ABAC 5100289 Drawings.pdf
PDF 958 KB Posted
- Solicitation number
- PE-47200-RFQ-2025-000000074
- Issued by
- Terrell County, Georgia
About this file
This is a set of electrical engineering drawings from NBP Engineers, Inc. for a project at Abraham Baldwin Agricultural College in Tifton, Georgia to replace main switchboards in Branch and Bowen Halls (Project No. 24094). The bid set is dated 12.05.2024 and includes detailed electrical schematics showing the main switchboard elevations and schedules for both buildings. The scope notes indicate the work involves disconnecting and removing existing MSB sections while preserving service entrance and sub-feeders, providing new MSB per elevation drawings, reconnecting service entrance conductors and sub-feeders, and reconnecting grounding electrode conductors.
The drawings specify technical requirements including a surge protection device (SPD) that must meet ANSI/IEEE C62.41 Category C standards with a 5-year warranty. All power outages must be coordinated with ABAC at least 10 days in advance through campus contact Tim Carpenter, with no outages exceeding 24 hours. For outages longer than 4 hours, the contractor is responsible for providing and paying for fire watch services. The switchboards operate at 208V 3-phase and 480V 3-phase respectively with 65 KAIC ratings. Existing conductors may be reused with field verification required for all breaker sizes prior to equipment submittal.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF
DRAWINGS
TITLESHEET NO.
NBP
ENGINEERS
NBP Project No.: 24094
Tifton, Georgia
Abraham Baldwin Agricultural College Replace Branch and Bowen Main Switchboards
PROJECT CONSULTANTS
NBP ENGINEERS, INC.
MACON, GEORGIA316 CORPORATE PARKWAY
CONSULTANTS
478-745-1691 www.nbpengineers.com
12.05.2024 BID SET
SITE MAP
E1 BOWEN HALL MSB ELEVATION/SCHEDULE
E2 BRANCH HALL MSB ELEVATION/SCHEDULE
CT COMPARTMENT
AND RECONNECT
CT'S TO NEW GEAR
RELOCATE EXISTING
1200A
BREAKER
MAIN
MAIN SECTION SUB-FEEDER SECTION
AHU
60/3
PANEL D
125/3
PANEL A
125/3
ELEV. RM
PANEL LPB
125/3
PANEL E
125/3
DRIVE
WATER
COLD
35/3
PANEL b
150/3
BOWEN HALL MSB ELEVATION/SCHEDULE
NOT TO SCALE
E-1
ELEVATION/SCHEDULE
BOWEN HALL MSB
DRIVE
WATER
HOT
125/3
PUMP
WATER
HOT
20/3
PUMP
WATER
HOT
20/3
PUMP
WATER
CHILL
50/3
PUMP
SYS
50/3
PANEL K & C
400/3
65 KAIC
208V, 3-PH
65 KAIC
SUBMITTAL.
VERIFY ALL BREAKER SIZES PRIOR TO EQUIPMENT
EXISTING CONDUCTORS MAY BE REUSED. FIELD
PROVIDE LUG LOCATIONS TO MATCH EXISTING, SO
BREAKER LOCATIONS ARE SHOWN SCHEMATICALLY.
SCOPE NOTES:
PROVIDE NEW MSB PER ELEVATION.
RECONNECT SERVICE ENTRANCE CONDUCTORS AND SUB-FEEDERS.
CONDUCTOR SIZE INSIDE MSB AS REQUIRED.
RECONNECT TO EXISTNG GROUNDING ELECTRODE CONDUCTOR. EXTEND WITH MATCHING
COORDINATION IS TIM CARPENTER.
APPROVED IN WRITING AT LEAST 10 DAYS IN ADVANCE. CAMPUS CONTACT FOR OUTAGE
ALL OUTAGES SHALL BE COORDINATED WITH ABAC, AND NOTICE SHALL BE GIVEN AND
REQUIRED FOR THE NEW MSB.
THE EXISTING MSB IS NOT MOUNTED ON A CONCRETE PAD. A CONCRETE PAD IS NOT G
F
E
D
C
B
A
SUB-FEEDERS.
DISCONNECT AND REMOVE EXISTING MSB SECTIONS. PRESERVE SERVICE ENTRANCE AND
(PAST THE 4 HOURS). NO OUTAGE SHALL BE LONGER THAN 24 HOURS.
FOR PROVIDING AND PAYING FOR A FIRE WATCH FOR AS LONG AS THE POWER IS OFF
IF BUILDING POWER IS OFF LONGER THAN 4 HOURS, THE CONTRACTOR IS RESPONSIBLE
H
SPD
30/3
SPACE
200/3
SPACE
200/3CONDUCTORS AND THE GROUND/NEUTRAL BAR.
LOAD SIDE OF THE MAIN DISCONNECT DEVICE AS CLOSE AS POSSIBLE TO THE PHASE
CURRENT CAPACITY SHALL BE 240kA PER PHASE, 120kA PER MODE. LOCATE THE SPD ON THE
INDICATOR LIGHT THAT REPORTS THE STATUS OF THE PROTECTION OF EACH PHASE. SURGE
HAVE SURGE COUNTER WITH RESET BUTTON. DEVICE SHALL HAVE GREEN/RED SOLID STATE
PROTECTED METAL OXIDE VARISTORS, PROTECTING L-N, L-G, L-L, AND N-G. DEVICE SHALL
BOARD SUBMITTAL. SPD SHALL BE ANSI/IEEE C62.41 CATEGORY C, UTILIZING THERMALLY
AS SWITCHBOARD. PROVIDE 5-YEAR WARRANTY. SUBMIT SPD PRODUCT DATA WITH SWITCH-
PROVIDE SURGE PROTECTION DEVICE (SPD) FOR SWITCHBOARD, BY SAME MANUFACTURER
SealProject Title
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
SCALE:
FILE PATH:
DESIGNED:
DATE:
PROJECT NUMBER:
P:\24094\24094e1.dgn
DATE PLOTTED
DGN FILE
05-DEC-2024
SHEET NUMBER:
Sheet Title
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
12.05.2024
AS SHOWN
P:\24094\24094e1.dgn
Replace Branch and Bowen Main Switchboards
Tifton, Georgia
Abraham Baldwin Agricultural College
24094
SHD
BCO
SHD
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
MAIN SECTIONSUB-FEEDER SECTION
BRANCH HALL MSB ELEVATION/SCHEDULE
NOT TO SCALE
E-2
ELEVATION/SCHEDULE
BRANCH HALL MSB
PUMP
ELEVATOR
100A/3P
PANEL H1A
60A/3P
PANEL H1B
45A/3P
SPARE
100A/3P
THRU X1B
PANEL L1B
125A/3P
H2B & H3B
PANELS
100A/3P
THRU X3R
PANEL L3R
60A/3P
SPARE
100A/3P
PANEL HEM
50A/3P
PANEL H3M
400A/3P
800A
BREAKER
MAIN
65 KAIC
TO NEW BREAKER IN SUBFEEDER SECTION.
FROM EXISTING BREAKER IN MAIN SECTION
EXTEND EXISTING CONDUCTORS, 4#6, 1#10G
65 KAIC
480V, 3-PH
SCOPE NOTES:
PROVIDE NEW MSB PER ELEVATION.
RECONNECT SERVICE ENTRANCE CONDUCTORS AND SUB-FEEDERS.
CONDUCTOR SIZE INSIDE MSB AS REQUIRED.
RECONNECT TO EXISTNG GROUNDING ELECTRODE CONDUCTOR. EXTEND WITH MATCHING
COORDINATION IS TIM CARPENTER.
APPROVED IN WRITING AT LEAST 10 DAYS IN ADVANCE. CAMPUS CONTACT FOR OUTAGE
ALL OUTAGES SHALL BE COORDINATED WITH ABAC, AND NOTICE SHALL BE GIVEN AND
REQUIRED FOR THE NEW MSB.
THE EXISTING MSB IS NOT MOUNTED ON A CONCRETE PAD. A CONCRETE PAD IS NOT G
F
E
D
C
B
A
ALL BREAKER SIZES PRIOR TO EQUIPMENT SUBMITTALS
EXISTING CONDUCTORS MAY BE REUSED. FIELD VERIFY
PROVIDE LUG LOCATIONS TO MATCH EXISTING, SO
BREAKER LOCATIONS ARE SHOWN SCHEMATICALLY.
H
SUB-FEEDERS.
DISCONNECT AND REMOVE EXISTING MSB SECTIONS. PRESERVE SERVICE ENTRANCE AND
(PAST THE 4 HOURS). NO OUTAGE SHALL BE LONGER THAN 24 HOURS.
FOR PROVIDING AND PAYING FOR A FIRE WATCH FOR AS LONG AS THE POWER IS OFF
IF BUILDING POWER IS OFF LONGER THAN 4 HOURS, THE CONTRACTOR IS RESPONSIBLE
CONDUCTORS AND THE GROUND/NEUTRAL BAR.
LOAD SIDE OF THE MAIN DISCONNECT DEVICE AS CLOSE AS POSSIBLE TO THE PHASE
CURRENT CAPACITY SHALL BE 240kA PER PHASE, 120kA PER MODE. LOCATE THE SPD ON THE
INDICATOR LIGHT THAT REPORTS THE STATUS OF THE PROTECTION OF EACH PHASE. SURGE
HAVE SURGE COUNTER WITH RESET BUTTON. DEVICE SHALL HAVE GREEN/RED SOLID STATE
PROTECTED METAL OXIDE VARISTORS, PROTECTING L-N, L-G, L-L, AND N-G. DEVICE SHALL
BOARD SUBMITTAL. SPD SHALL BE ANSI/IEEE C62.41 CATEGORY C, UTILIZING THERMALLY
AS SWITCHBOARD. PROVIDE 5-YEAR WARRANTY. SUBMIT SPD PRODUCT DATA WITH SWITCH-
PROVIDE SURGE PROTECTION DEVICE (SPD) FOR SWITCHBOARD, BY SAME MANUFACTURER
SPD
30A/3P
SPACE
200A/3P
SealProject Title
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
SCALE:
FILE PATH:
DESIGNED:
DATE:
PROJECT NUMBER:
P:\24094\24094e2.dgn
DATE PLOTTED
DGN FILE
05-DEC-2024
SHEET NUMBER:
Sheet Title
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
12.05.2024
AS SHOWN
P:\24094\24094e2.dgn
Replace Branch and Bowen Main Switchboards
Tifton, Georgia
Abraham Baldwin Agricultural College
24094
SHD
BCO
SHD
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
| 24094cov |
| 24094e1 |
| References |
| tb, 24094tb.dgn |
| 24094e2 |
| References |
| tb, 24094tb.dgn |