A5 - SOW - DMS WCU SAPCOM_V6_20251209.docx
DOCX document 111 KB Posted
- Attached to
- 42-0068-DMS WCU Upgrades
- Solicitation number
- N64498-26-SIMACQ-PD-42-0068
About this file
This Statement of Work (SOW) details the Naval Surface Warfare Center Philadelphia Division's requirements for hardware and software upgrades to the Waterjet Control Unit (WCU) on Littoral Combat Ship Independence Variant (LCS-2V) vessels. The project involves developing comprehensive solutions for seventeen shipsets across LCS 6-38, addressing critical obsolescence challenges in the waterjet propulsion system. Key technical objectives include developing software modifications to improve system reliability, creating new Human Machine Interface (HMI) screens, implementing feedback redundancy for control systems, resolving licensing issues with programmable logic controllers, and enabling ship personnel to calibrate and troubleshoot systems without original equipment manufacturer support.
The contract requires Defense Maritime Solutions (DMS) to develop prototypes, perform comprehensive testing, create installation procedures, backfit obsolete components, and deliver technical documentation for each shipset. The work will be performed primarily at DMS facilities in Virginia Beach, VA and Drunen, Netherlands, with an estimated forty travel trips required. The project encompasses multiple contract line items (CLINs) for design, development, procurement, and installation across different LCS hull configurations, with specific focus on addressing recurring hydraulic cylinder failures, software obsolescence, and system parameter monitoring. The Navy anticipates this upgrade will significantly improve operational readiness and reduce equipment downtime for the LCS fleet.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI_427_DMS SAPCOM_20251209.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOW – DMS SAPCOM – 2025
Statement of Work (SOW) for Defense Maritime Solutions, Inc. (DMS) Waterjet Control Unit (WCU) Upgrades
1.0 INTRODUCTION
1.0.1 The Naval Surface Warfare Center Philadelphia Division (NSWCPD) is a Department of Defense entity responsible for research and development, test and evaluation, engineering and fleet support organization for the Navy’s ships, submarines, military watercraft and unmanned vehicles. This requirement is for NSWCPD Code 427, which is responsible for Surface Ship Propellers, Shafting, Waterjets, and Bow Thrusters.
1.0.2 This contract is for non-personal services. It does not create employment rights with the U.S. Government whether actual, inherent, or implied.
1.0.3 Government/Contractor Relationship:
1.0.3.1 The services to be delivered under this Task Order are non-personal services and the parties recognize and agree that no employer-employee relationship exists or will exist under the Task Order between the Government and the Contractor's personnel. Therefore, it is in the best interest of the Government to provide both parties a full understanding of their respective obligations.
1.0.3.2 The Contractor employees shall identify themselves as Contractor personnel by introducing themselves or being introduced as Contractor personnel and displaying distinguishable badges or other visible identification for meetings with Government personnel. In addition, Contractor personnel shall appropriately identify themselves as Contractor employees in telephone conversations and in formal and informal written correspondence.
1.0.3.3 Contractor personnel under this Task Order shall not engage in any of the inherently Governmental functions listed at FAR Subpart 7.5 or DFARS Subpart 207.5.
1.0.4 Employee Relationship:
1.0.4.1 The services to be performed under this Task Order do not require the Contractor or its personnel to exercise personal judgment and discretion on behalf of the Government. Rather the Contractor's personnel will act and exercise personal judgment and discretion on behalf of the Contractor.
1.0.4.2 Rules, regulations, directives, and requirements that are issued by the U. S. Navy and NSWCPD under its responsibility for good order, administration, and security are applicable to all personnel who enter a government installation or who travel on Government transportation. This is not to be construed or interpreted to establish any degree of Government control that is inconsistent with a non-personal services contract.
1.0.4.3 Inapplicability of Employee Benefits: This Task Order does not create an employer-employee relationship. Accordingly, entitlements and benefits applicable to such relationships do not apply.
1.0.4.4 It is the Contractor's, as well as the Government's, responsibility to monitor Task Order activities and notify the Contracting Officer if the Contractor believes that the intent of this Section has been or may be violated.
1.0.4.4.1 The Contractor shall notify the Contracting Officer in writing via letter or email within three (3) calendar days from the date of any incident that the Contractor considers to constitute a violation of this Section. The notice should include the date, nature, and circumstances of the conduct; the name, function, and activity of each Government employee or Contractor official or employee involved or knowledgeable about such conduct; identify any documents or substance of any oral communication involved in the conduct; and the Contractor's estimated date when, absent a response, cost, schedule or performance will be impacted.
1.0.4.4.2 The Contracting Officer will, within five (5) calendar days after receipt of notice, respond to the notice in writing. In responding, the Contracting Officer will either:
| (i) | Confirm the conduct is in violation and when necessary direct the mode of further performance, |
| (ii) | Countermand any communication regarded as a violation, |
| (iii) | Deny that the conduct constitutes a violation and when necessary direct the mode of further performance, or |
| (iv) | In the event the notice is inadequate to make a decision, advise the Contractor what additional information is required, and establish the date by which it should be furnished by the Contractor. |
1.1 BACKGROUND
1.1.1 The Littoral Combat Ship Independence Variant (LCS-2V) fleet is facing significant obsolescence challenges with the Waterjet Control Unit (WCU) across LCS 6 through 38, impacting operational readiness and maintenance. These issues stem from obsolete and soon-to-be-obsolete hardware and software components, creating a critical sustainment risk for the Waterjet propulsion system. Different ships of the LCS-2V fleet face varying obsolescence timelines. LCS 6 through 24 are immediately impacted by obsolete Mitsubishi hardware and Beijer E1101 human machine interface (HMI) screens. LCS 26 through 30 is currently installed with the same obsolete Mitsubishi hardware, but the Beijer X2 Pro HMI screens are expected to become obsolete in 2027. LCS 32 through 38 face imminent software obsolescence with the WAGO Programmable Logic Controllers (PLC) license expiration, in addition to the 2027 obsolescence of the Beijer X2 Pro HMI screen.
1.1.2 Compounding the obsolescence issues are recurring failures of steering and reversing hydraulic cylinders due to wire breaks, affecting maneuverability. These failures interrupt the signal path between cylinder position sensors and the WCU, Engineering Control System (ECS) and bridge control (Bullnose), impacting both the primary Follow-Up (FU) and backup Non-Follow-Up (NFU) steering systems. The current system architecture lacks redundancy, if there is a loss of signal from a FU cylinder, the system cannot determine the position of the cylinder. This vulnerability underscores the need for a software or hardware solution that allows seamless switching between FU and NFU signals in case of failure. To address the widespread obsolescence concerns, a comprehensive effort with the original equipment manufacturer (OEM) is desired, encompassing costs for developing initial solutions for the LCS 32 through 38 configurations, as well as backfit solutions for LCS 6 through 30. This would include funding for prototype materials, shipset materials for onboard testing, and software modifications to enhance system reliability and functionality. Another issue that the Navy is facing is that there is inconsistency in the software to view system parameters. To assist with troubleshooting there should be a screen on the HMI that displays the inputs of the system and their corresponding readings. The Navy needs a screen programed into software that will show system parameters without a passcode.
1.1.3 These cylinder failures are happening more frequently than originally anticipated when this software configuration was implemented. Now, after years of operation, it has become apparent that The Navy needs to have the ability to calibrate the Waterjets without relying on OEM support. When a cylinder fails, the ship must secure the effected jet and limit steering angles of the two neighboring Waterjets, significantly impacting the ship’s maneuverability. The ship must operate in this degraded condition until an OEM technician can be brought on board to calibrate the new cylinder after installation of a replacement part. Even when a cylinder is replaced in a timely manner, the Waterjet is still considered down until a calibration can be completed. The ships’ dependency on OEM support prevents the ship from performing and meeting its mission requirements which comes at a high cost both financially and operationally to The Navy. These software enhancements should include the ability to calibrate cylinders and Regal cards at the Ship/Shore Facility and the capability to inject NFU signals into the FU circuit in the event of FU cylinder failure, restoring bridge control.
1.2 SCOPE OF WORK
1.2.1 The contractor shall provide all labor, materials, equipment, specialty tools and software, and technical expertise required to fulfill the following scopes of supply.
1.2.2 Defense Maritime Solutions (DMS) shall develop a solution for the obsolescence of the WCUs on the LCS 2V class. This upgrade shall be implemented across the whole LCS 2V class for a total of seventeen (17) shipsets.
1.2.2.1 DMS shall develop and implement a solution on LCS 32 through 38 to enable installation and licensing of the requisite Lipstronic software on the WCU WAGO PLCs. This solution shall address the current inability to license and install the software due to the expired agreement with the third-party vendor. The deliverable shall include all necessary procedures, software modifications, licensing agreements, and documentation required to ensure long-term sustainment of the WCU PLC software across the affected LCS-2V hulls.
1.2.2.2 DMS shall develop a new HMI software update that will allow trained ships force to view and adjust Waterjet steering and reversing cylinder position parameters which will allow the individuals to better operate, troubleshoot, and maintain the equipment and significantly reduce equipment downtime. This software upgrade package shall include a passcode protected calibration page that allows trained personnel within The Navy to access necessary parameters to properly calibrate the Waterjet steering and reversing cylinders and Regal cards. DMS will develop instructions to be included with the delivery that outlines how to upload the software package.
1.2.2.3 DMS shall define the requirements and develop the changes needed to create feedback redundancy of the Waterjet sensors for the FU and NFU control systems. This feedback redundancy upgrade shall provide the capability to exchange the signals between the FU and NFU control systems. This scope is for the delivery of a software and hardware update package for the FU and NFU control systems, including ILS products such as removal, installation, and operating instructions, electrical control drawings and diagram updates, and any other necessary documentation changes.
1.2.2.4 DMS shall develop a software change that allows Navy personnel to access all logic parameters. This change should allow users to easily see all Waterjet system parameters without the need for a passcode or lock. The parameter screen can be used for viewing purposes only and allows personnel to troubleshoot the system. The screen should display the current pressures readings from all pressure transducers, along with all true or false signals that the WCU is reading.
1.2.2.5 DMS shall procure new HMI screens for LCS 26 through 38 to address impending obsolescence in 2027. This procurement will provide new hardware for the WCU, enabling visual monitoring of parameters and facilitating troubleshooting. The replacement screen should in theory be a form fit, and function replacement, but could also be a full replacement. This solution should also include any associated ILS products to be updated.
1.2.2.6 DMS shall develop and deliver a fully functional prototype of the proposed WCU system for the LCS 32 through 38 configuration. This prototype shall incorporate all hardware and software modifications outlined in the approved design solution and be demonstrably capable of replicating all WCU functionalities. The prototype will be used for comprehensive testing and validation to ensure its compatibility and performance meet or exceed the requirements of the existing system.
1.2.2.7 DMS shall develop comprehensive shipboard installation and testing procedures for the redesigned WCU system and execute those procedures on a designated hull with the LCS 32 through 38 configuration. The installation procedures shall detail all necessary steps for the safe and efficient removal of the existing system and installation of the new design, including any required ship alterations. The testing procedures shall define specific tests, metrics, and data collection requirements to validate the performance, functionality, and reliability of the new WCU in a shipboard environment. The tests carried out should prove the entire functionality of the Waterjet system. All test results and associated data shall be documented and delivered in a comprehensive test report.
1.2.2.8 In addition, DMS shall backfit obsolete Mitsubishi hardware and HMI screens for LCS 6 through 30. As part of this backfit solution, DMS should provide a solution for obsolete components and thoroughly test these replacements to ensure compatibility and performance. Moreover, DMS shall backfit new, supported parts to ships with obsolete components, and the software changes that were previously stated above, ensuring long-term maintainability and operational readiness across the LCS fleet. The solution should include the removal of old obsolete components and installation of new replacement parts. The solution should include changes that will have to be made due to the different hydraulic and electric configurations on 6 through 26, 28 and 30, and 32 through 38 hulls.
1.2.3 The contractor shall develop and perform any testing to shock qualify the new WCU before installing on the rest of the ship sets.
1.2.4 The contractor shall aid in developing any Ship Design Changes (SCD) that need to be completed. The contractor shall also help with the development of any documentation that goes along with any of these changes.
1.2.5 The contractor shall provide a Rough Order of Magnitude (ROM) cost estimate to complete the recommended efforts to the Waterjet steering system.
2.0 APPLICABLE DOCUMENTS
2.1 NAVSEA S9247-AR-MMC-010 Rev 04, Technical Manual for Waterjet Propulsion System; Models WLD 1500 SR and WLD 1720 SR; Operation and Maintenance Manual; LCS 6-26 Hulls
2.2 NAVSEA S9247-AR-MMC-A10 Rev 01, Technical Manual for Waterjet Propulsion System; Models WLD 1500 SR and WLD 1720 SR; Operation and Maintenance Manual; LCS 28 and Follow Hulls
2.3 NAVSEA S9247-AR-MMC-020 Rev 02, Technical Manual for Waterjet Hydraulic and Lubrication System; Model WLD 1500 SR and WLD 1720 SR; Installation, Operation and Maintenance Manual
2.4 NAVSEA S9247-AR-MMC-A20 Rev 00, Technical Manual for Waterjet Hydraulic and Lubrication System; Model WLD 1500 SR and WLD 1720 SR; Installation, Operation and Maintenance Manual for LCS 28AF
2.5 NAVSEA S9247-AS-MMC-010 Rev 00, Technical Manual for Waterjet Control System; Lipstronic/j LCS
2.6 NAVSEA S9247-AS-MMC-A10 Rev 00, Technical Manual for Waterjet Control System; Lipstronic/j LCS 28, 30
2.7 NAVSEA S9247-AS-MMC-B10 Rev 00, Technical Manual for Waterjet Control System; Lipstronic/j LCS 32AF
2.8 Detail Specification MIL-DTL-901E, Shock Test, High Impact Shipboard Machinery, Equipment, and Systems
The Contractor shall reference and utilize the latest version available when performing tasks within this SOW.
3.0 REQUIREMENTS
3.1 The contractor shall provide all labor, materials, equipment, special tools, and technical expertise required to complete the scope of work described in Section 1.2. The operational condition of the Waterjet hydraulic steering system including cylinders, controls, and HMI screen directly impacts the operability of the Waterjets; therefore, the intent of these system design changes is to address multiple obsolescence issues on the Waterjet system WCU and improve the functionality of the overall Waterjet propulsion system. These changes will reduce the frequency of downtime as well as reduce the length of time the system is down due to an individual failure. In support of these efforts, the following requirements are established.
3.2 The contractor shall develop, submit and maintain a project plan that demonstrates the contractor’s understanding of the task order requirements and establishes critical and measurable task milestones (CDRL A001). The project plan shall also include the requisite tasks and sub-tasks that connect the project milestones, and the predecessor/successor relationship of each task and sub-task, such that a clear path to task completion is represented. For each task and sub-task, baseline start/end dates and task durations shall be established. As the project progresses, actual start/end dates and revised (if necessary) task durations shall be included in revisions to the project plan, in addition to the baseline start/end dates. The contractor shall attach a completion percentage to each task and sub-task, and the percentage complete for each task shall roll up to the milestone and overall project levels, such that a clear and supportable completion percentage is reflected at the task order, milestone and task/sub-task levels. The first submittal of the project plan shall be no later than two weeks after task order award, and subsequent submittals shall be made in conjunction with each bi-weekly status meeting.
3.3 Design and Develop for LCS 32 through 38 (CLIN 001): The contractor shall design and develop the following for ships LCS 32 through 38.
3.3.1 The contractor shall develop and implement a solution for the WAGO PLC software licensing issue affecting 32 through 38 hulls, ensuring licenses for the Lipstronic software can be provisioned and maintained. This should include securing a new licensing agreement with the appropriate vendor or developing an alternative licensing mechanism. (CDRL A002).
3.3.2 The contractor shall develop and include all necessary procedures, software modifications, licensing agreements, and documentation required to ensure long-term sustainment.
3.3.3 The contractor shall develop the following software package upgrade for LCS 32 through 38 resulting in four (4) shipsets (CDRL A002).
3.3.3.1 The contractor shall implement a new, password-protected calibration page within the HMI software, allowing trained Navy personnel to adjust cylinder position setpoints as defined in the Waterjet cylinder calibration procedure.
3.3.3.2 The contractor shall provide a solution to allow the In-Service Engineering Agents (ISEAs) to access the password protected software, so they are able to troubleshoot the system.
3.3.3.3 The contractor shall develop the hardware and software requirements for creating feedback redundancy within the steering control sensors and the signals between the FU and NFU systems. This feedback redundancy upgrade of the Waterjet system should exchange the signals between FU and NFU controls to reduce loss of steering casualties when a wire break occurs.
3.3.3.4 The contractor shall include all ILS products such as, removal, installation, and operating instructions, electrical control diagrams and drawings updates, and any other necessary documentation changes.
3.3.3.5 The software package shall include an update to allow personnel to access and display all system parameters without the need for a passcode or lock. The parameter screen can be used for viewing purposes only and allows personnel to troubleshoot the system.
3.3.3.6 This deliverable will include instructions for all software updates for uploading the new software package and any other instruction needed for testing, configuring, troubleshooting, and operating the new system and control screens.
3.3.3.7 The software package files shall be sent by the contractor to The Navy TPOC with installation and testing to be done by a qualified DMS field service engineer.
3.3.4 The contractor shall develop a fully functional prototype of the modified WCU system, incorporating all software and hardware changes, specifically for the LCS 32 through 38 configurations (CDRL A002).
3.3.4.1 The prototype shall be an approved design and be demonstrable of the capability of replicating all current WCU function.
3.3.4.2 This prototype shall undergo comprehensive testing and validation to ensure compatibility and performance meet or exceed existing system requirements. A comprehensive test report documenting the results shall be delivered.
3.3.4.3 The contractor shall provide prototype reports (CDRL A002) for approval before moving forward to installation onto other LCS 32 through 38 hulls.
3.3.5 The contractor shall develop all requirements, removal, installation and test procedures, operational instructions, and material for a WCU replacement kit. The contractor will procure all required components to complete these kits (CDRL A002).
3.3.5.1 The procedures shall define specific tests, metrics, and data collection requirements to validate the performance, functionality, and reliability of the new WCU in a shipboard environment. A comprehensive test report documenting the results shall be delivered.
3.4 Design and Develop for LCS 6 through 30 (CLIN 002): The contractor shall design and develop the following for ships LCS 6 through 30.
3.4.1 The contractor shall develop and include all necessary procedures, software modifications, licensing agreements, and documentation required to ensure long-term sustainment.
3.4.2 The contractor shall develop the following software package upgrade for LCS 6 through 30 resulting in thirteen (13) shipsets (CDRL A002).
3.4.2.1 The contractor shall implement a new, password-protected calibration page within the HMI software, allowing trained Navy personnel to adjust cylinder position setpoints as defined in the Waterjet cylinder calibration procedure.
3.4.2.2 The contractor shall provide a solution to allow the In-Service Engineering Agents (ISEAs) to access the password protected software, so they are able to troubleshoot the system.
3.4.2.3 The contractor shall develop the hardware and software requirements for creating feedback redundancy within the steering control sensors and the signals between the FU and NFU systems. This feedback redundancy upgrade of the Waterjet system should exchange the signals between FU and NFU controls to reduce loss of steering casualties when a wire break occurs.
3.4.2.4 The contractor shall include all ILS products such as, removal, installation, and operating instructions, electrical control diagrams and drawings updates, and any other necessary documentation changes.
3.4.2.5 The software package shall include an update to allow personnel to access and display all system parameters without the need for a passcode or lock. The parameter screen can be used for viewing purposes only and allows personnel to troubleshoot the system.
3.4.2.6 This deliverable will include instructions for all software updates for uploading the new software package and any other instruction needed for testing, configuring, troubleshooting, and operating the new system and control screens.
3.4.2.7 The software package files shall be sent by the contractor to The Navy TPOC with installation and testing to be done by a qualified DMS field service engineer.
3.4.3 The contractor shall develop a fully functional prototype of the modified WCU system, incorporating all software and hardware changes, specifically for the LCS 6 through 30 configurations (CDRL A002).
3.4.3.1 The prototype shall be an approved design and be demonstrable of the capability of replicating all current WCU function.
3.4.3.2 This prototype shall undergo comprehensive testing and validation to ensure compatibility and performance meet or exceed existing system requirements. A comprehensive test report documenting the results shall be delivered.
3.4.3.3 The contractor shall provide prototype reports (CDRL A002) for approval before moving forward to installation onto other LCS 6 through 30 hulls.
3.4.4 The contractor shall develop all requirements, removal, installation and test procedures, operational instructions, and material for a WCU replacement kit. The contractor will procure all required components to complete these kits (CDRL A002).
3.4.4.1 The procedures shall define specific tests, metrics, and data collection requirements to validate the performance, functionality, and reliability of the new WCU in a shipboard environment. A comprehensive test report documenting the results shall be delivered.
3.5 Procure, Implement, and Test (CLIN 003): The contractor shall provide all materials, equipment, tools, hardware, and software for the following:
3.5.1 The contractor shall provide a solution to replace the HMI screens on LCS 26 through 38. DMS shall provide seven (7) shipsets to the Navy. The hardware shall be available for purchase in case of operational issues. This deliverable shall include all technical document updates including but not limited to electrical and controls drawings, operation and troubleshooting instructions, installation procedures, and parts list. The contractor shall provide the government with all design changes for review (CDRL A002).
3.5.2 The installation and testing of the initial shipset shall be done by trained DMS personnel per OEM guidance. Any necessary changes or adjustments identified during installation and testing in this phase shall be implemented prior to the delivery of the remaining shipset deliverables.
3.5.3 The contractor shall develop and perform environmental qualification testing for the prototype units to prove that it will be Shock B qualified (CDRL A004).
3.5.4 The contractor shall adapt the developed WCU system modifications stated in Section 3.4 for LCS 6 through 30, accounting for differences in hydraulic system configurations. This includes developing specific removal, installation and testing procedures for these hulls and conducting shipboard testing on a designated vessel within this range. A comprehensive test report documenting the results shall be delivered (CDRL A002).
3.5.5 The contractor shall backfit obsolete Mitsubishi hardware and HMI screens for LCS 6 through 30. The contractor shall provide a solution for obsolete components and thoroughly test the replacements to ensure compatibility and performance (CDRL A002).
3.5.6 Any affected drawing shall be modified and updated to reflect the new arrangement of the WCU cabinet and delivered as a PDF in electronic format to The Navy TPOC.
3.6 Install on LCS 32 (CLIN 004): The contractor shall install the updated WCU design on
3.6.1 Following successful testing of one prototype on a LCS 32 through 38 configuration, the contractor shall develop and deliver WCU replacements to LCS 32.
3.6.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.6.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 32.
3.7 Install on LCS 34 (CLIN 005): The contractor shall install the updated WCU design on
3.7.1 Following successful testing of one prototype on a LCS 32 through 38 configuration, the contractor shall develop and deliver WCU replacements to LCS 34.
3.7.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.7.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 34.
3.8 Install on LCS 36 (CLIN 006): The contractor shall install the updated WCU design on
3.8.1 Following successful testing of one prototype on a LCS 32 through 38 configuration, the contractor shall develop and deliver WCU replacements to LCS 36.
3.8.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.8.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 36.
3.9 Install on LCS 38 (CLIN 007): The contractor shall install the updated WCU design on
3.9.1 Following successful testing of one prototype on a LCS 32 through 38 configuration, the contractor shall develop and deliver WCU replacements to LCS 38.
3.9.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.9.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 38.
3.10 Install on LCS 6 (CLIN 008): The contractor shall install the updated WCU design on
3.10.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 6.
3.10.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.10.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 6.
3.11 Install on LCS 8 (CLIN 009): The contractor shall install the updated WCU design on
3.11.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 8.
3.11.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.11.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 8.
3.12 Install on LCS 10 (CLIN 010): The contractor shall install the updated WCU design on
3.12.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 10.
3.12.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.12.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 10.
3.13 Install on LCS 12 (CLIN 011): The contractor shall install the updated WCU design on
3.13.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 12.
3.13.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.13.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 12.
3.14 Install on LCS 14 (CLIN 012): The contractor shall install the updated WCU design on
3.14.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 14.
3.14.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.14.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 14.
3.15 Install on LCS 16 (CLIN 013): The contractor shall install the updated WCU design on
3.15.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 16.
3.15.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.15.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 16.
3.16 Install on LCS 18 (CLIN 014): The contractor shall install the updated WCU design on
3.16.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 18.
3.16.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.16.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 18.
3.17 Install on LCS 20 (CLIN 015): The contractor shall install the updated WCU design on
3.17.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 20.
3.17.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.17.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 20.
3.18 Install on LCS 22 (CLIN 016): The contractor shall install the updated WCU design on
3.18.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 22.
3.18.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.18.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 22.
3.19 Install on LCS 24 (CLIN 017): The contractor shall install the updated WCU design on
3.19.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 24.
3.19.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.19.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 24.
3.20 Install on LCS 26 (CLIN 018): The contractor shall install the updated WCU design on
3.20.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 26.
3.20.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.20.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 26.
3.21 Install on LCS 28 (CLIN 019): The contractor shall install the updated WCU design on
3.21.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 28.
3.21.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.21.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 28.
3.22 Install on LCS 30 (CLIN 020): The contractor shall install the updated WCU design on
3.22.1 Following successful testing of one prototype on a LCS 6 through 30 configuration, the contractor shall develop and deliver WCU replacements to LCS 30.
3.22.1.1 Each replacement shall include all necessary hardware, software, removal procedures, installation procedures, test procedures, and operational instructions. The contractor is responsible for procuring all components required for these replacements (CDRL A002).
3.22.2 The contractor shall perform shipboard removal, installation and testing procedures for the redesigned WCU system and execute those procedures on LCS 30.
3.23 Drawings and Documentation Updates: All affected drawings and documentation, including but not limited to shall be updated to reflect the WCU system modifications and delivered electronically as PDFs to the Navy TPOC. This includes updates to electrical and control drawings, operational and troubleshooting instructions, installation procedures, and parts lists, ILS documentation, technical manuals, and maintenance procedures.
3.24 Project Plan and Reporting: The contractor shall develop and maintain a detailed project plan (CDRL A001) and submit a comprehensive technical report (CDRL A002) upon completion of all tasks. The report shall include all required details as outlined in previous responses.
3.25 Environmental Qualifications: Upon completion of the tested and approved WCU prototype the contractor shall develop and perform testing to ensure the system in shock, vibration, and environmentally qualified (CDRL A004)
3.26 Technical Report Development (CDRL A002): Upon completion of the SOW scope, as defined in Section 1.2 & 3.3 through 3.22, the contractor shall develop and submit a comprehensive report to include:
3.26.1 Detailed parts list of all hardware and software included in the deliverables described above.
3.26.2 Engineering drawing list of all updated and new drawings, schematics, etc. and copies of those documents created or used for the development, design, removal, installation and operation of these upgrades.
3.26.3 Operating procedures for using and troubleshooting the new Waterjet software and controls.
3.27 The contractor should develop and deliver ILS products for each configuration to include tech manual updates and APL creation and updates.
3.28 Conclusion and recommendations, to include:
3.28.1 Rough Order of Magnitude (ROM) estimate for additional removal, installation, inspections, testing, and/or analysis required to validate the software upgrades installed on LCS 6 through 38.
3.28.2 ROM estimate for generation of Engineering Change Proposal (ECP) to backfit HMI panels and WCU cabinets using replacement kits provided by DMS.
3.28.3 Any additional recommendation(s) and/or design change(s) which should reduce downtime frequency of the Waterjets and improve overall ship readiness.
3.28.4 Any Ship Design Change (SCD) change(s) and documentation that is associated with it.
3.29 Manufacturing Phase-Out or Discontinuation of Production, Diminishing Sources, and Obsolete Materials or Components
3.29.1 The contractor shall notify the contracting officer immediately upon determining the unavailability of obsolete materials or components. The contractor may recommend a solution to include the impact on the contract price and delivery. The contractor shall not initiate any item redesign or incur any additional costs without the express, written authorization of the contracting officer.
3.30 Diminishing Manufacturing Sources and Material Shortages Management (DMSMS) Contract Requirements
Not applicable.
3.31 Parts Obsolescence
Not applicable.
4.0 DATA REQUIREMENTS
· CDRL A001, Contract Status Report
· CDRL A002, Engineering and Technical Services Accomplishment Report
· CDRL A003, Travel Report
· CDRL A004, Dynamic Shock Analysis Extension Request
· CDRL A005, Unauthorized Supplier Purchase Report
· CDRL A006, Counterfeit Prevention Plan
· CDRL A007, Condition Found Report (CFR) (Command)
· CDRL A008, Equipment Installation Instructions
5.0 SECURITY REQUIREMENTS
5.1 SECURITY TRAINING. The Contractor is responsible for completing all required Government mandated training to maintain security and network access to government sites and IT systems to include but not limited to: Antiterrorism Level 1 Awareness; Records Management in the DON: Everyone's Responsibility; Training and Readiness: The Active Shooter; NAVSEA Introduction to Controlled Unclassified Information; Operations Security (OPSEC); NAVSEA Counterintelligence Training; Privacy and Personally Identifiable Information (PII) Awareness Training; NAVSEA Physical Security training and Cybersecurity 101 Training. Certificates of successful completion shall be sent to the COR and as otherwise specified in the contract.
5.1.1 In accordance with the National Industrial Security Program Operating Manual (NISPOM) (37 CFR Part 117), Contractor personnel that require access to Department of Navy (DON) information systems and/or work on-site require an open investigation or favorable adjudicated Tier 3 by the Vetting Risk Operations Center (VROC). An interim clearance is granted by VROC and recorded in the Defense Information System for Security (DISS). An open or closed investigation with a favorable adjudication is required prior to issuance of a badge providing access to NSWCPD buildings. Furthermore, if the Navy Central Adjudication Facility, have made an unfavorable determination access will be denied. For Common Access Card (CAC) you must have an open investigation and/or a favorably adjudicated investigation. Interim security clearance are acceptable for a CAC. Access will be denied for anyone that has eligibility pending in DISS. Vetting through the National Crime Information Center, Sex Offender Registry, and the Terrorist screening database shall be process for a contractor that does not have a favorable adjudicated investigation.
5.1.2 Within 30 days after Task Order award, the contractor shall submit a list of all contractor personnel, including subcontractor employees, who will have access to DON information systems and/or work on-site at one of the NSWCPD sites to the appointed Contracting Officer Representative (COR) via email. The contractor shall provide each employee's first name, last name, Task Order number, the NSWCPD technical code, work location, whether or not the employee has a CAC and or Standard Access Control Badge (SACB), the systems the employee can access (i.e., NMCI, RDT&E), and the name of the Contractor's local point of contact, phone number and email address. Throughout the period of performance of the contract, the Contractor shall immediately provide any updated information to the COR when any Contractor personnel changes occur including substitutions or departures.
5.2 ON SITE WORK. Contractor personnel that require a badge to work on-site at one of the NSWCPD sites must provide an I-9 form to verify proof of citizenship. The I-9 form should be signed by the company Facility Security Officer or the company Human Resource Department. In addition to the I-9 form, Contractors shall also bring their birth certificate, current United States Passport or naturalization certificate and state issued ID to the NSWCPD Security Officer at the time of badge request to verify citizenship. Any contractor that has unfavorable information that has not been favorably adjudicated, by Department of Defense Central Adjudication Facility (DOD CAF) will not be issued a badge. Finally, contractors shall supply a copy of their OPSEC Training Certificate or other proof that the training has been completed.
5.3 DD254 REQUIREMENT.
Not applicable.
5.4 OPERATIONS SECURITY (OPSEC)
5.4.1 The Contractor shall protect critical information associated with this contract to prevent unauthorized disclosure. The NSWC Philadelphia Division's (NSWCPD) Critical Information List (CIL)/ CIIL (Critical Indicators and information list) will be provided on site, if warranted. Performance under this contract requires the contractor to adhere to OPSEC requirements, which may include the NSWCPD Contractor OPSEC Plan. When the NSWCPD Contractor OPSEC Plan is required, the contractor shall return acknowledgment of the plan within 15 days of receipt. During the period of this contract, the Contractor may be exposed to, use, or produce, NSWCPD Critical Information (CI) and/or observables and indicators which may lead to discovery of CI. NSWCPD’s CI will not be distributed to unauthorized third parties, including foreign governments, or companies under Foreign Ownership, Control, or Influence (FOCI) unless such FOCI has been appropriately mitigated through measures approved by the Defense Counterintelligence and Security Agency. Questions concerning these requirements shall be directed to the PCO.
5.4.2 CUI correspondence transmitted internally on the contractor's unclassified networks or information systems, and externally, shall be protected per NIST SP-800-171, Protecting Controlled Unclassified Information (CUI) in Non-federal Systems and Organizations.
Assembled large components/systems being transported to and from testing areas, other production or government facilities (whether or not on public roadways) shall be in an enclosed van trailer or covered flatbed trailer. Component/System outside storage, staging, and test areas shall be shielded/obscured from public view wherever physically possible.
5.4.3 NSWCPD’s CI shall not be publicized in corporate wide newsletters, trade magazines, displays, intranet pages or public facing websites. Media requests related to this project shall be directed to the PCO, and the COR who will forward the required to the NSWCPD Public Release Authority for review.
5.4.4 Any attempt by unauthorized third parties to solicit, obtain, photograph, or record, or; incidents of loss/compromise of government Classified or CI, Business Sensitive, Company Proprietary information related to this or other program must be immediately reported to the contractor's Facility Security Officer and Cognizant Security Office and/or the Naval Criminal Investigative Service, and the NSWC PD Security Division (Code 105).
5.4.5 This SOW has been reviewed against the requirements of SECNAVINST 4200.35. SAIRC controls are not required.
5.5 RECEIPT, STORAGE, AND GENERATION OF CONTROLLED UNCLASSIFIED INFORMATION (CUI). All Controlled Unclassified Information (CUI) associated with this Task Order must follow the minimum marking requirements of DoDI 5200.48, Section 3, paragraph 3.4.a, and include the acronym "CUI" in the banner and footer of the document. In accordance with DoDI 5200.48, CUI must be safeguarded to prevent Unauthorized Disclosure (UD). CUI export controlled technical information or other scientific, technical, and engineering information must be marked with an export control warning as directed in DoDI 5230.24, DoDD 5230.25, and Part 250 of Title 32, CFR. Nonfederal information systems storing and processing CUI shall be protected per NIST SP-800-171, or subsequent revisions. All transmissions to personal email accounts (AOL, Yahoo, Hotmail, Comcast, etc.) and posting on social media websites (Facebook, Instagram, Twitter, LinkedIn, etc.) are prohibited. Destroy CUI associated with this Task Order by any of the following approved methods: A cross-cut shredder; a certified commercial destruction vendor; a central destruction facility; incineration; chemical decomposition; pulverizing, disintegration; or methods approved for classified destruction.
5.6 PLANNING, PROGRAMMING, BUDGETING AND EXECUTION (PPBE) DATA. When contractor employees, in the performance of their duties, are exposed to Planning, Programming, Budgeting and Execution (PPBE) data, a Non-Disclosure Agreement (NDA) with all affected contactor personnel must be executed in coordination with the COR and PCO to ensure safeguarding disclosure of this data.
5.7 U-NNPI SECURITY REQUIREMENTS
Not applicable.
5.8 U-NNPI
Not applicable.
6.0 PLACE OF PERFORMANCE
6.1 The contractor's primary place of performance shall be at the Contractor’s facilities in Virginia Beach, VA and Drunen, Netherlands. 100% of the work should occur at the Contractor’s facility.
6.1.1 The Government will not provide office space, phones, fax machines, computers, printers or other related work accommodations or equipment for Contractor personnel under this Contract.
7.0 TRAVEL
7.1 The Contractor may be required to travel from the primary performance location when supporting this requirement. The estimated number of trips is forty (40) for the entire period of performance.
The contractor shall be required to travel CONUS to accomplish the tasks contained in this contract. Travel in support of this requirement is anticipated to include, but may not be limited to, the following alternate performance locations:
CONUS/
OCONUS
| ORIGIN: |
| DESTINATION: |
| Number of Days Per Trip |
| Number of Trips |
| Number of People |
| CONUS |
| Virginia Beach, VA |
| San Diego, CA |
| 6 |
| 20 |
| 2 |
| CONUS |
| Drunen, Netherlands |
| San Diego, CA |
| 8 |
| 2 |
| 1 |
7.2 The number of times the Contractor may be required to travel to each location cited above may vary as program requirements dictate, provided that the total estimated travel cost is not exceeded. The numbers of trips and types of personnel traveling shall be limited to the minimum required to accomplish work requirements.
This is the start of the file's text. The full file is on GovTribe.