This Addendum #1 document modifies RFP 2627-03 for the Troy School District 2027 Roofing Program, a roof replacement project covering two Michigan schools: Morse Elementary School (475 Cherry Avenue, Troy, MI) and Hamilton Elementary School (5625 Northfield Parkway, Troy, MI). The scope of work encompasses removal and replacement of existing roofing systems, insulation, and flashing across approximately 69,323 square feet of roof area divided into five separate roof areas at Hamilton Elementary and one roof area at Morse Elementary. The project requires installation of 60-mil EPDM membrane roofing with R-30 insulation, new metal flashings, drain systems, and related accessories. Key dates include a revised bid submission deadline of 2:00 PM EST on Tuesday, November 10, 2026 (changed from 1:00 PM), with bids submitted exclusively through BuildingConnected.com. A pre-bid meeting was held on October 30, 2026, and RFIs were due November 6, 2026. Contract award is anticipated by December 2026, with work scheduled to commence approximately June 8, 2027, and substantial completion targeted for August 13, 2027, allowing approximately 48 workdays. Work hours are Monday through Friday, 10 hours per day, with Saturday as a rain makeup day. The Troy School District reserves the right to award contracts to multiple contractors.
The bid must include a five percent (5%) bid bond or certified check, and the successful contractor must provide both a payment bond and performance bond. Base bids include allowances specified on individual roof plans: $2,000 for Morse Elementary Roof Area A, $7,000 for Hamilton Elementary Roof Area A, $2,000 each for Roof Areas C, D, and E. The roofing contractor must provide the roof system manufacturer's twenty-year "No-Dollar-Limit" material and installation warranty and a five-year performance agreement. Unit pricing is required for additional work beyond the base bid. Liquidated damages are assessed at $500 per day after August 14, 2027. Contact for questions is Ann Crippen at WeatherTech Consulting Group (acrippen@wtcg.net, 586-731-3095 ext. 12), the project manager. No physical bids will be accepted; all submissions must be made electronically through the designated BuildingConnected.com portal.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid Advertisement - RFP 2627-03 TSD 2027 Roofing Program.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum 1
Project: RFP NUMBER 2627-03 – 2027 ROOFING PROGRAM
Bid Due date: 2:00 PM Local Time, Tuesday, November 10, 2026 (REVISED)
This Addendum is issued as modifications to the RFP previously issued to provide clarifications to the scope of work. This Addendum supersedes the original RFP. This along with the RFP becomes the bid documents.
I. General Information
1. For questions e-mail lecoleplanners3@gmail.com or through Buildingconnected.com.
2. Any bidder requesting to visit the site should contact Mark Paulus at lecoleplanners3@gmail.com or (248) 880-6791 to schedule a time. No bidder shall visit the building without scheduling it with Mark Paulus.
3. Invitation to Bid. Revise paragraph 3, sentence 3. Bids are to be submitted no later than 2 pm on November 10, 2026.
4. Bid Package. Revise page 3, paragraph 3, sentence 3. Bids are to be submitted no later than 2 pm on November 10, 2026.
5. Addendum #1 dated November 6, 2026, as prepared by WeatherTech Consulting Group, Inc. (Attached)
6. Pre-bid Meeting Minutes on October 30, 2026, as prepared by WeatherTech Consulting Group, Inc.
END
WeatherTech Consulting Group, Inc.
ADDENDUM 1
Troy School District
2627-03 2027 Roof Program
WeatherTech Consulting Group 45147 Cass Ave Utica, MI 48317 586-731-3095 Fax 586-731-6863 weathertech@wtcg.net www.wtcg.net
POST BID
ADDENDUM NO.: 01 DATE: 11/6/26
PROJECT IDENTIFICATION
PROJECT NAME: BID NO. 2627-03 Troy School District 2026 Roof Program
SITE ADDRESS: 5625 Northfield Pkwy Troy, MI 48098
ADDENDUM DESCRIPTION
The following is a summary of changes to the Bid Documents dated 10-01-26 that shall be considered as a part of your Bid. Addendum Drawings Re-Issued
SUMMARY OF ADDENDUM:
Item Description
1.
Changes to roof drawings:
Drawing A3.1 – Change measurements from 31’6” to 42’. Reference General Notes #3
Drawing A3.2:
1.Add: Keynote 6 Wall Ladder Replacement – Furnish and install a new wall ladder to match existing. Ref. Photo 7921 2.Change of scope – New Roof System:
a. Roof Membrane: EPDM, 60 mil, adhered to insulation.
b. Insulation: R30:
1) Top layer shall be set-in low-rise foam adhesive.
2) Bottom layer shall be set-in low-rise foam adhesive to vapor barrier.
c. Vapor Barrier shall be installed over metal deck. (Carlisle VapAir Seal MD or equivalent) Tapered Insulation: Roof Drains, see roof plan and details
d. Deck: Metal: Repair as necessary to comply w/ building codes.
e. Interior Ceiling: N/A
f. Building Height: Ground to building edge: 45 ft
2.
Roofing Contractors RFI’s:
Hamilton Elementary School - Drawings state to install new wood nailers on the perimeter edge. Can we leave the existing in place? Looks like with the new roof height, we shouldn’t need to add any.
Replace any missing or damaged nailers and add nailers to achieve required base flashing height.
PROJECT CONSULTANT:
ADDENDUM 1
Troy School District
2627-03 2027 Roof Program
WeatherTech Consulting Group 45147 Cass Ave Utica, MI 48317 586-731-3095 Fax 586-731-6863 weathertech@wtcg.net www.wtcg.net
COMPANY: WeatherTech Consulting Group
NAME: Ann Crippen
ADDRESS: 45147 Cass Ave Utica, MI 48317
WT OFFICE: (586) 731-3095
E-MAIL: acrippen@wtcg.net
SHEET 1 OF 9
Cover Sheet
A1.0
OWNER:
Troy School District 4400 Livernois Troy, MI 48098
PROJECT LOCATION:
See Project List
ROOFING CONSULTANTS:
WeatherTech Consulting Group, Inc.
Utica, MI 48317
CONTACT:
Rob Carson Director of Operations Phone: (248) 823-4067 E-Mail: RCarson@troy.k12.mi.us
CONTACT:
Michelle Kerns Bond Representative Phone: (248) 921-3929 E-Mail: mkerns@troy.k12.mi.us
CONTACT:
Ann Crippen Project Manager Phone: (586) 731-3095 x12 E-Mail: acrippen@wtcg.net
John McCaig, RRO Site Contact
Jack Runkle, AIA Design Review
Troy School District 2027 Roofing Program
Troy School District 2027 Roofing Program
Project Work Schedule
A1.0
A2.0
A3.0
A3.1
A3.2
A3.3
Cover Sheet
Roof Plan, Morse Elementary School Roof Area A
Roof Plan, Hamilton Elementary School - Roof Area A
Roof Plan, Hamilton Elementary School - Roof Area C
Roof Plan, Hamilton Elementary School - Roof Area D
Roof Plan, Hamilton Elementary School - Roof Area E
A4.0 Detail Sheet
A4.1 Detail Sheet
A4.2 Detail Sheet
Morse Elementary School 475 Cherry Ave, Troy, MI 48083 Hamilton Elementary School 5625 Northfield Pkwy, Troy, MI 48098
THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF
SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF
WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,
WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE
DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON
OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING
GROUP. COPYRIGHT 2023.
DESCRIPTION
COPYRIGHT:
WeatherTech Consulting Group, Inc.
DATE
ISSUE
Drawn By: MD
Checked By: AC, AW, JM
WeatherTech Consulting Group, Inc.
Roofing/Waterproofing Consultants Corporate Office:
45147 Cass Ave.
Utica, MI 48317
Phone #: 586-731-3095 Email: weathertech@wtcg.net
Web Site: www.wtcg.net
SHEET TITLE
CLIENT
PROFESSIONAL
PROJECT
File Name:
ELECTRONIC STAMP
TSD 2027 - A1.0 Cover Page
WTProject No: TSD-R102-27
PROJECT SUMMARY
SUMMARY OF WORK: Ref. Section 00 02 00 General: Troy School District (TSD) 2027 Roof Program work for two (2) schools. Roofing work includes roof replacement required to remediate all work identified in the specifications and drawings inclusive of all Bid Documents requirements.
Schedules: Ref. “PROJECT WORK SCHEDULE” on this Sheet A1.0 - Cover Page.
BID SUMMARY:
Instruction to Bidders 000113: Reference the Project Manual, specification 000113 for bid preparation, RFI dates and Pre-Bid Meeting information.
Allowances Section 012100: Allowances will be defined on individual school roof plans under “Allowances”. These allowances ll be stated on the bid form.
3. Unit Pricing Section 004322: Unit Pricing for unit work is defined on the Unit Price Bid Form in Section 000301. Unit Pricing bid values are entered by unit price individually on form.
4. Alternates Section 012300: Alternates are individually listed on school roof plans and bids for Alternates. Alternated bid value are to be entered on Bid Form (Section 000300) as enumerated.
5. TSD reserves the right to issue contracts to multiple contractors.
EXISTING ROOF SYSTEM CONSTRUCTION:
Ref. Roof Plans. All existing roof system constructions were determined by test cuts and observation; conditions may vary. Contractor s responsible for confirming all existing roof system constructions, measurements, cores and conditions.
NEW ROOF ASSEMBLY SUMMARY: Reference Roof Plans
1. Roof System: Ref. Roof Plan Schedules
a. Roof Membrane: EPDM, 60 mil, unreinforced and fully adhered.
b. Insulation: To meet a R-30 minimum, Min. two layers. Top layer must be adhered: Bottom layer mechanically- attached (unless otherwise stated on individual roof plans)
c. Underlayment: (as required) Modified base sheet, Ref. individual Roof Plans.
d. Deck: Multiple types, Ref. individual Roof Plans.
2. Roof System Performance:
a. Warranty: 20 yr. Materials manufacturer, No Dollar Limit (NDL) materials and installation.
b. Contractor to provide a 5-year contractor guarantee.
c. Wind: FM Global (FMG): FM Standard 4470 Meets - Windstorm Classification FMG 90.
d. Fire: Underwriters Laboratory External Fire Resistance - Class "A".
e. Energy: Michigan Uniform Energy Code: R30 condition dependent
f. Drainage: Drainage Performance Acknowledgement”
GENERAL SHEET NOTES
1. All work shall be executed in accordance with the appropriate document of the Contract Documents.
2. Any conflicts between specifications and drawings shall be brought to the attention of the Owner and Consultant immediately. In all situations the more restrictive and higher quality shall govern.
3. All dimensions to, of, and in existing building and roof shall be verified in the field by contractor. Field measure existing conditions to verify material quantities and dimensions prior to fabrication on component material.
4. Details shown are typical. Similar details apply to similar conditions unless otherwise indicated.
5. The drawings herein are related to an alteration/ restoration to an existing structure. The specified work was based upon as much observation, destructive testing, etc. as circumstances permitted.
GENERAL CONSTRUCTION DETAIL NOTES
Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A .0 - A .2. Contractor provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Flashing Heights: Perimeters, curbs, penetrations shall be raised as necessary to meet the new insulation heights, tapered edge strip and tapered insulation height to meet typical industry standard of 8 in. base flashing height.
Drains Existing: Remove existing drain flashings. Furnish and install ½ inch per foot sloped tapered insulation sump area (8 ft. x 8 ft. minimum) as detailed. Clean and reuse existing drains and accessories, replace all damaged, nonfunctional, incompatible, missing and broken drain components.
Replace all plastic strainers with new cast iron. All replacement bowls, strainers, and clamping rings shall be cast iron. Provide new stainless-steel bolts. All nonmetallic drains strainers shall be replaced with fitted. Ref. Details 1.09, 1.10, 1.11 and 1.12.
Tapered Insulation: Furnish and install new tapered insulation, crickets, saddles and kick-backs as designated on roof plan to provide a finished slope of 1/4 in/ ft. slope and a min length to width ratio of 3:1. All equipment w/ curb size greater than 24 in. shall have cricket install on up slope side.
Contractor responsible for identifying and notifying Consultant and Owner of all existing tapered insulation not called out on plans for determination of unit costing. Verify in Pre-bid Conference additional ponded areas identified on the roof and install as noted.
Curbs - Movable Equipment: Lift equipment from curbs; run new fully adhered membrane flashing up and over top of curb; install continuous sealing material over top of curb. Reset equipment and mechanically fasten to curb. Coordinate with Owner prior to moving equipment to install new flashings.
Metal equipment flashing and/or counter flashing must extend a minimum of 3 in. past the termination of the base flashing; add metal counter flashing as required. Ref. Details 1.17 and 1.18.
Curbs - Non-Movable Equipment: Terminate new fully adhered membrane flashing at unit framing member. Metal equipment flashing and/or counter flashing must extend a minimum of 3 in. past the termination of the base flashing; add metal counter flashing as required. Ref. Detail 2.01.
Equipment on Support Curbs - Non-Movable Equipment: Cut corners of metal flashing cap, terminate new adhered membrane flashing to curb nailer. Reposition metal; install new shop fabricated corner metal, riveted and set in sealant. Wire brush and apply rust inhibitive paint to rusted cap metal.
Ref. Detail 3.02.
Equipment on Support Curbs - Movable Equipment: Raise or move equipment to furnish and install new metal cap on curb. Ref. Detail 2.18.
Round Penetrations: All penetrations shall be cleaned down to surface where any sealant will contact; Install new prefabricated pipe boots or field wrap with membrane. Install draw band, sealants and rain collars as detailed. Ref. Details 2.03 and 2.04.
Heat Stacks: Install new metal jacks and collars. Clean surfaces and apply new field wrapped EPDM flashing. Reattach and reseal storm collars with high temperature sealant. Ref. Detail 2.05.
Steel Support Posts: Install split pipe boot or field wrap flashing with membrane. Terminate with draw band and sealant. Ref. Detail 2.02.
Prefabricated Pipe Chase Cover: Reuse existing pipe cover. Replace any damaged or missing clamping bands or sealants. Ref. Detail 3.01.
Gas Line and Conduit Support Blocks: Provide prefabricated pipe supports set on walkpads. Ref.
Details 3.03 and 3.11.
Condensate Drain Lines: Reuse, repair or replace all damaged or unusable drain lines. Add additional drain line to extend minimum 4 ft. from equipment or to any drains within 20 ft. Provide manufacturer's approved splash pan/pad/block where condensate drainage water would contact the roof membrane.
All utility service lines (gas, water, electric, cable, etc.) to be raised as necessary to accommodate new insulation height and meet code requirements.
Abandoned Curbs and Penetrations: Owner will mark all equipment to be removed. Remove all equipment and curbs as designated by owner and identified at the prebid conference. Where directed, remove curbs flush to deck surface, install framing and matching decking material. For abandoned curbs to remain in place, install new base flashing and install new 24 gauge sloped metal cap. Provide interior protection when removing any equipment or penetration. All small round abandoned penetrations that have no utility service as confirmed by Owner shall be removed to deck, patched according to deck type.
Pitch Pans: Pitch pans can only be used when approved by Consultant. In the event they are to be used, furnish and install new pitch pans, clean all penetrations down to original surface, blocking required at all pitch pans. Ref. Detail 2.09.
Door Threshold: Remove threshold plate and carry flashing up over and set in water block. Before resetting threshold, mechanically attach termination bar, fasten min. 6 in. o.c. Door Threshold: Remove and dispose of existing counter flashing. Roof flashing to extend up and under existing threshold plate.
Furnish and install new metal counter flashing and sealant.
Downspout Outlets: Provide concrete splash blocks set on walkpad at all roof downspout conductors.
Vent Thru Roof Piping: Install PVC pipe extensions to all VTR piping prior to installation of new pipe boot flashing as needed to allow a minimum 8-inch flashing height. Attach screen wire mesh over the top of the pipe. Ref. Detail 2.06.
Walk Pads: Provide walk pads at roof access hatches and ladder access locations. Use walk pads approved by the roofing membrane manufacturer.
Existing Expansion Joint: Install wood as needed to provide a minimum 8-inch flashing height;
Replace existing batt insulation and liner if needed; Re-install if able or furnish and install new gauge prefinished metal expansion joint cover. Ref. Detail 3.05.
Deck Flutes: All debris be removed from deck flutes.
Protection and Cleaning of Installed Roof Membrane: The roofing contractor is responsible for protection of installed sections of new roof membrane from staining and discoloration. Strategies for protection of installed membrane may include, but are not limited to, use of roof membranes with manufacturer-applied protective film, full coverage of installed membrane with sealed tarps, sequencing of roof membrane installation in a manner to limit tear-off dust, dirt and debris migration, and limiting traffic on installed membrane. Upon completion of installation, stained membrane shall be cleaned to the satisfaction of the owner and shall maintain the manufacturer-published initial solar reflectance of the product.
Review
OTB
09/21/2026 10/01/2026
Troy School District 4400 Livernois Troy, MI 48098
STATE OF MICHIGAN LARA RECORD LOCATOR
Project Manual
TABLE OF CONTENTS
00 00 00 Cover
00 01 10 TABLE OF CONTENTS
00 01 11 PROJECT DIRECTORY
BID REQUIREMENTS
00 01 12 INVITATION TO BID - TSD
00 01 13 INSTRUCTIONS TO BIDDERS - TSD
00 02 00 SUMMARY OF WORK
00 03 00 BID FORM
00 03 01 UNIT PRICE FORM
00 03 04 PAYMENT BOND
00 03 05 PERFORMANCE BOND
00 04 01 PARTIAL RELEASE OF LIEN
00 04 02 FINAL RELEASE OF LIEN
00 04 11 FAMILIAL DISCLOSURE/ IRAN ECONOMIC SANCTIONS
00 43 22 UNIT PRICING INFORMATION
00 43 36 LIST OF SUBCONTRACTORS
00 73 00 SUPPLEMENTAL CONDITIONS
DIVISION 1 - GENERAL REQUIREMENTS
01 06 00 REGULATORY REQUIREMENTS
01 14 19 USE OF SITE
01 20 03 CHANGES TO WORK
01 21 00 ALLOWANCES
01 23 00 ALTERNATES
01 29 00 PAYMENT PROCEDURES
01 32 00 CONSTRUCTION SCHEDULE
01 32 14 WEB SITE & DOCUMENTS
01 33 00 SUBMITTALS
01 33 26 QUALITY CONTROL
01 35 01 SAFETY
01 42 16 TERMS AND DEFINITIONS
01 50 00 CONSTRUCTION FACILITIES & TEMPORARY CONTROLS
01 74 23 FINAL CLEANING
01 77 00 CLOSE OUT
DIVISION 2 - SITE WORK
02 41 19 SELECTIVE DEMOLITION
DIVISION 6 - ROUGH CARPENTRY
06 10 00 ROUGH CARPENTRY
DIVISION 7 - THERMAL AND MOISTURE PROTECTION
07 22 50 SINGLE PLY ROOF INSULATION
07 54 00 FULLY ADHERED EPDM ROOFING
07 62 00 SHEET METAL FLASHING AND TRIM
07 72 00 ROOF ACCESSORIES
07 90 00 SEALERS
DIVISION 22 - PLUMBING
22 14 26.13 ROOF DRAINS
DRAWINGS - Ref. Sheet A1.0 - Sheet Index
DIRECTORY
PROJECT LIST
SHEET INDEX
SHEET NO. SHEET TILE
PR2026BCC-003717
H
'-6
'-6
15' 46'
61'
60'-7"
Slope Slope
Slope
Slope
THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF
SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF
WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,
WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE
DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON
OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING
GROUP. COPYRIGHT 2023.
DESCRIPTION
COPYRIGHT:
WeatherTech Consulting Group, Inc.
DATE
ISSUE
Drawn By: MD
Checked By: AC, AW, JM
WeatherTech Consulting Group, Inc.
Roofing/Waterproofing Consultants Corporate Office:
45147 Cass Ave.
Utica, MI 48317
Phone #: 586-731-3095 Email: weathertech@wtcg.net
Web Site: www.wtcg.net
SHEET TITLE
CLIENT
PROFESSIONAL
PROJECT
File Name:
ELECTRONIC STAMP
SHEET 2 OF 9
Roof Plan Morse Elementary School
Roof Area A
A2.0
WTProject No: TSD-R102-27
TSD 2026 - A4.0 Morse Elementary School
Review
OTB
09/21/2026 10/01/2026
KEY PLAN
Symbol Legend Symbol
Conduit, Vent Pipe or Other Penetration
W
GAS AD EJ
Slope H
L
Notes Symbol Notes Symbol Notes
Equipment Unit on Curb
Roof Hatch on Curb
Roof Ladder
Screen Support Stanchion
Gas Line
Roof Ridges and Valleys
Roof Drain
Overflow Scupper
Tapered Insulation or Saddles
Insulated Pipe or Heat Stack Penetration
Ductwork or Flanged
Abandoned Equipment Curb
Walkway Pad
Railing or Fancing
Area Divider
Roof Slope
New Roof Drain Scupper
Key Notes
Metal Roof Shingles or Clay Titles
Revision
Elevation Change
Expansion Joint
Pipe or Conduit on Support Block
Satellite Dish
Skylight on Curb
Equip. on Wood Sleeper or Support Curb
Pitch-Pan Pocket
AH S
Morse Elementary School Roof Area A Scale: 18" = 1'
Photos
Morse Elementary School 475 Cherry Dr.
Troy, MI 48083
Troy School District 2027 Roofing Program
Morse Elementary School - Troy School District Sheet Notes - Roof Area A
Schedule:
WORK DESCRIPTION - ROOF REPLACEMENT
1. Existing Roof System Construction
All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor responsible for confirming all existing roof system constructions and conditions.
Roof Area A Core Sample Results A. Roof Membrane: BUR B. Insulation:
1) Top Layer: Insulation ½” Fiberboard Insulation
2) Base Layer: Approx. 1 1/2 -inch ISO insulation
C. Deck: Metal Deck (slope in deck)
2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area A 4,135 sq. ft.
3. New Roof System: Roof Area A - Ref. Detail 1.01a.
a. Roof Membrane: EPDM, 60 mil, adhered to insulation.
b. Insulation: R30:
1) Top layer set-in low-rise foam adhesive.
2) Bottom layer mechanically attached to metal deck.
c. Tapered Insulation: Roof Drains, see roof plan and details
d. Deck: Metal: Repair as necessary to comply w/ building codes.
e. Interior Ceiling: N/A
f. Building Height: Ground to building edge: 50ft
4. Warranty/Guarantee:
a. Manufacturer to provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.
b. Roofing installer to provide a five (5) year Performance Agreement - see Specification Attachment C.
5. Allowances: $2000.00 to be added to Base Bid.
6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results to be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.
General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Key Notes:
All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
1. Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.
2. Metal Strainers: Replace plastic or missing strainers with new metal strainers. (4 total) Ref. Photo 7977.
3. Tapered Roof Sumps: Furnish and install 8 ft tapered roof sumps on all drains. Ref. Photo 7972.
4. New roof hatch: Furnish and install new roof hatch with safety cage and ladder-up bar. Ref. Photo 7973.
Troy School District 4400 Livernois Troy, MI 48098
3 4
Coutyard
68'-6"
'-3
'-3
58'-9"
6' -3
63'-3" 35'-6"
157'-6"
21'
178'-6"
'-9
'-9
'-3
68'-9"
21'-9"
'-6
14'
68'-6"
21'
'-6
'-6
'-6
21'-9"
'-3
15'-3"8'30'-6"
Slope
Slope
SlopeSlope
Slop e
Slop e
Slope
Slope
Slop e
Slope
Slop e
Slop e
Slop e
Slope
Slope
Slope
Slope
Slope
Slope
Slope Slope
SHEET 3 OF 9
Hamilton Elementary School
Roof Area A
A3.0
WTProject No: TSD-R102-27
TSD 2027 - A3.0 Hamilton Elementary School
Review
OTB
09/21/2026 10/01/2026
Hamilton Elementary School 5625 Northfield Pkwy.
Troy, MI 48098
Troy School District 2027 Reroofing Program
THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF
SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF
WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,
WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE
DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON
OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING
GROUP. COPYRIGHT 2023.
DESCRIPTION
COPYRIGHT:
WeatherTech Consulting Group, Inc.
DATE
ISSUE
Drawn By: MD
Checked By: DM, AC, AW
WeatherTech Consulting Group, Inc.
Roofing/Waterproofing Consultants Corporate Office:
45147 Cass Ave.
Utica, MI 48317
Phone #: 586-731-3095 Email: weathertech@wtcg.net
Web Site: www.wtcg.net
SHEET TITLE
CLIENT
PROFESSIONAL
PROJECT
File Name:
ELECTRONIC STAMP
Troy School District 4400 Livernois Troy, MI 48098
KEY PLAN
Hamilton Elementary School - Troy School District Sheet Notes - Roof Area A
Schedule:
WORK DESCRIPTION - ROOF REPLACEMENT
1. Existing Roof System Construction
All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.
Core Sample: (Contractor to verify at Pre-Bid Meeting) A. Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total (Photo 4326)
B. Plies with asphalt C. 2-inch Fiberglass D. Approx. 2 -inch polyisocyanurate insulation.
E. ½” Perlite
F. Deck: Metal: Slope in deck
2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area A 41,744 Sq. Ft.
3. New Roof System: Roof Area A- Ref. Detail 1.01a.
a. Roof Membrane: EPDM, 60 mil, adhered to insulation.
b. Insulation: R30:
1) Top layer shall be set-in low-rise foam adhesive.
2) Bottom layer shall be mechanically attached to metal deck.
c. Tapered Insulation: Roof Drains, see roof plan and details
d. Deck: Metal: Repair as necessary to comply w/ building codes.
e. Interior Ceiling: N/A
f. Building Height: Ground to building edge: 20 ft
4. Warranty:
a. Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.
b. Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment
C.
5. Allowances: $7000.00 shall be added to Base Bid.
6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.
General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Key Notes:
All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.
Metal Counter Flashing: Install new termination bar and new 24-gauge clear anodized aluminum counter flashings. Ref. Detail 1.14 (If applicable)
Deck Flutes: All debris be removed from deck flutes.
Expansion Joint: Replace the expansion joint metal with a similar profile and standing seams. Ref.
Photo 7776 and 7847
Metal Strainers: Replace plastic or missing strainers with new (matching) metal strainers. Ref. Photo 7849 (If applicable)
Gas Pipe Blocking: Reuse existing blockings with walkway underlayment. Ref. Photo 7779
Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11(all locations)
Hamilton Elementary School Roof Area A Scale: 116" = 1'
Symbol Legend Symbol
Conduit, Vent Pipe or Other Penetration
W
GAS AD EJ
Slope H
L
Notes Symbol Notes Symbol Notes
Equipment Unit on Curb
Roof Hatch on Curb
Roof Ladder
Screen Support Stanchion
Gas Line
Roof Ridges and Valleys
Roof Drain
Overflow Scupper
Tapered Insulation or Saddles
Insulated Pipe or Heat Stack Penetration
Ductwork or Flanged
Abandoned Equipment Curb
Walkway Pad
Railing or Fancing
Area Divider
Roof Slope
New Roof Drain Scupper
Key Notes
Metal Roof Shingles or Clay Titles
Revision
Elevation Change
Expansion Joint
Pipe or Conduit on Support Block
Satellite Dish
Skylight on Curb
Equip. on Wood Sleeper or Support Curb
Pitch-Pan Pocket
AH S
Photos
7776 7779
7847 7849
1 1
W
8'
21'
10'-6"
8'
7' -6
1' -6
26'-6"5'
31'-6"
W
Slope
Slope
Slope Slope
Slope
SHEET 4 OF 9
Hamilton Elementary School
Roof Area C
A3.1
WTProject No: TSD-R102-27
TSD 2027 - A8.0 Hamilton Elementary School
Review
OTB
09/21/2026 10/01/2026
Hamilton Elementary School 5625 Northfield Pkwy.
Troy, MI 48098
Troy School District 2027 Reroofing Program
THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF
SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF
WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,
WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE
DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON
OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING
GROUP. COPYRIGHT 2023.
DESCRIPTION
COPYRIGHT:
WeatherTech Consulting Group, Inc.
DATE
ISSUE
Drawn By: MD
Checked By: DM, AC, AW
WeatherTech Consulting Group, Inc.
Roofing/Waterproofing Consultants Corporate Office:
45147 Cass Ave.
Utica, MI 48317
Phone #: 586-731-3095 Email: weathertech@wtcg.net
Web Site: www.wtcg.net
SHEET TITLE
CLIENT
PROFESSIONAL
PROJECT
File Name:
ELECTRONIC STAMP
Troy School District 4400 Livernois Troy, MI 48098
KEY PLAN
Hamilton Elementary School - Troy School District Sheet Notes - Roof Area C
Schedule:
WORK DESCRIPTION - ROOF REPLACEMENT
1. Existing Roof System Construction
All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.
Core Sample Results A. Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total
B. Plies with asphalt C. 2-inch Fiberglass D. Approx. 2 -inch polyisocyanurate insulation.
E. ½” Perlite
F. Deck: Metal: Slope in deck
2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area C 5,444 Sq. Ft.
3. New Roof System: Roof Area C- Ref. Detail 1.01a.
a. Roof Membrane: EPDM, 60 mil, adhered to insulation.
b. Insulation: R30:
1) Top layer shall be set-in low-rise foam adhesive.
2) Bottom layer shall be mechanically attached to metal deck.
c. Tapered Insulation: Roof Drains, see roof plan and details
d. Deck: Metal: Repair as necessary to comply w/ building codes.
e. Interior Ceiling: N/A
f. Building Height: Ground to building edge: 20 ft
4. Warranty:
a. Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.
b. Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment
C.
5. Allowances: $2000.00 shall be added to Base Bid.
6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.
General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Key Notes:
All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.
Metal Counter Flashing: Install new termination bar and new 24-gauge clear anodized aluminum counter flashings. Ref. Detail 1.14; Photo 7941
Walkway Pad: Add new walkway pad at wall ladders and door. Ref. Photo 7940
Deck Flutes: All debris be removed from deck flutes.
Expansion Joint: Replace the expansion joint metal with a similar profile. Ref. Photo 7934
Metal Strainers: Replace plastic or missing strainers with new metal strainers. (if applicable)
Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11
Hamilton Elementary School Roof Area C Scale: 18" = 1'
Symbol Legend Symbol
Conduit, Vent Pipe or Other Penetration
W
GAS AD EJ
Slope H
L
Notes Symbol Notes Symbol Notes
Equipment Unit on Curb
Roof Hatch on Curb
Roof Ladder
Screen Support Stanchion
Gas Line
Roof Ridges and Valleys
Roof Drain
Overflow Scupper
Tapered Insulation or Saddles
Insulated Pipe or Heat Stack Penetration
Ductwork or Flanged
Abandoned Equipment Curb
Walkway Pad
Railing or Fancing
Area Divider
Roof Slope
New Roof Drain Scupper
Key Notes
Metal Roof Shingles or Clay Titles
Revision
Elevation Change
Expansion Joint
Pipe or Conduit on Support Block
Satellite Dish
Skylight on Curb
Equip. on Wood Sleeper or Support Curb
Pitch-Pan Pocket
AH S
Photos
Slope
Slope
Slope
Slope
2'
-9
61'
SHEET 5 OF 9
Hamilton Elementary School
Roof Area D
A3.2
WTProject No: TSD-R102-27
TSD 2027 - A3.0 Hamilton Elementary School
Review
OTB
09/21/2026 10/01/2026
Hamilton Elementary School 5625 Northfield Pkwy.
Troy, MI 48098
Troy School District 2027 Reroofing Program
THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF
SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF
WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,
WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE
DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON
OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING
GROUP. COPYRIGHT 2023.
DESCRIPTION
COPYRIGHT:
WeatherTech Consulting Group, Inc.
DATE
ISSUE
Drawn By: MD
Checked By: DM, AC, AW
WeatherTech Consulting Group, Inc.
Roofing/Waterproofing Consultants Corporate Office:
45147 Cass Ave.
Utica, MI 48317
Phone #: 586-731-3095 Email: weathertech@wtcg.net
Web Site: www.wtcg.net
SHEET TITLE
CLIENT
PROFESSIONAL
PROJECT
File Name:
ELECTRONIC STAMP
Troy School District 4400 Livernois Troy, MI 48098
KEY PLAN
Hamilton Elementary School - Troy School District Sheet Notes - Roof Area D
Schedule:
WORK DESCRIPTION - ROOF REPLACEMENT
Existing Roof System Construction All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.
Core Sample Results
Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total Plies with asphalt 2-inch Perlite Approx. 2 -inch polyisocyanurate insulation.
½” Perlite
Deck: Metal: Slope in deck
Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area D 9,450 Sq. Ft.
New Roof System: Roof Area D- Ref. Detail 1.01a.
Roof Membrane: EPDM, 60 mil, adhered to insulation.
Insulation: R30:
Top layer shall be set-in low-rise foam adhesive.
Bottom layer shall be
Tapered Insulation: Roof Drains, see roof plan and details Deck: Metal: Repair as necessary to comply w/ building codes.
Interior Ceiling: N/A Building Height: Ground to building edge: 45 ft
Warranty:
Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.
Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment C.
Allowances: $2000.00 shall be added to Base Bid.
Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.
General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Key Notes:
All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.
Walkway Pad: Add new walkway pad at ladder. Ref. Photo 7921
Deck Flutes: All debris be removed from deck flutes.
Metal Strainers: Replace plastic or missing strainers with new (matching type) metal strainers. (if applicable)
Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11
Hamilton Elementary School Roof Area D Scale: 18" = 1'
Symbol Legend Symbol
Conduit, Vent Pipe or Other Penetration
W
GAS AD EJ
Slope H
L
Notes Symbol Notes Symbol Notes
Equipment Unit on Curb
Roof Hatch on Curb
Roof Ladder
Screen Support Stanchion
Gas Line
Roof Ridges and Valleys
Roof Drain
Overflow Scupper
Tapered Insulation or Saddles
Insulated Pipe or Heat Stack Penetration
Ductwork or Flanged
Abandoned Equipment Curb
Walkway Pad
Railing or Fancing
Area Divider
Roof Slope
New Roof Drain Scupper
Key Notes
Metal Roof Shingles or Clay Titles
Revision
Elevation Change
Expansion Joint
Pipe or Conduit on Support Block
Satellite Dish
Skylight on Curb
Equip. on Wood Sleeper or Support Curb
Pitch-Pan Pocket
AH S
Photos
2'
10'-6" 7'-3" 40'-3" 58'
Slope
Slope
SlopeSlope
Slope
Slop e
SHEET 6 OF 9
Hamilton Elementary School
Roof Area E
A3.3
WTProject No: TSD-R102-27
TSD 2027 - A3.0 Hamilton Elementary School
Review
OTB
09/21/2026 10/01/2026
Hamilton Elementary School 5625 Northfield Pkwy.
Troy, MI 48098
Troy School District 2027 Reroofing Program
THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF
SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF
WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,
WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE
DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON
OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING
GROUP. COPYRIGHT 2023.
DESCRIPTION
COPYRIGHT:
WeatherTech Consulting Group, Inc.
DATE
ISSUE
Drawn By: MD
Checked By: DM, AC, AW
WeatherTech Consulting Group, Inc.
Roofing/Waterproofing Consultants Corporate Office:
45147 Cass Ave.
Utica, MI 48317
Phone #: 586-731-3095 Email: weathertech@wtcg.net
Web Site: www.wtcg.net
SHEET TITLE
CLIENT
PROFESSIONAL
PROJECT
File Name:
ELECTRONIC STAMP
Troy School District 4400 Livernois Troy, MI 48098
KEY PLAN
Hamilton Elementary School - Troy School District Sheet Notes - Roof Area E
Schedule:
WORK DESCRIPTION - ROOF REPLACEMENT
1. Existing Roof System Construction
All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.
Core Sample Results A. Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total
B. Plies with asphalt C. 2-inch Perlite D. Approx. 2 -inch polyisocyanurate insulation.
E. ½” Perlite
F. Deck: Metal: Slope in deck
2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area E 8,550 Sq. Ft.
3. New Roof System: Roof Area E- Ref. Detail 1.01a.
a. Roof Membrane: EPDM, 60 mil, adhered to insulation.
b. Insulation: R30:
1) Top layer shall be set-in low-rise foam adhesive.
2) Bottom layer shall be mechanically attached to metal deck.
c. Tapered Insulation: Roof Drains, see roof plan and details
d. Deck: Metal: Repair as necessary to comply w/ building codes.
e. Interior Ceiling: N/A
f. Building Height: Ground to building edge: 20 ft
4. Warranty:
a. Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.
b. Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment
C.
5. Allowances: $2000.00 shall be added to Base Bid.
6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.
General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Key Notes:
All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.
Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.
Metal Counter Flashing: Install new termination bar and new 24-gauge clear anodized aluminum counter flashings. Ref. Detail 1.14; Photo 7879
Deck Flutes: All debris be removed from deck flutes.
Expansion Joint: Replace the expansion joint metal with a similar profile. Ref. Photo 7888
Metal Strainers: Replace plastic or missing strainers with new (matching type) metal strainers. (if applicable)
Roof Drain Ring: Furnish and install new drain ring. Ref. Photo 7887
Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11
Hamilton Elementary School Roof Area E Scale: 18" = 1'
Symbol Legend Symbol
Conduit, Vent Pipe or Other Penetration
W
GAS AD EJ
Slope H
L
Notes Symbol Notes Symbol Notes
Equipment Unit on Curb
Roof Hatch on Curb
Roof Ladder
Screen Support Stanchion
Gas Line
Roof Ridges and Valleys
Roof Drain
Overflow Scupper
Tapered Insulation or Saddles
Insulated Pipe or Heat Stack Penetration
Ductwork or Flanged
Abandoned Equipment Curb
Walkway Pad
Railing or Fancing
Area Divider
Roof Slope
New Roof Drain Scupper
Key Notes
Metal Roof Shingles or Clay Titles
Revision
Elevation Change
Expansion Joint
Pipe or Conduit on Support Block
Satellite Dish
Skylight on Curb
Equip. on Wood Sleeper or Support Curb
Pitch-Pan Pocket
AH S
Photos
5 7
5 7
NEW ROOF CONSTRUCTION PROFILE FULLY
ADHERED SYSTEMS W/ NAILABLE DECK
SCALE: N.T.S
1.01a
NOTE 1 - ROOF MEMBRANE 60 MIL EPDM - FULLY ADHERED IN BONDING ADHESIVE; FIELD
SEAMS ADHERED WITH 6" (MINIMUM) WIDE SEAM TAPE.
NOTE 2 - APPLY LOW RISE FOAM ADHESIVE IN 3 4 TO 1 INCH WIDE WET BEADS SPACED AT 12
INCHES ON CENTER IN THE FIELD ON THE ROOF; REDUCE BEAD SPACING TO 6 INCHES IN
PERIMETERS AND 4 INCHES IN CORNERS PER FM 60 UPLIFT CRITERIA AS DEFINED IN FMG KISS
REVERTIBLE DATA SHEET 1 - 29.
NOTE 3 - TWO LAYERS OF 4 FT. X 4 FT. INSULATION ADHERED IN LOW RISE FOAM ADHESIVE
SHOWN FOR CLARITY - SEE SCHEDULE ON ROOF PLAN(S) FOR R-VALUES, TYPE AND
THICKNESS OF EACH INSULATION LAYER REQUIRED IN EACH ROOF AREA. TAPERED
INSULATION ALSO MAY BE REQUIRED ON SOME ROOF AREAS OR FOR CRICKETS AND SADDLES
- SEE SCHEDULE AND LAYOUT DRAWINGS ON ROOF PLAN(S) FOR TYPE AND FINISHED SLOPE
OF TAPERED INSULATION. STAGGER ALL INSULATION JOINTS
NAILABLE STRUCTURAL DECK
ROOF INSULATION - SEE NOTE 3
EPDM MEMBRANE SEE
SCHEDULE ON PLAN
6" SEAM TAPE
6"
BONDING ADHESIVE - SEE NOTE 1
LOW RISE FOAM ADHESIVE - SEE NOTE 2
FMG APPROVED FASTENER AND PLATE @ 12 " O.C.
3/4" MIN. - 1 1/4" MAX.
BUTYL TAPE OR 3" SEAM TAPE
2X WOOD BLOCKING TO MATCH HEIGHT OF
ROOF INSULATION - FASTEN @ 12" O.C.
EXTERIOR WALL
ROOF INSULATION
STRUCTURAL DECK
6" SEAM TAPE
EPDM MEMBRANE
FIELD CRIMP
2X WOOD BLOCKING TO MATCH HEIGHT OF
ROOF INSULATION - FASTEN @ 12" O.C.
EPDM BASE FLASHING ADHERED W/
BONDING ADHESIVE - RUN FLASHING
OVER CANT DAM AND DOWN ONTO
CLEAT AS SHOWN
24 GA. PREFINISHED GALV. STEEL
FASCIA COVER
22 GA. GALV. STEEL CANT-DAM W/
CONTINUOUS CLEAT - FASTEN 6" O.C. W/
RING SHANK ROOFING NAILS
CANT-DAM W/ FASCIA
SCALE: N.T.S
TAPERED INSULATION
1.10 1.11
ROOF DRAIN
SCALE: N.T.S
1.03
1.12OVERFLOW DRAIN
SCALE: N.T.S1.09
1.02 RAISED EDGE METAL AND FLASHING
SCALE: N.T.S
2"
4"
EPDM MEMBRANE
6" SEAM TAPE
REINFORCED ATTACHMENT STRIP
FASTENED @ 12" O.C.
24 GA. PREFINISHED GALV. STEEL GRAVEL
STOP - FASTEN 3" O.C. STAGGERED W/ RING
SHANK ROOFING NAILS
BUTYL TAPE OR 3" SEAM TAPE
22 GA. GAL STEEL CONTINUOUS
CLEAT-FASTEN 6" O.C. STAGGERED W/ RING
SHANK ROOFING
2X WOOD BLOCKING TO MATCH HEIGHT OF
ROOF INSULATION - FASTEN @ 12" O.C.
EXTERIOR WALL
ROOF INSULATION
STRUCTURAL DECK
ROOF DRAIN SUMP
SCALE: N.T.S
ROOF AND OVERFLOW DRAIN SUMP
SCALE: N.T.S
1.04
2" MIN.
VERIFY IN FIELD
2" MIN.
VERIFY
IN
FIELD
1"
45°
NOTE 1 - DIMENSIONS NOT GIVEN BE VERIFIED IN FIELD.
NOTE 2 - CONTINUOUS CLEAT NOT TO EXCEED 12 LF.
NOTE 3 - ALLOW 41" GAP BETWEEN CLEAT. OFFSET CLEAT JOINTS FROM COPING JOINTS.
TYPICAL PARAPET/COPING CAP
SCALE: N.T.S
20 GA. GALV.CONTINUOUS
CLEAT. FASTENED @ 6" O.C.
BOTTOM OF METAL CAP TO
BE 2" BENEATH UNDERSIDE
OF WOOD BLOCKING
2X WOOD BLOCKING TO
MATCH HEIGHT OF ROOF
INSULATION - FASTEN @ 12"
O.C.
GASKETED FASTENER @ 18"
O.C. DEPENDING ON WIND
ZONE AND K=LOCAL
CONDITIONS
22 GA. GALV. METAL COPING
W/ 1"/FT SLOPE MIN.
1.06 1.07 1.08
WeatherTech © Date: Rev 3/15
SEALANT
FACE SIDE
ROOF SIDE
24"24"
1. SHOP FABRICATED CORNERS TO PROVIDE POSITIVE SLOPE
2. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATION.
POP RIVET
24 GAUGE
PRE-FINSHED GALV.
WALL FLASHING SET IN
SEALANT
PARAPET
WALL
2"
METAL COPING
FORM COPING METAL TO
END UP WITH 2" ONTO
WALL
WeatherTech © Date: Rev 3/15
SEALANT
FASTENERS
FASTENERS
WeatherTech © Date: Rev 3/15
12' [4 m] MAX.
LENGTH EACH PIECE
OF COPING CAP
2'' [5 0 mm] APPROX.
OPTION:
SECTION:
1'' [25 mm] MIN.
1'' [25 mm] MIN.
SHEET METAL DOUBLE LOCK
STANDING SEAM
SHEET METAL COPING CAP
BUTTON PUNCH TO
HOLD IN PLACE
SHEET METAL SET IN
SEALANT
4.
3.
2.
NOTES:
1.
CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
REFER TO TABLE SM-19 FOR COPING CAP SECUREMENT OPTIONS.
COPING JOINERY IS SIMILAR ON BOTH SIDES.
REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.
COPING CAP W/ DOUBLE LOCK STANDING SEAM
SCALE: N.T.S
WALL TERMINATION
SCALE: N.T.S
PARAPET COPING CAP CORNERS
SCALE: N.T.S
NOTE 1 - GUTTER OUTLETS AND DOWNSPOUTS BE 24 GA. GALV. STEEL, 24 GA.
STAINLESS STEEL 16 O.Z. COLD ROLLED COPPER - SEE THE SCHEDULE(S) ON THE ROOF
PLAN(S) FOR SPECIFIC REQUIREMENTS FOR EACH ROOF AREA
NOTE 2 - PROVIDE 1 OUTLET MIN. IN EACH SECTION OF GUTTER.
NOTE 3 - GUTTER HEIGHT AND WIDTH OUTLET/DOWNSPOUT SIZE BE CALCULATED PER
SMACNA RECOMMENDATIONS BASED ON SIZE OF ROOF TO BE DRAINED.
X X
1" 2"
4"
SHEET METAL DOWNSPOUT - SEE
NOTES 1, 2 AND 3
#12 SCREWS
SHEET METAL GUTTER FASTENED TO
WOOD NAILER 6" O.C. W/ STAINLESS
STEEL RING SHANK NAILS - SOLDER
ALL JOINTS WATERTIGHT - SEE NOTE
1 AND 2.
10 GA. GALV. STEEL GUTTER STRAP
30" O.C.
1"
SHEET METAL OUTLET - SEE NOTES
1, 2 AND 3
SEE NOTES 3
#12 SCREWS
24 GA. GALV. STEEL DRIP EDGING -
FASTEN 4" O.C. STAGGERED.
6" SEAM TAPE
EPDM MEMBRANE
TAPERED INSULATION
BUTYL TAPE OR 3" SEAM TAPE
2X WOOD BLOCKING TO MATCH
HEIGHT OF ROOF INSULATION -
FASTEN @ 12" O.C.
EXTERIOR WALL
ROOF INSULATION
STRUCTURAL DECK
GUTTER
SCALE: N.T.S 1.13
CONTINUOUS BEAD OF SEALANT
TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER
STAINLESS STEEL CLAMPING RING BOLTS - REPLACE IF
MISSING, DAMAGED OR NON-STAINLESS STEEL BOLTS
STRUCTURAL DECK
DRAIN BOWL
DRAIN PIPING
TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER
1" MIN.
2"
CAST IRON DRAIN STRAINER - REPLACE IF MISSING OR
BROKEN. PLASTIC DRAIN STRAINER ARE ONLY ALLOWED
WITH APPROV BY CONSULTANT IN WRITING.
CLAMPING RING - REMOVE ALL BITUMINOUS MATERIALS
- REPLACE IF MISSING OR BROKEN DURING REMOVAL
EPDM MEMBRANE
NOTE - CONTRACTORS SHALL INSTALL TAPERED INSULATION. DO NOT SHAVE ROOF INSULATION TO
MATCH DRAIN INSULATION HEIGHT WITH DRAIN BOWL HEIGHT.
192"
48" 48" 48"48"
CONTINUOUS BEAD OF SEALANT
TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER
STAINLESS STEEL CLAMPING RING BOLTS - REPLACE IF
MISSING, DAMAGED OR NON-STAINLESS STEEL BOLTS
STRUCTURAL DECK
DRAIN BOWL
DRAIN PIPING
TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER
1" MIN.
2"
NOTE - CONTRACTORS SHALL INSTALL TAPERED INSULATION. DO NOT SHAVE ROOF INSULATION TO
MATCH DRAIN INSULATION HEIGHT WITH DRAIN BOWL HEIGHT.
192"
48" 48" 48"48"
CAST IRON DRAIN STRAINER - REPLACE IF MISSING OR
BROKEN. PLASTIC DRAIN STRAINER ARE ONLY ALLOWED
WITH APPROV BY CONSULTANT IN WRITING.
OVERFLOW CLAMPING RING - REMOVE ALL BITUMINOUS
MATERIALS - REPLACE IF MISSING OR BROKEN DURING
REMOVAL
EPDM MEMBRANE
CENTER LINE DRAIN CENTER LINE DRAIN
48"
192"
48"
ROOF DRAIN
ROOF DRAIN SUMP. TAPERED AT A MIN. 12"
PER FOOT
CENTER LINE DRAIN
SLOPE SLOPE
48"
48"
192"
48"
48"48"
SLOPE
SLOPE
SLOPE SLOPE
SLOPE
48"
48"
252"
48"
48"
48"
192"
48"
48"48"
48"
SLOPE
SLOPE
SLOPE
SLOPE
SLOPE
SLOPE
SLOPESLOPE
ROOF DRAIN
ROOF DRAIN SUMP. TAPERED AT A MIN. 12"
PER FOOT
CENTER LINE DRAIN CENTER LINE DRAIN
60"
NEW ROOF CONSTRUCTION PROFILE FULLY
ADHERED SYSTEMS W/ VAPOR BARRIER
SCALE: N.T.S
1.01b
NOTE 1 - ROOF MEMBRANE 60 MIL EPDM - FULLY ADHERED IN BONDING ADHESIVE; FIELD
SEAMS ADHERED WITH 6" (MINIMUM) WIDE SEAM TAPE.
NOTE 2 - APPLY LOW RISE FOAM ADHESIVE IN 3 4 TO 1 INCH WIDE WET BEADS SPACED AT 12
INCHES ON CENTER IN THE FIELD ON THE ROOF; REDUCE BEAD SPACING TO 6 INCHES IN
PERIMETERS AND 4 INCHES IN CORNERS PER FM 60 UPLIFT CRITERIA AS DEFINED IN FMG KISS
REVERTIBLE DATA SHEET 1 -…