This is Addendum 1 to Invitation to Bid No. RFB-83-27 issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for controls upgrades at Campbell Regional Juvenile Detention Center operated by the Department of Juvenile Justice in Newport, Kentucky. The project, identified as KFI Project Number 25-1309.00, involves upgrading building automation system (BAS) controls and integrating them with the Commonwealth Energy Management and Controls System (CEMCS). The addendum addresses three clarifications regarding project scope: the Owner shall perform CEMCS integration while the contractor ensures BAS points, histories, and alarms conform to CEMCS standards; the existing Microzone MZ-4 controller serving the chilled water system shall be removed and replaced with new chiller controls, with the existing chilled water pump to be reused and integrated into the new BAS; and reflected ceiling plans are available by request from the Owner. The addendum includes no specification or plan sheet changes beyond the clarifications provided. A comprehensive CEMCS controls points list spreadsheet is attached as Attachment B, detailing point naming conventions, trending requirements, and alarming specifications for system integration.

No pricing information, set-asides, incumbent contractor details, response deadlines, bid due dates, site visit requirements, or bidder's conference information is contained within this addendum document. The addendum was issued on October 6, 2026, and serves as a binding contract document applicable to any and all contracts and subcontracts unless otherwise specified. All contractors are required to examine each item of the addendum and ensure compliance with the attached documentation and CEMCS integration standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-83-27

FOR: Controls Upgrades Campbell Regional Juvenile Detention Center Department of Juvenile Justice Newport, Kentucky

DATE: October 6, 2026

RFB-2700000128

ADDENDUM NO. One (1)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-83-27 For: Controls Upgrades Campbell Regional Juvenile Detention Center Department of Juvenile Justice Newport, Kentucky

Janis Wilhoite, Statewide Procurement Analyst II Division of Engineering and Contract Administration

ADDENDUM

Page 1 of 2 Find a way.

Date: 10/6/2026 Project: DJJ – Campbell Controls Upgrades

KFI Project Number: 25-1309.00

Addendum Number: 01

THIS ADDENDUM IS A CONTRACT DOCUMENT AND MAY APPLY TO ANY OR ALL CONTRACTS AND SUBCONTRACTS UNLESS OTHERWISE SPECIFIED HEREIN OR SHOWN ON THE ATTACHED DRAWINGS (IF ANY). ALL WORK REQUIRED BY THIS ADDENDUM SHALL BE IN COMPLETE ACCORD WITH THE CONTRACT DOCUMENTS AND SUBSEQUENT ADDENDA THERETO. THE ITEMS LISTED IN THIS ADDENDUM ARE NOT IN ANY ORDER IN REGARD TO THE DRAWINGS OR THE SPECIFICATIONS. ALL CONTRACTORS ARE CAUTIONED TO EXAMINE EACH AND EVERY ITEM OF THIS ADDENDUM.

THE FOLLOWING CHANGES OR CLARIFICATIONS TO THE PLANS & SPECIFICATIONS SHALL BE INCLUDED AS PART OF THE CONTRACT DOCUMENT

BID RFIS:

1. The project description in the specs indicates that “The system is required to be interfaced with the Commonwealth Energy Management and Controls System (CEMCS) operated by the Division of Facility Efficiency under the Finance and Administration Cabinet.” The note on the points lists says “OWNER SHALL INTEGRATE POINTS INTO CEMCS. POINTS LIST SHOWN HERE MEANT TO SERVE AS A GUIDE FOR CEMCS INTEGRATION. Please clarify what (if any) scope the controls contractor (TCC) for this project is responsible for relative to interfacing the new system with the CEMCS.

a. Response: The Owner shall perform CEMCS integration. The Contractor shall only ensure the BAS points, histories and alarms, as identified in the drawings, conform to CEMCS standards.

The point information must be in a consistent format such that CEMCS staff can readily identify the location and nature of the point data being collected. See Attachment B – CEMCS_CONTROLS POINTS LIST SPREADSHEET for CEMCS point naming, trending requirements, and alarming requirements.

2. The system architecture on drawing IC300 shows existing Microzone MZ-4 serving the CHWS to remain. There is an expensive driver required to pull ASD controllers into a JACE. I would suggest that this controller be replaced as part of this project. I understand there is a chiller replacement project in progress. There is a temp chiller being used now, and it sounds like the new chiller might be in place before or during this controls project. I think the control points and wiring to the new chiller could be accounted for in this bid, so that the CHWS MZ can be replaced as part of this controls upgrade project. The other CHWS points on MZ-4 (pump control, temp sensors, etc.) are inside the mech room anyway and not affected by the chiller replacement. Please confirm intent for MZ-4.

a. Response: Final intent for MZ-4 is to be removed and replaced with new chiller controls. If the new chiller has been installed and is operational at the time this project is executed, the existing chiller control system shall be removed and replaced with controls provided for the new chiller. The CHWS_T, CH_FLOW, and CHWR_T points shall be replaced with new field devices. The existing chilled water pump shall be reused and integrated into the new BAS.

The new chiller, and all associated chiller controls shall be fully integrated into the new BAS.

Upon successful integration of the new chiller controls, existing microzone controller MZ-4 may be removed.

ADDENDUM

Page 2 of 2 Find a way.

3. Are reflected ceiling plans for the building available?

a. Response: Reflected ceiling plans for the building are available by request from Owner.

SPECIFICATION CHANGES:

1. NONE

PLAN SHEET CHANGES:

2. NONE

END OF ADDENDUM

Kentucky Archibus # Bldg Area Designator Discipline System Component

ID

Unique Identifier archibus# area designation AHU-001 #

Pr im ar y

Sy st e mSy st e m C om po ne ntDisplay Name Point Name I/O Type Read / Write Permission History

Alarm Priority Alarm Type Alarm High Threshold Alarm Low Threshold

Graphic Presentation Controls Point Name

AHU GeneraAHU Bldg Pres Building Static Pressure BLDG_SP AI Read TI_5 Priority 2 Out of Range >EFF_BLDG_SP_SPT + 0.2 <EFF_BLDG_SP_SPT - 0.2 Yes archibus#_area_designation_AHU-001_BLDG_SP_# AHU GeneraAHU Bldg Pres Building Static Pressure Setpoint BLDG_SP_SPT AV WriteA CoS_0.01 Yes archibus#_area_designation_AHU-001_BLDG_SP_SPT_# AHU GeneraAHU Staged C Cooling Stage 1 DXC_1_C BO Read BCoS Yes archibus#_area_designation_AHU-001_DXC_1_C_# AHU GeneraAHU Staged C Cooling Stage 1 Override DXC_1_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_1_C_OVRD_# AHU GeneraAHU Staged C Cooling Stage 2 DXC_2_C BO Read BCoS Yes archibus#_area_designation_AHU-001_DXC_2_C_# AHU GeneraAHU Staged C Cooling Stage 2 Override DXC_2_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_2_C_OVRD_# AHU GeneraAHU Staged C Cooling Stage 3 DXC_3_C BO Read BCoS Yes archibus#_area_designation_AHU-001_DXC_3_C_# AHU GeneraAHU Staged C Cooling Stage 3 Override DXC_3_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_3_C_OVRD_# AHU GeneraAHU Staged C Cooling Stage 4 DXC_4_C BO Read BCoS Yes archibus#_area_designation_AHU-001_DXC_4_C_# AHU GeneraAHU Staged C Cooling Stage 4 Override DXC_4_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_4_C_OVRD_# AHU GeneraAHU Dehumid Cooling Supply Air Temp SACLG_T AI Read TI_5 Priority 2 Out of Range >EFF_SA_T_SPT + 10 <EFF_SA_T_SPT - 10 Yes archibus#_area_designation_AHU-001_SACLG_T_# AHU GeneraAHU Modulati Cooling Valve CHW_VLV_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_CHW_VLV_C_# AHU GeneraAHU Modulati Cooling Valve Override CHW_VLV_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_CHW_VLV_C_OVRD_# AHU GeneraAHU Dehumid Dehumidification Setpoint SA_DHUM_SPT AV WriteO CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_DHUM_SPT_# AHU GeneraAHU Basic Uni Demand Limit Level DMAN_LMT_S AV Read CoS_1 No archibus#_area_designation_AHU-001_DMAN_LMT_S_# AHU GeneraAHU Modulati DX Modulating Comp DXC_SPD_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_DXC_SPD_C_# AHU GeneraAHU Modulati DX Modulating Comp Override DXC_SPD_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_DXC_SPD_C_OVRD_# AHU GeneraAHU EconomizEconomizer Mixed Air Temp Setpoint MA_T_SPT AV Read CoS_0.1 Yes archibus#_area_designation_AHU-001_MA_T_SPT_# AHU GeneraAHU EconomizEconomizer Mixed Air Temp Setpoint Override MA_T_SPT_OVRD AV WriteA CoS_0.1 Yes archibus#_area_designation_AHU-001_MA_T_SPT_OVRD_# AHU GeneraAHU Bldg Pres Effective Building Static Pressure Setpoint EFF_BLDG_SP_SPT AV Read CoS_0.01 Yes archibus#_area_designation_AHU-001_EFF_BLDG_SP_SPT_# AHU GeneraAHU VAV ContEffective Supply Air Static Pressure Setpoint EFF_SA_SP_SPT AV Read CoS_0.1 Yes archibus#_area_designation_AHU-001_EFF_SA_SP_SPT_# AHU GeneraAHU VAV ContEffective Supply Air Temp Setpoint EFF_SA_T_SPT AV Read CoS_0.1 Yes archibus#_area_designation_AHU-001_EFF_SA_T_SPT_# AHU GeneraAHU Single Zo Effective Zone Temp Setpoint EFF_ZN_T_SPT AV Read CoS_0.5 Yes archibus#_area_designation_AHU-001_EFF_ZN_T_SPT_# AHU GeneraAHU Basic Uni Emergency Shutdown EMER_OVRD BV Read BCoS Priority 1 Boolean Change of St N/A N/A No archibus#_area_designation_AHU-001_EMER_OVRD_# AHU GeneraAHU EconomizExhaust Air Dampers EA_DPR_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_EA_DPR_C_# AHU GeneraAHU EconomizExhaust Air Dampers Override EA_DPR_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_EA_DPR_C_OVRD_# AHU GeneraAHU Exhaust FExhaust Fan Start/Stop EFAN_RUN_C BO Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_EFAN_RUN_C_# AHU GeneraAHU Exhaust FExhaust Fan Start/Stop Override EFAN_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_EFAN_RUN_C_OVRD_# AHU GeneraAHU Exhaust FExhaust Fan Status EFAN_RUN_S BI Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_EFAN_RUN_S_# AHU GeneraAHU VFD on E Exhaust Fan VFD Fault EFAN_VFDFLT_S BI Read BCoS Priority 1 Boolean Change of St N/A N/A No archibus#_area_designation_AHU-001_EFAN_VFDFLT_S_# AHU GeneraAHU VFD on E Exhaust Fan VFD Speed EFAN_VFD_SPD_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_EFAN_VFD_SPD_C_# AHU GeneraAHU VFD on E Exhaust Fan VFD Speed Override EFAN_VFD_SPD_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_EFAN_VFD_SPD_C_OVRD_# AHU GeneraAHU Modulati Face and Bypass - Cool FABC_DPR_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_FABC_DPR_C_# AHU GeneraAHU Modulati Face and Bypass - Heat FABH_DPR_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_FABH_DPR_C_# AHU GeneraAHU Modulati Face and Bypass Cool Override FABC_DPR_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_FABC_DPR_C_OVRD_# AHU GeneraAHU Modulati Face and Bypass Heat Override FABH_DPR_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_FABH_DPR_C_OVRD_# AHU GeneraAHU Final Filt Final Filter Status FFLTR_DP_S BI Read BCoS Yes archibus#_area_designation_AHU-001_FFLTR_DP_S_# AHU GeneraAHU Basic Uni Freezestat FZ_S BI Read BCoS Priority 1 Boolean Change of St N/A N/A No archibus#_area_designation_AHU-001_FZ_S_# AHU GeneraAHU Recirc HW Heating Coil Pump Start/Stop HW_P_RUN_C BO Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_HW_P_RUN_C_# AHU GeneraAHU Recirc HW Heating Coil Pump Start/Stop Override HW_P_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_HW_P_RUN_C_OVRD_# AHU GeneraAHU Recirc HW Heating Coil Pump Status HW_P_RUN_S BI Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_HW_P_RUN_S_# AHU GeneraAHU Staged H Heating Stage 1 HT_1_C BO Read BCoS Yes archibus#_area_designation_AHU-001_HT_1_C_# AHU GeneraAHU Staged H Heating Stage 1 Override HT_1_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_1_C_OVRD_# AHU GeneraAHU Staged H Heating Stage 2 HT_2_C BO Read BCoS Yes archibus#_area_designation_AHU-001_HT_2_C_# AHU GeneraAHU Staged H Heating Stage 2 Override HT_2_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_2_C_OVRD_# AHU GeneraAHU Staged H Heating Stage 3 HT_3_C BO Read BCoS Yes archibus#_area_designation_AHU-001_HT_3_C_# AHU GeneraAHU Staged H Heating Stage 3 Override HT_3_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_3_C_OVRD_# AHU GeneraAHU Staged H Heating Stage 4 HT_4_C BO Read BCoS Yes archibus#_area_designation_AHU-001_HT_4_C_# AHU GeneraAHU Staged H Heating Stage 4 Override HT_4_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_4_C_OVRD_# AHU GeneraAHU Staged H Heating Stage 5 HT_5_C BO Read BCoS Yes archibus#_area_designation_AHU-001_HT_5_C_# AHU GeneraAHU Staged H Heating Stage 5 Override HT_5_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_5_C_OVRD_# AHU GeneraAHU Staged H Heating Stage 6 HT_6_C BO Read BCoS Yes archibus#_area_designation_AHU-001_HT_6_C_# AHU GeneraAHU Staged H Heating Stage 6 Override HT_6_C_OVRD BV WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_6_C_OVRD_# AHU GeneraAHU Modulati Heating Valve HW_VLV_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_HW_VLV_C_# AHU GeneraAHU Modulati Heating Valve Override HW_VLV_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_HW_VLV_C_OVRD_# AHU GeneraAHU VAV ContHigh Static Shutdown SA_HISP_S BO Read BCoS Priority 1 Boolean Change of St N/A N/A No archibus#_area_designation_AHU-001_SA_HISP_S_# AHU GeneraAHU HumidificHumidifier HUM_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_HUM_C_# AHU GeneraAHU HumidificHumidifier Override HUM_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_HUM_C_OVRD_# AHU GeneraAHU HumidificHumidifier Setpoint SA_HUM_SPT AV WriteO CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_HUM_SPT_# AHU GeneraAHU EconomizMixed Air Dampers MA_DPR_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_MA_DPR_C_# AHU GeneraAHU EconomizMixed Air Dampers Override MA_DPR_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_MA_DPR_C_OVRD_# AHU GeneraAHU EconomizMixed Air Temp MA_T AI Read TI_5 Priority 2 Out of Range >MA_T_SPT + 15 <40 Yes archibus#_area_designation_AHU-001_MA_T_# AHU GeneraAHU Basic Uni Occ Cooling Setpoint OCC_CLG_SPT AV WriteO CoS_0.5 Yes archibus#_area_designation_AHU-001_OCC_CLG_SPT_# AHU GeneraAHU Basic Uni Occ Heating Setpoint OCC_HTG_SPT AV WriteO CoS_0.5 Yes archibus#_area_designation_AHU-001_OCC_HTG_SPT_# AHU GeneraAHU Basic Uni Outside Air Dampers OA_DPR_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_OA_DPR_C_# AHU GeneraAHU Basic Uni Outside Air Dampers Override OA_DPR_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_OA_DPR_C_OVRD_# AHU GeneraAHU Pre-Filte Prefilter Status PFLTR_DP_S BI Read BCoS Yes archibus#_area_designation_AHU-001_PFLTR_DP_S_# AHU GeneraAHU Basic Uni Preheating Mixed Air Temp Setpoint PRHT_MA_T_SPT AV Read CoS_0.1 Yes archibus#_area_designation_AHU-001_PRHT_MA_T_SPT_# AHU GeneraAHU Basic Uni Preheating Mixed Air Temp Setpoint Override PRHT_MA_T_SPT_OVRD AV WriteA CoS_0.1 Yes archibus#_area_designation_AHU-001_PRHT_MA_T_SPT_OVRD_# AHU GeneraAHU Dehumid Reheating Valve PHT_VLV_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_PHT_VLV_C_# AHU GeneraAHU Dehumid Reheating Valve Override PHT_VLV_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_PHT_VLV_C_OVRD_# AHU GeneraAHU CO2 ContReturn Air Carbon Dioxide PPM RA_CO2 AI Read TI_15 Priority 3 Out of Range >RA_CO2_SPT + 200 N/A Yes archibus#_area_designation_AHU-001_RA_CO2_# AHU GeneraAHU CO2 ContReturn Air Carbon Dioxide PPM Setpoint RA_CO2_SPT AV WriteO TI_15 Yes archibus#_area_designation_AHU-001_RA_CO2_SPT_#

Primary System

HC Terminal Units

Lighting

Metering

Unitary Heat

Sub-System

AHU

Air Cooled Chiller

Air Source Heat Pump

Boiler Interface

Component

ATS 1

ATS 2

Basic Unit

Bldg Press Control

AHU GeneraAHU Dehumid Return Air Humidity RA_RH AI Read TI_15 Priority 3 Out of Range >65 <25 Yes archibus#_area_designation_AHU-001_RA_RH_# AHU GeneraAHU Basic Uni Return Air Smoke Detector RA_SD_S BI Read BCoS Priority 1 Boolean Change of St N/A N/A Yes archibus#_area_designation_AHU-001_RA_SD_S_# AHU GeneraAHU EconomizReturn Air Temp RA_T AI Read TI_15 Priority 3 Out of Range >EFF_ZN_T_SPT + 10 <EFF_ZN_T_SPT - 10 Yes archibus#_area_designation_AHU-001_RA_T_# AHU GeneraAHU Return FaReturn Fan Start/Stop RFAN_RUN_C BO Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_RFAN_RUN_C_# AHU GeneraAHU Return FaReturn Fan Start/Stop Override RFAN_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_RFAN_RUN_C_OVRD_# AHU GeneraAHU Return FaReturn Fan Status RFAN_RUN_S BI Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_RFAN_RUN_S_# AHU GeneraAHU VFD on R Return Fan VFD Fault RFAN_VFDFLT_S BI Read BCoS Priority 1 Boolean Change of St N/A N/A No archibus#_area_designation_AHU-001_RFAN_VFDFLT_S_# AHU GeneraAHU VFD on R Return Fan VFD Speed RFAN_VFD_SPD_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_RFAN_VFD_SPD_C_# AHU GeneraAHU VFD on R Return Fan VFD Speed Override RFAN_VFD_SPD_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_RFAN_VFD_SPD_C_OVRD_# AHU GeneraAHU Basic Uni Schedule OCC_S BV WriteO BCoS Yes archibus#_area_designation_AHU-001_OCC_S_# AHU GeneraAHU HumidificSupply Air Humidity SA_RH AI Read TI_15 Priority 3 Out of Range >90 <SA_HUM_SPT - 20% Yes archibus#_area_designation_AHU-001_SA_RH_# AHU GeneraAHU Basic Uni Supply Air Smoke Detector SA_SD_S BI Read BCoS Priority 1 Boolean Change of St N/A N/A Yes archibus#_area_designation_AHU-001_SA_SD_S_# AHU GeneraAHU VAV ContSupply Air Static Pressure SA_SP AI Read TI_15 Priority 2 Out of Range >EFF_SA_SP_SPT + 1 <EFF_SA_SP_SPT - 1 Yes archibus#_area_designation_AHU-001_SA_SP_# AHU GeneraAHU VAV ContSupply Air Static Pressure Setpoint SA_SP_SPT AV WriteA CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_SP_SPT_# AHU GeneraAHU VAV ContSupply Air Temp SA_T AI Read TI_5 Priority 2 Out of Range >EFF_SA_T_SPT + 10 <EFF_SA_T_SPT - 10 Yes archibus#_area_designation_AHU-001_SA_T_# AHU GeneraAHU VAV ContSupply Air Temp Setpoint SA_T_SPT AV WriteO CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_T_SPT_# AHU GeneraAHU Basic Uni Supply Fan Start/Stop SFAN_RUN_C BO Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_SFAN_RUN_C_# AHU GeneraAHU Basic Uni Supply Fan Start/Stop Override SFAN_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_SFAN_RUN_C_OVRD_# AHU GeneraAHU Basic Uni Supply Fan Status SFAN_RUN_S BI Read BCoS Priority 2 Boolean Command FaN/A N/A Yes archibus#_area_designation_AHU-001_SFAN_RUN_S_# AHU GeneraAHU VAV ContSupply Fan VFD Fault SFAN_VFDFLT_S BI Read BCoS Priority 1 Boolean Change of St N/A N/A No archibus#_area_designation_AHU-001_SFAN_VFDFLT_S_# AHU GeneraAHU VAV ContSupply Fan VFD Speed SFAN_VFD_SPD_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_SFAN_VFD_SPD_C_# AHU GeneraAHU VAV ContSupply Fan VFD Speed Override SFAN_VFD_SPD_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_SFAN_VFD_SPD_C_OVRD_# AHU GeneraAHU Basic Uni Unocc Cooling Setpoint UNOCC_CLG_SPT AV WriteO CoS_0.5 Yes archibus#_area_designation_AHU-001_UNOCC_CLG_SPT_# AHU GeneraAHU Basic Uni Unocc Heating Setpoint UNOCC_HTG_SPT AV WriteO CoS_0.5 Yes archibus#_area_designation_AHU-001_UNOCC_HTG_SPT_# AHU GeneraAHU CO2 ContZone Carbon Dioxide PPM ZN_CO2 AI Read TI_15 Priority 3 Out of Range >ZN_CO2_SPT + 200 N/A Yes archibus#_area_designation_AHU-001_ZN_CO2_# AHU GeneraAHU CO2 ContZone Carbon Dioxide PPM Setpoint ZN_CO2_SPT AV WriteO TI_15 Yes archibus#_area_designation_AHU-001_ZN_CO2_SPT_# AHU GeneraAHU Single Zo Zone Override ZN_T_OVRD AV Read BCoS Yes archibus#_area_designation_AHU-001_ZN_T_OVRD_# AHU GeneraAHU Single Zo Zone Temp ZN_T AI Read TI_15 Priority 3 Out of Range >EFF_ZN_T_SPT + 2 <EFF_ZN_T_SPT - 2 Yes archibus#_area_designation_AHU-001_ZN_T_# AHU GeneraAHU Single Zo Zone Temp ZN_T AI Read TI_15 Priority 3 Out of Range >EFF_ZN_T_SPT + 2 <EFF_ZN_T_SPT - 2 Yes archibus#_area_designation_AHU-001_ZN_T_# AHU GeneraAHU Single Zo Zone Temp Setpoint ZN_T_SPT AV WriteO TI_15 Yes archibus#_area_designation_AHU-001_ZN_T_SPT_# AHU GeneraAHU Single Zo Zone Temp Setpoint ZN_T_SPT AV WriteO TI_15 Yes archibus#_area_designation_AHU-001_ZN_T_SPT_# AHU GeneraER AHU Bldg Pres Building Static Pressure BLDG_SP AI Read TI_5 Priority 2 Out of Range >EFF_BLDG_SP_SPT + 0.2 <EFF_BLDG_SP_SPT - 0.2 Yes archibus#_area_designation_AHU-001_BLDG_SP_# AHU GeneraER AHU Bldg Pres Building Static Pressure Setpoint BLDG_SP_SPT AV WriteA CoS_0.01 Yes archibus#_area_designation_AHU-001_BLDG_SP_SPT_# AHU GeneraER AHU Staged C Cooling Stage 1 DXC_1_C BO Read BCoS archibus#_area_designation_AHU-001_DXC_1_C_# AHU GeneraER AHU Staged C Cooling Stage 1 Override DXC_1_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_1_C_OVRD_# AHU GeneraER AHU Staged C Cooling Stage 2 DXC_2_C BO Read BCoS archibus#_area_designation_AHU-001_DXC_2_C_# AHU GeneraER AHU Staged C Cooling Stage 2 Override DXC_2_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_2_C_OVRD_# AHU GeneraER AHU Staged C Cooling Stage 3 DXC_3_C BO Read BCoS archibus#_area_designation_AHU-001_DXC_3_C_# AHU GeneraER AHU Staged C Cooling Stage 3 Override DXC_3_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_3_C_OVRD_# AHU GeneraER AHU Staged C Cooling Stage 4 DXC_4_C BO Read BCoS archibus#_area_designation_AHU-001_DXC_4_C_# AHU GeneraER AHU Staged C Cooling Stage 4 Override DXC_4_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_4_C_OVRD_# AHU GeneraER AHU Dehumid Cooling Supply Air Temp SACLG_T AI Read TI_5 Priority 2 Out of Range >EFF_SA_T_SPT + 10 <EFF_SA_T_SPT - 10 Yes archibus#_area_designation_AHU-001_SACLG_T_# AHU GeneraER AHU Modulati Cooling Valve CHW_VLV_C AO Read TI_5 archibus#_area_designation_AHU-001_CHW_VLV_C_# AHU GeneraER AHU Modulati Cooling Valve Override CHW_VLV_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_CHW_VLV_C_OVRD_# AHU GeneraER AHU Dehumid Dehumidification Setpoint SA_DHUM_SPT AV WriteO CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_DHUM_SPT_# AHU GeneraER AHU Basic Uni Demand Limit Level DMAN_LMT_S AV Read CoS_1 Yes archibus#_area_designation_AHU-001_DMAN_LMT_S_# AHU GeneraER AHU EconomizEconomizer Mixed Air Temp Setpoint MA_T_SPT AV Read CoS_0.1 archibus#_area_designation_AHU-001_MA_T_SPT_# AHU GeneraER AHU EconomizEconomizer Mixed Air Temp Setpoint Override MA_T_SPT_OVRD AV WriteA CoS_0.1 archibus#_area_designation_AHU-001_MA_T_SPT_OVRD_# AHU GeneraER AHU Bldg Pres Effective Building Static Pressure Setpoint EFF_BLDG_SP_SPT AV Read CoS_0.01 archibus#_area_designation_AHU-001_EFF_BLDG_SP_SPT_# AHU GeneraER AHU VAV ContEffective Supply Air Static Pressure Setpoint EFF_SA_SP_SPT AV Read CoS_0.1 archibus#_area_designation_AHU-001_EFF_SA_SP_SPT_# AHU GeneraER AHU Basic Uni Effective Supply Air Temp Setpoint EFF_SA_T_SPT AV Read CoS_0.1 archibus#_area_designation_AHU-001_EFF_SA_T_SPT_# AHU GeneraER AHU Single Zo Effective Zone Temp Setpoint EFF_ZN_T_SPT AV Read CoS_0.5 archibus#_area_designation_AHU-001_EFF_ZN_T_SPT_# AHU GeneraER AHU Basic Uni Emergency Shutdown EMER_OVRD BV Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_EMER_OVRD_# AHU GeneraER AHU Exhaust FExhaust Air Dampers EA_DPR_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_EA_DPR_C_# AHU GeneraER AHU Exhaust FExhaust Air Dampers Override EA_DPR_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_EA_DPR_C_OVRD_# AHU GeneraER AHU Exhaust FExhaust Fan Start/Stop EXFAN_RUN_C BO Read BCOS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_EXFAN_RUN_C_# AHU GeneraER AHU Exhaust FExhaust Fan Start/Stop Override EXFAN_RUN_C_OVRD BV WriteA BCOS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_EXFAN_RUN_C_OVRD_# AHU GeneraER AHU Exhaust FExhaust Fan Status EXFAN_RUN_S BI Read BCOS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_EXFAN_RUN_S_# AHU GeneraER AHU VFD on E Exhaust Fan VFD Fault EXFAN_VFDFLT_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A archibus#_area_designation_AHU-001_EXFAN_VFDFLT_S_# AHU GeneraER AHU VFD on E Exhaust Fan VFD Speed EXFAN_VFD_SPD_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_EXFAN_VFD_SPD_C_# AHU GeneraER AHU VFD on E Exhaust Fan VFD Speed Override EXFAN_VFD_SPD_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_EXFAN_VFD_SPD_C_OVRD_# AHU GeneraER AHU Modulati Face and Bypass FAB_DPR_C AO Read TI_5 archibus#_area_designation_AHU-001_FAB_DPR_C_# AHU GeneraER AHU Modulati Face and Bypass - Cool FABC_DPR_C AO Read TI_5 archibus#_area_designation_AHU-001_FABC_DPR_C_# AHU GeneraER AHU Modulati Face and Bypass Cool Override FABC_DPR_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_FABC_DPR_C_OVRD_# AHU GeneraER AHU Modulati Face and Bypass Override FAB_DPR_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_FAB_DPR_C_OVRD_# AHU GeneraER AHU Final Filt Final Filter Status FFLTR_DP_S BI Read BCoS archibus#_area_designation_AHU-001_FFLTR_DP_S_# AHU GeneraER AHU Basic Uni Freezestat FZ_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_FZ_S_# AHU GeneraER AHU Heat WheHeat Wheel Bypass Dampers HTWHL_BPDPR_C AO Read TI_15 Yes archibus#_area_designation_AHU-001_HTWHL_BPDPR_C_# AHU GeneraER AHU Heat WheHeat Wheel Bypass Dampers Override HTWHL_BPDPR_C_OVRD AV WriteA TI_15 Yes archibus#_area_designation_AHU-001_HTWHL_BPDPR_C_OVRD_# AHU GeneraER AHU Heat WheHeat Wheel Discharge Air Temp HTWHL_DA_T AI Read TI_15 Yes archibus#_area_designation_AHU-001_HTWHL_DA_T_# AHU GeneraER AHU Heat WheHeat Wheel Start/Stop HTWHL_RUN_C BO Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_HTWHL_RUN_C_# AHU GeneraER AHU Heat WheHeat Wheel Start/Stop Override HTWHL_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_HTWHL_RUN_C_OVRD_# AHU GeneraER AHU Heat WheHeat Wheel Status HTWHL_RUN_S BI Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_HTWHL_RUN_S_# AHU GeneraER AHU Heat WheHeat Wheel VFD Fault HTWHL_VFDFLT_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_HTWHL_VFDFLT_S_# AHU GeneraER AHU Heat WheHeat Wheel VFD Speed HTWHL_VFD_SPD_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_HTWHL_VFD_SPD_C_# AHU GeneraER AHU Heat WheHeat Wheel VFD Speed Override HTWHL_VFD_SPD_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_HTWHL_VFD_SPD_C_OVRD_# AHU GeneraER AHU Recirc HW Heating Coil Pump Start/Stop HW_P_RUN_C BO Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_HW_P_RUN_C_# AHU GeneraER AHU Recirc HW Heating Coil Pump Start/Stop Override HW_P_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_HW_P_RUN_C_OVRD_# AHU GeneraER AHU Recirc HW Heating Coil Pump Status HW_P_RUN_S BI Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_HW_P_RUN_S_# AHU GeneraER AHU Staged H Heating Stage 1 HT_1_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_1_C_# AHU GeneraER AHU Staged H Heating Stage 1 Override HT_1_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_1_C_OVRD_# AHU GeneraER AHU Staged H Heating Stage 2 HT_2_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_2_C_# AHU GeneraER AHU Staged H Heating Stage 2 Override HT_2_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_2_C_OVRD_# AHU GeneraER AHU Staged H Heating Stage 3 HT_3_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_3_C_# AHU GeneraER AHU Staged H Heating Stage 3 Override HT_3_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_3_C_OVRD_# AHU GeneraER AHU Staged H Heating Stage 4 HT_4_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_4_C_# AHU GeneraER AHU Staged H Heating Stage 4 Override HT_4_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_4_C_OVRD_# AHU GeneraER AHU Staged H Heating Stage 5 HT_5_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_5_C_# AHU GeneraER AHU Staged H Heating Stage 5 Override HT_5_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_5_C_OVRD_#

AHU GeneraER AHU Staged H Heating Stage 6 HT_6_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_6_C_# AHU GeneraER AHU Staged H Heating Stage 6 Override HT_6_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_6_C_OVRD_# AHU GeneraER AHU Modulati Heating Valve HW_VLV_C AO Read TI_5 archibus#_area_designation_AHU-001_HW_VLV_C_# AHU GeneraER AHU Modulati Heating Valve Override HW_VLV_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_HW_VLV_C_OVRD_# AHU GeneraER AHU VAV ContHigh Static Shutdown SA_HISP_S BO Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_SA_HISP_S_# AHU GeneraER AHU HumidificHumidifier HUM_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_HUM_C_# AHU GeneraER AHU HumidificHumidifier Override HUM_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_HUM_C_OVRD_# AHU GeneraER AHU HumidificHumidifier Setpoint SA_HUM_SPT AV WriteO CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_HUM_SPT_# AHU GeneraER AHU EconomizMixed Air Dampers MA_DPR_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_MA_DPR_C_# AHU GeneraER AHU EconomizMixed Air Dampers Override MA_DPR_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_MA_DPR_C_OVRD_# AHU GeneraER AHU EconomizMixed Air Temp MA_T AI Read TI_5 Priority 2 Out of Range >MA_T_SPT + 15 <40 Yes archibus#_area_designation_AHU-001_MA_T_# AHU GeneraER AHU Basic Uni Occ Cooling Setpoint OCC_CLG_SPT AV WriteO CoS_0.5 Yes archibus#_area_designation_AHU-001_OCC_CLG_SPT_# AHU GeneraER AHU Basic Uni Occ Heating Setpoint OCC_HTG_SPT AV WriteO CoS_0.5 Yes archibus#_area_designation_AHU-001_OCC_HTG_SPT_# AHU GeneraER AHU CO2 ContOutside Air Carbon Dioxide PPM OA_CO2 AI Read TI_15 Yes archibus#_area_designation_AHU-001_OA_CO2_# AHU GeneraER AHU Basic Uni Outside Air Damper Status OA_DPR_S BI Read BCOS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_OA_DPR_S_# AHU GeneraER AHU Basic Uni Outside Air Dampers OA_DPR_C AO Read TI_5 Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_OA_DPR_C_# AHU GeneraER AHU Basic Uni Outside Air Dampers Override OA_DPR_C_OVRD AV WriteA TI_5 Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_OA_DPR_C_OVRD_# AHU GeneraER AHU Basic Uni Outside Air Temp OA_T AI Read TI_15 Yes archibus#_area_designation_AHU-001_OA_T_# AHU GeneraER AHU Pre-Filte Prefilter Status PFLTR_DP_S BI Read BCoS archibus#_area_designation_AHU-001_PFLTR_DP_S_# AHU GeneraER AHU Basic Uni Preheating Mixed Air Temp Setpoint PRHT_MA_T_SPT AV Read CoS_0.1 archibus#_area_designation_AHU-001_PRHT_MA_T_SPT_# AHU GeneraER AHU Basic Uni Preheating Mixed Air Temp Setpoint Override PRHT_MA_T_SPT_OVRD AV WriteA CoS_0.1 archibus#_area_designation_AHU-001_PRHT_MA_T_SPT_OVRD_# AHU GeneraER AHU Dehumid Preheating Valve PHT_VLV_C AO Read TI_5 archibus#_area_designation_AHU-001_PHT_VLV_C_# AHU GeneraER AHU Dehumid Preheating Valve Override PHT_VLV_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_PHT_VLV_C_OVRD_# AHU GeneraER AHU CO2 ContReturn Air Carbon Dioxide PPM RA_CO2 AI Read TI_15 Priority 3 Out of Range >RA_CO2_SPT + 200 N/A Yes archibus#_area_designation_AHU-001_RA_CO2_# AHU GeneraER AHU CO2 ContReturn Air Carbon Dioxide PPM Setpoint RA_CO2_SPT AV WriteO TI_15 Yes archibus#_area_designation_AHU-001_RA_CO2_SPT_# AHU GeneraER AHU Dehumid Return Air Humidity RA_RH AI Read TI_15 Priority 3 Out of Range >65 <25 Yes archibus#_area_designation_AHU-001_RA_RH_# AHU GeneraER AHU Basic Uni Return Air Smoke Detector RA_SD_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_RA_SD_S_# AHU GeneraER AHU EconomizReturn Air Temp RA_T AI Read TI_15 Priority 3 Out of Range >EFF_ZN_T_SPT + 10 <EFF_ZN_T_SPT - 10 Yes archibus#_area_designation_AHU-001_RA_T_# AHU GeneraER AHU Run-Arou Run-Around Loop Coil Discharge Air Temp RUNALP_DA_T AI Read TI_15 Yes archibus#_area_designation_AHU-001_RUNALP_DA_T_# AHU GeneraER AHU Run-Arou Run-Around Loop Mixing Valve RUNALP_VLV_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_RUNALP_VLV_C_# AHU GeneraER AHU Run-Arou Run-Around Loop Mixing Valve Override RUNALP_VLV_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_RUNALP_VLV_C_OVRD_# AHU GeneraER AHU Run-Arou Run-Around Loop Pump Start/Stop RUNALP_P_RUN_C BO Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_RUNALP_P_RUN_C_# AHU GeneraER AHU Run-Arou Run-Around Loop Pump Start/Stop Override RUNALP_P_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_RUNALP_P_RUN_C_OVRD_# AHU GeneraER AHU Run-Arou Run-Around Loop Pump Status RUNALP_P_RUN_S BI Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_RUNALP_P_RUN_S_# AHU GeneraER AHU Run-Arou Run-Around Loop Water Temp RUNALP_LW_T AI Read TI_15 Yes archibus#_area_designation_AHU-001_RUNALP_LW_T_# AHU GeneraER AHU Run-Arou Run-Around Loop Water Temp Setpoint RUNALP_LW_T_SPT AV WriteA CoS_0.1 Yes archibus#_area_designation_AHU-001_RUNALP_LW_T_SPT_# AHU GeneraER AHU Basic Uni Schedule OCC_S BV WriteO BCoS archibus#_area_designation_AHU-001_OCC_S_# AHU GeneraER AHU HumidificSupply Air Humidity SA_RH AI Read TI_15 Priority 3 Out of Range >90 <SA_HUM_SPT - 20% Yes archibus#_area_designation_AHU-001_SA_RH_# AHU GeneraER AHU Basic Uni Supply Air Smoke Detector SA_SD_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_SA_SD_S_# AHU GeneraER AHU VAV ContSupply Air Static Pressure SA_SP AI Read TI_15 Priority 2 Out of Range >EFF_SA_SP_SPT + 1 <EFF_SA_SP_SPT - 1 Yes archibus#_area_designation_AHU-001_SA_SP_# AHU GeneraER AHU VAV ContSupply Air Static Pressure Setpoint SA_SP_SPT AV WriteA CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_SP_SPT_# AHU GeneraER AHU VAV ContSupply Air Temp SA_T AI Read TI_5 Priority 2 Out of Range >EFF_SA_T_SPT + 10 <EFF_SA_T_SPT - 10 Yes archibus#_area_designation_AHU-001_SA_T_# AHU GeneraER AHU VAV ContSupply Air Temp Setpoint SA_T_SPT AV WriteO CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_T_SPT_# AHU GeneraER AHU Basic Uni Supply Fan Start/Stop SFAN_RUN_C BO Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_SFAN_RUN_C_# AHU GeneraER AHU Basic Uni Supply Fan Start/Stop Override SFAN_RUN_C_OVRD BV WriteA BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_SFAN_RUN_C_OVRD_# AHU GeneraER AHU Basic Uni Supply Fan Status SFAN_RUN_S BI Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_SFAN_RUN_S_# AHU GeneraER AHU VAV ContSupply Fan VFD Fault SFAN_VFDFLT_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_SFAN_VFDFLT_S_# AHU GeneraER AHU VAV ContSupply Fan VFD Speed SFAN_VFD_SPD_C AO Read TI_5 Yes archibus#_area_designation_AHU-001_SFAN_VFD_SPD_C_# AHU GeneraER AHU VAV ContSupply Fan VFD Speed Override SFAN_VFD_SPD_C_OVRD AV WriteA TI_5 Yes archibus#_area_designation_AHU-001_SFAN_VFD_SPD_C_OVRD_# AHU GeneraER AHU Basic Uni Unocc Cooling Setpoint UNOCC_CLG_SPT AV WriteO CoS_0.5 archibus#_area_designation_AHU-001_UNOCC_CLG_SPT_# AHU GeneraER AHU Basic Uni Unocc Heating Setpoint UNOCC_HTG_SPT AV WriteO CoS_0.5 archibus#_area_designation_AHU-001_UNOCC_HTG_SPT_# AHU GeneraER AHU CO2 ContZone Carbon Dioxide PPM ZN_CO2 AI Read TI_15 Priority 3 Out of Range >ZN_CO2_SPT + 200 N/A Yes archibus#_area_designation_AHU-001_ZN_CO2_# AHU GeneraER AHU CO2 ContZone Carbon Dioxide PPM Setpoint ZN_CO2_SPT AV WriteO TI_15 Yes archibus#_area_designation_AHU-001_ZN_CO2_SPT_# AHU GeneraER AHU Single Zo Zone Override ZN_T_OVRD AV Read BCoS Yes archibus#_area_designation_AHU-001_ZN_T_OVRD_# AHU GeneraER AHU Single Zo Zone Temp ZN_T AI Read TI_15 Priority 3 Out of Range >EFF_ZN_T_SPT + 2 <EFF_ZN_T_SPT - 2 Yes archibus#_area_designation_AHU-001_ZN_T_# AHU GeneraER AHU Single Zo Zone Temp Setpoint ZN_T_SPT AV WriteO TI_15 Priority 3 Out of Range >EFF_ZN_T_SPT + 5 <EFF_ZN_T_SPT - 5 Yes archibus#_area_designation_AHU-001_ZN_T_SPT_# AHU GeneraMAU Staged C Cooling Stage 1 DXC_1_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_1_C_# AHU GeneraMAU Staged C Cooling Stage 1 Override DXC_1_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_1_C_OVRD_# AHU GeneraMAU Staged C Cooling Stage 2 DXC_2_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_2_C_# AHU GeneraMAU Staged C Cooling Stage 2 Override DXC_2_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_2_C_OVRD_# AHU GeneraMAU Staged C Cooling Stage 3 DXC_3_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_3_C_# AHU GeneraMAU Staged C Cooling Stage 3 Override DXC_3_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_3_C_OVRD_# AHU GeneraMAU Staged C Cooling Stage 4 DXC_4_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_DXC_4_C_# AHU GeneraMAU Staged C Cooling Stage 4 Override DXC_4_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_DXC_4_C_OVRD_# AHU GeneraMAU Basic Uni Cooling Supply Air Temp SACLG_T AI Read TI_5 Priority 2 Out of Range >EFF_SA_T_SPT + 10 <EFF_SA_T_SPT - 10 Yes archibus#_area_designation_AHU-001_SACLG_T_# AHU GeneraMAU Modulati Cooling Valve CHW_VLV_C AO WriteA TI_5 Yes archibus#_area_designation_AHU-001_CHW_VLV_C_# AHU GeneraMAU Modulati Cooling Valve Override CHW_VLV_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_CHW_VLV_C_OVRD_# AHU GeneraMAU Dehumid Dehumidification Setpoint SA_DHUM_SPT AV WriteO CoS_0.1 Yes archibus#_area_designation_AHU-001_SA_DHUM_SPT_# AHU GeneraMAU Basic Uni Demand Limit Level DMAN_LMT_S AV Read CoS_1 Yes archibus#_area_designation_AHU-001_DMAN_LMT_S_# AHU GeneraMAU VAV ContEffective Supply Air Static Pressure Setpoint EFF_SA_SP_SPT AV Read CoS_0.1 archibus#_area_designation_AHU-001_EFF_SA_SP_SPT_# AHU GeneraMAU Basic Uni Effective Supply Air Temp Setpoint EFF_SA_T_SPT AV Read CoS_0.1 archibus#_area_designation_AHU-001_EFF_SA_T_SPT_# AHU GeneraMAU Basic Uni Emergency Shutdown EMER_OVRD BV Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_EMER_OVRD_# AHU GeneraMAU Modulati Face and Bypass - Cool FABC_DPR_C AO Read TI_5 archibus#_area_designation_AHU-001_FABC_DPR_C_# AHU GeneraMAU Modulati Face and Bypass Cool Override FABC_DPR_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_FABC_DPR_C_OVRD_# AHU GeneraMAU Modulati Face and Bypass Damper Heat Override FABH_DPR_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_FABH_DPR_C_OVRD_# AHU GeneraMAU Modulati Face and Bypass Dampers - Heat FABH_DPR_C AO Read TI_5 archibus#_area_designation_AHU-001_FABH_DPR_C_# AHU GeneraMAU Final Filt Final Filter Status FFLTR_DP_S BI Read BCoS archibus#_area_designation_AHU-001_FFLTR_DP_S_# AHU GeneraMAU Basic Uni Freezestat FZ_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_FZ_S_# AHU GeneraMAU Staged H Heating Stage 1 HT_1_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_1_C_# AHU GeneraMAU Staged H Heating Stage 1 Override HT_1_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_1_C_OVRD_# AHU GeneraMAU Staged H Heating Stage 2 HT_2_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_2_C_# AHU GeneraMAU Staged H Heating Stage 2 Override HT_2_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_2_C_OVRD_# AHU GeneraMAU Staged H Heating Stage 3 HT_3_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_3_C_# AHU GeneraMAU Staged H Heating Stage 3 Override HT_3_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_3_C_OVRD_# AHU GeneraMAU Staged H Heating Stage 4 HT_4_C BO WriteA BCoS Yes archibus#_area_designation_AHU-001_HT_4_C_# AHU GeneraMAU Staged H Heating Stage 4 Override HT_4_C_OVRD BV WriteA BCoS archibus#_area_designation_AHU-001_HT_4_C_OVRD_# AHU GeneraMAU Modulati Heating Valve HW_VLV_C AO WriteA TI_5 Yes archibus#_area_designation_AHU-001_HW_VLV_C_# AHU GeneraMAU Modulati Heating Valve Override HW_VLV_C_OVRD AV WriteA TI_5 archibus#_area_designation_AHU-001_HW_VLV_C_OVRD_# AHU GeneraMAU CO2 ContOutside Air Carbon Dioxide PPM OA_CO2 AI Read TI_15 Yes archibus#_area_designation_AHU-001_OA_CO2_#

AHU GeneraMAU Basic Uni Outside Air Damper OA_DPR_C BO Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_OA_DPR_C_# AHU GeneraMAU Basic Uni Outside Air Damper Override OA_DPR_C_OVRD BV WriteA BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_OA_DPR_C_OVRD_# AHU GeneraMAU Basic Uni Outside Air Damper Status OA_DPR_S BI Read BCoS Priority 2 Boolean Command Fail N/A N/A Yes archibus#_area_designation_AHU-001_OA_DPR_S_# AHU GeneraMAU Basic Uni Outside Air Temp OA_T AI Read TI_15 Yes archibus#_area_designation_AHU-001_OA_T_# AHU GeneraMAU Pre-Filte Prefilter Status PFLTR_DP_S BI Read BCoS archibus#_area_designation_AHU-001_PFLTR_DP_S_# AHU GeneraMAU Basic Uni Schedule OCC_S BV WriteO BCoS archibus#_area_designation_AHU-001_OCC_S_# AHU GeneraMAU Basic Uni Smoke Detector SD_S BI Read BCoS Priority 1 Boolean Change of Stat N/A N/A Yes archibus#_area_designation_AHU-001_SD_S_# AHU GeneraMAU HumidificSupply Air Humidity SA_RH AI Read TI_15 Priority 3 Out of Range >90 EFF_SA_SP_SPT + 1 EFF_SA_T_SPT + 10 EFF_BLDG_SP_SPT + 0.2 EFF_SA_T_SPT + 10 MA_T_SPT +…