND RELAY COIL X X X X X CMD HW_P_RUN_C Archibus#_01_XXX_IC_AHU_HW_P_RUN_C HOT WATER PUMP COMMAND RELAY COIL X X X X X CMD RFAN1_RUN_C Archibus#_01_XXX_IC_AHU_RFAN_RUN_C RETURN FAN COMMAND RELAY COIL X X X X X CMD RFAN2_RUN_C Archibus#_01_XXX_IC_AHU_RFAN_RUN_C RETURN FAN COMMAND RELAY COIL X X X X X
2021 KFI Engineers©
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
2343 Alexandria Drive Suite 200 Lexington, KY 40504 Tel: 859-271-3246 Email: kfi@kfi-eng.com
523CB9ZCA0800
09/02/2026
Au to de sk
D oc s:
//2
5-
D
JJ
C am pb el l C o.
V en til at io n
U pg ra de s /M
P2 5_
D
JJ
-C am pb el
C o.
Ve nt ila tio n U pg ra de s.
rv t
/8
/2
2:
:2
PM
RTS
25-1309.00
09/02/2026
TCC
MULTIZONE AIR HANDLING UNIT
IC600A
RTA
DJJ - CAMPBELL CONTROLS UPGRADES
BILL OF MATERIALS - MULTIZONE AHU
POINTS LIST - MULTIZONE AHU
NOTE: OWNER SHALL INTEGRATE POINTS INTO CEMCS. POINTS LIST SHOWN HERE MEANT TO SERVE AS A GUIDE FOR
CEMCS INTEGRATION.
No: Date: Revision:
1 10.08.26 Addendum 02
1 10.08.26 Addendum 02
C E N ENFO
SE
ENOIS AL GN I
E
AT
PR
S
T K
E
S.
JOSHUA
KRACK
L I S
D RE
Y
EFO K
CTN U
29466
POINT NAME DESCRIPTION QUANTITY EXISTING VALVE MODEL NUMBER SIZE GPM CV PD PSI PATTERN POSITION HW_VLV_C MULTIZONE AHU - HOT WATER VALVE 1 VS-9313-414-5-13 3" 206 101 4.16 3-WAY B-AB
CHW_VLV_C MULTIZONE AHU - CHILLED WATER VALVE 1 VS-9313-312-4-12 2-1/2" 94.2 67 1.9768 3-WAY B-AB HWS_MIXVLV_C BOILER / HOT WATER SYSTEM VALVE 1 VS-9313-312-4-12 2-1/2" 101 67 2.2724 3-WAY B-AB
2021 KFI Engineers©
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
2343 Alexandria Drive Suite 200 Lexington, KY 40504 Tel: 859-271-3246 Email: kfi@kfi-eng.com
523CB9ZCA0800
09/02/2026
Au to de sk
D oc s:
//2
5-
D
JJ
C am pb el l C o.
V en til at io n
U pg ra de s /M
P2 5_
D
JJ
-C am pb el
C o.
Ve nt ila tio n U pg ra de s.
rv t
/8
/2
2:
:2
PM
RTS
25-1309.00
09/02/2026
TCC
VALVE SCHEDULE
IC700
RTA
DJJ - CAMPBELL CONTROLS UPGRADES
No: Date: Revision:
1 10.08.26 Addendum 02
1 10.08.26 Addendum 02
EXISTING VALVE SCHEDULE
NOTE: VALVE INFORMATION SHOWN IN THE TABLE ABOVE IS BASED ON OWNER-PROVIDED AS-BUILT DOCUMENTATION.
VALVES SHALL BE REPLACED IN ACCORDANCE WITH THE ORIGINAL BID DOCUMENTS. REPLACEMENT VALVES SHALL BE OF LIKE TYPE, SIZE, AND PERFORMANCE CHARACTERISTICS, AND SHALL COMPLY WITH THE REQUIREMENTS OF SPECIFICATION SECTIONS 250000 – INTEGRATED AUTOMATION AND 250500 – INSTRUMENTATION AND CONTROL FOR
HVAC.
| DJJ - Campbell Controls Upgrades - Addendum 02.pdf |
| DJJ-Campbel Co-Ventilation Upgrades - Rev1.pdf |
| IC200 - CONTROLS OVERALL PLAN - LEVEL 01 |
| IC600 - MULTIZONE AIR HANDLING UNIT |
| IC600A - MULTIZONE AIR HANDLING UNIT |
| IC700 - VALVE SCHEDULE |
File details come from the government source that posted it. Updated .