Addendum #1 - RFP 2627-03 TSD 2027 Roofing Program.pdf

PDF 2 MB Posted

Attached to
RFP2627-03 TSD Roofing Projects 2027
Solicitation number
RFP TSD 270000000078 2
Issued by
Oakland County, Michigan

About this file

This Addendum #1 document modifies RFP 2627-03 for the Troy School District 2027 Roofing Program, a roof replacement project covering two Michigan schools: Morse Elementary School (475 Cherry Avenue, Troy, MI) and Hamilton Elementary School (5625 Northfield Parkway, Troy, MI). The scope of work encompasses removal and replacement of existing roofing systems, insulation, and flashing across approximately 69,323 square feet of roof area divided into five separate roof areas at Hamilton Elementary and one roof area at Morse Elementary. The project requires installation of 60-mil EPDM membrane roofing with R-30 insulation, new metal flashings, drain systems, and related accessories. Key dates include a revised bid submission deadline of 2:00 PM EST on Tuesday, November 10, 2026 (changed from 1:00 PM), with bids submitted exclusively through BuildingConnected.com. A pre-bid meeting was held on October 30, 2026, and RFIs were due November 6, 2026. Contract award is anticipated by December 2026, with work scheduled to commence approximately June 8, 2027, and substantial completion targeted for August 13, 2027, allowing approximately 48 workdays. Work hours are Monday through Friday, 10 hours per day, with Saturday as a rain makeup day. The Troy School District reserves the right to award contracts to multiple contractors.

The bid must include a five percent (5%) bid bond or certified check, and the successful contractor must provide both a payment bond and performance bond. Base bids include allowances specified on individual roof plans: $2,000 for Morse Elementary Roof Area A, $7,000 for Hamilton Elementary Roof Area A, $2,000 each for Roof Areas C, D, and E. The roofing contractor must provide the roof system manufacturer's twenty-year "No-Dollar-Limit" material and installation warranty and a five-year performance agreement. Unit pricing is required for additional work beyond the base bid. Liquidated damages are assessed at $500 per day after August 14, 2027. Contact for questions is Ann Crippen at WeatherTech Consulting Group (acrippen@wtcg.net, 586-731-3095 ext. 12), the project manager. No physical bids will be accepted; all submissions must be made electronically through the designated BuildingConnected.com portal.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum 1

Project: RFP NUMBER 2627-03 – 2027 ROOFING PROGRAM

Bid Due date: 2:00 PM Local Time, Tuesday, November 10, 2026 (REVISED)

This Addendum is issued as modifications to the RFP previously issued to provide clarifications to the scope of work. This Addendum supersedes the original RFP. This along with the RFP becomes the bid documents.

I. General Information

1. For questions e-mail lecoleplanners3@gmail.com or through Buildingconnected.com.

2. Any bidder requesting to visit the site should contact Mark Paulus at lecoleplanners3@gmail.com or (248) 880-6791 to schedule a time. No bidder shall visit the building without scheduling it with Mark Paulus.

3. Invitation to Bid. Revise paragraph 3, sentence 3. Bids are to be submitted no later than 2 pm on November 10, 2026.

4. Bid Package. Revise page 3, paragraph 3, sentence 3. Bids are to be submitted no later than 2 pm on November 10, 2026.

5. Addendum #1 dated November 6, 2026, as prepared by WeatherTech Consulting Group, Inc. (Attached)

6. Pre-bid Meeting Minutes on October 30, 2026, as prepared by WeatherTech Consulting Group, Inc.

END

WeatherTech Consulting Group, Inc.

ADDENDUM 1

Troy School District

2627-03 2027 Roof Program

WeatherTech Consulting Group 45147 Cass Ave Utica, MI 48317 586-731-3095 Fax 586-731-6863 weathertech@wtcg.net www.wtcg.net

POST BID

ADDENDUM NO.: 01 DATE: 11/6/26

PROJECT IDENTIFICATION

PROJECT NAME: BID NO. 2627-03 Troy School District 2026 Roof Program

SITE ADDRESS: 5625 Northfield Pkwy Troy, MI 48098

ADDENDUM DESCRIPTION

The following is a summary of changes to the Bid Documents dated 10-01-26 that shall be considered as a part of your Bid. Addendum Drawings Re-Issued

SUMMARY OF ADDENDUM:

Item Description

1.

Changes to roof drawings:

Drawing A3.1 – Change measurements from 31’6” to 42’. Reference General Notes #3

Drawing A3.2:

1.Add: Keynote 6 Wall Ladder Replacement – Furnish and install a new wall ladder to match existing. Ref. Photo 7921 2.Change of scope – New Roof System:

a. Roof Membrane: EPDM, 60 mil, adhered to insulation.

b. Insulation: R30:

1) Top layer shall be set-in low-rise foam adhesive.

2) Bottom layer shall be set-in low-rise foam adhesive to vapor barrier.

c. Vapor Barrier shall be installed over metal deck. (Carlisle VapAir Seal MD or equivalent) Tapered Insulation: Roof Drains, see roof plan and details

d. Deck: Metal: Repair as necessary to comply w/ building codes.

e. Interior Ceiling: N/A

f. Building Height: Ground to building edge: 45 ft

2.

Roofing Contractors RFI’s:

Hamilton Elementary School - Drawings state to install new wood nailers on the perimeter edge. Can we leave the existing in place? Looks like with the new roof height, we shouldn’t need to add any.

Replace any missing or damaged nailers and add nailers to achieve required base flashing height.

PROJECT CONSULTANT:

ADDENDUM 1

Troy School District

2627-03 2027 Roof Program

WeatherTech Consulting Group 45147 Cass Ave Utica, MI 48317 586-731-3095 Fax 586-731-6863 weathertech@wtcg.net www.wtcg.net

COMPANY: WeatherTech Consulting Group

NAME: Ann Crippen

ADDRESS: 45147 Cass Ave Utica, MI 48317

WT OFFICE: (586) 731-3095

E-MAIL: acrippen@wtcg.net

SHEET 1 OF 9

Cover Sheet

A1.0

OWNER:

Troy School District 4400 Livernois Troy, MI 48098

PROJECT LOCATION:

See Project List

ROOFING CONSULTANTS:

WeatherTech Consulting Group, Inc.

Utica, MI 48317

CONTACT:

Rob Carson Director of Operations Phone: (248) 823-4067 E-Mail: RCarson@troy.k12.mi.us

CONTACT:

Michelle Kerns Bond Representative Phone: (248) 921-3929 E-Mail: mkerns@troy.k12.mi.us

CONTACT:

Ann Crippen Project Manager Phone: (586) 731-3095 x12 E-Mail: acrippen@wtcg.net

John McCaig, RRO Site Contact

Jack Runkle, AIA Design Review

Troy School District 2027 Roofing Program

Troy School District 2027 Roofing Program

Project Work Schedule

A1.0

A2.0

A3.0

A3.1

A3.2

A3.3

Cover Sheet

Roof Plan, Morse Elementary School Roof Area A

Roof Plan, Hamilton Elementary School - Roof Area A

Roof Plan, Hamilton Elementary School - Roof Area C

Roof Plan, Hamilton Elementary School - Roof Area D

Roof Plan, Hamilton Elementary School - Roof Area E

A4.0 Detail Sheet

A4.1 Detail Sheet

A4.2 Detail Sheet

Morse Elementary School 475 Cherry Ave, Troy, MI 48083 Hamilton Elementary School 5625 Northfield Pkwy, Troy, MI 48098

THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF

SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF

WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,

WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE

DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON

OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING

GROUP. COPYRIGHT 2023.

DESCRIPTION

COPYRIGHT:

WeatherTech Consulting Group, Inc.

DATE

ISSUE

Drawn By: MD

Checked By: AC, AW, JM

WeatherTech Consulting Group, Inc.

Roofing/Waterproofing Consultants Corporate Office:

45147 Cass Ave.

Utica, MI 48317

Phone #: 586-731-3095 Email: weathertech@wtcg.net

Web Site: www.wtcg.net

SHEET TITLE

CLIENT

PROFESSIONAL

PROJECT

File Name:

ELECTRONIC STAMP

TSD 2027 - A1.0 Cover Page

WTProject No: TSD-R102-27

PROJECT SUMMARY

SUMMARY OF WORK: Ref. Section 00 02 00 General: Troy School District (TSD) 2027 Roof Program work for two (2) schools. Roofing work includes roof replacement required to remediate all work identified in the specifications and drawings inclusive of all Bid Documents requirements.

Schedules: Ref. “PROJECT WORK SCHEDULE” on this Sheet A1.0 - Cover Page.

BID SUMMARY:

Instruction to Bidders 000113: Reference the Project Manual, specification 000113 for bid preparation, RFI dates and Pre-Bid Meeting information.

Allowances Section 012100: Allowances will be defined on individual school roof plans under “Allowances”. These allowances ll be stated on the bid form.

3. Unit Pricing Section 004322: Unit Pricing for unit work is defined on the Unit Price Bid Form in Section 000301. Unit Pricing bid values are entered by unit price individually on form.

4. Alternates Section 012300: Alternates are individually listed on school roof plans and bids for Alternates. Alternated bid value are to be entered on Bid Form (Section 000300) as enumerated.

5. TSD reserves the right to issue contracts to multiple contractors.

EXISTING ROOF SYSTEM CONSTRUCTION:

Ref. Roof Plans. All existing roof system constructions were determined by test cuts and observation; conditions may vary. Contractor s responsible for confirming all existing roof system constructions, measurements, cores and conditions.

NEW ROOF ASSEMBLY SUMMARY: Reference Roof Plans

1. Roof System: Ref. Roof Plan Schedules

a. Roof Membrane: EPDM, 60 mil, unreinforced and fully adhered.

b. Insulation: To meet a R-30 minimum, Min. two layers. Top layer must be adhered: Bottom layer mechanically- attached (unless otherwise stated on individual roof plans)

c. Underlayment: (as required) Modified base sheet, Ref. individual Roof Plans.

d. Deck: Multiple types, Ref. individual Roof Plans.

2. Roof System Performance:

a. Warranty: 20 yr. Materials manufacturer, No Dollar Limit (NDL) materials and installation.

b. Contractor to provide a 5-year contractor guarantee.

c. Wind: FM Global (FMG): FM Standard 4470 Meets - Windstorm Classification FMG 90.

d. Fire: Underwriters Laboratory External Fire Resistance - Class "A".

e. Energy: Michigan Uniform Energy Code: R30 condition dependent

f. Drainage: Drainage Performance Acknowledgement”

GENERAL SHEET NOTES

1. All work shall be executed in accordance with the appropriate document of the Contract Documents.

2. Any conflicts between specifications and drawings shall be brought to the attention of the Owner and Consultant immediately. In all situations the more restrictive and higher quality shall govern.

3. All dimensions to, of, and in existing building and roof shall be verified in the field by contractor. Field measure existing conditions to verify material quantities and dimensions prior to fabrication on component material.

4. Details shown are typical. Similar details apply to similar conditions unless otherwise indicated.

5. The drawings herein are related to an alteration/ restoration to an existing structure. The specified work was based upon as much observation, destructive testing, etc. as circumstances permitted.

GENERAL CONSTRUCTION DETAIL NOTES

Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A .0 - A .2. Contractor provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Flashing Heights: Perimeters, curbs, penetrations shall be raised as necessary to meet the new insulation heights, tapered edge strip and tapered insulation height to meet typical industry standard of 8 in. base flashing height.

Drains Existing: Remove existing drain flashings. Furnish and install ½ inch per foot sloped tapered insulation sump area (8 ft. x 8 ft. minimum) as detailed. Clean and reuse existing drains and accessories, replace all damaged, nonfunctional, incompatible, missing and broken drain components.

Replace all plastic strainers with new cast iron. All replacement bowls, strainers, and clamping rings shall be cast iron. Provide new stainless-steel bolts. All nonmetallic drains strainers shall be replaced with fitted. Ref. Details 1.09, 1.10, 1.11 and 1.12.

Tapered Insulation: Furnish and install new tapered insulation, crickets, saddles and kick-backs as designated on roof plan to provide a finished slope of 1/4 in/ ft. slope and a min length to width ratio of 3:1. All equipment w/ curb size greater than 24 in. shall have cricket install on up slope side.

Contractor responsible for identifying and notifying Consultant and Owner of all existing tapered insulation not called out on plans for determination of unit costing. Verify in Pre-bid Conference additional ponded areas identified on the roof and install as noted.

Curbs - Movable Equipment: Lift equipment from curbs; run new fully adhered membrane flashing up and over top of curb; install continuous sealing material over top of curb. Reset equipment and mechanically fasten to curb. Coordinate with Owner prior to moving equipment to install new flashings.

Metal equipment flashing and/or counter flashing must extend a minimum of 3 in. past the termination of the base flashing; add metal counter flashing as required. Ref. Details 1.17 and 1.18.

Curbs - Non-Movable Equipment: Terminate new fully adhered membrane flashing at unit framing member. Metal equipment flashing and/or counter flashing must extend a minimum of 3 in. past the termination of the base flashing; add metal counter flashing as required. Ref. Detail 2.01.

Equipment on Support Curbs - Non-Movable Equipment: Cut corners of metal flashing cap, terminate new adhered membrane flashing to curb nailer. Reposition metal; install new shop fabricated corner metal, riveted and set in sealant. Wire brush and apply rust inhibitive paint to rusted cap metal.

Ref. Detail 3.02.

Equipment on Support Curbs - Movable Equipment: Raise or move equipment to furnish and install new metal cap on curb. Ref. Detail 2.18.

Round Penetrations: All penetrations shall be cleaned down to surface where any sealant will contact; Install new prefabricated pipe boots or field wrap with membrane. Install draw band, sealants and rain collars as detailed. Ref. Details 2.03 and 2.04.

Heat Stacks: Install new metal jacks and collars. Clean surfaces and apply new field wrapped EPDM flashing. Reattach and reseal storm collars with high temperature sealant. Ref. Detail 2.05.

Steel Support Posts: Install split pipe boot or field wrap flashing with membrane. Terminate with draw band and sealant. Ref. Detail 2.02.

Prefabricated Pipe Chase Cover: Reuse existing pipe cover. Replace any damaged or missing clamping bands or sealants. Ref. Detail 3.01.

Gas Line and Conduit Support Blocks: Provide prefabricated pipe supports set on walkpads. Ref.

Details 3.03 and 3.11.

Condensate Drain Lines: Reuse, repair or replace all damaged or unusable drain lines. Add additional drain line to extend minimum 4 ft. from equipment or to any drains within 20 ft. Provide manufacturer's approved splash pan/pad/block where condensate drainage water would contact the roof membrane.

All utility service lines (gas, water, electric, cable, etc.) to be raised as necessary to accommodate new insulation height and meet code requirements.

Abandoned Curbs and Penetrations: Owner will mark all equipment to be removed. Remove all equipment and curbs as designated by owner and identified at the prebid conference. Where directed, remove curbs flush to deck surface, install framing and matching decking material. For abandoned curbs to remain in place, install new base flashing and install new 24 gauge sloped metal cap. Provide interior protection when removing any equipment or penetration. All small round abandoned penetrations that have no utility service as confirmed by Owner shall be removed to deck, patched according to deck type.

Pitch Pans: Pitch pans can only be used when approved by Consultant. In the event they are to be used, furnish and install new pitch pans, clean all penetrations down to original surface, blocking required at all pitch pans. Ref. Detail 2.09.

Door Threshold: Remove threshold plate and carry flashing up over and set in water block. Before resetting threshold, mechanically attach termination bar, fasten min. 6 in. o.c. Door Threshold: Remove and dispose of existing counter flashing. Roof flashing to extend up and under existing threshold plate.

Furnish and install new metal counter flashing and sealant.

Downspout Outlets: Provide concrete splash blocks set on walkpad at all roof downspout conductors.

Vent Thru Roof Piping: Install PVC pipe extensions to all VTR piping prior to installation of new pipe boot flashing as needed to allow a minimum 8-inch flashing height. Attach screen wire mesh over the top of the pipe. Ref. Detail 2.06.

Walk Pads: Provide walk pads at roof access hatches and ladder access locations. Use walk pads approved by the roofing membrane manufacturer.

Existing Expansion Joint: Install wood as needed to provide a minimum 8-inch flashing height;

Replace existing batt insulation and liner if needed; Re-install if able or furnish and install new gauge prefinished metal expansion joint cover. Ref. Detail 3.05.

Deck Flutes: All debris be removed from deck flutes.

Protection and Cleaning of Installed Roof Membrane: The roofing contractor is responsible for protection of installed sections of new roof membrane from staining and discoloration. Strategies for protection of installed membrane may include, but are not limited to, use of roof membranes with manufacturer-applied protective film, full coverage of installed membrane with sealed tarps, sequencing of roof membrane installation in a manner to limit tear-off dust, dirt and debris migration, and limiting traffic on installed membrane. Upon completion of installation, stained membrane shall be cleaned to the satisfaction of the owner and shall maintain the manufacturer-published initial solar reflectance of the product.

Review

OTB

09/21/2026 10/01/2026

Troy School District 4400 Livernois Troy, MI 48098

STATE OF MICHIGAN LARA RECORD LOCATOR

Project Manual

TABLE OF CONTENTS

00 00 00 Cover

00 01 10 TABLE OF CONTENTS

00 01 11 PROJECT DIRECTORY

BID REQUIREMENTS

00 01 12 INVITATION TO BID - TSD

00 01 13 INSTRUCTIONS TO BIDDERS - TSD

00 02 00 SUMMARY OF WORK

00 03 00 BID FORM

00 03 01 UNIT PRICE FORM

00 03 04 PAYMENT BOND

00 03 05 PERFORMANCE BOND

00 04 01 PARTIAL RELEASE OF LIEN

00 04 02 FINAL RELEASE OF LIEN

00 04 11 FAMILIAL DISCLOSURE/ IRAN ECONOMIC SANCTIONS

00 43 22 UNIT PRICING INFORMATION

00 43 36 LIST OF SUBCONTRACTORS

00 73 00 SUPPLEMENTAL CONDITIONS

DIVISION 1 - GENERAL REQUIREMENTS

01 06 00 REGULATORY REQUIREMENTS

01 14 19 USE OF SITE

01 20 03 CHANGES TO WORK

01 21 00 ALLOWANCES

01 23 00 ALTERNATES

01 29 00 PAYMENT PROCEDURES

01 32 00 CONSTRUCTION SCHEDULE

01 32 14 WEB SITE & DOCUMENTS

01 33 00 SUBMITTALS

01 33 26 QUALITY CONTROL

01 35 01 SAFETY

01 42 16 TERMS AND DEFINITIONS

01 50 00 CONSTRUCTION FACILITIES & TEMPORARY CONTROLS

01 74 23 FINAL CLEANING

01 77 00 CLOSE OUT

DIVISION 2 - SITE WORK

02 41 19 SELECTIVE DEMOLITION

DIVISION 6 - ROUGH CARPENTRY

06 10 00 ROUGH CARPENTRY

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

07 22 50 SINGLE PLY ROOF INSULATION

07 54 00 FULLY ADHERED EPDM ROOFING

07 62 00 SHEET METAL FLASHING AND TRIM

07 72 00 ROOF ACCESSORIES

07 90 00 SEALERS

DIVISION 22 - PLUMBING

22 14 26.13 ROOF DRAINS

DRAWINGS - Ref. Sheet A1.0 - Sheet Index

DIRECTORY

PROJECT LIST

SHEET INDEX

SHEET NO. SHEET TILE

PR2026BCC-003717

H

'-6

'-6

15' 46'

61'

60'-7"

Slope Slope

Slope

Slope

THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF

SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF

WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,

WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE

DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON

OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING

GROUP. COPYRIGHT 2023.

DESCRIPTION

COPYRIGHT:

WeatherTech Consulting Group, Inc.

DATE

ISSUE

Drawn By: MD

Checked By: AC, AW, JM

WeatherTech Consulting Group, Inc.

Roofing/Waterproofing Consultants Corporate Office:

45147 Cass Ave.

Utica, MI 48317

Phone #: 586-731-3095 Email: weathertech@wtcg.net

Web Site: www.wtcg.net

SHEET TITLE

CLIENT

PROFESSIONAL

PROJECT

File Name:

ELECTRONIC STAMP

SHEET 2 OF 9

Roof Plan Morse Elementary School

Roof Area A

A2.0

WTProject No: TSD-R102-27

TSD 2026 - A4.0 Morse Elementary School

Review

OTB

09/21/2026 10/01/2026

KEY PLAN

Symbol Legend Symbol

Conduit, Vent Pipe or Other Penetration

W

GAS AD EJ

Slope H

L

Notes Symbol Notes Symbol Notes

Equipment Unit on Curb

Roof Hatch on Curb

Roof Ladder

Screen Support Stanchion

Gas Line

Roof Ridges and Valleys

Roof Drain

Overflow Scupper

Tapered Insulation or Saddles

Insulated Pipe or Heat Stack Penetration

Ductwork or Flanged

Abandoned Equipment Curb

Walkway Pad

Railing or Fancing

Area Divider

Roof Slope

New Roof Drain Scupper

Key Notes

Metal Roof Shingles or Clay Titles

Revision

Elevation Change

Expansion Joint

Pipe or Conduit on Support Block

Satellite Dish

Skylight on Curb

Equip. on Wood Sleeper or Support Curb

Pitch-Pan Pocket

AH S

Morse Elementary School Roof Area A Scale: 18" = 1'

Photos

Morse Elementary School 475 Cherry Dr.

Troy, MI 48083

Troy School District 2027 Roofing Program

Morse Elementary School - Troy School District Sheet Notes - Roof Area A

Schedule:

WORK DESCRIPTION - ROOF REPLACEMENT

1. Existing Roof System Construction

All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor responsible for confirming all existing roof system constructions and conditions.

Roof Area A Core Sample Results A. Roof Membrane: BUR B. Insulation:

1) Top Layer: Insulation ½” Fiberboard Insulation

2) Base Layer: Approx. 1 1/2 -inch ISO insulation

C. Deck: Metal Deck (slope in deck)

2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area A 4,135 sq. ft.

3. New Roof System: Roof Area A - Ref. Detail 1.01a.

a. Roof Membrane: EPDM, 60 mil, adhered to insulation.

b. Insulation: R30:

1) Top layer set-in low-rise foam adhesive.

2) Bottom layer mechanically attached to metal deck.

c. Tapered Insulation: Roof Drains, see roof plan and details

d. Deck: Metal: Repair as necessary to comply w/ building codes.

e. Interior Ceiling: N/A

f. Building Height: Ground to building edge: 50ft

4. Warranty/Guarantee:

a. Manufacturer to provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.

b. Roofing installer to provide a five (5) year Performance Agreement - see Specification Attachment C.

5. Allowances: $2000.00 to be added to Base Bid.

6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results to be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.

General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Key Notes:

All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

1. Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.

2. Metal Strainers: Replace plastic or missing strainers with new metal strainers. (4 total) Ref. Photo 7977.

3. Tapered Roof Sumps: Furnish and install 8 ft tapered roof sumps on all drains. Ref. Photo 7972.

4. New roof hatch: Furnish and install new roof hatch with safety cage and ladder-up bar. Ref. Photo 7973.

Troy School District 4400 Livernois Troy, MI 48098

3 4

Coutyard

68'-6"

'-3

'-3

58'-9"

6' -3

63'-3" 35'-6"

157'-6"

21'

178'-6"

'-9

'-9

'-3

68'-9"

21'-9"

'-6

14'

68'-6"

21'

'-6

'-6

'-6

21'-9"

'-3

15'-3"8'30'-6"

Slope

Slope

SlopeSlope

Slop e

Slop e

Slope

Slope

Slop e

Slope

Slop e

Slop e

Slop e

Slope

Slope

Slope

Slope

Slope

Slope

Slope Slope

SHEET 3 OF 9

Hamilton Elementary School

Roof Area A

A3.0

WTProject No: TSD-R102-27

TSD 2027 - A3.0 Hamilton Elementary School

Review

OTB

09/21/2026 10/01/2026

Hamilton Elementary School 5625 Northfield Pkwy.

Troy, MI 48098

Troy School District 2027 Reroofing Program

THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF

SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF

WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,

WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE

DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON

OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING

GROUP. COPYRIGHT 2023.

DESCRIPTION

COPYRIGHT:

WeatherTech Consulting Group, Inc.

DATE

ISSUE

Drawn By: MD

Checked By: DM, AC, AW

WeatherTech Consulting Group, Inc.

Roofing/Waterproofing Consultants Corporate Office:

45147 Cass Ave.

Utica, MI 48317

Phone #: 586-731-3095 Email: weathertech@wtcg.net

Web Site: www.wtcg.net

SHEET TITLE

CLIENT

PROFESSIONAL

PROJECT

File Name:

ELECTRONIC STAMP

Troy School District 4400 Livernois Troy, MI 48098

KEY PLAN

Hamilton Elementary School - Troy School District Sheet Notes - Roof Area A

Schedule:

WORK DESCRIPTION - ROOF REPLACEMENT

1. Existing Roof System Construction

All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.

Core Sample: (Contractor to verify at Pre-Bid Meeting) A. Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total (Photo 4326)

B. Plies with asphalt C. 2-inch Fiberglass D. Approx. 2 -inch polyisocyanurate insulation.

E. ½” Perlite

F. Deck: Metal: Slope in deck

2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area A 41,744 Sq. Ft.

3. New Roof System: Roof Area A- Ref. Detail 1.01a.

a. Roof Membrane: EPDM, 60 mil, adhered to insulation.

b. Insulation: R30:

1) Top layer shall be set-in low-rise foam adhesive.

2) Bottom layer shall be mechanically attached to metal deck.

c. Tapered Insulation: Roof Drains, see roof plan and details

d. Deck: Metal: Repair as necessary to comply w/ building codes.

e. Interior Ceiling: N/A

f. Building Height: Ground to building edge: 20 ft

4. Warranty:

a. Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.

b. Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment

C.

5. Allowances: $7000.00 shall be added to Base Bid.

6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.

General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Key Notes:

All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.

Metal Counter Flashing: Install new termination bar and new 24-gauge clear anodized aluminum counter flashings. Ref. Detail 1.14 (If applicable)

Deck Flutes: All debris be removed from deck flutes.

Expansion Joint: Replace the expansion joint metal with a similar profile and standing seams. Ref.

Photo 7776 and 7847

Metal Strainers: Replace plastic or missing strainers with new (matching) metal strainers. Ref. Photo 7849 (If applicable)

Gas Pipe Blocking: Reuse existing blockings with walkway underlayment. Ref. Photo 7779

Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11(all locations)

Hamilton Elementary School Roof Area A Scale: 116" = 1'

Symbol Legend Symbol

Conduit, Vent Pipe or Other Penetration

W

GAS AD EJ

Slope H

L

Notes Symbol Notes Symbol Notes

Equipment Unit on Curb

Roof Hatch on Curb

Roof Ladder

Screen Support Stanchion

Gas Line

Roof Ridges and Valleys

Roof Drain

Overflow Scupper

Tapered Insulation or Saddles

Insulated Pipe or Heat Stack Penetration

Ductwork or Flanged

Abandoned Equipment Curb

Walkway Pad

Railing or Fancing

Area Divider

Roof Slope

New Roof Drain Scupper

Key Notes

Metal Roof Shingles or Clay Titles

Revision

Elevation Change

Expansion Joint

Pipe or Conduit on Support Block

Satellite Dish

Skylight on Curb

Equip. on Wood Sleeper or Support Curb

Pitch-Pan Pocket

AH S

Photos

7776 7779

7847 7849

1 1

W

8'

21'

10'-6"

8'

7' -6

1' -6

26'-6"5'

31'-6"

W

Slope

Slope

Slope Slope

Slope

SHEET 4 OF 9

Hamilton Elementary School

Roof Area C

A3.1

WTProject No: TSD-R102-27

TSD 2027 - A8.0 Hamilton Elementary School

Review

OTB

09/21/2026 10/01/2026

Hamilton Elementary School 5625 Northfield Pkwy.

Troy, MI 48098

Troy School District 2027 Reroofing Program

THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF

SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF

WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,

WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE

DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON

OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING

GROUP. COPYRIGHT 2023.

DESCRIPTION

COPYRIGHT:

WeatherTech Consulting Group, Inc.

DATE

ISSUE

Drawn By: MD

Checked By: DM, AC, AW

WeatherTech Consulting Group, Inc.

Roofing/Waterproofing Consultants Corporate Office:

45147 Cass Ave.

Utica, MI 48317

Phone #: 586-731-3095 Email: weathertech@wtcg.net

Web Site: www.wtcg.net

SHEET TITLE

CLIENT

PROFESSIONAL

PROJECT

File Name:

ELECTRONIC STAMP

Troy School District 4400 Livernois Troy, MI 48098

KEY PLAN

Hamilton Elementary School - Troy School District Sheet Notes - Roof Area C

Schedule:

WORK DESCRIPTION - ROOF REPLACEMENT

1. Existing Roof System Construction

All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.

Core Sample Results A. Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total

B. Plies with asphalt C. 2-inch Fiberglass D. Approx. 2 -inch polyisocyanurate insulation.

E. ½” Perlite

F. Deck: Metal: Slope in deck

2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area C 5,444 Sq. Ft.

3. New Roof System: Roof Area C- Ref. Detail 1.01a.

a. Roof Membrane: EPDM, 60 mil, adhered to insulation.

b. Insulation: R30:

1) Top layer shall be set-in low-rise foam adhesive.

2) Bottom layer shall be mechanically attached to metal deck.

c. Tapered Insulation: Roof Drains, see roof plan and details

d. Deck: Metal: Repair as necessary to comply w/ building codes.

e. Interior Ceiling: N/A

f. Building Height: Ground to building edge: 20 ft

4. Warranty:

a. Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.

b. Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment

C.

5. Allowances: $2000.00 shall be added to Base Bid.

6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.

General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Key Notes:

All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.

Metal Counter Flashing: Install new termination bar and new 24-gauge clear anodized aluminum counter flashings. Ref. Detail 1.14; Photo 7941

Walkway Pad: Add new walkway pad at wall ladders and door. Ref. Photo 7940

Deck Flutes: All debris be removed from deck flutes.

Expansion Joint: Replace the expansion joint metal with a similar profile. Ref. Photo 7934

Metal Strainers: Replace plastic or missing strainers with new metal strainers. (if applicable)

Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11

Hamilton Elementary School Roof Area C Scale: 18" = 1'

Symbol Legend Symbol

Conduit, Vent Pipe or Other Penetration

W

GAS AD EJ

Slope H

L

Notes Symbol Notes Symbol Notes

Equipment Unit on Curb

Roof Hatch on Curb

Roof Ladder

Screen Support Stanchion

Gas Line

Roof Ridges and Valleys

Roof Drain

Overflow Scupper

Tapered Insulation or Saddles

Insulated Pipe or Heat Stack Penetration

Ductwork or Flanged

Abandoned Equipment Curb

Walkway Pad

Railing or Fancing

Area Divider

Roof Slope

New Roof Drain Scupper

Key Notes

Metal Roof Shingles or Clay Titles

Revision

Elevation Change

Expansion Joint

Pipe or Conduit on Support Block

Satellite Dish

Skylight on Curb

Equip. on Wood Sleeper or Support Curb

Pitch-Pan Pocket

AH S

Photos

Slope

Slope

Slope

Slope

2'

-9

61'

SHEET 5 OF 9

Hamilton Elementary School

Roof Area D

A3.2

WTProject No: TSD-R102-27

TSD 2027 - A3.0 Hamilton Elementary School

Review

OTB

09/21/2026 10/01/2026

Hamilton Elementary School 5625 Northfield Pkwy.

Troy, MI 48098

Troy School District 2027 Reroofing Program

THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF

SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF

WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,

WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE

DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON

OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING

GROUP. COPYRIGHT 2023.

DESCRIPTION

COPYRIGHT:

WeatherTech Consulting Group, Inc.

DATE

ISSUE

Drawn By: MD

Checked By: DM, AC, AW

WeatherTech Consulting Group, Inc.

Roofing/Waterproofing Consultants Corporate Office:

45147 Cass Ave.

Utica, MI 48317

Phone #: 586-731-3095 Email: weathertech@wtcg.net

Web Site: www.wtcg.net

SHEET TITLE

CLIENT

PROFESSIONAL

PROJECT

File Name:

ELECTRONIC STAMP

Troy School District 4400 Livernois Troy, MI 48098

KEY PLAN

Hamilton Elementary School - Troy School District Sheet Notes - Roof Area D

Schedule:

WORK DESCRIPTION - ROOF REPLACEMENT

Existing Roof System Construction All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.

Core Sample Results

Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total Plies with asphalt 2-inch Perlite Approx. 2 -inch polyisocyanurate insulation.

½” Perlite

Deck: Metal: Slope in deck

Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area D 9,450 Sq. Ft.

New Roof System: Roof Area D- Ref. Detail 1.01a.

Roof Membrane: EPDM, 60 mil, adhered to insulation.

Insulation: R30:

Top layer shall be set-in low-rise foam adhesive.

Bottom layer shall be

Tapered Insulation: Roof Drains, see roof plan and details Deck: Metal: Repair as necessary to comply w/ building codes.

Interior Ceiling: N/A Building Height: Ground to building edge: 45 ft

Warranty:

Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.

Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment C.

Allowances: $2000.00 shall be added to Base Bid.

Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.

General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Key Notes:

All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.

Walkway Pad: Add new walkway pad at ladder. Ref. Photo 7921

Deck Flutes: All debris be removed from deck flutes.

Metal Strainers: Replace plastic or missing strainers with new (matching type) metal strainers. (if applicable)

Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11

Hamilton Elementary School Roof Area D Scale: 18" = 1'

Symbol Legend Symbol

Conduit, Vent Pipe or Other Penetration

W

GAS AD EJ

Slope H

L

Notes Symbol Notes Symbol Notes

Equipment Unit on Curb

Roof Hatch on Curb

Roof Ladder

Screen Support Stanchion

Gas Line

Roof Ridges and Valleys

Roof Drain

Overflow Scupper

Tapered Insulation or Saddles

Insulated Pipe or Heat Stack Penetration

Ductwork or Flanged

Abandoned Equipment Curb

Walkway Pad

Railing or Fancing

Area Divider

Roof Slope

New Roof Drain Scupper

Key Notes

Metal Roof Shingles or Clay Titles

Revision

Elevation Change

Expansion Joint

Pipe or Conduit on Support Block

Satellite Dish

Skylight on Curb

Equip. on Wood Sleeper or Support Curb

Pitch-Pan Pocket

AH S

Photos

2'

10'-6" 7'-3" 40'-3" 58'

Slope

Slope

SlopeSlope

Slope

Slop e

SHEET 6 OF 9

Hamilton Elementary School

Roof Area E

A3.3

WTProject No: TSD-R102-27

TSD 2027 - A3.0 Hamilton Elementary School

Review

OTB

09/21/2026 10/01/2026

Hamilton Elementary School 5625 Northfield Pkwy.

Troy, MI 48098

Troy School District 2027 Reroofing Program

THESE DRAWINGS AND SPECIFICATIONS, AS INSTRUMENTS OF

SERVICE, ARE AND SHALL REMAIN THE PROPERTYOF

WEATHERTECH CONSULTING GROUP AND PROJECT OWNER,

WHETHER THE PROJECTS FOR WHICH THEY ARE MADE FOR ARE EXECUTED OR NOT. THESE

DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANY PERSON OR ENTITY ON

OTHER PROJECTS WITHOUT THE WRITTEN CONSENT OF THE WEATHERTECH CONSULTING

GROUP. COPYRIGHT 2023.

DESCRIPTION

COPYRIGHT:

WeatherTech Consulting Group, Inc.

DATE

ISSUE

Drawn By: MD

Checked By: DM, AC, AW

WeatherTech Consulting Group, Inc.

Roofing/Waterproofing Consultants Corporate Office:

45147 Cass Ave.

Utica, MI 48317

Phone #: 586-731-3095 Email: weathertech@wtcg.net

Web Site: www.wtcg.net

SHEET TITLE

CLIENT

PROFESSIONAL

PROJECT

File Name:

ELECTRONIC STAMP

Troy School District 4400 Livernois Troy, MI 48098

KEY PLAN

Hamilton Elementary School - Troy School District Sheet Notes - Roof Area E

Schedule:

WORK DESCRIPTION - ROOF REPLACEMENT

1. Existing Roof System Construction

All existing roof system constructions were determined by limited test cuts and observation; conditions may vary. Contractor shall be responsible for confirming all existing roof system constructions and conditions.

Core Sample Results A. Roof Membrane: Gravel BUR with asphalt - Approx 5-inch total

B. Plies with asphalt C. 2-inch Perlite D. Approx. 2 -inch polyisocyanurate insulation.

E. ½” Perlite

F. Deck: Metal: Slope in deck

2. Roof System Construction Work includes removal and disposal of existing roofing, insulation, flashing systems and all sheet metal flashings down to the surface of the deck, repair deteriorated decking, install new roof insulation, fully adhered EPDM single ply roof membrane including all flashing, new roof related sheet metal, and accessories as detailed in the specifications and drawings. Approx. Roof Area E 8,550 Sq. Ft.

3. New Roof System: Roof Area E- Ref. Detail 1.01a.

a. Roof Membrane: EPDM, 60 mil, adhered to insulation.

b. Insulation: R30:

1) Top layer shall be set-in low-rise foam adhesive.

2) Bottom layer shall be mechanically attached to metal deck.

c. Tapered Insulation: Roof Drains, see roof plan and details

d. Deck: Metal: Repair as necessary to comply w/ building codes.

e. Interior Ceiling: N/A

f. Building Height: Ground to building edge: 20 ft

4. Warranty:

a. Manufacturer shall provide a 20 year "No-Dollar-Limit" material and installation warranty covering the roof system, flashings and manufacturer's accessories.

b. Roofing installer shall provide a five (5) year Performance Agreement - see Specification Attachment

C.

5. Allowances: $2000.00 shall be added to Base Bid.

6. Asbestos: Ref. to Section 024119 and Appendix 1: Asbestos testing results shall be supplied by TSD selected 3rd party firm and will be incorporated into Appendix 1. Refer to Appendix 1 for asbestos testing results.

General Construction Details: Ref. A1.0 Use the General Construction Details on Sheet A1.0 for detail construction description as applicable when any detail is not specifically called out in Key Notes for the applicable Roof Area and Section. Detail drawings called out in General Construction Details can be found on Sheets A4.0 to A4.2. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Key Notes:

All detail references in Key Notes are considered typical and applicable to like conditions except as specifically amended on this Sheet. Refer to Sheet A1.0 General Construction Detail Notes for applicable construction detail descriptions and Sheets A4.0 to A4.2 for construction detail drawings. Contractor shall provide Shop Drawing as necessary for field conditions not directly identified in Contract Documents.

Perimeter Wood Nailers: Furnish and install new wood nailers on perimeter edges to level wall cap and provide base flashing required heights. Ref. Detail 1.05.

Metal Counter Flashing: Install new termination bar and new 24-gauge clear anodized aluminum counter flashings. Ref. Detail 1.14; Photo 7879

Deck Flutes: All debris be removed from deck flutes.

Expansion Joint: Replace the expansion joint metal with a similar profile. Ref. Photo 7888

Metal Strainers: Replace plastic or missing strainers with new (matching type) metal strainers. (if applicable)

Roof Drain Ring: Furnish and install new drain ring. Ref. Photo 7887

Drain Sumps: Furnish and install tapered roof sumps (8ft) to assure proper drainage. Ref. Details 1.09 and 1.11

Hamilton Elementary School Roof Area E Scale: 18" = 1'

Symbol Legend Symbol

Conduit, Vent Pipe or Other Penetration

W

GAS AD EJ

Slope H

L

Notes Symbol Notes Symbol Notes

Equipment Unit on Curb

Roof Hatch on Curb

Roof Ladder

Screen Support Stanchion

Gas Line

Roof Ridges and Valleys

Roof Drain

Overflow Scupper

Tapered Insulation or Saddles

Insulated Pipe or Heat Stack Penetration

Ductwork or Flanged

Abandoned Equipment Curb

Walkway Pad

Railing or Fancing

Area Divider

Roof Slope

New Roof Drain Scupper

Key Notes

Metal Roof Shingles or Clay Titles

Revision

Elevation Change

Expansion Joint

Pipe or Conduit on Support Block

Satellite Dish

Skylight on Curb

Equip. on Wood Sleeper or Support Curb

Pitch-Pan Pocket

AH S

Photos

5 7

5 7

NEW ROOF CONSTRUCTION PROFILE FULLY

ADHERED SYSTEMS W/ NAILABLE DECK

SCALE: N.T.S

1.01a

NOTE 1 - ROOF MEMBRANE 60 MIL EPDM - FULLY ADHERED IN BONDING ADHESIVE; FIELD

SEAMS ADHERED WITH 6" (MINIMUM) WIDE SEAM TAPE.

NOTE 2 - APPLY LOW RISE FOAM ADHESIVE IN 3 4 TO 1 INCH WIDE WET BEADS SPACED AT 12

INCHES ON CENTER IN THE FIELD ON THE ROOF; REDUCE BEAD SPACING TO 6 INCHES IN

PERIMETERS AND 4 INCHES IN CORNERS PER FM 60 UPLIFT CRITERIA AS DEFINED IN FMG KISS

REVERTIBLE DATA SHEET 1 - 29.

NOTE 3 - TWO LAYERS OF 4 FT. X 4 FT. INSULATION ADHERED IN LOW RISE FOAM ADHESIVE

SHOWN FOR CLARITY - SEE SCHEDULE ON ROOF PLAN(S) FOR R-VALUES, TYPE AND

THICKNESS OF EACH INSULATION LAYER REQUIRED IN EACH ROOF AREA. TAPERED

INSULATION ALSO MAY BE REQUIRED ON SOME ROOF AREAS OR FOR CRICKETS AND SADDLES

- SEE SCHEDULE AND LAYOUT DRAWINGS ON ROOF PLAN(S) FOR TYPE AND FINISHED SLOPE

OF TAPERED INSULATION. STAGGER ALL INSULATION JOINTS

NAILABLE STRUCTURAL DECK

ROOF INSULATION - SEE NOTE 3

EPDM MEMBRANE SEE

SCHEDULE ON PLAN

6" SEAM TAPE

6"

BONDING ADHESIVE - SEE NOTE 1

LOW RISE FOAM ADHESIVE - SEE NOTE 2

FMG APPROVED FASTENER AND PLATE @ 12 " O.C.

3/4" MIN. - 1 1/4" MAX.

BUTYL TAPE OR 3" SEAM TAPE

2X WOOD BLOCKING TO MATCH HEIGHT OF

ROOF INSULATION - FASTEN @ 12" O.C.

EXTERIOR WALL

ROOF INSULATION

STRUCTURAL DECK

6" SEAM TAPE

EPDM MEMBRANE

FIELD CRIMP

2X WOOD BLOCKING TO MATCH HEIGHT OF

ROOF INSULATION - FASTEN @ 12" O.C.

EPDM BASE FLASHING ADHERED W/

BONDING ADHESIVE - RUN FLASHING

OVER CANT DAM AND DOWN ONTO

CLEAT AS SHOWN

24 GA. PREFINISHED GALV. STEEL

FASCIA COVER

22 GA. GALV. STEEL CANT-DAM W/

CONTINUOUS CLEAT - FASTEN 6" O.C. W/

RING SHANK ROOFING NAILS

CANT-DAM W/ FASCIA

SCALE: N.T.S

TAPERED INSULATION

1.10 1.11

ROOF DRAIN

SCALE: N.T.S

1.03

1.12OVERFLOW DRAIN

SCALE: N.T.S1.09

1.02 RAISED EDGE METAL AND FLASHING

SCALE: N.T.S

2"

4"

EPDM MEMBRANE

6" SEAM TAPE

REINFORCED ATTACHMENT STRIP

FASTENED @ 12" O.C.

24 GA. PREFINISHED GALV. STEEL GRAVEL

STOP - FASTEN 3" O.C. STAGGERED W/ RING

SHANK ROOFING NAILS

BUTYL TAPE OR 3" SEAM TAPE

22 GA. GAL STEEL CONTINUOUS

CLEAT-FASTEN 6" O.C. STAGGERED W/ RING

SHANK ROOFING

2X WOOD BLOCKING TO MATCH HEIGHT OF

ROOF INSULATION - FASTEN @ 12" O.C.

EXTERIOR WALL

ROOF INSULATION

STRUCTURAL DECK

ROOF DRAIN SUMP

SCALE: N.T.S

ROOF AND OVERFLOW DRAIN SUMP

SCALE: N.T.S

1.04

2" MIN.

VERIFY IN FIELD

2" MIN.

VERIFY

IN

FIELD

1"

45°

NOTE 1 - DIMENSIONS NOT GIVEN BE VERIFIED IN FIELD.

NOTE 2 - CONTINUOUS CLEAT NOT TO EXCEED 12 LF.

NOTE 3 - ALLOW 41" GAP BETWEEN CLEAT. OFFSET CLEAT JOINTS FROM COPING JOINTS.

TYPICAL PARAPET/COPING CAP

SCALE: N.T.S

20 GA. GALV.CONTINUOUS

CLEAT. FASTENED @ 6" O.C.

BOTTOM OF METAL CAP TO

BE 2" BENEATH UNDERSIDE

OF WOOD BLOCKING

2X WOOD BLOCKING TO

MATCH HEIGHT OF ROOF

INSULATION - FASTEN @ 12"

O.C.

GASKETED FASTENER @ 18"

O.C. DEPENDING ON WIND

ZONE AND K=LOCAL

CONDITIONS

22 GA. GALV. METAL COPING

W/ 1"/FT SLOPE MIN.

1.06 1.07 1.08

WeatherTech © Date: Rev 3/15

SEALANT

FACE SIDE

ROOF SIDE

24"24"

1. SHOP FABRICATED CORNERS TO PROVIDE POSITIVE SLOPE

2. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATION.

POP RIVET

24 GAUGE

PRE-FINSHED GALV.

WALL FLASHING SET IN

SEALANT

PARAPET

WALL

2"

METAL COPING

FORM COPING METAL TO

END UP WITH 2" ONTO

WALL

WeatherTech © Date: Rev 3/15

SEALANT

FASTENERS

FASTENERS

WeatherTech © Date: Rev 3/15

12' [4 m] MAX.

LENGTH EACH PIECE

OF COPING CAP

2'' [5 0 mm] APPROX.

OPTION:

SECTION:

1'' [25 mm] MIN.

1'' [25 mm] MIN.

SHEET METAL DOUBLE LOCK

STANDING SEAM

SHEET METAL COPING CAP

BUTTON PUNCH TO

HOLD IN PLACE

SHEET METAL SET IN

SEALANT

4.

3.

2.

NOTES:

1.

CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.

REFER TO TABLE SM-19 FOR COPING CAP SECUREMENT OPTIONS.

COPING JOINERY IS SIMILAR ON BOTH SIDES.

REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

COPING CAP W/ DOUBLE LOCK STANDING SEAM

SCALE: N.T.S

WALL TERMINATION

SCALE: N.T.S

PARAPET COPING CAP CORNERS

SCALE: N.T.S

NOTE 1 - GUTTER OUTLETS AND DOWNSPOUTS BE 24 GA. GALV. STEEL, 24 GA.

STAINLESS STEEL 16 O.Z. COLD ROLLED COPPER - SEE THE SCHEDULE(S) ON THE ROOF

PLAN(S) FOR SPECIFIC REQUIREMENTS FOR EACH ROOF AREA

NOTE 2 - PROVIDE 1 OUTLET MIN. IN EACH SECTION OF GUTTER.

NOTE 3 - GUTTER HEIGHT AND WIDTH OUTLET/DOWNSPOUT SIZE BE CALCULATED PER

SMACNA RECOMMENDATIONS BASED ON SIZE OF ROOF TO BE DRAINED.

X X

1" 2"

4"

SHEET METAL DOWNSPOUT - SEE

NOTES 1, 2 AND 3

#12 SCREWS

SHEET METAL GUTTER FASTENED TO

WOOD NAILER 6" O.C. W/ STAINLESS

STEEL RING SHANK NAILS - SOLDER

ALL JOINTS WATERTIGHT - SEE NOTE

1 AND 2.

10 GA. GALV. STEEL GUTTER STRAP

30" O.C.

1"

SHEET METAL OUTLET - SEE NOTES

1, 2 AND 3

SEE NOTES 3

#12 SCREWS

24 GA. GALV. STEEL DRIP EDGING -

FASTEN 4" O.C. STAGGERED.

6" SEAM TAPE

EPDM MEMBRANE

TAPERED INSULATION

BUTYL TAPE OR 3" SEAM TAPE

2X WOOD BLOCKING TO MATCH

HEIGHT OF ROOF INSULATION -

FASTEN @ 12" O.C.

EXTERIOR WALL

ROOF INSULATION

STRUCTURAL DECK

GUTTER

SCALE: N.T.S 1.13

CONTINUOUS BEAD OF SEALANT

TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER

STAINLESS STEEL CLAMPING RING BOLTS - REPLACE IF

MISSING, DAMAGED OR NON-STAINLESS STEEL BOLTS

STRUCTURAL DECK

DRAIN BOWL

DRAIN PIPING

TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER

1" MIN.

2"

CAST IRON DRAIN STRAINER - REPLACE IF MISSING OR

BROKEN. PLASTIC DRAIN STRAINER ARE ONLY ALLOWED

WITH APPROV BY CONSULTANT IN WRITING.

CLAMPING RING - REMOVE ALL BITUMINOUS MATERIALS

- REPLACE IF MISSING OR BROKEN DURING REMOVAL

EPDM MEMBRANE

NOTE - CONTRACTORS SHALL INSTALL TAPERED INSULATION. DO NOT SHAVE ROOF INSULATION TO

MATCH DRAIN INSULATION HEIGHT WITH DRAIN BOWL HEIGHT.

192"

48" 48" 48"48"

CONTINUOUS BEAD OF SEALANT

TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER

STAINLESS STEEL CLAMPING RING BOLTS - REPLACE IF

MISSING, DAMAGED OR NON-STAINLESS STEEL BOLTS

STRUCTURAL DECK

DRAIN BOWL

DRAIN PIPING

TAPERED ROOF INSULATION - MIN. 12" PER FOOT TAPER

1" MIN.

2"

NOTE - CONTRACTORS SHALL INSTALL TAPERED INSULATION. DO NOT SHAVE ROOF INSULATION TO

MATCH DRAIN INSULATION HEIGHT WITH DRAIN BOWL HEIGHT.

192"

48" 48" 48"48"

CAST IRON DRAIN STRAINER - REPLACE IF MISSING OR

BROKEN. PLASTIC DRAIN STRAINER ARE ONLY ALLOWED

WITH APPROV BY CONSULTANT IN WRITING.

OVERFLOW CLAMPING RING - REMOVE ALL BITUMINOUS

MATERIALS - REPLACE IF MISSING OR BROKEN DURING

REMOVAL

EPDM MEMBRANE

CENTER LINE DRAIN CENTER LINE DRAIN

48"

192"

48"

ROOF DRAIN

ROOF DRAIN SUMP. TAPERED AT A MIN. 12"

PER FOOT

CENTER LINE DRAIN

SLOPE SLOPE

48"

48"

192"

48"

48"48"

SLOPE

SLOPE

SLOPE SLOPE

SLOPE

48"

48"

252"

48"

48"

48"

192"

48"

48"48"

48"

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPESLOPE

ROOF DRAIN

ROOF DRAIN SUMP. TAPERED AT A MIN. 12"

PER FOOT

CENTER LINE DRAIN CENTER LINE DRAIN

60"

NEW ROOF CONSTRUCTION PROFILE FULLY

ADHERED SYSTEMS W/ VAPOR BARRIER

SCALE: N.T.S

1.01b

NOTE 1 - ROOF MEMBRANE 60 MIL EPDM - FULLY ADHERED IN BONDING ADHESIVE; FIELD

SEAMS ADHERED WITH 6" (MINIMUM) WIDE SEAM TAPE.

NOTE 2 - APPLY LOW RISE FOAM ADHESIVE IN 3 4 TO 1 INCH WIDE WET BEADS SPACED AT 12

INCHES ON CENTER IN THE FIELD ON THE ROOF; REDUCE BEAD SPACING TO 6 INCHES IN

PERIMETERS AND 4 INCHES IN CORNERS PER FM 60 UPLIFT CRITERIA AS DEFINED IN FMG KISS

REVERTIBLE DATA SHEET 1 -…