Addendum 1 - Bid Set - Extrusion Utilities.pdf
PDF 8 MB Posted
- Solicitation number
- 98-20250072
- Issued by
- Gaston County, North Carolina
About this file
This document is a comprehensive set of engineering and construction drawings for the Machine Connections FIC Extrusion project at Gaston College, located at 7224 Wilkinson Blvd. in Belmont, North Carolina. The project is being designed by AeroRaq Engineering Inc., a Charlotte-based engineering services firm. The drawings cover multiple disciplines including mechanical, plumbing, electrical, and lighting systems for what appears to be a manufacturing or research facility focused on fiber extrusion technologies. The documents are dated June 1, 2025, with a project number of 01-2025007, and include detailed plans for equipment installations, power distribution, HVAC systems, compressed air lines, and electrical infrastructure.
The drawings provide extensive technical specifications for electrical panels, transformers, power distribution, conduit routing, and equipment connections across various voltage systems (120/208V and 480V). The electrical design includes multiple panel boards (DNH3, DNH4, DNL3, etc.), transformers ranging from 45 to 75 kVA, and detailed circuit mapping for different areas including the Reactor, Small Spin, Large Spin, and Chemical Storage areas. The mechanical plans show precise locations for equipment installations, ductwork, and rooftop mechanical units, while the plumbing drawings outline compressed air and water line configurations. The overall design emphasizes compliance with North Carolina building and electrical codes, with specific attention to installation requirements, support structures, and system integration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FIC Extrusion - Gaston College v2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Schedule of Drawings A0.1 Cover Sheet A0.2 Appendix B M0.1 Mechanical Schedules M1.1 Mechanical Plan M2.1 Mechanical Details P0.1 Plumbing Schedules P1.1 Plumbing Plan P1.2 Plumbing Plan E0.1 Electrical Schedules E1.1 Electrical Plan E1.2 Electrical Plan E1.3 Electrical Plan E1.4 Electrical Plan E2.1 Lighting Plan E3.1 Electrical Details E3.2 Electrical Details
Abbrevations and References NFPA - National Fire Protection Agency SMANCA - Sheet Metal & Air Conditioning Contractor's National Association NCFG - North Carolina Fuel Gas Code NCMC - North Carolina Mechanical Code NEC - National Electric Code NEMA - National Electrical Manufacturers Association ANSI - American National Standards Institute UL - Underwriters Laboratory
AFF - Above Finished Floor AFG - Above Finished Grade AFUE - Annual Fuel Utilization Effiency APPROX - Approximate ALUM - Aluminum BFF - Below Finished Floor BFG - Below Finished Grade BHP - Brake Horse Power CAP. - Capacity CFM - Cubic Feet per Minute CONN. - Connection COORD. - Coordinate CU. FT. - Cubic Foot DB - Dry Bulb DISTR. - Distribution DWG. - Drawing DX - Direct Expansion ETR - Existing to remain ESP - External Static Pressure EQUIV. - Equivalent EXH. - Exhaust FPM - Feet per Minute GALV. - Galvanized Hp - Horse Power KW - Kilowatt MCA - Minimum Circuit Ampacity MIN. - Minimum NC - Normally Closed NO - Normally Open NPSH - Net Positive Suction Head O.A. - Outside Air Occup. - Occupancy PSI - Pounds per Square Inch QTY. Quantity RECT. - Rectangular RPM - Revolutions per Minute SCH. - Schedule SEER - Seasonal Energy Efficiency Rating SENS. - Sensible SPEC. - Specification Sq ft. - Square Feet TYP. - Typical Installation / Materials UON - Unless Otherwise Noted VAV - Variable Air Volume VRV - Variable Refrigerant Volume WB - Wet Bulb
Gaston College
Belmont, North Carolina Machine Connections FIC Extrusion
Site Address: 7224 Wilkinson Blvd. Belmont NC 28012 General Requirements & Notes:
1. All work shall comply with the North Carolina Building Code
2. All mechanical work shall be done by trained and qualified technicians
3. All electrical work shall be done by trained and qualified electricians
4. Install mechanical equipment in accordance with manufacturers recommendations
5. Drawings and documents are diagrammatic and are intended to convey scope and general arrangements unless otherwise indicated
6. Contractor is responsible for surveying site conditions and determining the best route for equipment, wiring, ducting, piping and conduits
7. Contractor will notify engineer immediately if an issue arises that cannot be immediately resolved
8. Install equipment to allow manufacturers recommended clearances
9. Provide a 48 hour notice before any power or gas shutdown
10. Seal Penetrations through floors or fire walls to maintain the integrity of the fire and acoustic ratings of the walls and floors.
11. All trades shall coordinate their work with the other disciplines to maintain schedule integrity.
12. Submittals drawings and paperwork will be approved by engineer before equipment and materials will be ordered
13. Not all abbreviations may apply to this project.
Design Complies with the 2018 North Carolina Building Code
Scope of Work This project involves the addition of electrical and plumbing utilities to industrial training equipment. The addition of HVAC equipment to provide fume removal is also included.
Location Map
G0.1
COPYRIGHT
Project No:
01-2025007
Scale: N/A
Date: 06-01-2025
Title: Cover Sheet
M a c h i n e
C o n n e c t i o n s
F
I C
E x t r u s i o n
G a s t o n
C o l l e g e
W i l k i n s o n
B l v d
B e l m o n t
N o r t h a r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is L ak e
Pa rk w ay
, S ui te C
6-
C ha rl ot te
, N or th C ar ol in a
Fi rm L ic en se
C -3
Ph on e:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
09/08/2025
G0.2
COPYRIGHT
Project No:
01-2025007
Scale: N/A
Date: 06-01-2025
Title: Appendix B
M a c h i n e
C o n n e c t i o t r u s i o n
G a s t o n
C o l l e g e l k i n s o n
B l v d
B e l m o n t
N o r r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is L ak e
Pa rk w ay
, S ui te C
6-
C ha rl ot te
, N or th C ar ol in a
Fi rm L ic en se
C -3
Ph on e:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written
Rect. Diffuser, 4
Way Distr.
Rect. Diffuser, 3
Way Distr.
Rect. Diffuser, 2
Way Distr.
Rect. Diffuser, 1
Way Distr.
Round Diffuser
Return Air Grille
Exhaust Grille or
Exhaust Fan
Register and Grille, adjustable
Register, Diffuser &
Grille, Call out
Neck Size
Air Volume Flow
Spec. Type
Legends, Symbols & Icons
10 x 12
Rect. Rigid Duct
10 Dia
Round Rigid Duct
Rigid Duct Transition
10 x 12
Lined Rect. Rigid Duct
Rect. Corner
Diffuser, 2 Way
Distr.
Flexible Duct
Vertical Duct Conn.
Normal to viewing plane
Stand. Rect. Take-off w. Vol. Damper
Rect. to Round Take-off
Round. to Round Take-off
90 deg. Turn Elbow w.
Turning Vanes
Smooth Turn Elbow
Raduis = 1.5 Duct Depth
Manual Damper
S D
Smoke Damper
F D
Fire Damper
D D
Duct Smoke Detector
T,1
Thermostat
Spec. Type
TS,1
Temperature Sensor
Spec. Type
PS,1
Pressure Sensor
Spec. Type
HS,1
Humidity Sensor
Spec. Type
BK,1
Boiler Kill Switch
Spec. Type
DH
Duct Heater
VAV,
A1
Variable Air Volume
Box, Static or Fan
Spec. Type
FS,1
Flow Switch
Spec. Type
Gate Valve
Ball Valve
Butterfly Valve
Check Valve
Actuated Valve
Pressure Reducer
Pressure Safety
Valve (Relief)
Strainer
Line Reducer
HWS
Hot Water Supply
HWR
Hot Water Return
CHWS
Chilled Water Supply
CHWR
Chilled Water Return
COND
Condensate Line
GAS
Gas Supply Line
Angle Valve
Three Way Valve
Connect to existing at this point
Remove to this point
Key Note Icon
A , 10" x 12"
400 CFM 1
Accessories:
1. Roof mounted
2. Coating Permatector
3. NEMA 3R housing
4. UL Listed
5. VFD Rated
Fan Schedule
Plan ID Service Manufacturer Model #
Air Flow
(CFM)
ESP
(in w.c.)
Fan Speed
(rpm)
Motor Hp /
Watts
Voltage/
Phase
Controller Accessories Comments
F-1 Exhaust Greenheck FJ-12, Series 300
1000 1.0 1770
HP
480 V/ 3ɸ
Switch 1,2,3,4,5 1,2,3,4
F-2 Exhaust Greenheck FJ-4, Series 300
500 1.0 1770
HP
480 V/ 3ɸ
Switch 1,2,3,4,5 1,2,3,4
F-3 Exhaust Greenheck FJ-12, Series 300
1000 1.0 1770
HP
480 V/ 3ɸ
Switch 1,2,3,4,5 1,2,3,4
Comments:
1. Base equation is Vbz = (Rp* Pz + Ra * Az) / Ez for single zone systems
2. Each area treated as single zone.
3. Fiber Extrusion area is served by RTU 6 & 7.
4. Filament Area is served by RTU 3, 4, & 5.
Outside Air Requirements per North Carolina Mechanical Code:
Area
Rp
CFM/person
(pp OA
Rate)
Pz
Zone
Population
Ra
CFM/Sqft
(area OA rate)
Az
Zone occupiable floor area
CFM/Sqft
(exhaust air flow rate)
Vbz
Breathing
Zone Air
Ez
Zone
Efficiency
Voz
Outdoor Air
Requirement
(single zone)
Outdoor Air
Provided
Fiber Extrusion 0.06 3316 199 0.8 249
Filament Area 0.06 6554 393 0.8 492
Totals: 741
General Installation Requirements
1. Drawings are diagrammatic and are intended to convey scope and general arrangements unless otherwise indicated. They do not show every rise, fitting, offset and detail. It is the contractor's responsibility to read and understand the scope and intent of the drawings and specifications and deliver a complete and operational system that performs to the specifications and documents provided.
2. All mechanical permits and inspection fees shall be obtained and paid by the mechanical contractor.
3. Contractor is responsible for materials and installing the work in accordance with all applicable local, state and national codes.
4. Do not scale drawing for measurements.
5. It is the contractor's responsibility to verfiy duct and pipe paths are free of obstruction and reroute as necessary should an obstruction occur.
6. It is the contractor's responsibility to coordinate with the gas and power company to arrange and facilitate shutdown of utilities as necessary to integrate new system.
7. It is the contractor responsibility to survey existing conditions and make adjustments to duct size, route and configurations to deliver the required air to the system zones.
8. Install all equipment using the manufacturer's recommended installation procedures.
9. It is the contractor's responsiblity to notify and coordinate with building owner when work will cause any interruption in services to building whether utilities, path obstruction, etc..
10. The contractor will provide protection of materials, tools and equipment during the construction phase including protective covers, skids, plugs, caps, boxs and temporary fences.
11. All equipment shall be U.L. Listed.
12. All cutting and patching of walls and floors for mechanical equipment shall be the responsibility of the mechanical contractor.
13. The roof warranty is maintained by Piedmont Commercial Roofing, Inc. Contact Mike Stewart; (704
624 5544 - Office) PiedmontRoofing@charlotte.twcbc.com. The roof warranty must be remain intact by using the warranty contractor for flashing and sealing curbs and penetrations.
Mechanical Installation Requirements
1. Furnish all labor, material and equipment required for the complete installation and operation of all systems in this section of work in accordance with recommended practice and all applicable codes.
2. Mechanical contractor shall guarantee all work and materials for one year, effective the day the project is accepted by the owner. Refrigerant compressors shall be guaranteed for five years.
3. Seal the joints airtight between package units and supply ducts. Seal joints above the roof and not transversing through the target spaces.
4. Airtight seals shall be field applied mastic complying with UL 181 A-M or mastic tape complying with UL 181 A-P
5. Provide and install permanent tags in a location that is readily visible on all installed equipment that includes all pertinent operating information including; make, model no., capacity, voltage, ampacity, heating data, cooling data. See specs for details.
6. Contractor will locate equipment as such so that maintenance personnel will have access to panels, control boards and valves.
7. Contractor will perform a test and balance of the system in accordance with the 2018 NCECC section 503.2.9. Test shall result in +5% to -5% of design flow.
8. Contractor will follow the latest SMANCA HVAC Duct Construction Standards for duct sheet thickness and fastening methods.
9. All control wire shall be provided by Mechanical Contractor.
10. Support the duct routes with a maximum of 10' between centerline of supports.
11. All equipment supports are required to meet ASCE 9.6
Comments:
1. Ceiling mounted
2. Steel Fixed nozzle at 7' stack height
3. Controlled by VFD
4. Comparable manufacturers are Greenheck, Dayton and Loren Cook
D
D
X
Y
B: CFM
X
X
X
X
A: CFM
B: CFM
A: CFM
C
C
F M
C
C
F M
Y Y
D
D
Y
Y
20deg Max
R = D
1.5 x D
R2 = X + Y
R1 = (x+y)/2
Volume Dampers, typ.
Note: Duct turns and bends details are for low pressure duct only.
C: cfm x Y=X
A: cfm
C: cfm x Y=X
A: cfm
For C < 12" For C >= 12"
For D < 12" For X or Y < 12"
For Round take-offs to rectangular duct.
Volume
Dampers, typ.
Angle Iron
Anchor rod with nuts with locking washer and locking nut
Fasten to load bearing structure using tap and drill concrete anchors with expansion shields
Fasten to load bearing structure using tap and drill concrete anchors with expansion shields
Support metal shall be the same gauge or thickness as the duct wall
Angle brackets
Hanger rods sized for duct weight with min.
3/8" diameter
Raised Curb
Wood Nailer
Alternate curb bearing location for heavy weight loading conditions
Wood nailer
Sealing Material
Gasketed fasteners, min.
two fasteners per side
Removable sheet metal counterflashing
Fasteners approx. 8" O.C., sealed with flashing cement
Extended field plies above head of cant
Multiple-ply membrane base flashing
(8" min. height) feathered at the field of roof (for roof systems with factory applied granule surfacing, the multi-ply membrane base flashing can be installed between the base ply and granule-surfaced sheet)
Multiple-ply modified bitumen roof membrane
Coverboard Insulation
Thermal Insulation
Roof Deck
Min. 24"
Min. 2' stripping of existing material around curb and patching to form new system
Duct Turns and Bends Scale: N/AM0.1
Duct Supports Scale: N/AM0.1
Roof Curb Detail Scale: N/AM0.1
Custom Fume Hood Detail Scale: N/AM0.1
4 Duct Penetration Detail Scale: N/AM0.1
Min. 16 gauge flashing, same material is duct;
Aluminum or galvanized steel
20 Mil coat MBR
Flashing cement
30 Mil tack coat MBR
Flashing cement
Insulate opening with 2" rigid
3lb insulation
60 mil coat of MBR flashing cement.
Completely cover scrim and flashing
Flashing cement Extend horizontally
6" pass flashing along roof top
Sized by approved shop drawings
Min. 8"
Min. 6" 24"
Min. 2' stripping of existing material around curb and patching to form new system
Install a min. of two plies over strip
Use metal capped nails, secured with flashing cement, spaced no more than 8" apart
Base sheet
Structural roof decking, Steel or concrete depending on section
Multiple-ply modified bitumen roof membrane
Overlayment insulation
Roof Tapered Insulation
Roof Thermal Insulation
Aggregate surfacing
Height of Switches Scale: N/AM0.1
Note: Support screws must connect to roof deck and not the concrete joists.
10'
9"
14"
36"
50"
Fasten to load bearing structure using tap and drill concrete anchors with expansion shields
Notes:
1. Hood shall be made of 304L sheet metal, 20 gauge, minimum 6 supports of 1/4" threaded rods or 1" x 20" gauge straps.
2. Support screws must connect to roof deck and not the concrete joists.
3. Hood shall be installed 7 feet from the top of protected equipment.
3'
9"
12"
36" 16"
Fasten to load bearing structure using tap and drill concrete anchors with expansion shields
FRONT VIEW SIDE VIEW
M0.1
COPYRIGHT
Project No:
01-2025007
Scale: N/A
Date: 06-01-2025
Title: Mechanical
Schedules
M a c h i n e
C o n n e c t i o n s
F t r u s i o n
G a s t o n
C o l l e g e
W i l k i n s o n
B l v d
B e l m o n t
N o r t h
C a r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
09/08/2025
AutoCAD SHX Text
OTHER DEVICES SHALL BE INSTALLED
AutoCAD SHX Text
ALL THERMOSTATS, SWITCHES, AND
AutoCAD SHX Text
RECEPTACLE WHERE APPLICABLE
AutoCAD SHX Text
EACH ITEM BEING PLUMB & SQUARE.
AutoCAD SHX Text
IN A NEAT AND ORDERLY FASHION, WITH
AutoCAD SHX Text 54"
AutoCAD SHX Text
THIS DIMENSION MAY BE MODIFIED UNDER
AutoCAD SHX Text
CERTAIN CONDITIONS TO A MAXIMUM
AutoCAD SHX Text
OF 5"
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text
CEILING
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text
LIGHT SWITCH
AutoCAD SHX Text
NOTED.
AutoCAD SHX Text 2"
AutoCAD SHX Text
OR COMPUTER OUTLET EXCEPT AS NOTED.
AutoCAD SHX Text
FIRE ALARM MANUAL PULL STATION
AutoCAD SHX Text
TYPICAL WALL RECEPTACLE OR PHONE
AutoCAD SHX Text 18"
AutoCAD SHX Text 48"
AutoCAD SHX Text
FIRE ALARM SIGNALING DEVICE
AutoCAD SHX Text
WALL OR CASED OPNG.
AutoCAD SHX Text
TO BE FLUSH WITH EDGE OF LIGHT SWITCH
AutoCAD SHX Text
THERMOSTAT - EDGE OF T'STAT (OR EDGE
AutoCAD SHX Text
OF GUARD COVER WHEN APPLICABLE)
AutoCAD SHX Text
OR COMPUTER OUTLET, UNLESS OTHERWISE
AutoCAD SHX Text
COUNTER HEIGHT RECEPTACLE, OR PHONE
AutoCAD SHX Text
EDGE OF DOOR FRAME OR
AutoCAD SHX Text
FRAME WHERE APPLICABLE).
AutoCAD SHX Text
COVER PLATE BELOW.
AutoCAD SHX Text
(ALIGN TOP WITH TOP OF DOOR
AutoCAD SHX Text 3"
AutoCAD SHX Text L
AutoCAD SHX Text x
F x
" F
F x
R o u e d u c t u n d e r w a t e r l i n e s a d u p p o r t j o i s t s
P e n e t r a r o o f a t t h e s e p r e c i l c a t i o n
P e n e t r a o f a t t h e s e p r e c i c a t i o n
P e n e t r a o f a t t h e s e p r e c i c a t i o n
M1.1
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 06-01-2025
Title: Mechanical Plan
M a c h i n e
C o n n e c t i o n s
F t r u s i o n
G a s t o n
C o l l e g e
W i l k i n s o n
B l v d
B e l m o n t
N o r t h
C a r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
Mechanical Plan Scale: 14" = 1' - 0"M1.1
09/08/2025
Key Plan
AutoCAD SHX Text Chem
AutoCAD SHX Text Storage
AutoCAD SHX Text Small PET Reactor
AutoCAD SHX Text One Shot
AutoCAD SHX Text Reactor
AutoCAD SHX Text Melt Spin
AutoCAD SHX Text Compounding
AutoCAD SHX Text Work Bench/Pack Storage
AutoCAD SHX Text 480277400A
AutoCAD SHX Text Blow Down Tank
AutoCAD SHX Text Work Bench
AutoCAD SHX Text Rheology
AutoCAD SHX Text Chip Drying
AutoCAD SHX Text Ultra Sonic
AutoCAD SHX Text Small Cleaning Oven
AutoCAD SHX Text Soak Tank
AutoCAD SHX Text Big Cleaning Oven
AutoCAD SHX Text Large Spin
Small Spin
Legends, Symbols & Icons
TM,1
Thermometer
Spec. Type
TS,1
Temperature Sensor
Spec. Type
PS,1
Pressure Sensor
Spec. Type
HS,1
Humidity Sensor
Spec. Type
BK,1
Boiler Kill Switch
Spec. Type
FS,1
Flow Switch
Spec. Type
Gate Valve
Ball Valve
Butterfly Valve
Check Valve
Actuated Valve
Pressure Reducer
Pressure Safety
Valve (Relief)
Strainer
Line Reducer
Domestic cold water supply
ECW
Domestic existing cold water supply
Domestic 120° hot water supply
Domestic existing 120° hot water supply
Gas supply line
Angle Valve
Three Way Valve
Connect to existing at this point
Remove to this point
Key Note Icon
E120
GAS
Domestic 140° hot water supply
Domestic existing 140° hot water supply
E140
Tempered water supply
TW
Filtered water supply
FW
Sanitary sewer line
Vent line
SD - A
Storm drain (above ground)
Storm drain (below ground)
Condensate line
SD - B
CL
Grease waste line
GW
Sump pump discharge
SPD
Pipe turning down
Pipe turning up
Pipe capped
Fixture supply with shut-off
Domestic 120° hot water return
Domestic 140° hot water return
120R
140R
Fire line
F
Wet stand pipe
WSP
Dry stand pipe
DSP
Main sprinkler supply
MS
Branch and head sprinkler
Floor drain fd
Hub drain hd
Roof drain rd
Floor cleanout fco
End of line cleanout co
Wall cleanout wco
Union
Hose bibb
Gas Cock
SA - "1"
Shock arrestor
(number indicates pdi size)
Backflow preventer
Fire proof wall hydrant
FPH
Fire proof wall hydrant box
FPHB
EJ
Expansion joint
Pipe anchor
Trap primer
Pipe sleeve
Flexible connection
M
P1
Pump
Meter
TP
Air vent (manual - auto)
M
Globe Valve
Plumbing Installation Requirements
1. Furnish all labor, material and equipment required for the completion and operation of all systems in this section of work in accordance with applicable codes.
2. All plumbing fixtures and plumbing system equipment shall be provided complete with all accessories, hangers, valves, stops, tailpieces, traps, faucets, strainers, etc. See fixture schedule.
3. All plumbing work shall be installed in compliance with the current issue of the local and state plumbing codes and the relevant NFPA codes.
4. Provide access panels as required at valve locations to provide access to control valves.
Coordinate for type and location.
5. Provide for access to all equipment requiring cleaning or adjustment.
6. Provide a pressure reducing valve where water main pressure entering building exceeds 80 PSI.
7. Provide full port valves in all branch lines of the hot and cold water distribution systems on
" and larger cold water and hot water and as shown on plans, risers and schematic details.
General Installation Requirements
1. Furnish all labor, materials and equipment required for the completion and operation of all systems in this section of work in accordance with all applicable codes.
2. Furnish and install complete systems of soil, waste, vent, hot and cold water piping from all plumbing fixtures and other equipment.
3. Coordinate with structural, mechanical and electrical trades to ensure no conflicts and code compliance is maintained by the systems.
4. Any substituted equipment that is submitted and approved with connections other than what is shown on drawings and schedules, it is the responsibility of the contractor to provide proper connections to the equipment.
5. Copper piping shall be protected against contact with masonry or dissimilar metals. All hangers, supports, anchors and clips shall be copper or copper plated. Where copper piping is carried on iron or steel trapeze hangers with other piping, then permanent electrolytic isolation material shall protect the copper against contact with other materials.
6. All pipe insulation shall run continuously through floors, walls and partitions.
7. Domestic water piping above slab shall be Type "L" copper. Domestic water piping below slab shall be Type "K" copper.
8. Compressed air lines shall be carbon steel schedule 40. New lines and extensions shall be painted and stenciled to match existing lines.
Compressed Air - Three drop detail Scale: N/A
P0.1
44"
3"
Sediment leg
Isolation Valve
Branch
Isolation Valve
Compressed Air - Two drop detail Scale: N/A
P0.1
44"
3"
Sediment leg
Isolation Valve
Branch
Isolation Valve
Compressed Air - One drop detail Scale: N/A
P0.1
44"
3"
Sediment leg
Isolation Valve
Branch
Isolation Valve
Floor Floor Floor
Potable Water Air - Two drop detail Scale: N/A
P0.1
44"
Isolation Valve
Branch
Isolation Valve
Floor
P0.1
COPYRIGHT
Project No:
01-2025007
Scale: N/A
Date: 06-01-2025
Title: Plumbing
Schedules
M a c h i n e
C o n n e c t i o n s
F t r u s i o n
G a s t o n
C o l l e g e l k i n s o n
B l v d
B e l m o n t
N o r t h
C a r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written
CA
CA3" 3"
3" CA
1 1 /4"
C A
1 1 /4"
C A
3"3"
3/4 " C
A
3" CA
3/4
3/4 " C
A
3" CA
1 1 /2"
D
CW
2" D
HW
3/4" DCW
1 1/2" DHW
3/4" DCW
2" DHW
1" DCW
1 1 /2"
3/4
FILAMENT
EXTRUDERS
REACTOR
102 103
1 1 /2"
3/4
1" C
A
1 1 /4"
C A
4" CA
4" CA
1"
P1.1
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 06-01-2025
Title: Plumbing Plan
M a c h i n e
C o n n e c t i o n s
F t r u s i o n
G a s t o n
C o l l e g e
W i l k i n s o n
B l v d
B e l m o n t
N o r t h
C a r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
Plumbing Notes Keyed to Plan
1. Connect to 1
" compressed air line here. Extend CA pipe to 44" above finish floor and add three valved hose connections. See detail 1:P0.1.
2. Connect to 1" compressed air line here. Extend CA pipe to near small spin machine.
3. Route 1" compressed air line here to 44" above finish floor and two valved hose connections. See detail 2:P0.1.
4. Connect to 1
" compressed air line here. Extend pipe to near small Dynisco machine.
5. Tee off the main CA line and route a
" compressed air line here to 44" above finish floor with one valved hose connections. See detail 3:P0.1.
6. Tee off the main CA line and route a
" compressed air line here to 44" above finish floor with one valved hose connections. See detail 3:P0.1.
7. Tee off the main potable cold water line and route a 1" line here to 44" above finished floor with two valved hose connections. See detail 4:P0.1.
Plumbing Plan Scale: 14" = 1' - 0"P1.1
09/08/2025
Key Plan
AutoCAD SHX Text Small PET Reactor
AutoCAD SHX Text Reactor
AutoCAD SHX Text Work Bench/Pack Storage
AutoCAD SHX Text 480277400A
AutoCAD SHX Text Blow Down Tank
AutoCAD SHX Text Work Bench
AutoCAD SHX Text False Twist
AutoCAD SHX Text Rheology
AutoCAD SHX Text Chip Drying
AutoCAD SHX Text Draw Frame
AutoCAD SHX Text Ultra Sonic
AutoCAD SHX Text Small Cleaning Oven
AutoCAD SHX Text Soak Tank
AutoCAD SHX Text Big Cleaning Oven
AutoCAD SHX Text Large Spin
1/2"
1/2"
3" 3"
C A
3" CA
1 1
/4" C
A
1 1 /4"
C A
3"3"
3/4 " C
A
3" CA
3"
D
CW
3" D
HW
2" DCW
3" DHW
1/2
3" D
HW
2" D
CW
EXTRUDERS
CHEMICAL
STORAGE
1 1/2"
1 1/2"
3/4" 3" DHW
2" DCW
3/4"
1" C
A
1 1 /4"
C A
4" CA
P1.2
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 06-01-2025
Title: Plumbing Plan
M a c h i n e
C o n n e c t i o n s
F t r u s i o n
G a s t o n
C o l l e g e
W i l k i n s o n
B l v d
B e l m o n t
N o r t h
C a r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
Plumbing Notes Keyed to Plan
1. Connect to 1
" compressed air line here. Extend CA pipe to 44" above finish floor and add three valved hose connections. See detail 1:P0.1.
2. Connect to 1" compressed air line here. Extend CA pipe to near small spin machine.
3. Route 1" compressed air line here to 44" above finish floor and two valved hose connections. See detail 2:P0.1.
4. Connect to 1
" compressed air line here. Extend pipe to near small Dynisco machine.
5. Tee off the main CA line and route a
" compressed air line here to 44" above finish floor with one valved hose connections. See detail 3:P0.1.
6. Tee off the main CA line and route a
" compressed air line here to 44" above finish floor with one valved hose connections. See detail 3:P0.1.
7. Tee off the main potable cold water line and route a 1" line here to 44" above finished floor with two valved hose connections. See detail 4:P0.1.
Plumbing Plan Scale: 14" = 1' - 0"P1.2
09/08/2025
Key Plan
AutoCAD SHX Text Chem
AutoCAD SHX Text Storage
AutoCAD SHX Text Small PET Reactor
AutoCAD SHX Text One Shot
AutoCAD SHX Text Reactor
AutoCAD SHX Text Melt Spin
AutoCAD SHX Text Compounding
AutoCAD SHX Text Rheology
AutoCAD SHX Text Chip Drying
AutoCAD SHX Text Draw Frame
AutoCAD SHX Text Small Cleaning Oven
AutoCAD SHX Text Big Cleaning Oven
Legends, Symbols & Icons Duplex Outlet, 15 Amp, 3W, 125V, Flush mounted
Switch, inline, 125V, single pull. flush mounted
Non-metallic cable (romex type) wiring
General Installation Requirements
1. All installation work will be completed during normal business hours, exceptions will be made.
2. Competitive equipment may be used in lieu of models specified.
3. Drawing are diagrammatic, contractor will verify equipment positions and adjust power and controls conduit path accordingly.
4. Support conduit per NEC 2020.
5. Coordinate installation with other trades.
6. All wire must 75° C rated or higher, THW, THHW.
Electrical Installation Requirements
1. All electrical work must be done by a NC licensed electrician.
2. All electrical work must comply with the NEC 2020.
3. Wire connection shall be twist tied with appropriate sized cap.
4. All contractor provided electric materials, devices, appliances and equipment shall be label-listed by a North Carolina approved third party testing agency.
5. The new circuit breakers shall match existing breakers for actual interrupt capacity.
6. Conductors shall match existing color code as follows.
6.1. 277/480V, 3 Phase, 4 - Wire 208/120V, 3 Phase, 4-Wire
6.2. Phase A - Brown Phase A - Black
6.3. Phase B - Orange Phase B - Red
6.4. Phase C - Yellow Phase C - Blue
6.5. Neutral - Grey Neutral - White
7. Relocate light fixtures from under the location of the designated hood locations.
8. Surge Protector shall be Siemens TPS3 C 12 10 0 X 02 or equivalent.
9. Lockout breakers are required where lockable disconnect are not present.
10. Contractor to install circuits and update panels as shown in schedules.
Conduit and Wire for Power
Conduit and wire concealed under floor
Low voltage control wire
Home run to panelboard
Empty Conduit
Connect to existing at this point
Remove to this point
EC
NM
S a
Switch, inline, 125V, three way. flush mounted S
Switch, inline, low voltage, single pull. flush mounted
S
L
Switch, inline, 125V, double pull. flush mounted S dp
Switch, inline, 125V, 4 way. flush mounted S
Switch, inline, 125V, key operated. flush mounted S k
Switch, door operated see spec for details S d
Switch, weather proof enclosure see spec for details
S wp
Switch, momentary contact S mc
Quad Outlet, 15 Amp, 3W, 125V, Flush mounted
Outlet, 20 Amp, 3W, 250V, NEMA 6-20R a
Outlet, 20 Amp, 3W, 250V, NEMA L6-20R b
Outlet, 15 Amp, 3W, 250V, NEMA 6-15R c
GFCI Duplex Outlet, 15 Amp, 3W, 125V, Flush Mount
GFCI
GFCI Duplex Outlet, 15 Amp, 3W, 125V, WP, Outdoor Duty
GFCI-WP
D
Outlet - Box - Mounted Dimmer
D
Outlet - Box - Mounted Switch and Dimmer
S
R
Outlet - Box - Relay
J
Junction Box
DS
Disconnect Box, see specs for details
Automatic transfer switch, see specs for details
T
S
Data Communications Outlet
Residential Telephone jack, typ.ph
SD
Smoke detector, see specs for details
Audible horn or annunciator, see specs for details
TV
AV Outlet
Panelboard, see schedule for details
PNL - A
Transformer, dry type, see schedule for details
M Motor, Type 1,see schedule for specs
M C
Motor controller, Type 1,see schedule for specs
M C
Combination motor controller & disconnect, Type 1,see schedule for specs
M C
Combination motor controller & circuit breaker, Type 1,see schedule for specs
CB
DS
Push button station, momentary contact
Push button station, maintained contact
H
A
O
Hand - Off - Auto type, motor control unit
A1
H1
M1
MD1
D1
R1
Lighting fixture, flourescent, 4 bulb, see schedule for details
Lighting fixture, high pressure sodium, see schedule for details
Lighting fixture, metal halide, see schedule for details
Lighting fixture w/ motion detector, 2 bulb, see schedule for details
Lighting fixture, directional, single bulb, see schedule for details
Lighting fixture, recessed, single bulb, see schedule for details
E1
FL1
E
Emergency exit sign, see schedule for details
Emergency exit sign and egress lighting, see schedule for details
Emergency notification appliance
Emergency pull station
M
Power supply meter
Emergency annunciator appliance F
L1
Lighting fixture, miscellaneous, see schedule for details
Occupancy Sensor and Switch S
Disconnect Schedule
Tag
Manufacturer
Description
Fuse/ C/B Volts/Ph
Mounting
D1 Generic
NEMA 1, 100 Amp Rated Disconnect, Heavy Duty
480/3ɸ
Wall
D2 Generic
NEMA 1, 60 Amp Rated Disconnect, Heavy Duty
480/3ɸ
Wall
D3 Generic
NEMA 1, 60 Amp Rated Disconnect, Heavy Duty
480/3ɸ
Wall
D4 Generic
NEMA 3R, 30 Amp Rated Disconnect, Heavy Duty
480/3ɸ
Rack
D5 Generic
NEMA 1, 30 Amp Rated Disconnect, Heavy Duty
480/3ɸ
Rack
D6 Generic
NEMA 3R, 60 Amp Rated Disconnect, Heavy Duty
250/3ɸ
Wall
Conductor Sizing Table
For 120V - 20A Branch Circuits Only, Unless Otherwise Noted
These tables are based on an evenly distributed load allowing 3% voltage drop at last outlet:
For 277V - 20A Branch Circuits Only, Unless Otherwise Noted
If distance A + B in feet is (see diagram below)
0' to 100'
100' to 175'
175' to 300'
300' to 450'
Use copper wire in metallic conduit, AWG size as follows on entire circuit and size conduit accordingly
#12 (min.)
#10
#8
#6 (max.)
If distance A + B in feet is (see diagram below)
0' to 250'
250' to 400'
400' to 700'
700' to 1000'
Use copper wire in metallic conduit, AWG size as follows on entire circuit and size conduit accordingly
#12 (min.)
#10
#8
#6 (max.)
PNL - A
R1
R1
A (FT)
B (FT)
1st device on CKT
Last device on CKT wire length from first to last device on CKT
PNL - A
R1
R1
A (FT)
B (FT)
1st device on CKT
Last device on CKT wire length from first to last device on CKT
SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings: E0.1, E1.1, E1.2, E3.1 and E3.2
1.2 SUMMARY
A. This section includes the following
1. Electrical equipment coordination and installation.
2. Common electrical installation requirements.
1.3 COORDINATION
A. Coordinate arrangement, mounting, and support of electrical equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by standard electrical supply manufacturers.
2.2 INSPECTIONS
A. Contractor shall contact the Gaston County Inspections to schedule electrical inspections and to schedule a final inspection.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Comply with NEC C. Comply with North Carolina Electrical Building Code D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.
E. EMT to be used only in dry indoor locations with steel compression fittings and connectors.
END SECTION 260500
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings: E0.1 and E1.1
1.2 SUMMARY
B. This section includes the following
1. Requirements for building wire and cable
1.3 COORDINATION
A. Coordinate electrical testing of electrical items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by standard electrical supply manufacturers.
B. All building wire and cables should be listed by a North Carolina “approved” third party testing agency
2.2 INSPECTIONS
A. Contractor shall contact the Gaston County Inspections to schedule electrical inspections and to schedule a final inspection.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Comply with NEC C. Comply with North Carolina Electrical Building Code
3.2 WORK REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Provide and install an individual neutral wire for each branch circuit.
B. Conductors for power and lighting that are sized #10 AWG and smaller shall be solid copper conductors. All power conductors that are #8 AWG and larger shall be class B stranded copper conductors.
C. The minimum size for power branch circuit wiring is #12 AWG.
D. Fire alarm and control wiring may be equipped with stranded conductors that are sized #14
AWG.
E. Branch circuit conductors should be sized to prevent a voltage drop exceeding (3%) and the maximum voltage drop on both feeders and branch circuits should not exceed (5%)
F. Provide and install a full size individual neutral wire for each circuit.
G. The insulation type for interior wiring shall be dual-rated THHN/THWN or XHHW.
H. Where the conductor length from the panel to the first outlet on a 277 volt circuit exceeds 125 feet, the branch circuit conductors from the panel to the first outlet shall not be smaller than #10 AWG.
I. Where the conductor length from the panel to the first outlet on a 120 volt circuit exceeds 50 feet, the branch circuit conductors from the panel to the first outlet shall not be smaller than #10 AWG.
J. Joints in solid conductors shall be spliced using Ideal "wirenuts", 3M Company "Scotchlock" or T&B connectors in junction boxes, outlet boxes and lighting fixtures.
K. "Sta-kon" or other permanent type crimp connectors shall not be used for branch circuit connections.
L. Joints in stranded conductors shall be spliced by approved mechanical connectors and gum rubber tape or friction tape. Solderless mechanical connectors for splices and taps, provided with U/L-approved insulating covers, may be used instead of mechanical connectors plus tape.
M. Conductors, in all cases, shall be continuous from outlet to outlet and no splicing shall be made except within outlet or junction boxes, troughs and gutters.
N. The feeder, branch circuits shall be color coded.
END SECTION 260519
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings: E0.1 and E1.1
1.2 SUMMARY
C. This section includes the following
2. Grounding and bonding for raceways
1.3 COORDINATION
A. Coordinate electrical testing of electrical items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by standard electrical supply manufacturers.
B. All building wire and cables should be listed by a North Carolina “approved” third party testing agency
2.2 INSPECTIONS
A. Contractor shall contact the Gaston County Inspections to schedule electrical inspections and to schedule a final inspection.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Comply with NEC C. Comply with North Carolina Electrical Building Code
3.2 WORK REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. The raceway system shall be not be relied on for ground continuity. A green grounding conductor, properly sized per NEC Table 250-122, shall be run in all power raceways.”
B. Provide and install a green grounding conductor in all power C. Test grounding and bonding system with a ground resistance tester demonstrating the resistance to ground is less than 25 ohms. Where the resistance is more than 25 ohms additional grounding will be required.
D. Grounding conductors, where insulated, shall be colored solid green. Conductors intended as neutral shall be colored solid white on 120/208 volt circuits and natural gray on 277/480 volt circuits.
END SECTION 260526
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings: E0.1 and E1.1
1.2 SUMMARY
A. This section includes the following
1. Identification and labeling electrical systems
1.3 COORDINATION
A. Electrician will properly label all electrical equipment with labels.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Comply with NEC C. Comply with North Carolina Electrical Building Code
3.2 WORK REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Furnish and install engraved laminated phenolic nameplates for all safety switches, panelboards, transformers, switchboards, motor control centers and other electrical equipment supplied for the project for identification. Nameplates shall be securely attached to equipment with self-tapping stainless steel screws; if the screw sharp end is protected;
otherwise Rivets shall be used. Letters shall be approximately 1/2 inch high minimum.
Embossed, self-adhesive plastic tape is not acceptable for marking equipment. Nameplate material colors shall be:
1. Blue surface with white core for 120/208 volt equipment.
2. Black surface with white core for 277/480 volt equipment.
3. Bright red surface with white core for all equipment related to fire alarm system.
4. Dark red (burgundy) surface with white core for all equipment related to security.
5. Green surface with white core for all equipment related to "emergency" systems.
6. Orange surface with white core for all equipment related to telephone systems.
7. Brown surface with white core for all equipment related to data systems.
8. White surface with black core for all equipment related to paging systems.
9. Purple surface with white core for all equipment related to TV systems.
B. All empty conduit runs and conduit with conductors for future use shall be identified for use and shall indicate where they terminate. Identification shall be by tags with string or wire attached to conduit or outlet.
C. All outlet boxes, junction boxes and pull boxes shall have their covers and exterior visible surfaces painted with colors to match the surface color scheme outlined above. This includes covers on boxes above lift-out and other type accessible ceilings.
END SECTION 260553
SECTION 262726 - WIRING DEVICES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings: E0.1 and E1.1
1.2 SUMMARY
A. This section includes the following
1. Specifications for the installations of wiring devices
1.3 COORDINATION
A. Coordinate electrical testing of electrical items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by standard electrical supply manufacturers.
B. Device shall be third party tested as noted per sub-section 3.2 part B.
2.2 INSPECTIONS
A. Contractor shall contact the Gaston County Inspections to schedule electrical inspections and to schedule a final inspection.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Comply with NEC C. Comply with North Carolina Electrical Building Code
3.2 WORK REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Toggle switches shall be single pole, three-way, or four-way as indicated on the drawings.
Switches shall be of the grounding type, with hex-head grounding screw, rated 20A, 120/277 volt, A.C only. Lighted handle switches shall have neon lights of the correct voltage rating where indicated on the drawings. All switches shall have quiet operating mechanisms without the use of mercury switches. All switches shall be listed by an "approved" third-party agency, approved for the voltage and amperage indicated.
B. Cover plates for flush mounted wiring devices and for telephone outlets shall be Type "302" stainless steel or nylon type, standard size, single or ganged as shown on the drawings. Cover plate mounting screws shall be slotted head oval screws and shall match the finish and material of the plate, and shall be furnished with the plate by the plate manufacturer.
Quantity of 2% spare cover plates of each type shall be provided to the owner.
C. Switch and receptacle cover plates on exposed work shall be galvanized cast ferrous metal, standard size, and shall be single or ganged as indicated on the drawings.
D. Exterior mounted switch and receptacle plates, and those noted to be weatherproof, shall be weatherproof PVC cover plates, standard size, single or ganged as indicated on the drawings, and shall be "approved” third party listed as "rain-tight while in use."
E. All receptacles (unless otherwise noted) shall be federal specification grade duplex receptacles.
END SECTION 262726
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings: E0.1 and E1.1
1.2 SUMMARY
A. This section includes the following
1. Specifications for the installations of safety switches
1.3 COORDINATION
A. Coordinate electrical testing of electrical items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by standard electrical supply manufacturers.
B. Device shall be third party listed.
2.2 INSPECTIONS
A. Contractor shall contact the Gaston County Inspections to schedule electrical inspections and to schedule a final inspection.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Comply with NEC C. Comply with North Carolina Electrical Building Code
3.2 WORK REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Safety switches shall be the "heavy duty" type. General duty switches are not acceptable.
B. Switches shall have defeatable door interlocks that prevent the door from opening when the operating handle is in the "on" position.
C. Switches shall have handles whose positions are easily recognizable in the "on" or "off" position. For safety reasons, padlock shall be provided for switches located in the public areas.
D. Switches shall have non-teasible, positive, quick make-quick break mechanisms.
E. Switches shall be properly labeled.
END SECTION 262816
Transformer Schedule
Tag
Manufacturer
Description kVA
Rating
Primary
Voltage
Secondary
Voltage
Weight (lbs) Mounting
T 5 Maddox
Dry Type, Ventilated
480 / 3 ph 400 / 3ph
220 Floor
Notes:
1. Model Maddox or equivalent
2. 150° C Rise, 45 DB
3. Comparable Manufacturers are: Schneider Electric, Siemens
E0.1
COPYRIGHT
Project No:
01-2025007
Scale: N/A
Date: 06-01-2025
Title: Electrical Schedules
M a c h i n e
C o n n e c t i o t r u s i o n
G a s t o n
C o l l e g e l k i n s o n
B l v d
B e l m o n t
N o r r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e
N um be r:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written
09/10/25
PNL 'DNH2'
T4
PNL 'DNL2'
PNL 'DNH3'
PNL 'DNH4'
PNL 'DNL3'
Pnl "DNH3", ckt 19,21,23 3 - #3/0, 1 - #6G in 2" C
FGB Main Controller
New Panel
Desiccant Dryer, power thru disconnect mounted on uni-strut support
Pnl "DNH3", ckt 25,27,29 3 - #12, 1 - #12G in 3 4" C
Pnl "DNH3", ckt 28,30,32 3 - #12, 1 - #12G in 3 4" C
LBGB Main
Pnl "DNH3", ckt 22,24,26 3 - #12, 1 - #12G in 3 4" C
Preheater, (on platform mezzanine), thru 1st level
Tx (XF-003). Install on unistrut
Pnl "DNH4", ckt 8,10,12 3 - #4, 1 - #8G in 1 14" C
T5
Pnl "DNH2", ckt 7,9,11 3 - #10, 1 - #10G in 3 4" C
Pnl "DNH2", ckt 8,10,12 3 - #10, 1 - #10G in 1" C
DNH4, ckt
14,16,18, 4 - #12, "C
Hopper 3, daisy chain power thru hopper 4, Hopper 4
D2
D3
D5
D5
D5
Desiccant Dryer, power thru disconnect mounted on uni-strut support
D5
DNH4, ckt 20,22,24, 4 - #12, "C
D5
Hopper 2
Hopper 1, daisy chain power thru hopper 2, D5
DNH4, ckt
26,28,30, 4 - #12, "C
W100, Dehum machine
AEC,
GPAC-20
D6
DNL3, ckt
15,17,19, 4 - #10, "C
Draw Frame, power from disconnect to equipment Tx.
E1.1
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 06-01-2025
Title: Electrical Plan
M a c h i n e
C o n n e c t i o t r u s i o n
G a s t o n
C o l l e g e l k i n s o n
B l v d
B e l m o n t
N o r r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e
N um be r:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
Electrical Plan - 480 V Power Scale: 14" = 1' - 0"E1.1
09/10/25
Key Plan
AutoCAD SHX Text Small PET Reactor
AutoCAD SHX Text Reactor
AutoCAD SHX Text Work Bench/Pack Storage
AutoCAD SHX Text 480277400A
AutoCAD SHX Text Blow Down Tank
AutoCAD SHX Text Work Bench
AutoCAD SHX Text False Twist
AutoCAD SHX Text
BR-FD425
AutoCAD SHX Text
BR-MS
AutoCAD SHX Text
FD-S
AutoCAD SHX Text Rheology
AutoCAD SHX Text Chip Drying
AutoCAD SHX Text Draw Frame
AutoCAD SHX Text Ultra Sonic
AutoCAD SHX Text Small Cleaning Oven
AutoCAD SHX Text Soak Tank
AutoCAD SHX Text Big Cleaning Oven
AutoCAD SHX Text Large Spin
Pnl "DNH3", ckt 7,9,11 3 - #4, 1 - #8G in 1 14" C
D1
Compounder, power from disconnect to equipment Tx.
"C
Dehum machine
E1.2
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 06-01-2025
Title: Electrical Plan
M a c h i n e
C o n n e c t i o t r u s i o n
G a s t o n
C o l l e g e l k i n s o n
B l v d
B e l m o n t
N o r r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e
N um be r:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
Electrical Plan - 480 V Power Scale: 14" = 1' - 0"E1.2
09/10/25
Key Plan
AutoCAD SHX Text Chem
AutoCAD SHX Text Storage
AutoCAD SHX Text Small PET Reactor
AutoCAD SHX Text One Shot
AutoCAD SHX Text Melt Spin
AutoCAD SHX Text Compounding
AutoCAD SHX Text Crimp Cut
PNL 'DNH2'
T4
PNL 'DNL2'
PNL 'DNH3'
PNL 'DNH4'
PNL 'DNL3'
New Panel
Pnl "DNL3", ckt 7 2 - #12, 1 - #12G in 12" C
Pnl "DNL3", ckt 5 2 - #12, 1 - #12G in 12" C
Pnl "DNL3", ckt 1,3 2 - #12, 1 - #12G in 12" C
Pnl "DNL3", ckt 2 2 - #12, 1 - #12G in 12" C
Pnl "DNL3", ckt 4 2 - #12, 1 - #12G in 12" C
Loaders and gravity feeders, route conduit under platform and install recepts on uni-strut
Pnl "DNL3", ckt 6 2 - #12, 1 - #12G in 12" C
Pnl "DNL3", ckt 8 2 - #12, 1 - #12G in 12" C
Winder c
E1.3
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 06-01-2025
Title: Electrical Plan
M a c h i n e
C o n n e c t i o t r u s i o n
G a s t o n
C o l l e g e l k i n s o n
B l v d
B e l m o n t
N o r r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e
N um be r:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
Electrical Plan - 120/208 V Power Scale: 14" = 1' - 0"E1.3
09/10/25
Key Plan
AutoCAD SHX Text Small PET Reactor
AutoCAD SHX Text Reactor
AutoCAD SHX Text Work Bench/Pack Storage
AutoCAD SHX Text 480277400A
AutoCAD SHX Text Blow Down Tank
AutoCAD SHX Text Work Bench
AutoCAD SHX Text False Twist
AutoCAD SHX Text
BR-FD425
AutoCAD SHX Text
BR-MS
AutoCAD SHX Text
FD-S
AutoCAD SHX Text Rheology
AutoCAD SHX Text Chip Drying
AutoCAD SHX Text Draw Frame
AutoCAD SHX Text Ultra Sonic
AutoCAD SHX Text Small Cleaning Oven
AutoCAD SHX Text Soak Tank
AutoCAD SHX Text Big Cleaning Oven
AutoCAD SHX Text Large Spin
Pnl "DNL3", ckt 9,11 2 - #12, 1 - #12G in 12" C b b
Pnl "DNL3", ckt 10,12 2 - #12, 1 - #12G in 12" C
Pnl "DNL3", ckt 13 2 - #12, 1 - #12G in 12" C a a
Pnl "DNL2", ckt 13,15 2 - #12, 1 - #12G in 12" C
Pnl "DNL2", ckt 22,24 2 - #12, 1 - #12G in 12" C
E1.4
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 06-01-2025
Title: Electrical Plan
M a c h i n e
C o n n e c t i o t r u s i o n
G a s t o n
C o l l e g e l k i n s o n
B l v d
B e l m o n t
N o r r o l i n a
A er oR aq
E ng in ee ri ng
In c
En gi ne er in g
Se rv ic es
D av is P ar kw ay , S ui te
C 6-
C ha rl ot te , N or th
C ar ol in a
Fi rm
L ic en se
C
-3
Ph on e
N um be r:
Revisions
No. Date
Seal:
Note:
This drawing is the property of the firm, AeroRaq Engineering.
Reproduction in part or in whole is forbidden without written permission.
Electrical Plan - 120/208 V Power Scale: 14" = 1' - 0"E1.4
09/10/25
Key Plan
AutoCAD SHX Text Chem
AutoCAD SHX Text Storage
AutoCAD SHX Text Small PET Reactor
AutoCAD SHX Text One Shot
AutoCAD SHX Text Melt Spin
AutoCAD SHX Text Compounding
AutoCAD SHX Text Crimp Cut
AutoCAD SHX Text
BR-FD425
M
WP
EF-3
DNH4-13,15,17
DNH4-19,21,23
DNH4-25,27,29
RTU-6
RTU-7
RTU-8
CU-3
EF-6
F-1
F-2
F-3
E1.5
COPYRIGHT
Project No:
01-2025007
Scale:
" = 1' - 0"
Date: 08-01-2025
Title: Electrical Roof
Plan
M a c h i n e
C o n n e c t i o t r u s i o n
G a s t o n
C o l l e g e…