Addendum_1_-_Demolition_Plans.pdf

PDF 2 MB Posted

Attached to
C25715002 - Agua Puera Creek Restoration Project (Abalone Farm Demolition)
Solicitation number
0000037210
Issued by
San Mateo County, Santa Cruz County, San Mateo City, Santa Cruz City, California

About this file

This is an addendum containing demolition plans and construction documents prepared by the California Department of Parks and Recreation (DPR), Facilities and Development Division, for the Abalone Farm Demolition project at Wilder Ranch State Park in Santa Cruz County. The project involves the demolition of a former abalone farm facility, including the removal of existing deteriorating buildings, clearing of trash and rubbish from the site, disconnection and removal of electrical equipment and wiring, removal and capping of existing water lines, and removal of seawater piping systems. The demolition plans indicate that the building to be demolished is a 21,705-square-foot, two-story structure (22 feet in height) of Type V-B construction built in an unknown year on a 41,600-square-foot project area. Contractors must complete all work within 120 calendar days from the date of written notice to commence work, with the contract term running from April 1, 2026 (or upon DGS-OLS approval) through March 31, 2027. A mandatory job walk was scheduled for April 1, 2026 at 11:00 AM Pacific Time, with bid opening on April 8, 2026 at 2:00 PM Pacific Time.

The project estimate is $400,000.00, assuming minimal hazardous materials, though hazardous materials on site are believed to be minimal and will be discussed at the mandatory job walk. Contractors must hold a C-21 Demolition Contractor license and a Hazardous Substance Removal Certificate (HAZ license) to be eligible. The contractor must remove all materials from demolition work and trash from the site and dispose of them properly, including offering lighting fixtures, wiring devices, panelboards, and equipment to the state and delivering all removed fluorescent and mercury vapor lamps to a certified recycler. The work must comply with current editions of applicable California codes including the California Building Code, California Electrical Code, California Mechanical Code, California Plumbing Code, California Energy Code, California Green Building Standards, 2010 ADA Accessibility Standards, and State Fire Marshal regulations. DVBE participation has been waived for this solicitation. Questions concerning the bid solicitation must be submitted to g.g-miksicek@parks.ca.gov no later than 4:00 PM, seven days before the bid opening date.

View the file

Other files

File Type Posted
Bid.Solicitation_C25715002_v4.pdf PDF
Bid.Forms_C25715002_v3.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

20 20

WILDER RANCH

STATE PARK

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

No. C83449 Exp. 03-31-25

Fi le

: C :\U se rs

\d lo fh ol m \O ne D riv e

- C al ifo rn ia S ta te

P ar ks \D es kt op \A ut oc ad T ak e

H om e Fi le s\

Ta ke

H om e\ W ild er

R an ch S

P Ab al on e Fa rm D em o\

D ra w in gs \3

-3 6-

\S he et

S et

\G 0.

C

O

VE

R S

H

EE

T.

dw g D at e:

D ec em be r 1

9:

a m

12-2-24

DLOFHOLM

KROSE

DLOFHOLM

C O

VE

R

S H

EE

T

AB

AL

O N

E

FA

R M

D

EM

O

LI

TI

O

N W

IL

D

ER

R

AN

C

H S

TA

TE

P

AR

K

CONSTRUCTION DOCUMENTS

G0.1

CALIFORNIA DEPARTMENT OF PARKS AND RECREATION

FACILITIES AND DEVELOPMENT DIVISION

SITE ADDRESS

GENERAL NOTES

SHEET INDEX

LOCATION MAP

N

S

W E

BUILDING CODE REVIEW

1. OCCUPANCY CLASSIFICATION AND USE U

2. BUILDING CONSTRUCTION TYPE V-B

3. NUMBER OF STORIES 2

4. ACTUAL BUILDING HEIGHT 22 FT

5. BUILDING AREA IN SQUARE FEET 21705 SQ FT

6. AREA OF PROJECT IN SQUARE FEET 41600 SQ FT

7. SEPERATED OR NON-SEPERATED USE NS

8. ALLOWABLE AREA PER C.B.C. 5500 SQ FT

9. AREA INCREASES NONE

10. HEIGHT INCREASES NONE

11. FIRE SPRINKLERS NO

TYPE: (WET, DRY, PRE-ACTION OR DELUGE)

12. FIRE ALARM NO

TYPE: (MANUAL, AUTOMATIC, ETC)

13. OTHER FIRE PROTECTION SYSTEMS, IF ANY NO

14. SMOKE CONTROL SYSTEM NO

15. OCCUPANT LOAD FOR ENTIRE BUILDING N/A

AND EACH FLOOR

16. YEAR BUILDING WAS CONSTRUCTED UNKNOWN

17. IN A HIGH FIRE HAZARD SEVERITY ZONE? NO

DEFERRED SUBMITTALS

SCOPE OF WORK

PREPARED BY

SYMBOLS LEGEND

STATE OF CALIFORNIA

DEPARTMENT OF PARKS AND RECREATION

FACILITIES AND DEVELOPMENT DIVISION

NORTHERN SERVICE CENTER

2241 HARVARD ST, SUITE 200

SACRAMENTO, CA 95815

AASHTO AMERICAN ASSOCIATION OF

STATE HIGHWAY AND

TRANSPORTATION OFFICIALS

AB AGGREGATE BASE

APPROX. APPROXIMATELY

CBC CALIFORNIA BUILDING CODE

COMP COMPACTION

CONC CONCRETE

CONT CONTINUOUS

DIA DIAMETER

E EXISTING

EA EACH

FL FLOWLINE

FT FOOT

GB GRADE BREAK

ID INNER DIAMETER

IN INCH

INC INCORPORATED

LB POUND

LBS POUNDS

LG LONG

MAX MAXIMUM

NOM NOMINAL

OC ON CENTER

PCC PORTLAND CEMENT CONCRETE

PED PEDESTRIAN

PSF POUNDS PER SQUARE FOOT

REL RELATIVE

S STRUCTURAL

S/N SERIAL NUMBER

SF SQUARE FEET

SFM SEWER FORCE MAIN

SPEC SPECIFICATIONS

SS SANITARY SEWER

T TELEPHONE

TYP TYPICAL

W/ WITH

ABBREVIATIONS

DIMENSION LINE

FACE OF MATERIAL

DETAIL NUMBER1

SHEET NUMBER

REVISION

NUMBER

DIMENSION LINE

CENTER LINE

A1

SECTION NUMBER

SHEET NUMBER

A A1

X'-X"

X'-X"

CL

VICINITY MAP

N

S

W E

1- ALL MATERIALS SHOWN OR NOTED ON THE PLANS ARE NEW

UNLESS CALLED OUT OTHERWISE.

2- THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL

EXISTING CONDITIONS SHOWN OR DIMENSIONED HERE. ANY

DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF

THE STATE REPRESENTATIVE FOR RESOLUTION BEFORE

PROCEEDING WITH THAT PORTION OF THE WORK.

3- ALL WORK SHALL COMPLY WITH THE CURRENT EDITION OF

THE FOLLOWING LISTED CODES, AND ALL OTHERS HAVING

JURISDICTION OVER THE WORK.

TITLE 19, CCR, PUBLIC SAFETY, SFM REGULATIONS.

2022 CA ADMINISTRATIVE CODE TITLE 24, PT 1.

2022 CA BUILDLING CODE (CBC) TITLE 24, PT 2.

2022 CA ELECTRICAL CODE (CEC) TITLE 24, PT 3.

2022 CA MECHANICAL CODE (CMC) TITLE 24, PT 4

2022 CA PLUMBING CODE (CPC) TITLE 24, PT 5.

2022 CA ENERGY CODE CCR TITLE 24, PT 6.

2022 CA GREEN BUILDING STANDARDS TITLE 24, PT 11.

2022 CA REFERENCED STANDARDS TITLE 24, PT 12.

2010 ADA STANDARD FOR ACCESSIBLE DESIGN.

THE SECRETARY OF THE INTERIOR'S STANDARDS FOR THE

TREATMENT OF HISTORIC PROPERTIES.

4- CONDUCT ALL WORK IN ACCORDANCE WITH THE LATEST

SAFETY RULES AND REGULATIONS OF ALL AUTHORITIES AND

AGENCIES HAVING JURISDICTION OVER THE WORK.

5- ALL WORK SHALL BE IN ACCORDANCE WITH THE

CONSTRUCTION DOCUMENTS. WHERE DETAILED

INFORMATION OR CLARIFICATION IS REQUIRED, THE MATTER

SHALL BE REFERRED TO THE STATE REPRESENTATIVE FOR

WRITTEN RESOLUTION.

6- THE CONTRACTOR SHALL NOT SCALE THE DRAWINGS, BUT

SHALL RELY ONLY ON THE WRITTEN DIMENSIONS GIVEN. IF A

DISCREPANCY OCCURS OR NO DIMENSION IS GIVEN, THE

CONTRACTOR SHALL NOTIFY THE STATE REPRESENTATIVE

FOR WRITTEN CLARIFICATION BEFORE PROCEEDING WITH

THAT PORTION OF THE WORK.

7. COMPLIANCE WITH ADA REGULATIONS FOR SLOPES STATED

ON THE PLANS WILL BE VERIFIED BY THE STATE'S

REPRESENTATIVE UTILIZING A 24 INCH DIGITAL LEVEL. THE 24

INCH DIGITAL LEVEL WILL BE SUPPLIED BY THE STATE AND

WILL BE CALIBRATED BY THE STATE'S REPRESENTATIVE

PRIOR TO THE TAKING OF ANY MEASUREMENTS.

MEASUREMENTS WILL BE TAKEN IN MULTIPLE DIRECTIONS

WITH THE 24” DIGITAL LEVEL TO VERIFY COMPLIANCE WITH

SLOPES SPECIFIED ON THE PLANS. WORK THAT DOES NOT

MEET THE REQUIREMENTS SHALL BE CONSIDERED

NON-COMPLIANT AND WILL NOT BE ACCEPTED BY THE STATE.

ANY AREA WHICH IS NON-COMPLIANT SHALL BE REMOVED

AND REPLACED AT THE CONTRACTOR'S EXPENSE.

ABALONE FARM DEMOLITION

WILDER RANCH STATE PARK

CSFM # 24-N-3400-C-NW

SHEET INDEX

PAGE SHEET TITLE SHEET

001 COVER SHEET G0.1

002 DEMOLITION PLAN C0.1

003 FIRE DEPARTMENT NOTES C0.2

245 DAVENPORT LANDING ROAD

DAVENPORT, CA 95017

WILDER RANCH

STATE PARK

DEMOLISH EXISTING DETERIORATING BUILDINGS. CLEAR EXISTING SITE OF TRASH/RUBBISH.

REMOVE AND CAP EXISTING WATER LINE. DISCONNECT AND REMOVE ELECTRICAL EQUIPMENT

AND WIRING.

004 ELECTRICAL SYMBOLS AND

ABBREVIATIONS

E0.1

005 ELECTRICAL DEMOLITION PLAN E0.2

006 ELECTRICAL PARTIAL SINGLE

LINE

E0.3

11-26-24SFM BACKCHECK

AutoCAD SHX Text Merced

AutoCAD SHX Text Eureka

AutoCAD SHX Text Santa Cruz

AutoCAD SHX Text Madera

AutoCAD SHX Text Hollister

AutoCAD SHX Text Salinas

AutoCAD SHX Text Fresno

AutoCAD SHX Text Visalia

AutoCAD SHX Text Hanford

AutoCAD SHX Text San Luis

AutoCAD SHX Text Obispo

AutoCAD SHX Text Bakersfield

AutoCAD SHX Text Santa Barbara

AutoCAD SHX Text Ventura

AutoCAD SHX Text Independence

AutoCAD SHX Text Susanville

AutoCAD SHX Text Quincy

AutoCAD SHX Text Downieville

AutoCAD SHX Text Oroville

AutoCAD SHX Text Willows

AutoCAD SHX Text Red Bluff

AutoCAD SHX Text Redding

AutoCAD SHX Text Weaverville

AutoCAD SHX Text Colusa

AutoCAD SHX Text Nevada City

AutoCAD SHX Text Marysville

AutoCAD SHX Text Auburn

AutoCAD SHX Text Santa Rosa

AutoCAD SHX Text Napa

AutoCAD SHX Text Fairfield

AutoCAD SHX Text Sacramento

AutoCAD SHX Text Woodland

AutoCAD SHX Text Placerville

AutoCAD SHX Text Bridgeport

AutoCAD SHX Text Markleeville

AutoCAD SHX Text San Andreas

AutoCAD SHX Text Jackson

AutoCAD SHX Text Sonora

AutoCAD SHX Text Stockton

AutoCAD SHX Text Mariposa

AutoCAD SHX Text Modesto

AutoCAD SHX Text Oakland

AutoCAD SHX Text Martinez

AutoCAD SHX Text Redwood City

AutoCAD SHX Text San Francisco

AutoCAD SHX Text San Rafael

AutoCAD SHX Text San Jose

AutoCAD SHX Text Ukiah

AutoCAD SHX Text Lakeport

AutoCAD SHX Text Yuba City

AutoCAD SHX Text Merced

AutoCAD SHX Text Placerville

AutoCAD SHX Text Woodland

AutoCAD SHX Text Sacramento

AutoCAD SHX Text Santa Rosa

AutoCAD SHX Text Napa

AutoCAD SHX Text Jackson

AutoCAD SHX Text Fairfield

AutoCAD SHX Text Martinez

AutoCAD SHX Text San Andreas

AutoCAD SHX Text Stockton

AutoCAD SHX Text San Rafael

AutoCAD SHX Text San Francisco

AutoCAD SHX Text Oakland

AutoCAD SHX Text Sonora

AutoCAD SHX Text Modesto

AutoCAD SHX Text Redwood City

AutoCAD SHX Text San Jose

AutoCAD SHX Text Santa Cruz

AutoCAD SHX Text Hollister

AutoCAD SHX Text Salinas

RW

RW

RW

RW

RW

RW

RW

RW

FW

FW

FW

W

W W W

W W

BUILDING TO BE DEMOLISHED

APPROXIMATE

PROPERTY LINE

BUILDINGS TO REMAIN, TYP.

BUILDING TO BE DEMOLISHED

POLY TANKS TO BE REMOVED

GENERAL AREA OF

TRASH TO BE

REMOVED, TYP.

NOTES:

1. PROPERTY BOUNDARY LINE SHOWN IS APPROXIMATED FROM LEASE EXHIBITS. ACTUAL PROPERTY

BOUNDARY LINE WILL NEED TO BE ESTABLISHED BY PROFESSIONAL LAND SURVEYOR.

2. UNDERGROUND WET AND DRY UTILITIES ARE REPRESENTED IN THEIR APPROXIMATE LOCATION BASED ON

RECORD DRAWINGS, CONVERSATIONS WITH FIELD STAFF, AND TOPOGRAPHIC SURVEY. ENGINEER MAKES NO GUARANTEE OF ACCURACY. CONTRACTOR TO FIELD VERIFY AND NOTIFY ENGINEER OF ANY DISCREPANCIES.

3. ALL MATERIALS FROM DEMOLITION WORK AND TRASH WILL BE REMOVED AND DISPOSED OF BY CONTRACTOR.

(E) CONCRETE DRAINAGE DITCH TO REMAIN, TYP.

(E) WATER LINE TO BE CAPPED

AT THE STREET

WOODEN DECK AND STAIRS

DOWN TO LOWER LEVEL

GENERAL AREA OF

TRASH TO BE

REMOVED, TYP.

REMOVE PVC SEA WATER

LINES TO APPROX. THIS

POINT. EXACT LOCATION

TO BE DETERMINED BY

STATES REP.

PVC PIPES FOR SEAWATER

TO BE REMOVED

(E) FIRE HYDRANT

(E) FIRE HYDRANT

ASPHALT ROAD

LEGEND

BUILDINGS TO BE DEMOLISHED AND DISPOSED OF

EXISTING WATERLINE TO REMAIN

EXISTING WATERLINE TO BE REMOVED

EXISTING FIRE WATER LINE TO REMAIN

EXISTING CONCRETE DRAINAGE DITCH TO BE REMOVED

AREA OF GENERAL TRASH TO BE REMOVED

APPROXIMATE PROPERTY BOUNDARY

EXISTING SEAWATER PIPING TO BE REMOVED

EXISTING SEWATERR PIPING TO REMAIN

W

W

FW

RW

RW

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

No. C83449 Exp. 03-31-25

C0.1

12-2-24

DLOFHOLM

KROSE

DLOFHOLM

D

EM

O

LI

TI

O

N P

LA

N

Fi le

: C :\U se rs

\d lo fh ol m \O ne D riv e

- C al ifo rn ia S ta te

P ar ks \D es kt op \A ut oc ad T ak e

H om e Fi le s\

Ta ke

H om e\ W ild er

R an ch S

P Ab al on e Fa rm D em o\

D ra w in gs \3

-3 6-

\C iv il\

C 0.

D

EM

O

LI

TI

O N

P

LA

N .d w g

D at e:

D ec em be r 1

9:

a m

AB

AL

O N

E

FA

R M

D

EM

O

LI

TI

O

N W

IL

D

ER

R

AN

C

H S

TA

TE

P

AR

K

CONSTRUCTION DOCUMENTS

1 11-26-24SFM BACKCHECK

Fence to be removed and cut at baseAccess Pt #1

Access Pt #2

Alberto.Bonilla Highlight

Alberto.Bonilla Line

Alberto.Bonilla Line

Alberto.Bonilla Line

Alberto.Bonilla Line

FW

FW

FW 22.00'

FIRE ACCESS ROUTE

FIRE HYDRANT

FIRE HYDRANT

DAVENPORT LANDING RD

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

No. C83449 Exp. 03-31-25

Fi le

: C :\U se rs

\d lo fh ol m \O ne D riv e

- C al ifo rn ia S ta te

P ar ks \D es kt op \A ut oc ad T ak e

H om e Fi le s\

Ta ke

H om e\ W ild er

R an ch S

P Ab al on e Fa rm D em o\

D ra w in gs \3

-3 6-

\C iv il\

C 0.

FI

R E

D

EP

AR

TM

EN

T

N O

TE

S.

dw g

D at e:

D ec em be r 1

9:

a m

#####.003

12-2-24

DLOFHOLM

KROSE

DLOFHOLM

FI

R

E D

EP

AR

TM

EN

T N

O

TE

S

AB

AL

O N

E

FA

R M

D

EM

O

LI

TI

O

N W

IL

D

ER

R

AN

C

H S

TA

TE

P

AR

K

CONSTRUCTION DOCUMENTS

C0.2

FIRE SAFETY PLAN - CONSTRUCTION

1. NAME AND CONTACT INFORMATION OF SITE SAFETY DIRECTOR:

JACOB BENTLEY

DISTRICT MAINTENANCE CHIEF

CALIFORNIA STATE PARKS

SANTA CRUZ DISTRICT

(831)251-2884

2. DOCUMENTATION OF THE TRAINING OF THE SITE SAFETY DIRECTOR AND FIRE WATCH PERSONNEL:

· PROJECT MANAGEMENT TRAINING

3. PROCEDURES FOR REPORTING EMERGENCIES:

REPORT ALL EMERGENCIES TO THE SITE SAFETY DIRECTOR, DISTRICT MAINTENANCE CHIEF - JACOB BENTLEY, AND THE LOCAL FIRE DEPARTMENT

(SANTA CRUZ COUNTY FIRE DEPARTMENT/CAL-FIRE).

4. FIRE DEPARTMENT VEHICLE ACCESS ROUTES:

SEE MAP ON PLANS.

CONSTRUCTION SITE SHALL BE READILY ACCESSIBLE BY FIRE DEPARTMENT APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER DRIVING SURFACE OF NOT LESS THAN 20 FEET UNOBSTRUCTED WIDTH HAVING A MINIMUM 13'-6" VERTICAL CLEARANCE.

5. LOCATION OF FIRE PROTECTION EQUIPMENT, INCLUDING PORTABLE FIRE EXTINGUISHERS, STANDPIPES, FIRE DEPARTMENT CONNECTIONS, AND FIRE

HYDRANTS:

SEE MAP ON PLAN.

ALL VEHICLES AND HEAVY EQUIPMENT SHALL HAVE A FIRE EXTINGUISHER ONBOARD.

6. SMOKING AND COOKING POLICIES, DESIGNATED AREAS TO BE USED WHERE APPROVED, AND SIGNAGE LOCATIONS IN ACCORDANCE WITH SECTION 3305.8.:

N/A (NO SMOKING OR COOKING ALLOWED ON PREMISES).

7. LOCATION AND SAFETY CONSIDERATIONS FOR TEMPORARY HEATING EQUIPMENT:

N/A (NO TEMPORARY HEATING EQUIPMENT FOR THIS PROJECT)

8. HOT WORK PERMIT PLAN:

N/A (NO HOT WORK FOR THIS PROJECT)

9. PLANS FOR CONTROL OF COMBUSTIBLE WASTE MATERIAL:

ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, SUCH AS WOOD, PLASTIC, INSULATION, PAINTS AND VARNISHES, ADHESIVES AND SEALANTS, DUST, AND DEBRIS SHALL BE REMOVED FROM THE WORK SITE AT THE END OF EACH WORK SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. MATERIALS SUSCEPTIBLE TO SPONTANEOUS IGNITION, SUCH AS OILY RAGS, SHALL BE STORED IN A LISTED DISPOSAL CONTAINER.

YARD STORAGE OF EQUIPMENT TO BE INSTALLED OR COMBUSTIBLE CONSTRUCTION MATERIALS SHALL NOT BE STORED CLOSER THAN 30 FEET FROM

ANY STRUCTURE UNDER CONSTRUCTION OR ALTERATION.

10. LOCATIONS AND METHODS FOR STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AND OTHER HAZARDOUS MATERIALS:

STORAGE - FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE AREAS SHALL BE MAINTAINED CLEAR OF COMBUSTIBLE VEGETATION AND WASTE MATERIALS. SUCH STORAGE AREAS SHALL NOT BE USED FOR THE STORAGE OF COMBUSTIBLE MATERIALS. SMOKING AND OTHER SOURCES OF IGNITION SHALL BE PROHIBITED IN AREAS WHERE FLAMMABLE AND COMBUSTIBLE LIQUIDS ARE STORED OR USED. STORAGE OF CLASS I AND CLASS II LIQUIDS SHALL NOT EXCEED 60 GALLONS WITHIN 50 FEET OF THE STRUCTURE UNLESS APPROVED BY SDFD.

TANKS - TANKS AND CONTAINERS FOR THE STORAGE OF LIQUIDS ABOVE GROUND SHALL BE CONSPICUOUSLY MARKED WITH THE NAME OF THE PRODUCT THAT THEY CONTAIN AND THE WORDS: "FLAMMABLE--KEEP FIRE AND FLAME AWAY." TANKS SHALL BEAR THE ADDITIONAL MARKING: "KEEP 50 FEET FROM BUILDINGS." a. TANKS MORE THAN 100 GALLONS IN CAPACITY, WHICH ARE PERMANENTLY INSTALLED OR MOUNTED AND USED FOR THE STORAGE OF CLASS I, II, OR III LIQUIDS, SHALL BE PROVIDED WITH A PLACARD IN ACCORDANCE WITH NFPA 704. b. PORTABLE FIRE EXTINGUISHERS WITH

A MINIMUM RATING OF 20-B:C SHALL BE PROVIDED WITHIN 30 FEET OF THE TANK.

HANDLING AT POINT OF FINAL USE - THE STORAGE, USE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AT CONSTRUCTION SITES SHALL BE IN ACCORDANCE WITH CFC SECTION 5706.2. VENTILATION SHALL BE PROVIDED FOR OPERATIONS INVOLVING THE APPLICATION OF MATERIALS CONTAINING FLAMMABLE SOLVENTS. CLASS I AND CLASS II LIQUIDS SHALL BE KEPT IN APPROVED SAFETY CONTAINERS.

LEAKAGE AND SPILLS - LEAKING VESSELS SHALL BE IMMEDIATELY REPAIRED OR TAKEN OUT OF SERVICE AND SPILLS SHALL BE CLEANED UP AND

DISPOSED OF PROPERLY. PROVISIONS FOR SITE SECURITY.

E0.1

12-02-2024

RT

NSC

RT

EL

EC

TR

IC

AL

S

YM

BO

LS

A

N D

AB

BR

EV

IA

TI

O

N S

Fi le

: C :\U se rs

\k en ne th

.h en de rs on \A pp D at a\

R oa m in g\ Au to de sk \C

AD

S ta nd ar ds

\S he et S et \e le c-bo rd er .d w t L ay ou t:

La yo ut

D at e:

J ul y

- 1

2:

p m

U se r:

ke nn et h.

he nd er so n

AB

AL

O N

E

FA

R M

D

EM

O

LI

TI

O

N W

IL

D

ER

R

AN

C

H S

TA

TE

P

AR

K

XXXXX.004

DPR ACCESS COMPLIANCE REVIEW

ACCESSIBILITY SECTION

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

ACCESSIBILITY COMPLIANCE AND STATE FIRE

MARSHAL SIGNED ORIGINALS ARE ON FILE AT THE

DEPARTMENT OF PARKS AND RECREATION,

NORTHERN SERVICE CENTER

CERTIFICATION #

Reviewed by Date

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

POWER SYMBOLS:

M MOTOR OUTLET

FUSED DISCONNECT SWITCH

SWITCH XX/XX/XX = AMP SWITCH/POLES/AMP FUSE

HEAVY DUTY NON-FUSED DISCONNECT SWITCH

SWITCH XX/XX = AMP SWITCH/POLES

MOTOR STARTER

COMBINATION MOTOR STARTER

T MANUAL MOTOR STARTER WITH THERMAL OVERLOADT1

45KVA

TRANSFORMER

T TRANSFORMER

G GENERATOR

M METER

STATIONARY CIRCUIT BREAKER;

RATING AS SHOWN ON PLANS

SWITCH AND FUSE; RATING AS SHOWN ON PLANS

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

GROUND ROD IN GROUND WELL

JJ , JUNCTION BOX

PC PHOTOCELL

TC TIME CLOCK

ST SHUNT TRIP

CP CONTROL PANEL FURNISHED

WITH EQUIPMENT

240V/208V/120V SURFACE MOUNTED

PANELBOARD OR TERMINAL CABINET

240V/208V/120V FLUSH MOUNTED

PANELBOARD OR TERMINAL CABINET

480V/277V SURFACE MOUNTED

PANELBOARD OR TERMINAL CABINET

480V/277V FLUSH MOUNTED

PANELBOARD OR TERMINAL CABINET

GB WALL MOUNTED GROUND BAR

TRANSFER SWITCH

DESIGNATION SYMBOLS:

A COLUMN LINE

150NG FEEDER DESIGNATION TAG

1 KEY NOTE TAG

A

E1.1

DETAIL REFERENCE BUBBLE

DETAIL NUMBER

SHEET BEARING DETAIL

EF

MOTOR DESIGNATION TAG

A

FIXTURE DESIGNATION

UPPER CASE LETTER INDICATES LUMINAIRE TYPE

LOWER CASE LETTER INDICATES SWITCH LEG

NUMBER INDICATES CIRCUIT NUMBER (WHERE SHOWN)

a

22 NUMBER INDICATES CIRCUIT NUMBER (WHERE SHOWN)

CONDUIT SYMBOLS:

CONDUIT INSTALLED CONCEALED ABOVE CEILINGS OR IN

WALLS IN FINISHED AREAS OR EXPOSED IN UNFINISHED

AREAS

CONDUIT INSTALLED BELOW FINISHED FLOOR OR BELOW

GRADE

INDICATES CONDUIT TURNING UP

INDICATES CONDUIT TURNING DOWN

CONDUIT STUBBED OUT WITH BUSHING

CONDUIT STUBBED OUT AND CAPPED

FLEXIBLE CONDUIT WITH SINGLE POINT OF CONNECTION

AT ELECTRICAL EQUIPMENT

GROUNDING CONDUCTOR

CONDUIT HOMERUN; ROUTE TO PANELBOARD, CABINET,

OR TERMINAL BOARD INDICATED, AND TERMINATE

CONDUCTORS TO CIRCUIT OVER CURRENT PROTECTIVE

DEVICE

CONDUIT CHANGE IN ELEVATION

ABBREVIATIONS

A, AMP AMPERE

AC ALTERNATING CURRENT

ACT ABOVE COUNTER TOP

AIC AMPERE INTERRUPTING CAPACITY

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GROUND

ATS AUTOMATIC TRANSFER SWITCH

AF FRAME RATING IN AMPERES

AS SWITCH RATING IN AMPERES

AT TRIP RATING IN AMPERES

AWG AMERICAN WIRE GAUGE

AV AUDIO VISUAL

BATT BATTERY

C CONDUIT

CB CIRCUIT BREAKER

CFOI CONTRACTOR FURNISHED OWNER INSTALLED

CL CENTERLINE

CEC CALIFORNIA ELECTRICAL CODE

CKT CIRCUIT

CLG CEILING

COAX COAXIAL CABLE

COMM COMMUNICATION

CU COPPER

DC DIRECT CURRENT

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DIST DISTRIBUTION

DWG DRAWING

(E) EXISTING TO REMAIN

(ER) REMOVE EXISTING

(EL) RELOCATE EXISTING

EC EMPTY CONDUIT

ELEC ELECTRICAL

ELEV ELEVATION

EMER EMERGENCY

EMT ELECTRIC METALLIC TUBING

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

(F) FUTURE

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

FARA FIRE ALARM REMOTE ANNUNCIATOR

FCIP FIRE ALARM CONTROL AND INDICATING PANEL

FLA FULL LOAD AMPS

FPRP FIRE ALARM PUMP STATUS PANEL

FVNR FULL-VOLTAGE, NON-REVERSING

FVR FULL VOLTAGE, REVERSING

GFCI GROUND FAULT CIRCUIT INTERRUPTING

GFR GROUND FAULT RELAY

G, GND GROUND

GEN GENERATOR

IG ISOLATED GROUND

HID HIGH INTENSITY DISCHARGE

HOA HAND - OFF - AUTO

HP HORSEPOWER

HPF HIGH POWER FACTOR

HPS HIGH PRESSURE SODIUM

KW KILOWATT

KWH KILOWATT-HOUR

LRC LIGHTING RELAY CABINET

MECH MECHANICAL

MCB MAIN CIRCUIT BREAKER

MCM THOUSAND CIRCULAR MILS

MH MANHOLE

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

P POLE

PB PULL BOX

PF POWER FACTOR

ø, PH PHASE

PNL PANEL

PRI PRIMARY

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

RSC RIGID STEEL CONDUIT

SEC SECONDARY, SECOND

SECUR SECURITY

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYS SYSTEM

TB, TTB TERMINAL BACKBOARD

TC TERMINAL CABINET

TEL TELEPHONE

TP TAMPER PROOF

TSTAT THERMOSTAT

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT AMPERES

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

WP WEATHERPROOF

XFMR TRANSFORMER

XP EXPLOSION PROOF

GENERAL NOTES

1. METHODS AND MATERIALS SHALL BE IN ACCORDANCE WITH

OSHA AND ALL LOCAL, STATE AND NATIONAL CODES, LAWS

AND ORDINANCES APPLICABLE TO THE WORK UNDER THIS

CONTRACT.

2. EXISTING CONDITIONS HAVE BEEN VERIFIED THROUGH

OBSERVATIONS OF WORK WHICH ARE READILY VISIBLE

AND/OR EXISTING CONSTRUCTION DRAWINGS. NO ATTEMPT

HAS BEEN MADE TO EXPOSE CONCEALED CONSTRUCTION TO

DISRUPT BUILDING OPERATIONS AND SYSTEMS.

3. VISIT AND INVESTIGATE THE SITE BEFORE SUBMITTING A BID.

OBSERVE CONDITIONS RELATING TO WORK AND OBTAIN THE

EXACT SUCH INFORMATION AS MAY BE NECESSARY TO

PROVIDE AN INTELLIGENT AND CONCLUSIVE BID. NO

ALLOWANCE WILL BE MADE FOR ANY EXTRA EXPENSE DUE TO

THE FAILURE TO MAKE SUCH A VISIT AND INVESTIGATION.

4. LOCATIONS OF DISCONNECT SWITCHES, STARTERS, ETC. ARE

TENTATIVE. FINAL LOCATIONS SHALL SUIT SPACE AND

EQUIPMENT CONDITIONS. COORDINATE AND MAINTAIN

WORKING SPACE PER CEC.

5. MAKE ALL FINAL ELECTRICAL CONNECTIONS TO ALL

EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. THIS

SHALL INCLUDE BUT NOT BE LIMITED TO THE CONNECTION OF

ALL MECHANICAL AND OTHER EQUIPMENT WHICH IS TO BE

INSTALLED AS PART OF THIS CONSTRUCTION CONTRACT.

6. LOCATE JUNCTION AND PULL BOXES GENERALLY NOT

EXPOSED IN FINISHED SPACES. PROVIDE PULL BOXES AS

INDICATED AND WHEREVER NECESSARY TO FACILITATE

PULLING OF WIRE AND COORDINATE LOCATIONS WITH OTHER

TRADES. COVERS OF JUNCTION AND PULL BOXES SHALL BE

ACCESSIBLE FOR ALL RACEWAY RUNS. PROVIDE BOXES

EVERY 200 FEET, AND AFTER EVERY TWO RIGHT ANGLE

BENDS AND AS INDICATED. COORDINATE LOCATIONS WITH

OTHER TRADES.

7. WHERE WIRE SIZE IS LISTED ON DRAWINGS FOR REFERENCE,

CONTRACTOR SHALL MODIFY WIRE SIZE AS NEEDED TO

ALLOW FOR VOLTAGE DROP. CONTRACTOR TO FIELD VERIFY

ACTUAL LENGTHS OF CABLES DURING INSTALLATION.

8. PROVIDE SUFFICIENT ACCESS AND WORKING CLEARANCE

ABOUT THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH

CEC 110.26(A).

9. AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED AND

THE RACEWAY SHALL NOT BE USED AS THE EQUIPMENT

GROUNDING CONDUCTOR, UNLESS OTHERWISE SPECIFIED.

10. PROVIDE A DISCONNECTING MEANS WITHIN SIGHT OF EACH

MOTOR PER CEC 430.102(B).

11. FURNISH ALL LABOR, MATERIALS, EQUIPMENT & SERVICES

NECESSARY TO CONSTRUCT AND INSTALL COMPLETE &

OPERATIONAL ELECTRICAL SYSTEMS INDICATED ON THE

DRAWINGS & IN THE SPECIFICATIONS.

12. REPLACE ANY MATERIALS DAMAGED BY THE CONTRACTOR

WITH NEW EXACT REPLACEMENT MATERIALS, TO THE

SATISFACTION OF THE OWNER. CONTRACTOR SHALL BEAR

THE TOTAL COST OF SUCH REPLACEMENT.

13. ALL EQUIPMENT TO BE INSTALLED OR CONNECTED MUST BE

LISTED, LABELED, OR CERTIFIED FOR ITS USE BY NATIONALLY

RECOGNIZED TESTING AGENCY (NRTA) AS RECOGNIZED BY

THE US DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND

HEALTH ADMINISTRATION. OWNER FURNISHED EQUIPMENT

SHALL BE LISTED, LABELED, OR CERTIFIED FOR ITS USE BY A

NATIONALLY RECOGNIZED TESTING AGENCY.

14. ALL ABANDONED CONDUIT IN ACCESSIBLE SPACES OR

SURFACE MOUNTED SHALL BE REMOVED. ABANDONED

CONDUIT IN HARDBOARD WALLS OR CEILING MUST BE

TAGGED ABANDONED AND CAPPED OFF. CUT FLUSH AND CAP

ANY ABANDONED CONDUITS STUBBING OUT OF SLAB.

15. IDENTIFY ALL CONDUCTORS AT EACH JUNCTION BOX, OUTLET

BOX, CABINET, PULL BOX, ETC. WITH VINYL CLOTH

SELF-ADHESIVE TAGS SHOWING PANEL AND CIRCUIT

NUMBERS, CIRCUIT TYPE, CONTROL WIRE NUMBERS OR

OTHER APPROPRIATE INFORMATION.

16. AT THE END OF THE PROJECT AND PRIOR TO APPROVAL OF

FINAL PAYMENT. PROVIDE REPRODUCIBLE "AS-BUILT" SET OF

DOCUMENTS AND THE DOCUMENTS SHALL BE IN AUTOCAD

FORMAT WHICH IS ACCEPTABLE TO THE OWNER.

1. VISIT THE SITE BEFORE SUBMITTING A BID TO OBSERVE

EXISTING CONDITION.

2. SCHEDULE WORK IN EXISTING BUILDINGS WITH DPR.

MINIMIZE DISRUPTION OF NORMAL OPERATIONS.

3. REMOVE WIRING DEVICES, FIXTURES, COMPONENTS,

ELECTRICAL EQUIPMENT AND BOXES NOT REQUIRED TO

REMAIN IN SERVICE IN REMODELED AREAS WHEN THIS

PROJECT IS COMPLETE.

a. REMOVE WIRE, CONDUITS AND BOXES FOR SUCH

DEVICE BACK TO SOURCE. WHERE CIRCUIT IS

INTERRUPTED BY SICH REMOVAL OF A DEVICE OR

FIXTURE FROM THAT CIRCUIT, INSTALL WIRE AND

CONDUIT AS REQUIRED TO RESTORE SERVICE TO THE

REMAINING DEVICES AND FIXTURES ON THAT CIRCUIT.

b. WHERE THIS WORK IS NOT POSSIBLE WITHOUT

DISTURBING AREAS NOT BEING RENOVATED, CONSULT

WITH THE STATE REPRESENTATIVE BEFORE

PERFORMING THE WORK.

c. LEAVE IN PLACE CONCEALED CONDUIT LOCATED IN

PARTITIONS OR HARD CEILINGS NOT TO BE

DEMOLISHED. REMOVE CONDUCTORS FROM SUCH

CONDUITS. LABEL SUCH CONDUITS AS "ABANDONED"

AT EACH END AND NOTE WHERE IT REEMERGES FROM

THE CONCEALED AREAS. CAP SUCH CONDUITS.

d. WHERE ELECTRICAL CIRCUITS, FEEDERS OR WIRING

RUNS THROUGH A SPACE TO BE DEMOLISHED,

MAINTAIN THEM. NOTIFY STATE REPRESENTATIVE OF

ANY DEFECTS IN SUCH INSTALLATIONS. REPAIR ANY

DAMAGE CAUSED BY DEMOLITION OR CONSTRUCTION

PERFORMED UNDER THIS CONTRACT.

e. WHERE EXISTING CIRCUITS, FEEDERS OR WIRING RUNS

SERVING OTHER AREAS ARE SERVED FROM SPACE TO

BE DEMOLISHED, RECONNECT THEM TO OTHER

SOURCES AS REQUIRED TO MAINTAIN SERVICE TO THE

EXISTING DEVICES.

4. WHERE DRAWINGS INDICATE EXISTING ELECTRICAL

EQUIPMENT OR DEVICES ARE TO REMAIN IN SERVICE,

RELOCATED OR REUSED, REFURBISH THEM. CLEAN SUCH

ITEMS AND NOTIFY STATE REPRESENTATIVE OF ANY

DEFECTS IN SUCH INSTALLATIONS. REPAIR ANY DAMAGE

CAUSED BY DEMOLITION OR CONSTRUCTION PERFORMED

UNDER THIS CONTRACT

5. OFFER LIGHTING FIXTURES, WIRING DEVICES,

PANELBOARDS AND EQUIPMENT TO THE STATE. TURN

ITEMS OVER TO THE STATE REPRESENTATIVE IF HE

CHOOSES TO RETAIN THESE ITEMS. REMOVE ITEMS

REJECTED BY THE STATE REPRESENTATIVE FROM THE

PROJECT SITE AND DISPOSE THEM IN A LEGAL MANNER.

6. DELIVER TO CERTIFIED RECYCLER ALL REMOVED

FLUORESCENT AND MERCURY VAPOR LAMPS. PROVIDE

PROOF OF DELIVER TO THE STATE.

GENERAL DEMOLITION NOTES

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text No. E19863

AutoCAD SHX Text

EXP. 03/31/26

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text K

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text Y

G

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

WWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWW

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W

WW

W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W W

W

W W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W

WW

WWW

WW

WWW

WW

WW

WWW

WW

WWW

WW

WW

WWW

WW

WW

WWW

WW

WWW

WW

WW

WWW

WW

WW

WWW

WW

WWW

WW

WW

WWW

WW

WWW

(E) UTILITY XFMR

(E) METER/DISCONNECT

(E)LC1

(E)LC3

(E)LC2

M

(ER) LC1-25,27,29

(ER) LC2-13,15

(ER) LC2-5,7

1 2

M

(ER) LC1-14,16

E0.2

12-02-2024

RT

NSC

RT

EL

EC

TR

IC

AL

D

EM

O

LI

TI

O N

P

LA

N

Fi le

: C :\U se rs

\rt ak et a\

O ne

D riv e

- C al ifo rn ia

S ta te P ar ks

\D es kt op

\P R

O

JE

C

TS

\W ild er R an ch

S P\

Ab al on e

Fa rm

D em o\

_D ra w in gs \X

R

EF

\c -b as e.

dw g

La yo ut : M od el

D at e:

S ep te m be r 1

1:

p m U se r:

rta ke ta

AB

AL

O N

E

FA

R M

D

EM

O

LI

TI

O

N W

IL

D

ER

R

AN

C

H S

TA

TE

P

AR

K

XXXXX.005

DPR ACCESS COMPLIANCE REVIEW

ACCESSIBILITY SECTION

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

ACCESSIBILITY COMPLIANCE AND STATE FIRE

MARSHAL SIGNED ORIGINALS ARE ON FILE AT THE

DEPARTMENT OF PARKS AND RECREATION,

NORTHERN SERVICE CENTER

CERTIFICATION #

Reviewed by Date

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

SCALE@22X341 ELECTRICAL DEMO PLAN

1:20

N

S

W E

SHEET NOTES:

DISCONNECT AND REMOVE ALL ELECTRICAL

EQUIPMENT, DEVICES AND ASSOCIATED

CIRCUITRY BACK TO SOURCE IN

DEMOLITION AREA. VERIFY EXACT

EQUIPMENT ON SITE. REFER TO SHEET E0.3

FOR EXISTING ELECTRICAL PANEL

INFORMATION. CIRCUIT TRACE AS NEEDED

FOR REMOVAL.

DISCONNECT AND REMOVE EXISTING

BLOWER AND ASSOCIATED WIRING BACK

TO SOURCE. VERIFY EXACT LOCATION AT

JOB SITE.

DISCONNECT AND REMOVE EXISTING

HEATER AND ASSOCIATED WIRING BACK TO

SOURCE. VERIFY EXACT LOCATION AT JOB

SITE.

DISCONNECT AND REMOVE EXISTING WASH

DOWN PUMP AND ASSOCIATED WIRING

BACK TO SOURCE. VERIFY EXACT

LOCATION AT JOB SITE.

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text No. E19863

AutoCAD SHX Text

EXP. 03/31/26

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text K

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text N

O

E0.3

12-02-2024

RT

NSC

RT

EL

EC

TR

IC

AL

P

AR

TI

AL

S

IN

G

LE

L

IN

E

Fi le

: C :\U se rs

\k en ne th

.h en de rs on \A pp D at a\

R oa m in g\ Au to de sk \C

AD

S ta nd ar ds

\S he et S et \e le c-bo rd er .d w t L ay ou t:

La yo ut

D at e:

J ul y

- 1

2:

p m

U se r:

ke nn et h.

he nd er so n

AB

AL

O N

E

FA

R M

D

EM

O

LI

TI

O

N W

IL

D

ER

R

AN

C

H S

TA

TE

P

AR

K

XXXXX.006

DPR ACCESS COMPLIANCE REVIEW

ACCESSIBILITY SECTION

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

ACCESSIBILITY COMPLIANCE AND STATE FIRE

MARSHAL SIGNED ORIGINALS ARE ON FILE AT THE

DEPARTMENT OF PARKS AND RECREATION,

NORTHERN SERVICE CENTER

CERTIFICATION #

Reviewed by Date

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

(E)T-833

M (E)

#1010047461

(E)MAIN

400A, 480V, 3PH, 3W

(E)400A 3P

UTILITY

XFMR

(E)MANUAL

TRANSFER SWITCH

(E)LC1

225A, 480V, 3PH, 3W

(E)T1

25KVA

(E)LC2

100A, 120/240V, 1PH, 3W

(ER)20A

3P

M

(ER)NURSERY

NORTH &

SOUTH

BLOWER

GENERAL NOTES:

1. CONTRACTOR TO FIELD VERIFY ALL

CIRCUITS TO BE DISCONNECTED AND

REMOVED.

(E)LC3

100A, 120/240V, 1PH, 3W

(E) (E)

(ER)50A

2P

(ER)NORTH

HEATER

(ER)60A

2P

(ER)SOUTH

HEATER

(ER)30A

2P

(ER)WASH

DOWN PUMP

M

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text No. E19863

AutoCAD SHX Text

EXP. 03/31/26

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text K

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text Y

Y

Wilder Ranch Abalone Farm Demo ENG CD 12-13-24
G0.1 COVER SHEET
C0.1 DEMOLITION PLAN
C0.2 FIRE DEPARTMENT NOTES
241202 Wilder Ranch Demo Elec
E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS
Sheets and Views
E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E0.2 ELECTRICAL DEMOLITION PLAN
Sheets and Views
E0.2 ELECTRICAL DEMOLITION PLAN
E0.3 ELECTRICAL PARTIAL SINGLE LINE
Sheets and Views
E0.3 ELECTRICAL PARTIAL SINGLE LINE

File details come from the government source that posted it. Updated .