This document is a Brand Name or Equal Specification for a free-standing relocatable lithium battery storage locker manufactured by Safety Storage Incorporated. The detailed specification outlines a Class I Div 2 storage building with dimensions of 38L x 14W x 9H, weighing not more than 42,900 lbs, and featuring a 1,828-gallon sump capacity. The locker includes multiple safety and functional components such as double fire-rated doors (3HR and 1-1/2HR), hurricane zone wind load structural upgrade, R10 wall/ceiling/subfloor insulation, crane lifting eyes, aircraft tie-downs, water sprinkler sub-assembly, access ramps, air conditioners, heaters, and extensive explosion-proof electrical systems including ventilation, lighting, gas detection, and alarm systems.

The associated federal contract opportunity is a small business set-aside solicitation (N61331-25-T-JK34) issued by the Department of the Navy Naval Sea Systems Command. Vendors must email quotes to jamell.l.kilgore.civ@us.navy.mil by Tuesday, 12 Aug 2025 at 11am Central Time, including full specifications, CAGE code, and lead time. The government will award the contract based on best value considering pricing, delivery, quality, and past performance. The procurement requires one Safety Storage Locker with a 150-day delivery timeline after contract award, and vendors must be capable of invoicing through Wide Area Workflow (WAWF) with NET 30-day payment terms.

View the file

Other files

File Type Posted
A5 - Statement of Work.pdf PDF
C12. Clauses-Supply.pdf PDF
A8 - Exhibit A CDRL.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BRAND NAME OR EQUAL SPECIFICATIONS

FOR

FREE STANDING RELOCATABLE LITHIUM BATTERY STORAGE LOCKER

The structure includes the following components for storage of flammable or combustible liquids and other hazardous materials.

Brand: Safety Storage Incorporated

Building Type: Class I Div 2 min. Interior/ General Purpose Exterior

Dimensions: 38L x 14W x 9H Model "FS" Storage Building

Weight: Not to exceed with Options 42,900 lbs

Sump Capacity (Gal): 1828 gallons

Protection: 14’W FS/S Model - High Velocity Hurricane Zone Wind Load Structural Upgrade

Doors: Double Door, 60 W x 80"H, 3HR Fire-Rated

Doors: Double Door, 60 W x 80"H, 1-1/2HR Fire-Rated (± 70 psf windstorm rating)

Panic Exit: Panic Exit Rim Device on the Active Leaf (Not for Windstorm Doors)

Wall Insulation 817.00 R10 Wall Insulation (Free Standing Model)

Ceiling Insulation: 469.00 R10 Ceiling Insulation (Free Standing Model)

Subfloor Insulation: 469.00 R10 Subfloor Insulation, Door Insulation: R10 Insulation, Double Door (Fire-Rated & Noncombustible Steel Models)

Register Adjustable manual regulation of air flow

Crane Lifting Eyes: Set of 4 (Maximum capacity: 24,000lbs)

Aircraft Tie-Downs: 5"W x 6"H galvanized 1" thick "D" ring welded to structure with 3" diameter interior clearance and 180° swing at full strength rating.

Water Sprinkler Sub Assembly: Water sprinkler piping subassembly equipped with UL Listed and FM Approved sprinkler head(s) and an exterior 1-1/2 NPT (National Pipe Thread) fitting (threaded & capped).

Sprinkler Heads 5 each

Ramps: Access Ramp (48 W x 88 L) fabricated from 3/16 plate steel with 12GA formed side walls and protected with a safety yellow coating. Securely held in place with two 1/2 diameter inserts located in the door thresholds.

Air Conditioners: (Class I, Division 2 Grp A-D), UL and cUL Listed, 14,500/14,000 (BTU/hr), 230/208V

Heater: (Fan-Forced, 15.0kW, 240/208V, 3-Phase, 51, 180 BTU/HR) (Explosion-Proof) (Class I, Division 1 Groups C&D)

Exterior Guard: Bolt-on exterior air conditioner guard, constructed of heavy gauge tubular steel, with a corrosive-resistant polyurethane finish

Exhaust Ventilation: Exterior Low Mount (Explosion Proof) (Class I, Division 1 Groups C&D) with

Snap-Type Switch (Non Explosion-Proof)

Heat Sensor: Exhaust Shutdown (Explosion-Proof) (Class I, Division 1 Groups C&D)

Fan Timer: 24Hr Mechanical (Non Explosion-Proof)

Interior Lighting Fixture: 20W (Class I, Division 2 Groups A-D) with Exterior Light Switch (Non-

Explosion-Proof)

Interior Lighting Fixture: Additional LED Low Profile Lighting Fixture, 20W (Class I, Division 2 Groups

A-D) (Does not include switch)

Exterior Lighting: 300W Quartz (Non Explosion-Proof), with Photocell (Non Explosion Proof)

Emergency Local Alarm System: Non Explosion-Proof Switch and Alarm

Sprinkler Flow Switch System: (Non Explosion-Proof)

Gas Detection System: (Class I, Division 1 Groups B-D) with Non Explosion-Proof Alarm Horn

Strobe Light: (Non Explosion Proof)

Receptacle: 120V (Single Gang) While-In-Use Weather Cover (Non-Explosion-Proof)

Load Center: Three Phase (Nema 3R)

Special Coating: Maxshell (Exterior Only)

Gas Detector: iTrans 2 Detector