Addendum 1~1.pdf
PDF 141 KB Posted
- Solicitation number
- S-P00140-00002948
- Issued by
- Lane County, Oregon
About this file
This document is an Addendum to the Invitation to Bid (ITB) #22-098-G issued by the Eugene Water & Electric Board (EWEB) for medium voltage vacuum interrupter switchgear equipment for its power plant at International Paper in Springfield, Oregon. The addendum deletes and replaces Section 26 13 19, Paragraph 2-2.20 of the original ITB document with new requirements for a ground-test device that can be inserted into the switchgear units to permit grounding and testing. The closing date and time for the ITB remains unchanged at May 10, 2022.
The ITB is for EWEB's procurement of medium voltage vacuum interrupter switchgear equipment for its power plant located in Springfield, Oregon, which falls within the jurisdictions of Lane County and Sumpter City. No additional details on pricing, set asides, incumbents, funding sources, or contract terms are provided in the addendum.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Fillable Bid schedule - Hayesville Dr - Addendum 1.xlsx | XLSX spreadsheet | |
| Bid Tab 22-098-G Switchgear for IP.pdf | ||
| 22-098-G Switchgear for IP.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM # 1 May 3, 2022 Title: Switchgear for IP Power Plant 4
RFP # 22-098-G
This addendum adds additional information to the original ITB document.
CHANGES TO ITB DOCUMENT:
Section 26 13 19 – Medium Voltage Vacuum Interrupter Switchgear Sub-section 2-2.20 Ground Test Device
Delete Section 26 13 19, Paragraph 2-2.20 in its entirety and replace it with the following paragraph:
2-2.20. Ground-Test Device. A grounding, phasing, and testing device shall be furnished. The device shall be designed so that it can be inserted in the switchgear units in place of and in the same manner as the circuit breaker removable elements, to permit grounding either the bus or the feeder/generator, or to make connections to either the bus or the feeder for testing purposes. The device shall be a simple manual device in compliance with IEEE C37.20.6 to effectively ground either the bus or the feeder when the device is inserted in the unit. The device shall be manually connected using cables or bus bar provided by the manufacturer. Complete assembly of the fully rated ground connections shall be via a hot stick or with the ground and test cart removed from the cubicle. The device shall have momentary and four-second current-carrying capacities at least equal to those of the circuit breaker. The device shall connect solidly to the ground bus in the unit when in the operating position. No provisions for automatic tripping of the device shall be included. The device shall be provided with suitable windows or a transparent enclosure and barriers to permit visual observation of the positions of all grounding connections.
External connections for testing shall be made using a hot-stick and voltage testers on the face of the device. The ports shall be provided with closing shutters or covers.
CLOSING DATE AND TIME
May 10, 2022. Remains unchanged.
This addendum constitutes a MATERIAL CHANGE to the Request for Proposals.