This document is a Brand Name or Equal Specifications file for a free-standing relocatable chemical storage and containment structure by Safety Storage Incorporated. The specification details a Class I Div 2 storage building with dimensions of 8L x 14W x 9H, designed for storing flammable or combustible liquids and hazardous materials. Key features include double fire-rated doors, a 1,828-gallon sump capacity, high velocity hurricane zone wind load structural upgrade, R10 wall/ceiling/subfloor insulation, crane lifting eyes, aircraft tie-downs, water sprinkler system with 5 sprinkler heads, access ramp, UL-listed air conditioners and heaters, exhaust ventilation, interior and exterior lighting, gas detection system, and special exterior Maxshell coating.

The associated federal contract opportunity is a small business set-aside solicitation (N61331-25-T-JK27) issued by the Department of the Navy Naval Sea Systems Command for DLA Distribution Guam, Marianas. Vendors must email quotes by 16 June 2025 at 11am Central Time to jamell.l.kilgore.civ@us.navy.mil, including full specifications, CAGE code, and lead time. The procurement requires small businesses under NAICS 332311, with ability to invoice through Wide Area Workflow (WAWF). Award will be based on best value considering pricing, delivery, quality, and past performance, with a 150-day delivery timeline after contract award.

View the file

Other files

File Type Posted
A5 - Statement of Work.pdf PDF
A8 - Exhibit A CDRL.pdf PDF
C12 - Clauses-Supply_Over_SAT.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BRAND NAME OR EQUAL SPECIFICATIONS

FOR

FREE STANDING RELOCATABLE CHEMICAL STORAGE AND CONTAINMENT STRUCTURE

The structure includes the following components for storage of flammable or combustible liquids and other hazardous materials.

Brand: Safety Storage Incorporated

Building Type: Class I Div 2 min. Interior/ General Purpose Exterior

Dimensions: 8L x 14W x 9H Model "FS" Storage Building

Weight: Not to exceed with Options 42,900 lbs

Sump Capacity (Gal): 1828 gallons

Protection: High Velocity Hurricane Zone Wind Load Structural Upgrade

Doors: Double Door, 60 W x 80"H, 3HR Fire-Rated

Doors: Double Door, 60 W x 80"H, 1-1/2HR Fire-Rated (± 70 psf windstorm rating)

Panic Exit: Panic Exit Rim Device on the Active Leaf (Not for Windstorm Doors)

Wall Insulation 817.00 R10 Wall Insulation (Free Standing Model)

Ceiling Insulation: 469.00 R10 Ceiling Insulation (Free Standing Model)

Subfloor Insulation: 469.00 R10 Subfloor Insulation, Door Insulation: R10 Insulation, Double Door (Fire-Rated & Noncombustible Steel Models)

Register Adjustable manual regulation of air flow

Crane Lifting Eyes: Set of 4 (Maximum capacity: 24,000lbs)

Aircraft Tie-Downs: 5"W x 6"H galvanized 1" thick "D" ring welded to structure with 3" diameter interior clearance and 180° swing at full strength rating.

Water Sprinkler Sub Assembly: Water sprinkler piping subassembly equipped with UL Listed and FM Approved sprinkler head(s) and an exterior 1-1/2 NPT (National Pipe Thread) fitting (threaded & capped).

Sprinkler Heads 5 each

Ramps: Access Ramp (48 W x 88 L) fabricated from 3/16 plate steel with 12GA formed side walls and protected with a safety yellow coating. Securely held in place with two 1/2 diameter inserts located in the door thresholds.

Air Conditioners: UL-Listed (Class I, Division 2 Groups A-D) air conditioner. Hermetically sealed compressor with solid-state control relays and commercial grade enclosed motor with hermetically sealed overload for arc-free operation. Hot gas bypass allows operation at outdoor ambient temperatures as low as 45°F without freezing up.

Heater: UL Listed (Class I, Division 1 Groups C&D) Fan-Forced Heater (51,180 Btu/hr, 15.0kW, 240/208V, 3-Phase) with built-in Thermostat (Class I, Division 1 Groups C&D). The heater s NEC Operating Temperature Code is T3B and it is rated for hazardous atmospheres with autoignition temperatures at or above 329°F.

Exterior Guard: Bolt-on exterior air conditioner guard, constructed of heavy gauge tubular steel, with a corrosive-resistant polyurethane finish

Exhaust Ventilation: UL Listed totally enclosed (Class I, Division 1 Groups C&D) motor (60 Hz, 1- Phase) housed inside an exterior end wall enclosure. Non-static & non-sparking

12 diameter fan blade to preclude the ignition of hazardous vapors. Exterior exhaust fan housing constructed of heavy gauge steel, with an exterior polyurethane finish for maximum chemical & corrosion resistance. Interior exhaust vent located within 12 of the floor for the extraction of heavier-than-air vapors. Exterior exhaust fan port opening protected with a UL Classified fire damper having a 3-hour fire protection rating. Fire damper has a galvanized steel frame, curtain-type galvanized steel blades, and a UL Listed 165°F fusible link. Exterior exhaust port equipped with shutter assembly. Equipped with an exterior UL Listed Non Explosion-Proof fan switch (snap type) suitable for outdoor locations. Automatic system shutdown if fire occurs.

Heat Sensor: Exhaust Shutdown (Explosion-Proof) (Class I, Division 1 Groups C&D)

Fan Timer: 24Hr Mechanical (Non Explosion-Proof)

Interior Lighting Fixture: Interior ETL/CETL-Listed (Class I, Division 2 Groups A-D) LED low profile light fixture with one 20W lamp and an exterior UL Listed Non Explosion-Proof light switch (snap type) suitable for outdoor locations.

Interior Lighting Fixture: Additional Interior ETL/CETL-Listed (Class I, Division 2 Groups A-D) LED low profile light fixture with one 20W lamp.

Exterior Lighting: 300W Quartz (Non Explosion-Proof), with Photocell (Non Explosion Proof)

Emergency Local Alarm System: Non Explosion-Proof Switch and Alarm

Sprinkler Flow Switch System: (Non Explosion-Proof)

Gas Detection System: (Class I, Division 1 Groups B-D) with Non Explosion-Proof Alarm Horn

Strobe Light: (Non Explosion Proof)

Receptacle: 120V (Single Gang) While-In-Use Weather Cover (Non-Explosion-Proof)

Load Center: UL Listed, 208/120V or 240/120V, 125A, three-phase load center (NEMA 3R) with circuit breaker(s) and main breaker.

Special Coating: Maxshell (Exterior Only)

Gas Detector: iTrans 2 Detector