Addendum_1_-_Demolition_Plans.pdf
PDF 2 MB Posted
- Solicitation number
- 0000037210
- Issued by
- San Mateo County, Santa Cruz County, San Mateo City, Santa Cruz City, California
About this file
This is an addendum containing demolition plans and construction documents prepared by the California Department of Parks and Recreation (DPR), Facilities and Development Division, for the Abalone Farm Demolition project at Wilder Ranch State Park in Santa Cruz County. The project involves the demolition of a former abalone farm facility, including the removal of existing deteriorating buildings, clearing of trash and rubbish from the site, disconnection and removal of electrical equipment and wiring, removal and capping of existing water lines, and removal of seawater piping systems. The demolition plans indicate that the building to be demolished is a 21,705-square-foot, two-story structure (22 feet in height) of Type V-B construction built in an unknown year on a 41,600-square-foot project area. Contractors must complete all work within 120 calendar days from the date of written notice to commence work, with the contract term running from April 1, 2026 (or upon DGS-OLS approval) through March 31, 2027. A mandatory job walk was scheduled for April 1, 2026 at 11:00 AM Pacific Time, with bid opening on April 8, 2026 at 2:00 PM Pacific Time.
The project estimate is $400,000.00, assuming minimal hazardous materials, though hazardous materials on site are believed to be minimal and will be discussed at the mandatory job walk. Contractors must hold a C-21 Demolition Contractor license and a Hazardous Substance Removal Certificate (HAZ license) to be eligible. The contractor must remove all materials from demolition work and trash from the site and dispose of them properly, including offering lighting fixtures, wiring devices, panelboards, and equipment to the state and delivering all removed fluorescent and mercury vapor lamps to a certified recycler. The work must comply with current editions of applicable California codes including the California Building Code, California Electrical Code, California Mechanical Code, California Plumbing Code, California Energy Code, California Green Building Standards, 2010 ADA Accessibility Standards, and State Fire Marshal regulations. DVBE participation has been waived for this solicitation. Questions concerning the bid solicitation must be submitted to g.g-miksicek@parks.ca.gov no later than 4:00 PM, seven days before the bid opening date.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid.Solicitation_C25715002_v4.pdf | ||
| Bid.Forms_C25715002_v3.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
20 20
WILDER RANCH
STATE PARK
SHEET NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
DATE:
FACILITIES AND
DEVELOPMENT DIVISION
PROJECT MILESTONE:
DPR ACCESSIBILITY COMPLIANCE REVIEW
ACCESSIBILITY COMPLIANCE AND SFM SIGNED
ORIGINALS ARE ON FILE AT THE DEPARTMENT OF
PARKS & RECREATION, NORTHERN SERVICE CENTER
Certification #
Reviewed by
DateCASp#
No. C83449 Exp. 03-31-25
Fi le
: C :\U se rs
\d lo fh ol m \O ne D riv e
- C al ifo rn ia S ta te
P ar ks \D es kt op \A ut oc ad T ak e
H om e Fi le s\
Ta ke
H om e\ W ild er
R an ch S
P Ab al on e Fa rm D em o\
D ra w in gs \3
-3 6-
\S he et
S et
\G 0.
C
O
VE
R S
H
EE
T.
dw g D at e:
D ec em be r 1
9:
a m
12-2-24
DLOFHOLM
KROSE
DLOFHOLM
C O
VE
R
S H
EE
T
AB
AL
O N
E
FA
R M
D
EM
O
LI
TI
O
N W
IL
D
ER
R
AN
C
H S
TA
TE
P
AR
K
CONSTRUCTION DOCUMENTS
G0.1
CALIFORNIA DEPARTMENT OF PARKS AND RECREATION
FACILITIES AND DEVELOPMENT DIVISION
SITE ADDRESS
GENERAL NOTES
SHEET INDEX
LOCATION MAP
N
S
W E
BUILDING CODE REVIEW
1. OCCUPANCY CLASSIFICATION AND USE U
2. BUILDING CONSTRUCTION TYPE V-B
3. NUMBER OF STORIES 2
4. ACTUAL BUILDING HEIGHT 22 FT
5. BUILDING AREA IN SQUARE FEET 21705 SQ FT
6. AREA OF PROJECT IN SQUARE FEET 41600 SQ FT
7. SEPERATED OR NON-SEPERATED USE NS
8. ALLOWABLE AREA PER C.B.C. 5500 SQ FT
9. AREA INCREASES NONE
10. HEIGHT INCREASES NONE
11. FIRE SPRINKLERS NO
TYPE: (WET, DRY, PRE-ACTION OR DELUGE)
12. FIRE ALARM NO
TYPE: (MANUAL, AUTOMATIC, ETC)
13. OTHER FIRE PROTECTION SYSTEMS, IF ANY NO
14. SMOKE CONTROL SYSTEM NO
15. OCCUPANT LOAD FOR ENTIRE BUILDING N/A
AND EACH FLOOR
16. YEAR BUILDING WAS CONSTRUCTED UNKNOWN
17. IN A HIGH FIRE HAZARD SEVERITY ZONE? NO
DEFERRED SUBMITTALS
SCOPE OF WORK
PREPARED BY
SYMBOLS LEGEND
STATE OF CALIFORNIA
DEPARTMENT OF PARKS AND RECREATION
FACILITIES AND DEVELOPMENT DIVISION
NORTHERN SERVICE CENTER
2241 HARVARD ST, SUITE 200
SACRAMENTO, CA 95815
AASHTO AMERICAN ASSOCIATION OF
STATE HIGHWAY AND
TRANSPORTATION OFFICIALS
AB AGGREGATE BASE
APPROX. APPROXIMATELY
CBC CALIFORNIA BUILDING CODE
COMP COMPACTION
CONC CONCRETE
CONT CONTINUOUS
DIA DIAMETER
E EXISTING
EA EACH
FL FLOWLINE
FT FOOT
GB GRADE BREAK
ID INNER DIAMETER
IN INCH
INC INCORPORATED
LB POUND
LBS POUNDS
LG LONG
MAX MAXIMUM
NOM NOMINAL
OC ON CENTER
PCC PORTLAND CEMENT CONCRETE
PED PEDESTRIAN
PSF POUNDS PER SQUARE FOOT
REL RELATIVE
S STRUCTURAL
S/N SERIAL NUMBER
SF SQUARE FEET
SFM SEWER FORCE MAIN
SPEC SPECIFICATIONS
SS SANITARY SEWER
T TELEPHONE
TYP TYPICAL
W/ WITH
ABBREVIATIONS
DIMENSION LINE
FACE OF MATERIAL
DETAIL NUMBER1
SHEET NUMBER
REVISION
NUMBER
DIMENSION LINE
CENTER LINE
A1
SECTION NUMBER
SHEET NUMBER
A A1
X'-X"
X'-X"
CL
VICINITY MAP
N
S
W E
1- ALL MATERIALS SHOWN OR NOTED ON THE PLANS ARE NEW
UNLESS CALLED OUT OTHERWISE.
2- THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL
EXISTING CONDITIONS SHOWN OR DIMENSIONED HERE. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF
THE STATE REPRESENTATIVE FOR RESOLUTION BEFORE
PROCEEDING WITH THAT PORTION OF THE WORK.
3- ALL WORK SHALL COMPLY WITH THE CURRENT EDITION OF
THE FOLLOWING LISTED CODES, AND ALL OTHERS HAVING
JURISDICTION OVER THE WORK.
TITLE 19, CCR, PUBLIC SAFETY, SFM REGULATIONS.
2022 CA ADMINISTRATIVE CODE TITLE 24, PT 1.
2022 CA BUILDLING CODE (CBC) TITLE 24, PT 2.
2022 CA ELECTRICAL CODE (CEC) TITLE 24, PT 3.
2022 CA MECHANICAL CODE (CMC) TITLE 24, PT 4
2022 CA PLUMBING CODE (CPC) TITLE 24, PT 5.
2022 CA ENERGY CODE CCR TITLE 24, PT 6.
2022 CA GREEN BUILDING STANDARDS TITLE 24, PT 11.
2022 CA REFERENCED STANDARDS TITLE 24, PT 12.
2010 ADA STANDARD FOR ACCESSIBLE DESIGN.
THE SECRETARY OF THE INTERIOR'S STANDARDS FOR THE
TREATMENT OF HISTORIC PROPERTIES.
4- CONDUCT ALL WORK IN ACCORDANCE WITH THE LATEST
SAFETY RULES AND REGULATIONS OF ALL AUTHORITIES AND
AGENCIES HAVING JURISDICTION OVER THE WORK.
5- ALL WORK SHALL BE IN ACCORDANCE WITH THE
CONSTRUCTION DOCUMENTS. WHERE DETAILED
INFORMATION OR CLARIFICATION IS REQUIRED, THE MATTER
SHALL BE REFERRED TO THE STATE REPRESENTATIVE FOR
WRITTEN RESOLUTION.
6- THE CONTRACTOR SHALL NOT SCALE THE DRAWINGS, BUT
SHALL RELY ONLY ON THE WRITTEN DIMENSIONS GIVEN. IF A
DISCREPANCY OCCURS OR NO DIMENSION IS GIVEN, THE
CONTRACTOR SHALL NOTIFY THE STATE REPRESENTATIVE
FOR WRITTEN CLARIFICATION BEFORE PROCEEDING WITH
THAT PORTION OF THE WORK.
7. COMPLIANCE WITH ADA REGULATIONS FOR SLOPES STATED
ON THE PLANS WILL BE VERIFIED BY THE STATE'S
REPRESENTATIVE UTILIZING A 24 INCH DIGITAL LEVEL. THE 24
INCH DIGITAL LEVEL WILL BE SUPPLIED BY THE STATE AND
WILL BE CALIBRATED BY THE STATE'S REPRESENTATIVE
PRIOR TO THE TAKING OF ANY MEASUREMENTS.
MEASUREMENTS WILL BE TAKEN IN MULTIPLE DIRECTIONS
WITH THE 24” DIGITAL LEVEL TO VERIFY COMPLIANCE WITH
SLOPES SPECIFIED ON THE PLANS. WORK THAT DOES NOT
MEET THE REQUIREMENTS SHALL BE CONSIDERED
NON-COMPLIANT AND WILL NOT BE ACCEPTED BY THE STATE.
ANY AREA WHICH IS NON-COMPLIANT SHALL BE REMOVED
AND REPLACED AT THE CONTRACTOR'S EXPENSE.
ABALONE FARM DEMOLITION
WILDER RANCH STATE PARK
CSFM # 24-N-3400-C-NW
SHEET INDEX
PAGE SHEET TITLE SHEET
001 COVER SHEET G0.1
002 DEMOLITION PLAN C0.1
003 FIRE DEPARTMENT NOTES C0.2
245 DAVENPORT LANDING ROAD
DAVENPORT, CA 95017
WILDER RANCH
STATE PARK
DEMOLISH EXISTING DETERIORATING BUILDINGS. CLEAR EXISTING SITE OF TRASH/RUBBISH.
REMOVE AND CAP EXISTING WATER LINE. DISCONNECT AND REMOVE ELECTRICAL EQUIPMENT
AND WIRING.
004 ELECTRICAL SYMBOLS AND
ABBREVIATIONS
E0.1
005 ELECTRICAL DEMOLITION PLAN E0.2
006 ELECTRICAL PARTIAL SINGLE
LINE
E0.3
11-26-24SFM BACKCHECK
AutoCAD SHX Text Merced
AutoCAD SHX Text Eureka
AutoCAD SHX Text Santa Cruz
AutoCAD SHX Text Madera
AutoCAD SHX Text Hollister
AutoCAD SHX Text Salinas
AutoCAD SHX Text Fresno
AutoCAD SHX Text Visalia
AutoCAD SHX Text Hanford
AutoCAD SHX Text San Luis
AutoCAD SHX Text Obispo
AutoCAD SHX Text Bakersfield
AutoCAD SHX Text Santa Barbara
AutoCAD SHX Text Ventura
AutoCAD SHX Text Independence
AutoCAD SHX Text Susanville
AutoCAD SHX Text Quincy
AutoCAD SHX Text Downieville
AutoCAD SHX Text Oroville
AutoCAD SHX Text Willows
AutoCAD SHX Text Red Bluff
AutoCAD SHX Text Redding
AutoCAD SHX Text Weaverville
AutoCAD SHX Text Colusa
AutoCAD SHX Text Nevada City
AutoCAD SHX Text Marysville
AutoCAD SHX Text Auburn
AutoCAD SHX Text Santa Rosa
AutoCAD SHX Text Napa
AutoCAD SHX Text Fairfield
AutoCAD SHX Text Sacramento
AutoCAD SHX Text Woodland
AutoCAD SHX Text Placerville
AutoCAD SHX Text Bridgeport
AutoCAD SHX Text Markleeville
AutoCAD SHX Text San Andreas
AutoCAD SHX Text Jackson
AutoCAD SHX Text Sonora
AutoCAD SHX Text Stockton
AutoCAD SHX Text Mariposa
AutoCAD SHX Text Modesto
AutoCAD SHX Text Oakland
AutoCAD SHX Text Martinez
AutoCAD SHX Text Redwood City
AutoCAD SHX Text San Francisco
AutoCAD SHX Text San Rafael
AutoCAD SHX Text San Jose
AutoCAD SHX Text Ukiah
AutoCAD SHX Text Lakeport
AutoCAD SHX Text Yuba City
AutoCAD SHX Text Merced
AutoCAD SHX Text Placerville
AutoCAD SHX Text Woodland
AutoCAD SHX Text Sacramento
AutoCAD SHX Text Santa Rosa
AutoCAD SHX Text Napa
AutoCAD SHX Text Jackson
AutoCAD SHX Text Fairfield
AutoCAD SHX Text Martinez
AutoCAD SHX Text San Andreas
AutoCAD SHX Text Stockton
AutoCAD SHX Text San Rafael
AutoCAD SHX Text San Francisco
AutoCAD SHX Text Oakland
AutoCAD SHX Text Sonora
AutoCAD SHX Text Modesto
AutoCAD SHX Text Redwood City
AutoCAD SHX Text San Jose
AutoCAD SHX Text Santa Cruz
AutoCAD SHX Text Hollister
AutoCAD SHX Text Salinas
RW
RW
RW
RW
RW
RW
RW
RW
FW
FW
FW
W
W W W
W W
BUILDING TO BE DEMOLISHED
APPROXIMATE
PROPERTY LINE
BUILDINGS TO REMAIN, TYP.
BUILDING TO BE DEMOLISHED
POLY TANKS TO BE REMOVED
GENERAL AREA OF
TRASH TO BE
REMOVED, TYP.
NOTES:
1. PROPERTY BOUNDARY LINE SHOWN IS APPROXIMATED FROM LEASE EXHIBITS. ACTUAL PROPERTY
BOUNDARY LINE WILL NEED TO BE ESTABLISHED BY PROFESSIONAL LAND SURVEYOR.
2. UNDERGROUND WET AND DRY UTILITIES ARE REPRESENTED IN THEIR APPROXIMATE LOCATION BASED ON
RECORD DRAWINGS, CONVERSATIONS WITH FIELD STAFF, AND TOPOGRAPHIC SURVEY. ENGINEER MAKES NO GUARANTEE OF ACCURACY. CONTRACTOR TO FIELD VERIFY AND NOTIFY ENGINEER OF ANY DISCREPANCIES.
3. ALL MATERIALS FROM DEMOLITION WORK AND TRASH WILL BE REMOVED AND DISPOSED OF BY CONTRACTOR.
(E) CONCRETE DRAINAGE DITCH TO REMAIN, TYP.
(E) WATER LINE TO BE CAPPED
AT THE STREET
WOODEN DECK AND STAIRS
DOWN TO LOWER LEVEL
GENERAL AREA OF
TRASH TO BE
REMOVED, TYP.
REMOVE PVC SEA WATER
LINES TO APPROX. THIS
POINT. EXACT LOCATION
TO BE DETERMINED BY
STATES REP.
PVC PIPES FOR SEAWATER
TO BE REMOVED
(E) FIRE HYDRANT
(E) FIRE HYDRANT
ASPHALT ROAD
LEGEND
BUILDINGS TO BE DEMOLISHED AND DISPOSED OF
EXISTING WATERLINE TO REMAIN
EXISTING WATERLINE TO BE REMOVED
EXISTING FIRE WATER LINE TO REMAIN
EXISTING CONCRETE DRAINAGE DITCH TO BE REMOVED
AREA OF GENERAL TRASH TO BE REMOVED
APPROXIMATE PROPERTY BOUNDARY
EXISTING SEAWATER PIPING TO BE REMOVED
EXISTING SEWATERR PIPING TO REMAIN
W
W
FW
RW
RW
SHEET NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
DATE:
FACILITIES AND
DEVELOPMENT DIVISION
PROJECT MILESTONE:
DPR ACCESSIBILITY COMPLIANCE REVIEW
ACCESSIBILITY COMPLIANCE AND SFM SIGNED
ORIGINALS ARE ON FILE AT THE DEPARTMENT OF
PARKS & RECREATION, NORTHERN SERVICE CENTER
Certification #
Reviewed by
DateCASp#
No. C83449 Exp. 03-31-25
C0.1
12-2-24
DLOFHOLM
KROSE
DLOFHOLM
D
EM
O
LI
TI
O
N P
LA
N
Fi le
: C :\U se rs
\d lo fh ol m \O ne D riv e
- C al ifo rn ia S ta te
P ar ks \D es kt op \A ut oc ad T ak e
H om e Fi le s\
Ta ke
H om e\ W ild er
R an ch S
P Ab al on e Fa rm D em o\
D ra w in gs \3
-3 6-
\C iv il\
C 0.
D
EM
O
LI
TI
O N
P
LA
N .d w g
D at e:
D ec em be r 1
9:
a m
AB
AL
O N
E
FA
R M
D
EM
O
LI
TI
O
N W
IL
D
ER
R
AN
C
H S
TA
TE
P
AR
K
CONSTRUCTION DOCUMENTS
1 11-26-24SFM BACKCHECK
Fence to be removed and cut at baseAccess Pt #1
Access Pt #2
Alberto.Bonilla Highlight
Alberto.Bonilla Line
Alberto.Bonilla Line
Alberto.Bonilla Line
Alberto.Bonilla Line
FW
FW
FW 22.00'
FIRE ACCESS ROUTE
FIRE HYDRANT
FIRE HYDRANT
DAVENPORT LANDING RD
SHEET NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
DATE:
FACILITIES AND
DEVELOPMENT DIVISION
PROJECT MILESTONE:
DPR ACCESSIBILITY COMPLIANCE REVIEW
ACCESSIBILITY COMPLIANCE AND SFM SIGNED
ORIGINALS ARE ON FILE AT THE DEPARTMENT OF
PARKS & RECREATION, NORTHERN SERVICE CENTER
Certification #
Reviewed by
DateCASp#
No. C83449 Exp. 03-31-25
Fi le
: C :\U se rs
\d lo fh ol m \O ne D riv e
- C al ifo rn ia S ta te
P ar ks \D es kt op \A ut oc ad T ak e
H om e Fi le s\
Ta ke
H om e\ W ild er
R an ch S
P Ab al on e Fa rm D em o\
D ra w in gs \3
-3 6-
\C iv il\
C 0.
FI
R E
D
EP
AR
TM
EN
T
N O
TE
S.
dw g
D at e:
D ec em be r 1
9:
a m
#####.003
12-2-24
DLOFHOLM
KROSE
DLOFHOLM
FI
R
E D
EP
AR
TM
EN
T N
O
TE
S
AB
AL
O N
E
FA
R M
D
EM
O
LI
TI
O
N W
IL
D
ER
R
AN
C
H S
TA
TE
P
AR
K
CONSTRUCTION DOCUMENTS
C0.2
FIRE SAFETY PLAN - CONSTRUCTION
1. NAME AND CONTACT INFORMATION OF SITE SAFETY DIRECTOR:
JACOB BENTLEY
DISTRICT MAINTENANCE CHIEF
CALIFORNIA STATE PARKS
SANTA CRUZ DISTRICT
(831)251-2884
2. DOCUMENTATION OF THE TRAINING OF THE SITE SAFETY DIRECTOR AND FIRE WATCH PERSONNEL:
· PROJECT MANAGEMENT TRAINING
3. PROCEDURES FOR REPORTING EMERGENCIES:
REPORT ALL EMERGENCIES TO THE SITE SAFETY DIRECTOR, DISTRICT MAINTENANCE CHIEF - JACOB BENTLEY, AND THE LOCAL FIRE DEPARTMENT
(SANTA CRUZ COUNTY FIRE DEPARTMENT/CAL-FIRE).
4. FIRE DEPARTMENT VEHICLE ACCESS ROUTES:
SEE MAP ON PLANS.
CONSTRUCTION SITE SHALL BE READILY ACCESSIBLE BY FIRE DEPARTMENT APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER DRIVING SURFACE OF NOT LESS THAN 20 FEET UNOBSTRUCTED WIDTH HAVING A MINIMUM 13'-6" VERTICAL CLEARANCE.
5. LOCATION OF FIRE PROTECTION EQUIPMENT, INCLUDING PORTABLE FIRE EXTINGUISHERS, STANDPIPES, FIRE DEPARTMENT CONNECTIONS, AND FIRE
HYDRANTS:
SEE MAP ON PLAN.
ALL VEHICLES AND HEAVY EQUIPMENT SHALL HAVE A FIRE EXTINGUISHER ONBOARD.
6. SMOKING AND COOKING POLICIES, DESIGNATED AREAS TO BE USED WHERE APPROVED, AND SIGNAGE LOCATIONS IN ACCORDANCE WITH SECTION 3305.8.:
N/A (NO SMOKING OR COOKING ALLOWED ON PREMISES).
7. LOCATION AND SAFETY CONSIDERATIONS FOR TEMPORARY HEATING EQUIPMENT:
N/A (NO TEMPORARY HEATING EQUIPMENT FOR THIS PROJECT)
8. HOT WORK PERMIT PLAN:
N/A (NO HOT WORK FOR THIS PROJECT)
9. PLANS FOR CONTROL OF COMBUSTIBLE WASTE MATERIAL:
ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, SUCH AS WOOD, PLASTIC, INSULATION, PAINTS AND VARNISHES, ADHESIVES AND SEALANTS, DUST, AND DEBRIS SHALL BE REMOVED FROM THE WORK SITE AT THE END OF EACH WORK SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. MATERIALS SUSCEPTIBLE TO SPONTANEOUS IGNITION, SUCH AS OILY RAGS, SHALL BE STORED IN A LISTED DISPOSAL CONTAINER.
YARD STORAGE OF EQUIPMENT TO BE INSTALLED OR COMBUSTIBLE CONSTRUCTION MATERIALS SHALL NOT BE STORED CLOSER THAN 30 FEET FROM
ANY STRUCTURE UNDER CONSTRUCTION OR ALTERATION.
10. LOCATIONS AND METHODS FOR STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AND OTHER HAZARDOUS MATERIALS:
STORAGE - FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE AREAS SHALL BE MAINTAINED CLEAR OF COMBUSTIBLE VEGETATION AND WASTE MATERIALS. SUCH STORAGE AREAS SHALL NOT BE USED FOR THE STORAGE OF COMBUSTIBLE MATERIALS. SMOKING AND OTHER SOURCES OF IGNITION SHALL BE PROHIBITED IN AREAS WHERE FLAMMABLE AND COMBUSTIBLE LIQUIDS ARE STORED OR USED. STORAGE OF CLASS I AND CLASS II LIQUIDS SHALL NOT EXCEED 60 GALLONS WITHIN 50 FEET OF THE STRUCTURE UNLESS APPROVED BY SDFD.
TANKS - TANKS AND CONTAINERS FOR THE STORAGE OF LIQUIDS ABOVE GROUND SHALL BE CONSPICUOUSLY MARKED WITH THE NAME OF THE PRODUCT THAT THEY CONTAIN AND THE WORDS: "FLAMMABLE--KEEP FIRE AND FLAME AWAY." TANKS SHALL BEAR THE ADDITIONAL MARKING: "KEEP 50 FEET FROM BUILDINGS." a. TANKS MORE THAN 100 GALLONS IN CAPACITY, WHICH ARE PERMANENTLY INSTALLED OR MOUNTED AND USED FOR THE STORAGE OF CLASS I, II, OR III LIQUIDS, SHALL BE PROVIDED WITH A PLACARD IN ACCORDANCE WITH NFPA 704. b. PORTABLE FIRE EXTINGUISHERS WITH
A MINIMUM RATING OF 20-B:C SHALL BE PROVIDED WITHIN 30 FEET OF THE TANK.
HANDLING AT POINT OF FINAL USE - THE STORAGE, USE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AT CONSTRUCTION SITES SHALL BE IN ACCORDANCE WITH CFC SECTION 5706.2. VENTILATION SHALL BE PROVIDED FOR OPERATIONS INVOLVING THE APPLICATION OF MATERIALS CONTAINING FLAMMABLE SOLVENTS. CLASS I AND CLASS II LIQUIDS SHALL BE KEPT IN APPROVED SAFETY CONTAINERS.
LEAKAGE AND SPILLS - LEAKING VESSELS SHALL BE IMMEDIATELY REPAIRED OR TAKEN OUT OF SERVICE AND SPILLS SHALL BE CLEANED UP AND
DISPOSED OF PROPERLY. PROVISIONS FOR SITE SECURITY.
E0.1
12-02-2024
RT
NSC
RT
EL
EC
TR
IC
AL
S
YM
BO
LS
A
N D
AB
BR
EV
IA
TI
O
N S
Fi le
: C :\U se rs
\k en ne th
.h en de rs on \A pp D at a\
R oa m in g\ Au to de sk \C
AD
S ta nd ar ds
\S he et S et \e le c-bo rd er .d w t L ay ou t:
La yo ut
D at e:
J ul y
- 1
2:
p m
U se r:
ke nn et h.
he nd er so n
AB
AL
O N
E
FA
R M
D
EM
O
LI
TI
O
N W
IL
D
ER
R
AN
C
H S
TA
TE
P
AR
K
XXXXX.004
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT THE
DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
FACILITIES AND
DEVELOPMENT DIVISION
PROJECT MILESTONE:
POWER SYMBOLS:
M MOTOR OUTLET
FUSED DISCONNECT SWITCH
SWITCH XX/XX/XX = AMP SWITCH/POLES/AMP FUSE
HEAVY DUTY NON-FUSED DISCONNECT SWITCH
SWITCH XX/XX = AMP SWITCH/POLES
MOTOR STARTER
COMBINATION MOTOR STARTER
T MANUAL MOTOR STARTER WITH THERMAL OVERLOADT1
45KVA
TRANSFORMER
T TRANSFORMER
G GENERATOR
M METER
STATIONARY CIRCUIT BREAKER;
RATING AS SHOWN ON PLANS
SWITCH AND FUSE; RATING AS SHOWN ON PLANS
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
GROUND ROD IN GROUND WELL
JJ , JUNCTION BOX
PC PHOTOCELL
TC TIME CLOCK
ST SHUNT TRIP
CP CONTROL PANEL FURNISHED
WITH EQUIPMENT
240V/208V/120V SURFACE MOUNTED
PANELBOARD OR TERMINAL CABINET
240V/208V/120V FLUSH MOUNTED
PANELBOARD OR TERMINAL CABINET
480V/277V SURFACE MOUNTED
PANELBOARD OR TERMINAL CABINET
480V/277V FLUSH MOUNTED
PANELBOARD OR TERMINAL CABINET
GB WALL MOUNTED GROUND BAR
TRANSFER SWITCH
DESIGNATION SYMBOLS:
A COLUMN LINE
150NG FEEDER DESIGNATION TAG
1 KEY NOTE TAG
A
E1.1
DETAIL REFERENCE BUBBLE
DETAIL NUMBER
SHEET BEARING DETAIL
EF
MOTOR DESIGNATION TAG
A
FIXTURE DESIGNATION
UPPER CASE LETTER INDICATES LUMINAIRE TYPE
LOWER CASE LETTER INDICATES SWITCH LEG
NUMBER INDICATES CIRCUIT NUMBER (WHERE SHOWN)
a
22 NUMBER INDICATES CIRCUIT NUMBER (WHERE SHOWN)
CONDUIT SYMBOLS:
CONDUIT INSTALLED CONCEALED ABOVE CEILINGS OR IN
WALLS IN FINISHED AREAS OR EXPOSED IN UNFINISHED
AREAS
CONDUIT INSTALLED BELOW FINISHED FLOOR OR BELOW
GRADE
INDICATES CONDUIT TURNING UP
INDICATES CONDUIT TURNING DOWN
CONDUIT STUBBED OUT WITH BUSHING
CONDUIT STUBBED OUT AND CAPPED
FLEXIBLE CONDUIT WITH SINGLE POINT OF CONNECTION
AT ELECTRICAL EQUIPMENT
GROUNDING CONDUCTOR
CONDUIT HOMERUN; ROUTE TO PANELBOARD, CABINET,
OR TERMINAL BOARD INDICATED, AND TERMINATE
CONDUCTORS TO CIRCUIT OVER CURRENT PROTECTIVE
DEVICE
CONDUIT CHANGE IN ELEVATION
ABBREVIATIONS
A, AMP AMPERE
AC ALTERNATING CURRENT
ACT ABOVE COUNTER TOP
AIC AMPERE INTERRUPTING CAPACITY
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GROUND
ATS AUTOMATIC TRANSFER SWITCH
AF FRAME RATING IN AMPERES
AS SWITCH RATING IN AMPERES
AT TRIP RATING IN AMPERES
AWG AMERICAN WIRE GAUGE
AV AUDIO VISUAL
BATT BATTERY
C CONDUIT
CB CIRCUIT BREAKER
CFOI CONTRACTOR FURNISHED OWNER INSTALLED
CL CENTERLINE
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CLG CEILING
COAX COAXIAL CABLE
COMM COMMUNICATION
CU COPPER
DC DIRECT CURRENT
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DIST DISTRIBUTION
DWG DRAWING
(E) EXISTING TO REMAIN
(ER) REMOVE EXISTING
(EL) RELOCATE EXISTING
EC EMPTY CONDUIT
ELEC ELECTRICAL
ELEV ELEVATION
EMER EMERGENCY
EMT ELECTRIC METALLIC TUBING
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
(F) FUTURE
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FARA FIRE ALARM REMOTE ANNUNCIATOR
FCIP FIRE ALARM CONTROL AND INDICATING PANEL
FLA FULL LOAD AMPS
FPRP FIRE ALARM PUMP STATUS PANEL
FVNR FULL-VOLTAGE, NON-REVERSING
FVR FULL VOLTAGE, REVERSING
GFCI GROUND FAULT CIRCUIT INTERRUPTING
GFR GROUND FAULT RELAY
G, GND GROUND
GEN GENERATOR
IG ISOLATED GROUND
HID HIGH INTENSITY DISCHARGE
HOA HAND - OFF - AUTO
HP HORSEPOWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
KW KILOWATT
KWH KILOWATT-HOUR
LRC LIGHTING RELAY CABINET
MECH MECHANICAL
MCB MAIN CIRCUIT BREAKER
MCM THOUSAND CIRCULAR MILS
MH MANHOLE
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
P POLE
PB PULL BOX
PF POWER FACTOR
ø, PH PHASE
PNL PANEL
PRI PRIMARY
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
RSC RIGID STEEL CONDUIT
SEC SECONDARY, SECOND
SECUR SECURITY
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYS SYSTEM
TB, TTB TERMINAL BACKBOARD
TC TERMINAL CABINET
TEL TELEPHONE
TP TAMPER PROOF
TSTAT THERMOSTAT
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT AMPERES
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
GENERAL NOTES
1. METHODS AND MATERIALS SHALL BE IN ACCORDANCE WITH
OSHA AND ALL LOCAL, STATE AND NATIONAL CODES, LAWS
AND ORDINANCES APPLICABLE TO THE WORK UNDER THIS
CONTRACT.
2. EXISTING CONDITIONS HAVE BEEN VERIFIED THROUGH
OBSERVATIONS OF WORK WHICH ARE READILY VISIBLE
AND/OR EXISTING CONSTRUCTION DRAWINGS. NO ATTEMPT
HAS BEEN MADE TO EXPOSE CONCEALED CONSTRUCTION TO
DISRUPT BUILDING OPERATIONS AND SYSTEMS.
3. VISIT AND INVESTIGATE THE SITE BEFORE SUBMITTING A BID.
OBSERVE CONDITIONS RELATING TO WORK AND OBTAIN THE
EXACT SUCH INFORMATION AS MAY BE NECESSARY TO
PROVIDE AN INTELLIGENT AND CONCLUSIVE BID. NO
ALLOWANCE WILL BE MADE FOR ANY EXTRA EXPENSE DUE TO
THE FAILURE TO MAKE SUCH A VISIT AND INVESTIGATION.
4. LOCATIONS OF DISCONNECT SWITCHES, STARTERS, ETC. ARE
TENTATIVE. FINAL LOCATIONS SHALL SUIT SPACE AND
EQUIPMENT CONDITIONS. COORDINATE AND MAINTAIN
WORKING SPACE PER CEC.
5. MAKE ALL FINAL ELECTRICAL CONNECTIONS TO ALL
EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. THIS
SHALL INCLUDE BUT NOT BE LIMITED TO THE CONNECTION OF
ALL MECHANICAL AND OTHER EQUIPMENT WHICH IS TO BE
INSTALLED AS PART OF THIS CONSTRUCTION CONTRACT.
6. LOCATE JUNCTION AND PULL BOXES GENERALLY NOT
EXPOSED IN FINISHED SPACES. PROVIDE PULL BOXES AS
INDICATED AND WHEREVER NECESSARY TO FACILITATE
PULLING OF WIRE AND COORDINATE LOCATIONS WITH OTHER
TRADES. COVERS OF JUNCTION AND PULL BOXES SHALL BE
ACCESSIBLE FOR ALL RACEWAY RUNS. PROVIDE BOXES
EVERY 200 FEET, AND AFTER EVERY TWO RIGHT ANGLE
BENDS AND AS INDICATED. COORDINATE LOCATIONS WITH
OTHER TRADES.
7. WHERE WIRE SIZE IS LISTED ON DRAWINGS FOR REFERENCE,
CONTRACTOR SHALL MODIFY WIRE SIZE AS NEEDED TO
ALLOW FOR VOLTAGE DROP. CONTRACTOR TO FIELD VERIFY
ACTUAL LENGTHS OF CABLES DURING INSTALLATION.
8. PROVIDE SUFFICIENT ACCESS AND WORKING CLEARANCE
ABOUT THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH
CEC 110.26(A).
9. AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED AND
THE RACEWAY SHALL NOT BE USED AS THE EQUIPMENT
GROUNDING CONDUCTOR, UNLESS OTHERWISE SPECIFIED.
10. PROVIDE A DISCONNECTING MEANS WITHIN SIGHT OF EACH
MOTOR PER CEC 430.102(B).
11. FURNISH ALL LABOR, MATERIALS, EQUIPMENT & SERVICES
NECESSARY TO CONSTRUCT AND INSTALL COMPLETE &
OPERATIONAL ELECTRICAL SYSTEMS INDICATED ON THE
DRAWINGS & IN THE SPECIFICATIONS.
12. REPLACE ANY MATERIALS DAMAGED BY THE CONTRACTOR
WITH NEW EXACT REPLACEMENT MATERIALS, TO THE
SATISFACTION OF THE OWNER. CONTRACTOR SHALL BEAR
THE TOTAL COST OF SUCH REPLACEMENT.
13. ALL EQUIPMENT TO BE INSTALLED OR CONNECTED MUST BE
LISTED, LABELED, OR CERTIFIED FOR ITS USE BY NATIONALLY
RECOGNIZED TESTING AGENCY (NRTA) AS RECOGNIZED BY
THE US DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION. OWNER FURNISHED EQUIPMENT
SHALL BE LISTED, LABELED, OR CERTIFIED FOR ITS USE BY A
NATIONALLY RECOGNIZED TESTING AGENCY.
14. ALL ABANDONED CONDUIT IN ACCESSIBLE SPACES OR
SURFACE MOUNTED SHALL BE REMOVED. ABANDONED
CONDUIT IN HARDBOARD WALLS OR CEILING MUST BE
TAGGED ABANDONED AND CAPPED OFF. CUT FLUSH AND CAP
ANY ABANDONED CONDUITS STUBBING OUT OF SLAB.
15. IDENTIFY ALL CONDUCTORS AT EACH JUNCTION BOX, OUTLET
BOX, CABINET, PULL BOX, ETC. WITH VINYL CLOTH
SELF-ADHESIVE TAGS SHOWING PANEL AND CIRCUIT
NUMBERS, CIRCUIT TYPE, CONTROL WIRE NUMBERS OR
OTHER APPROPRIATE INFORMATION.
16. AT THE END OF THE PROJECT AND PRIOR TO APPROVAL OF
FINAL PAYMENT. PROVIDE REPRODUCIBLE "AS-BUILT" SET OF
DOCUMENTS AND THE DOCUMENTS SHALL BE IN AUTOCAD
FORMAT WHICH IS ACCEPTABLE TO THE OWNER.
1. VISIT THE SITE BEFORE SUBMITTING A BID TO OBSERVE
EXISTING CONDITION.
2. SCHEDULE WORK IN EXISTING BUILDINGS WITH DPR.
MINIMIZE DISRUPTION OF NORMAL OPERATIONS.
3. REMOVE WIRING DEVICES, FIXTURES, COMPONENTS,
ELECTRICAL EQUIPMENT AND BOXES NOT REQUIRED TO
REMAIN IN SERVICE IN REMODELED AREAS WHEN THIS
PROJECT IS COMPLETE.
a. REMOVE WIRE, CONDUITS AND BOXES FOR SUCH
DEVICE BACK TO SOURCE. WHERE CIRCUIT IS
INTERRUPTED BY SICH REMOVAL OF A DEVICE OR
FIXTURE FROM THAT CIRCUIT, INSTALL WIRE AND
CONDUIT AS REQUIRED TO RESTORE SERVICE TO THE
REMAINING DEVICES AND FIXTURES ON THAT CIRCUIT.
b. WHERE THIS WORK IS NOT POSSIBLE WITHOUT
DISTURBING AREAS NOT BEING RENOVATED, CONSULT
WITH THE STATE REPRESENTATIVE BEFORE
PERFORMING THE WORK.
c. LEAVE IN PLACE CONCEALED CONDUIT LOCATED IN
PARTITIONS OR HARD CEILINGS NOT TO BE
DEMOLISHED. REMOVE CONDUCTORS FROM SUCH
CONDUITS. LABEL SUCH CONDUITS AS "ABANDONED"
AT EACH END AND NOTE WHERE IT REEMERGES FROM
THE CONCEALED AREAS. CAP SUCH CONDUITS.
d. WHERE ELECTRICAL CIRCUITS, FEEDERS OR WIRING
RUNS THROUGH A SPACE TO BE DEMOLISHED,
MAINTAIN THEM. NOTIFY STATE REPRESENTATIVE OF
ANY DEFECTS IN SUCH INSTALLATIONS. REPAIR ANY
DAMAGE CAUSED BY DEMOLITION OR CONSTRUCTION
PERFORMED UNDER THIS CONTRACT.
e. WHERE EXISTING CIRCUITS, FEEDERS OR WIRING RUNS
SERVING OTHER AREAS ARE SERVED FROM SPACE TO
BE DEMOLISHED, RECONNECT THEM TO OTHER
SOURCES AS REQUIRED TO MAINTAIN SERVICE TO THE
EXISTING DEVICES.
4. WHERE DRAWINGS INDICATE EXISTING ELECTRICAL
EQUIPMENT OR DEVICES ARE TO REMAIN IN SERVICE,
RELOCATED OR REUSED, REFURBISH THEM. CLEAN SUCH
ITEMS AND NOTIFY STATE REPRESENTATIVE OF ANY
DEFECTS IN SUCH INSTALLATIONS. REPAIR ANY DAMAGE
CAUSED BY DEMOLITION OR CONSTRUCTION PERFORMED
UNDER THIS CONTRACT
5. OFFER LIGHTING FIXTURES, WIRING DEVICES,
PANELBOARDS AND EQUIPMENT TO THE STATE. TURN
ITEMS OVER TO THE STATE REPRESENTATIVE IF HE
CHOOSES TO RETAIN THESE ITEMS. REMOVE ITEMS
REJECTED BY THE STATE REPRESENTATIVE FROM THE
PROJECT SITE AND DISPOSE THEM IN A LEGAL MANNER.
6. DELIVER TO CERTIFIED RECYCLER ALL REMOVED
FLUORESCENT AND MERCURY VAPOR LAMPS. PROVIDE
PROOF OF DELIVER TO THE STATE.
GENERAL DEMOLITION NOTES
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text No. E19863
AutoCAD SHX Text
EXP. 03/31/26
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text B
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text Y
G
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W
WW
W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W W
W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W
WW
WWW
WW
WWW
WW
WW
WWW
WW
WWW
WW
WW
WWW
WW
WW
WWW
WW
WWW
WW
WW
WWW
WW
WW
WWW
WW
WWW
WW
WW
WWW
WW
WWW
(E) UTILITY XFMR
(E) METER/DISCONNECT
(E)LC1
(E)LC3
(E)LC2
M
(ER) LC1-25,27,29
(ER) LC2-13,15
(ER) LC2-5,7
1 2
M
(ER) LC1-14,16
E0.2
12-02-2024
RT
NSC
RT
EL
EC
TR
IC
AL
D
EM
O
LI
TI
O N
P
LA
N
Fi le
: C :\U se rs
\rt ak et a\
O ne
D riv e
- C al ifo rn ia
S ta te P ar ks
\D es kt op
\P R
O
JE
C
TS
\W ild er R an ch
S P\
Ab al on e
Fa rm
D em o\
_D ra w in gs \X
R
EF
\c -b as e.
dw g
La yo ut : M od el
D at e:
S ep te m be r 1
1:
p m U se r:
rta ke ta
AB
AL
O N
E
FA
R M
D
EM
O
LI
TI
O
N W
IL
D
ER
R
AN
C
H S
TA
TE
P
AR
K
XXXXX.005
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT THE
DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
FACILITIES AND
DEVELOPMENT DIVISION
PROJECT MILESTONE:
SCALE@22X341 ELECTRICAL DEMO PLAN
1:20
N
S
W E
SHEET NOTES:
DISCONNECT AND REMOVE ALL ELECTRICAL
EQUIPMENT, DEVICES AND ASSOCIATED
CIRCUITRY BACK TO SOURCE IN
DEMOLITION AREA. VERIFY EXACT
EQUIPMENT ON SITE. REFER TO SHEET E0.3
FOR EXISTING ELECTRICAL PANEL
INFORMATION. CIRCUIT TRACE AS NEEDED
FOR REMOVAL.
DISCONNECT AND REMOVE EXISTING
BLOWER AND ASSOCIATED WIRING BACK
TO SOURCE. VERIFY EXACT LOCATION AT
JOB SITE.
DISCONNECT AND REMOVE EXISTING
HEATER AND ASSOCIATED WIRING BACK TO
SOURCE. VERIFY EXACT LOCATION AT JOB
SITE.
DISCONNECT AND REMOVE EXISTING WASH
DOWN PUMP AND ASSOCIATED WIRING
BACK TO SOURCE. VERIFY EXACT
LOCATION AT JOB SITE.
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text No. E19863
AutoCAD SHX Text
EXP. 03/31/26
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text B
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text N
O
E0.3
12-02-2024
RT
NSC
RT
EL
EC
TR
IC
AL
P
AR
TI
AL
S
IN
G
LE
L
IN
E
Fi le
: C :\U se rs
\k en ne th
.h en de rs on \A pp D at a\
R oa m in g\ Au to de sk \C
AD
S ta nd ar ds
\S he et S et \e le c-bo rd er .d w t L ay ou t:
La yo ut
D at e:
J ul y
- 1
2:
p m
U se r:
ke nn et h.
he nd er so n
AB
AL
O N
E
FA
R M
D
EM
O
LI
TI
O
N W
IL
D
ER
R
AN
C
H S
TA
TE
P
AR
K
XXXXX.006
DPR ACCESS COMPLIANCE REVIEW
ACCESSIBILITY SECTION
SHEET NO.
OF
DRAWN:
REVISIONS
CHECKED:
DATE
DESIGNED:
DATE:
ACCESSIBILITY COMPLIANCE AND STATE FIRE
MARSHAL SIGNED ORIGINALS ARE ON FILE AT THE
DEPARTMENT OF PARKS AND RECREATION,
NORTHERN SERVICE CENTER
CERTIFICATION #
Reviewed by Date
FACILITIES AND
DEVELOPMENT DIVISION
PROJECT MILESTONE:
(E)T-833
M (E)
#1010047461
(E)MAIN
400A, 480V, 3PH, 3W
(E)400A 3P
UTILITY
XFMR
(E)MANUAL
TRANSFER SWITCH
(E)LC1
225A, 480V, 3PH, 3W
(E)T1
25KVA
(E)LC2
100A, 120/240V, 1PH, 3W
(ER)20A
3P
M
(ER)NURSERY
NORTH &
SOUTH
BLOWER
GENERAL NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL
CIRCUITS TO BE DISCONNECTED AND
REMOVED.
(E)LC3
100A, 120/240V, 1PH, 3W
(E) (E)
(ER)50A
2P
(ER)NORTH
HEATER
(ER)60A
2P
(ER)SOUTH
HEATER
(ER)30A
2P
(ER)WASH
DOWN PUMP
M
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text No. E19863
AutoCAD SHX Text
EXP. 03/31/26
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text B
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text Y
Y
| Wilder Ranch Abalone Farm Demo ENG CD 12-13-24 |
| G0.1 COVER SHEET |
| C0.1 DEMOLITION PLAN |
| C0.2 FIRE DEPARTMENT NOTES |
| 241202 Wilder Ranch Demo Elec |
| E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS |
| Sheets and Views |
| E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS |
| E0.2 ELECTRICAL DEMOLITION PLAN |
| Sheets and Views |
| E0.2 ELECTRICAL DEMOLITION PLAN |
| E0.3 ELECTRICAL PARTIAL SINGLE LINE |
| Sheets and Views |
| E0.3 ELECTRICAL PARTIAL SINGLE LINE |
File details come from the government source that posted it. Updated .