PROJECT LOCATION: 12295
STRONG RD.
GULF SHORES, AL 36542
PROJECT LOCATION: 12295
STRONG RD.
GULF SHORES, AL 36542
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C e rt ifi c a te o f A u th o ri za tio n N u m b e r:
P
E F
E xp ir a tio n
/3
/2
P e a ch tr e e D u n w o o d y R o a d
B u ild in g C
S u ite
A tla n ta
G
.3
.1 w ile yw ils o n .c o m
E m p lo ye e -O w n e d
/2
/2
:3 :4
P
M fs h \U se rP ro fil e
\n e s se r\ D o cu m e n ts \2
R
C
A rc h
B o n
S e co u r_ n e ss e r4
C N
F R
.r vt
COVER SHEET
F
IS
H
W
IL
D L
IF
E
S E
R V
IC
E
S B
O N
S E
C O
U R
N A
T
IO
N A
L W
IL
D
L
IF
E R
E F
U G
E
B O
N S
E C
O U
R V
IS
IT
O R
C E
N T
E R
A
D M
IN
IS
T R
A T
IO
N
SAT
NXE
05/02/2024
230182
G-001
NXE
S
T R
O N
G R
D
G U
L F
S H
O R
E S
A
L
IS
SU
ED
F
O R
C O
N
STR
U C
TIO
N
NOT TO SCALE
VICINITY MAP
NOT TO SCALE
LOCATION MAP
M R
K D
A T
E R
E V
I S
IO
N D
E S
C R
IP
T
IO
N
120'60'30'0'
SCALE: 1"=60'-0"
120'60'30'0'
SCALE: 1"=60'-0"
120'60'30'0'
100'50'25'0'
SCALE: 1"=50'-0"
20'10'5'0'
SCALE: 1"=10'-0"
80'40'20'0'
SCALE: 1"=40'-0"
80'40'20'0'
SCALE: 1"=40'-0"
80'40'20'0'
60'30'15'0'
SCALE: 1"=30'-0"
60'30'15'0'
SCALE: 1"=30'-0"
60'30'15'0'
40'20'10'0'
SCALE: 1"=20'-0"
40'20'10'0'
SCALE: 1"=20'-0"
40'20'10'0'
9"6"3"0'
SCALE: 3"=1'-0"
1'6"3"0'
SCALE: 2"=1'-0"
18"1'6"0'
SCALE: 1-1/2"=1'-0"
2'1'6"0'
SCALE: 1"=1'-0"
3'2'1'0'
SCALE: 3/4"=1'-0"
4'2'1'0'
SCALE: 1/2"=1'-0"
6'4'2'0'
SCALE: 3/8"=1'-0"
8'4'2'0'
SCALE: 1/4"=1'-0"
12'8'4'0'
SCALE: 3/16"=1'-0"
16'8'4'0'
SCALE: 1/8"=1'-0"
24'16'8'0'
SCALE: 3/32"=1'-0"
32'16'8'0'
SCALE: 1/16"=1'-0"
ARCHITECTURAL GRAPHIC SCALES ENGINEERING GRAPHIC SCALES
FISH & WILDLIFE SERVICES
BON SECOUR NATIONAL
WILDLIFE REFUGE
BON SECOUR VISITOR CENTER & ADMINISTRATION
12295 STRONG RD.
GULF SHORES, AL 36542
ISSUED FOR
CONSTRUCTION
05/02/2024
5/ 2/
5/ 2/
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C e rt ifi c a te o f A u th o ri za tio n N u m b e r:
P
E F
E xp ir a tio n
/3
/2
P e a ch tr e e D u n w o o d y R o a d
B u ild in g C
S u ite n ta
.3
.1 yw ils o n .c o m
E m p lo ye e -O w n e d
/2
/2
:3 :5
P
M fs h \U se rP ro fil e
\n e s se r\ D o cu m e n ts \2
R
C
A rc h
B o n
S e co u r_ n e ss e r4
C N
F R
.r vt
SHEET INDEX & PROJECT
GENERAL NOTES
F
IS
H
W
IL
D L
IF
E
S E
R V
IC
E
S B
O N
S E
C O
U R
N A
T
IO
N A
L W
IL
D
L
IF
E R
E F
U G
E
B O
N S
E C
O U
R V
IS
IT
O R
C E
N T
E R
A
D M
IN
IS
T R
A T
IO
N
SAT
NXE
05/02/2024
230182
G-002
NXE
S
T R
O N
G R
D
G U
L F
S H
O R
E S
A
L
IS
SU
ED
F
O R
C O
N
STR
U C
TIO
N
SHEET INDEX
SHEET NUMBER SHEET NAME
REVISION
NUMBER DATE DESCRIPTION
P-801 DOMESTIC WATER RISER DIAGRAMS
P-802 SANITARY WASTE RISER DIAGRAM
11 MECHANICAL
M-001 LEGEND, ABBREVIATIONS & GENERAL NOTES
M-101 FIRST FLOOR DUCTWORK PLAN
M-201 FIRST FLOOR MECHANICAL PIPING PLAN
M-301 ENLARGED PLANS AND SECTIONS
M-501 DETAILS
M-601 SCHEDULES
M-701 CONTROLS
12 ELECTRICAL
E-001 ELECTRICAL LEGENDS AND SYMBOLS
E-002 ELECTRICAL GENERAL NOTES AND ABBREVIATIONS
E-100 SITE PLAN
E-101 LIGHTING PLAN
E-102 POWER PLAN
E-103 MECHANICAL POWER PLAN
E-104 TELECOMMUNICATION & TECHNICAL SECURITY PLAN
E-105 LIGHTNING PROTECTION & GROUNDING PLAN
E-501 DETAILS
E-601 LIGHTING DIAGRAMS
E-701 ONE-LINE & PANEL SCHEDULES
SHEET INDEX
SHEET NUMBER SHEET NAME
REVISION
NUMBER DATE DESCRIPTION
00 GENERAL
G-001 COVER SHEET
G-002 SHEET INDEX & PROJECT GENERAL NOTES
GL001 LIFE SAFETY - CODE ANALYSIS
GL101 LIFE SAFETY - FIRST FLOOR PLAN
04 CIVIL
V-001 TOPOGRAPHIC SURVEY
C-001 CIVIL NOTES, ABBREVIATIONS, AND LEGENDS
C-101 EXISTING CONDITIONS AND DEMOLITION PLAN
C-102 SITE PLAN
C-103 GRADING PLAN
C-104 EROSION AND SEDIMENT CONTROL PLAN
C-501 CIVIL DETAILS
C-502 CIVIL DETAILS
06 STRUCTURAL
S-001 STRUCTURAL GENERAL NOTES
S-002 STRUCTURAL GENERAL NOTES
S-003 SPECIAL INSPECTIONS
S-004 SPECIAL INSPECTIONS
S-005 SPECIAL INSPECTIONS
S-101 FOUNDATION PLAN
S-102 ROOF FRAMING PLAN
S-201 TRUSS ELEVATIONS
S-202 CFS STRAP BRACE ELEVATIONS
S-203 TOWER ELEVEVATIONS
S-301 STRUCTURAL SECTIONS
S-311 STRUCTURAL SECTIONS
S-312 STRUCTURAL SECTIONS
S-401 PARTIAL PLANS
S-501 TYPICAL FOUNDATION DETAILS
S-511 TYPICAL CFS DETAILS
S-521 TYPICAL FRAMING DETAILS
S-601 WALL WIND PRESSURE ELEVATIONS
S-602 ROOF UPLIFT DIAGRAM
07 ARCHITECTURAL
AG001 GENERAL NOTES & ABBREVIATIONS
AG002 LEGENDS
A-101 OVERALL FIRST FLOOR PLAN
A-102 FIRST FLOOR RCP
A-103 ROOF PLANS
A-104 ROOF PLANS
A-201 OVERALL BUILDING ELEVATIONS
A-202 OVERALL BUILDING ELEVATIONS
A-301 OVERALL BUILDING SECTIONS
A-302 OVERALL BUILDING SECTIONS
A-311 WALL SECTIONS
A-401 TOILET ACCESSORY DIAGRAMS
A-402 SHOWER ACCESSORY DIAGRAMS
A-410 ENLARGED RESTROOM PLANS AND ELEVATIONS
A-411 INTERIOR ELEVATIONS & DETAILS
A-412 MILLWORK PLANS & SECTIONS
A-550 COLUMN PLAN & SECTION DETAILS
A-561 SECTION DETAILS
A-601 AIR, THERMAL AND MOISTURE PROTECTION
DIAGRAMS
A-602 HORIZONTAL ASSEMBLIES
A-603 EXTERIOR VERTICAL ASSEMBLIES
A-604 EXTERIOR VERTICAL ASSEMBLIES & EXPANSION
JOINT & PENETRATION DETAILS
A-611 INTERIOR PARTITION SCHEDULE
A-631 DOOR SCHEDULE
A-632 DOOR DETAILS
A-640 WINDOW SCHEDULE
A-641 WINDOW DETAILS
A-701 MATERIAL AND FINISH SCHEDULE
A-702 INTERIOR DETAILS
A-901 2D/3D PRESENTATION VIEWS
08 INTERIOR
I-801 FURNITURE PLAN
I-811 SIGNAGE SCHEDULES
I-812 TYPICAL SIGNAGE DETAILS & DOORWAY LOCATIONS
10 PLUMBING
P-001 LEGEND, ABBREVIATIONS & GENERAL NOTES
P-101 FIRST FLOOR PRESSURE PIPING PLAN
P-201 FIRST FLOOR SANITARY PIPING PLAN
P-301 ENLARGED PLANS AND SECTIONS
P-501 DETAILS
P-601 SCHEDULES
M R
K D
A T
E R
E V
I S
IO
N D
E S
C R
IP
T
IO
N
PROJECT GENERAL NOTES
20 THE CONTRACTOR OR ANY OF HIS EMPLOYEES, OR
SUB-CONTRACTORS MUST NOT SCALE THESE DRAWINGS FOR
DIMENSIONS. IF THERE IS ANY QUESTION CONCERNING THE
DIMENSIONS THE CONTRACTOR MUST CONTACT THE ARCHITECT TO
CLARIFY THE DIMENSIONS.
21 VERIFY THAT THERE ARE NO UTILITIES IN THE AREA OF
CONSTRUCTION OR PROTECT ALL KNOWN UTILITIES BEFORE ANY
WORK IS STARTED.
22 FIELD VERIFY ALL CONDITIONS, DIMENSIONS AND CLEARANCES
PRIOR TO THE COMMENCEMENT OF WORK OR ORDERING OF
MATERIALS. ANY DEVIATIONS FROM THE CONTRACT DOCUMENTS
MUST BE REPORTED TO THE ARCHITECT IN WRITING PRIOR TO THE
PROCEEDING WITH THAT PORTION OF WORK.
23 THE FLOOR ELEVATIONS INDICATED ON ARCHITECTURAL DRAWINGS
ARE REFERENCED FROM THE TOP OF THE FIRST FLOOR
STRUCTURE/SLAB (DATUM) ELEVATION OF 00.00 FEET. REFER TO
CIVIL DRAWINGS FOR ABSOLUTE ELEVATION.
24 DIMENSIONS INDICATED FOR INTERIOR ARE FROM THE FACE OF
STUD FACE OF MASONRY STRUCTURE OR FACE OF EXISTING
SURFACES UNLESS OTHERWISE NOTED.
25 DIMENSIONS INDICATED FOR EXTERIOR ARE FROM THE EXTERIOR
FACE OF WALL.
26 DIMENSIONS FOR EXISTING WORK ARE INDICATED AS "±". ALL
DISCREPANCIES MUST BE BROUGHT TO THE IMMEDIATE ATTENTION
OF THE CONTRACTING OFFICER IN WRITING.
27 ALL WOOD MUST BE PRESSURE TREATED WHEN IN CONTACT THE
GROUND OR CONCRETE.
28 ALL WOOD BLOCKING AND MISCELLANEOUS STEEL SHOWN IN
DETAILS AND SECTIONS MUST BE CONTINUOUS UNLESS
SPECIFICALLY NOTED OTHERWISE.
29 MAINTAIN ALL MEANS OF EGRESS DURING CONSTRUCTION OR MAKE
ARRANGEMENTS FOR CODE COMPLIANT EXITS FOR TIMES WHEN
THE BUILDING IS OCCUPIED.
30 COORDINATE ALL WORK INCLUDING, SOFFIT FRAMING AS NEEDED
WITH ALL WORK SHOWN ON THE MECHANICAL, PLUMBING,
FIRE-PROTECTION, ELECTRICAL AND STRUCTURAL DRAWINGS.
31 FOLLOW LATEST ASTM C840 AND USG GYPSUM CONSTRUCTION
HANDBOOK FOR THE INSTALLATION AND RECOMMENDED
LOCATIONS OF CONTROL JOINTS IN GYPSUM BOARD WALLS AND
CEILINGS, TYPICAL U.N.O.
PROJECT GENERAL NOTES
1. THE DRAWINGS ARE PREPARED AND COORDINATED WITH THE
PROJECT MANUAL WHICH INCLUDE TECHNICAL SPECIFICATIONS.
THEY, ALONG WITH OTHER DOCUMENTS ISSUED BY WILEY | WILSON
AND ENUMERATED IN THE OWNER-CONTRACTOR AGREEMENT,
MUST FORM THE CONSTRUCTION DOCUMENTS. A DIRECTIVE
STATED IN ONE DOCUMENT MUST BE UNDERSTOOD AS STATED IN
ALL. ANY AMBIGUITIES OR INCONSISTENCIES MUST BE RESOLVED
BY WILEY | WILSON.
2 DRAWING REFERENCES ARE FOR CONVENIENCE ONLY AND DO NOT
LIMIT THE EXTENT OF APPLICATION OF THE DRAWINGS OR DETAILS.
ALL DIMENSIONS, DESCRIPTIONS AND/OR SYMBOLS WITHIN A
DRAWING ARE COMPLEMENTARY. DRAWINGS AND SPECIFICATIONS
WHETHER TAKEN SEPARATELY OR TOGETHER ARE TO BE
INTERPRETED ACCORDING TO THEIR FULL INTENT, MEANING, AND
SPIRIT; AND MUST BE DEEMED TO EXPLIN MUTUALLY EACH OTHER
AND TO BE DESCRIPTION OF THE WORK TO BE DONE UNDER THE
CONTRACT.
3 THE OWNER RESERVES THE RIGHT TO REJECT MATERIAL AND OR
WORK THAT IS NOT IN STRICT ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
4 ALL WORK INDICATED MUST INCLUDE ALL LABOR, MATERIALS AND
FINISHED ASSEMBLIES NECESSARY TO MAKE A COMPLETE,
PROPERLY WORKING AND FINISHED INSTALLATION.
5 COMPLY WITH ALL APPLICABLE AND GOVERNING CODES AND
REGULATIONS; AND MUST COMPLY WITH ALL LIFE SAFETY
REQUIREMENTS OF APPLICABLE GOVERNING AUTHORITIES. ALL
WORK MUST BE PERFORMED IN STRICT ACCORDANCE WITH ALL
APPLICABLE FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.
SEE SHEET GL001 FOR ADDITIONAL CODE INFORMATION.
6 ALL WORK MUST BE IN ACCORDANCE WITH ACCEPTED HIGH
QUALITY CONSTRUCTION PRACTICES AND STANDARDS AND DONE IN
A WORKMAN-LIKE MANNER.
7 IF AN UNSAFE CONDITION OR A LIFE THREATHENING HAZARD IS
NOTED AT THE SITE, NOTIFY THE ARCHITECT AND THE AUTHORITY
HAVING JURISDICTION IMMEDIATELY.
8 CONFIRM AND VERIFY WITH THE OWNER PRIOR TO STARTING WORK
ANY RULES OR REGULATIONS FOR THE USE AND CONSTRUCTION ON
THE PROPERTY WITH RESPECT TO BUT NOT LIMITED TO HOURS OF
CONSTRUCTION, LIMITS OF WORK, OPERATIONS OF THE BUILDING,
SAFETY OF THE OWNERS EMPLOYEES OR GENERAL LOCATIONS OF
DUMPSTERS, USE OF THE OWNER’S UTILITIES AND FACILITIES,
SCHEDULING OF DELIVERIES, ETC.
9 COORDINATE WITH THE OWNER ALL WORK SO AS TO AVOID
DISRUPTION TO THE NORMAL OPERATIONS AND WORK OF THE
OWNER.
10 INSTALL ALL MANUFACTURED ITEMS IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
11 MANUFACTURER'S NAMES AND/OR MODEL NUMBERS CITED ARE
USED TO PROVIDE AN INDICATION OF QUALITY, STYLE AND/OR SIZE
DESIRED. OTHER MANUFACTURERS ARE ACCEPTABLE IF PRODUCTS
ARE EQUAL IN QUALITY, STYLE AND SIZE.
12 MANUFACTURER'S NAMEPLATES, INCLUDING TRADEMARK AND
OTHER IDENTIFYING SYMBOLS, MUST NOT BE PERMITTED IN
SURFACES VISIBLE TO THE PUBLIC, UNLESS OTHERWISE INDICATED
IN THE CONTRACT DOCUMENTS.
13 REMOVE ALL CONSTRUCTION AND/OR DEMOLITION DEBRIS FROM
THE JOB SITE TO MAINTAIN A CLEAN AND SAFE ENVIRONMENT AND
TO PREVENT THE POSSIBILITY OF A FIRE OR LIFE SAFETY HAZARD.
14 ANY DISCREPANCIES BETWEEN THE EXISTING CONDITIONS AND THE
CONTRACT DOCUMENTS, OR ANY AMBIGUITIES OR
INCONSISTENCIES CONTAINED THEREIN, MUST BE REPORTED TO
THE ARCHITECT IMMEDIATELY, AND A SUITABLE RESOLUTION
ESTABLISHED PRIOR TO THE SUBMITTAL OF BIDS OR THE BEGINNING
OF THE AFFECTED WORK. WORK THAT PROCEEDS IN VIOLATION OF
THIS PRINCIPLE IS AT THE CONTRACTOR'S OWN RISK, AND THE COST
OF ANY CHANGES REQUIRED BY THE CLIENT TO SUITABLY MODIFY
SUCH WORK MUST BE SOLELY THE RESPONSIBILITY OF THE
CONTRACTOR.
15 SAFEGUARD THE OWNERS' PROPERTY AND ADJACENT PROPERTIES
DURING CONSTRUCTION AND MUST PROTECT FROM DAMAGE ANY
EXISTING OR ADJACENT FINISHES, MATERIALS, FIXTURES OR
BUILDING ASSEMBLIES. REPAIR ALL AREAS AFFECTED BY THE
CONSTRUCTION AS REQUIRED TO MAINTAIN THEIR EXISTING
APPEARANCE, UNLESS NOTED OTHERWISE.
16 MUST NOT REMOVE, ALTER, LOAD, PENETRATE OR ADD TO ANY
EXISTING BUILDING ASSEMBLY OR STRUCTURE WHICH MAY
COMPROMISE ITS INTEGRITY OR STRUCTURAL STABILITY OR THE
INTEGRITY AND STRUCTURAL STABILITY OF ADJACENT BUILDING
ASSEMBLIES WITHOUT PRIOR INVESTIGATION, REMEDY OR ACTION.
17 IF DEMOLITION IS REQUIRED, PROTECT ALL AREAS SCHEDULED TO
REMAIN. REPAIR ALL SURFACES AND FINISHES TO MATCH EXISTING,
AFTER DEMOLITION IS COMPLETE. IF A PORTION OF AN EXISTING
WALL TO REMAIN IS DEMOLISHED, THE ENTIRE WALL OR CEILING
MUST BE PAINTED AFTER NEW CONSTRUCTION IS COMPLETED.
DEMOLITION OF ENTIRE PROJECT IS REQUIRED
18 IF DEMOLITION IS REQUIRED, THE CONTRACTOR MUST BE
RESPONSIBLE FOR MAINTAINING THE STRUCTURAL INTEGRITY OF
THE BUILDING DURING DEMOLITION AND CONSTRUCTION. THE
CONTRACTOR MUST BRACE ALL STRUCTURAL ELEMENTS DURING
DEMOLITION AND NEW CONSTRUCTION AS REQUIRED. THE
CONTRACTOR MUST INFORM THE ARCHITECT OF ANY STRUCTURAL
CONDITIONS UNCOVERED DURING THE DEMOLITION AND NEW WORK
WHICH ARE NOT ADDRESSED ON THE CONSTRUCTION DOCUMENTS.
19 IF DEMOLITION IS REQUIRED, CONTRACTOR MUST MAINTAIN SAFE
PUBLIC ACCESS TO AND FROM ALL BUILDING EXITS AT ALL TIMES.
CONTRACTOR MUST COORDINATE WITH OWNER THE SCHEDULING
OF WORK TIMES, PRIOR TO COMMENCEMENT OF ANY AND ALL
WORK.
5/ 2/
PROJECT SCOPE:
NEW CONSTRUCTION OF A VISITOR CENTER AND OFFICES FOR THE BON SECOUR WILDLIFE REFUGE
ZONING:
N/A
OCCUPANCY CLASSIFICATION (IBC CH 3, 304, 311:
BUSINESS GROUP B
CONTROL AREAS (IBC TABLE 414.2.2):
PERMITTED: N/A
PROPOSED: N/A
ALLOWABLE HEIGHT IN FEET (IBC TABLE 504.3):
MAXIMUM PERMITTED: 55 FEET, NOT SPRINKLERED (TYPE IIB)
PROVIDED: 30 FEET 0 INCHES
ALLOWABLE NUMBER OF STORIES (IBC TABLE 504.4):
MAXIMUM PERMITTED: 2 STORIES, NOT SPRINKLERED (TYPE IIB)
PROVIDED: 1 STORY
AREA LIMITATION (IBC 505.2.1):
MAXIMUM PERMITTED: AGGREGATE FLOOR AREA OF MEZZANINE NOT > 1/3 OF FLOOR AREA OF THAT SPACE.
PROVIDED: N/A
ALLOWABLE FLOOR AREA (IBC TABLE 506.2):
MAXIMUM PERMITTED: 23,000 SQFT NOT SPRINKLERED GROUP-B (TYPE IIB)
PROVIDED: 4440 GROSS SQFT
FIRE RESISTANCE REQUIREMENTS (IBC TABLE 601):
CONSTRUCTION TYPE:
PROPOSED: TYPE IIB
STRUCTURAL FRAME, INCLUDING COLUMNS:
REQUIRED: NO FIRE RESISTANCE RATING
PROVIDED: NO FIRE RESISTANCE RATING
FLOORS, INCLUDING SUPPORT BEAMS:
REQUIRED: NO FIRE RESISTANCE RATING
PROVIDED: NO FIRE RESISTANCE RATING
ROOF, INCLUDING SUPPORT BEAMS:
REQUIRED: NO FIRE RESISTANCE RATING
PROVIDED: NO FIRE RESISTANCE RATING
EXTERIOR WALL PROJECTION DISTANCE (IBC TABLE 705.2):
REQUIRED: EXCEPTION - BUILDINGS ON SAME LOT NOT REQUIRED TO COMPLY
PROVIDED: NO FIRE SEPARATION DISTANCE FOR PROJECTIONS.
BUILDINGS ON SAME LOT (IBC TABLE 705.3):
ASSUME IMAGINARY LINE BETWEEN BUILDINGS FOR DETERMINING REQUIRED WALL AND OPENING PROTECTION
FIRE-RESISTANCE RATINGS (IBC TABLE 705.5):
MIN. DISTANCE OF PROJECTION: 30FEET OR GREATER FIRE SEPARATION DISTANCE MUST HAVE NO LIMIT FOR EXPOSURE
FROM BOTH SIDES.
PROVIDED: BUILDING SEPARATION IS MORE THAN 30 FEET FROM ADJACENT STRUCTURES.
ALLOWABLE AREA BASED ON FIRE SEPARATION DISTANCE (IBC TABLE 705.8):
MAXIMUM PERMITTED: ALLOWABLE AREA PERMITTED FOR 30 FEET OR GREATER SEPARATION DISTANCE
PROVIDED: NO LIMIT
FIRE BARRIERS: INTERIOR FIRE RESISTANCE SEPARATION (IBC SECTION 707):
MECHANICAL ROOM (IBC TABLE 509).1:
REQUIRED: 1-HOUR FIRE RESISTANCE RATING WHERE EQUIPMENT IS OVER 400,000 BTU PER HOUR INPUT
PROVIDED: NOT EXCEEDED, NOT REQUIRED
INFORMATION TECHNOLOGY EQUIPMENT (ITE) ROOM (NFPA 75 SECTION 6.1.3.4):
REQUIRED: 1-HOUR FIRE RESISTANCE RATING
PROVIDED: 1-HOUR FIRE RESISTANCE RATING
STORAGE ROOMS
NOT REQUIRED TO BE SEPARATED BY SMOKE OR FIRE RESISTANCE RATED CONSTRUCTION IN
ACCORDANCE WITH IBC, AS THESE SPACES STORE ROUTINE OFFICE SUPPLIES.
OPENING PROTECTION IN 1-HOUR WALLS, EXCLUDING SHAFT, EXIT ENCLOSURE AND EXIT PASSAGEWAY WALLS (IBC TABLE 716.1(2)):
REQUIRED: 45-MINUTE FIRE DOORS
PROVIDED: N/A
OPENING PROTECTION IN 2-HOUR WALLS, EXCLUDING SHAFT, EXIT ENCLOSURE AND EXIT PASSAGEWAY WALLS (IBC TABLE 716.1(2)):
REQUIRED: 1 1/2-HOUR FIRE DOORS
PROVIDED: N/A TO PROJECT
CORRIDORS (IBC 1020):
REQURIED: OCCUPANT LOAD SERVED BY CORRIDOR GREATER THAN 30 MUST HAVE 1 HOUR FIRE-RESISTANCE RATING.
PROVIDED: N/A
MEANS OF EGRESS:
OCCUPANT LOAD (IBC 1004):
REQUIRED: 150 GROSS SQFT FOR BUSINESS AREAS, 500 GROSS FOR WAREHOUSES
TOTAL OCCUPANT LOAD: SEE SHEET GI002
NUMBER OF EXITS (IBC 1006.1):
REQUIRED: 2 (OCCUPANCY LOAD DOES NOT EXCEED 600 PERSONS)
PROVIDED: 2
TWO EXITS ARE REQUIRED .
THE EXITS ARE ALSO ARRANGED TO DISCHARGE DIRECTLY TO THE OUTSIDE AND CONFIGURED TO
PREVENT UNOCCUPIED AREAS FROM OPENING DIRECTLY INTO AN EXIT ENCLOSURE.
EXIT CAPACITY (IBC SECTION 1005.3.2):
REQUIRED: 32 INCHES (0.2 INCH PER OCCUPANT FOR OTHER EGRESS COMPONENTS)
PROVIDED: 32 INCHES
TRAVEL DISTANCE (IBC 1017.1):
MAXIMUM PERMITTED: 200 FEET WITHOUT SPRINKLER SYSTEM
MAXIMUM PROVIDED: -- FEET
COMMON PATH OF TRAVEL ( IBC SECTION 1016.2.1):
MAXIMUM PERMITTED: 75 FEET WITHOUT SPRINKLER SYSTEM
MAXIMUM PROVIDED: -- FEET -- INCHES
DEAD-END CORRIDORS (IBC 1020.5):
MAXIMUM PERMITTED: 20 FEET
MAXIMUM PROVIDED: 20 FEET
INTERIOR FINISHES (IBC CHAPTER 8):
EXIT ENCLOSURES: CLASS A OR B
EXIT ACCESS CORRIDORS: CLASS A OR B
ROOMS AND ENCLOSED SPACES: CLASS A, B OR C
FLOOR FINISH: CLASS I OR II
SPECIFIC WALL AND FLOOR FINISHES WILL BE SHOWN ON THE INTERIOR FINISH SCHEDULE
EMERGENCY LIGHTING (IBC 1008.3.5):
ALL MEANS OF EGRESS, INCLUDING EXIT ACCESS CORRIDORS AND EXIT DISCHARGE WILL BE PROVIDED WITH EMERGENCY LIGHTING. EMERGENCY LIGHTING WILL BE PROVIDED VIA STANDARD FIXTURES ON THE EMERGENCY POWER SYSTEM CONNECTED TO A CENTRALIZED INVERTER SYSTEM. EMERGENCY LIGHTING WILL ALSO BE PROVIDED IN THE MECHANICAL ROOM. EMERGENCY LIGHTING WILL BE PROVIDED FOR A MINIMUM OF 1½ HOURS IN THE EVENT OF INTERNAL POWER FAILURE. AVERAGE ILLUMINATION WILL NOT BE LESS THAN 10 LUX (1-FOOT CANDLE) WITH A MINIMUM OF 1 LUX (0.1-FOOT
CANDLE) AT ANY POINT.
EXIT SIGNS (IBC 1013.1):
EXIT SIGNS MUST BE INTERNALLY-ILLUMINATED LED TYPE. BACKUP POWER TO THE EXIT SIGNS WILL BE VIA A CENTRALIZED INVERTER SYSTEM CONNECTED TO THE EMERGENCY CIRCUIT. SIGNS WILL BE LOCATED AT ALL BUILDING EXITS AND
WHENEVER THE DIRECTION TO THE EXIT IS NOT READILY APPARENT.
PORTABLE FIRE EXTINGUISHERS (IBC SECTION 906):
PORTABLE FIRE EXTINGUISHERS REQUIRED IN GROUPS A,B,E,F,H,I,M,R-1,R-2,R-4 AND S OCCUPANCIES. PORTABLE FIRE EXTINGUISHERS WILL BE SIZED AND SPACED IN ACCORDANCE WITH NFPA 10. AT LEAST ONE CLASS 4A:80B:C RATED DRY CHEMICAL PORTABLE FIRE EXTINGUISHER WILL BE PROVIDED FOR EVERY 11,250 SQUARE FEET OF FLOOR AREA AND LOCATED SUCH THAT AN OCCUPANT TRAVELS NO MORE THAN 75 FEET BEFORE REACHING A PORTABLE FIRE EXTINGUISHER IN ALL AREAS OF THE. ONE CLASS 4A:80B:C RATED PORTABLE FIRE EXTINGUISHER WILL BE LOCATED WITHIN 30 FEET OF THE
APPROPRIATE HAZARD, SUCH AS THE MAIN ELECTRICAL PANEL.
FIRE ALARM SYSTEM (IBC SECTION 907):
A FIRE ALARM SYSTEM IS NOT REQUIRED PER CODE. PER EXCEPTION FOR GROUP-B HAVING LESS THAN 500 OCCUPANT LOAD
AND FOR GROUP-S NOT SELF-STORAGE.
ACCESSIBILITY:
ACCESSIBILITY MUST BE AS PER THE 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
PLUMBING FIXTURE COUNT:
PLUMBING CALCULATIONS ARE BASED ON IPC TABLE 403.1 BUSINESS OCCUPANCY.
REQUIRES 1 WATER CLOSET PER 25 FOR THE FIRST 50 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50 OCCUPANTS.
REQUIRES LAVARTORIES OF 1 PER 40 FOR THE FIRST 80 AND 1 PER 80 FOR THE REMAINDER EXCEEDING 80. DRINKING
FOUNTAIN REQUIRES 1 PER 100 OCCUPANTS. 1 SERVICE SINK IS REQUIRED.
The 2021 International Building Code adopted on July 1, 2022 as the State Building Code and enforced by the Division of Construction Management (DCM) includes the following:
Companion Codes
• 2021 International Existing Building Code July 1, 2022
• 2021 International Plumbing Code July 1, 2022
• 2021 International Fuel Gas Code July 1, 2022
• 2021 International Mechanical Code July 1, 2022
• 2020 National Electrical Code (NFPA 70) July 1, 2022
• 2021 International Fire Code July 1, 2022
• July 1, 2022 ANSI/ASHRAE/IES Standard 90.1-2013 Energy Standard for Buildings Except Low-Rise
Residential Buildings, with exceptions permitted to:
• 6.5.1 – Economizers
• 8.4.2 - Automatic Receptacle Control
• 8.4.3 - Electrical Energy Monitoring
• 2010 ADA Standards for Accessible Design April 18, 2011
• These requirements supersede the accessibility requirements contained in the International Building Code and
ANSI A117.1.
DCM Code Supplements
• 2020 ICC/NSSA-500 Standard for the Design and Construction of Storm Shelters July 1, 2022
• 2019 National Fire Alarm and Signaling Code (NFPA 72) July 1, 2022
APPLICABLE BUILDING CODES:
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C e rt ifi c a te o f A u th o ri za tio n N u m b e r:
P
E F
E xp ir a tio n
/3
/2
P e a ch tr e e D u n w o o d y R o a d
B u ild in g C
S u ite n ta
.3
.1 yw ils o n .c o m
E m p lo ye e -O w n e d
/2
/2
:3 :5
P
M fs h \U se rP ro fil e
\n e s se r\ D o cu m e n ts \2
R
C
A rc h
B o n
S e co u r_ n e ss e r4
C N
F R
.r vt
LIFE SAFETY - CODE
ANALYSIS
F
IS
H
W
IL
D L
IF
E
S E
R V
IC
E
S B
O N
S E
C O
U R
N A
T
IO
N A
L W
IL
D
L
IF
E R
E F
U G
E
B O
N S
E C
O U
R V
IS
IT
O R
C E
N T
E R
A
D M
IN
IS
T R
A T
IO
N
SAT
NXE
05/02/2024
230182
GL001
NXE
S
T R
O N
G R
D
G U
L F
S H
O R
E S
A
L
IS
SU
ED
F
O R
C O
N
STR
U C
TIO
N
M R
K D
A T
E R
E V
I S
IO
N D
E S
C R
IP
T
IO
N
OCCUPANCY USE CLASSIFICATION - IBC
# Room Name Occupancy
Classification Area (SF) Floor Area per
OCC
IBC
Occupancy
Gross or Net
Calc Occupant
Load xxx EXTERIOR 1498.91 SF
1498.91 SF 0
101 VISITORS CENTER GROUP-B 424.53 SF 150.00 SF Gross 3
102 CONFERENCE GROUP-B 231.59 SF 150.00 SF Gross 2
103 BREAK GROUP-B 169.60 SF 150.00 SF Gross 2
104 DOUBLE GROUP-B 120.59 SF 150.00 SF Gross 1
105 PRIVATE OFFICE GROUP-B 174.86 SF 150.00 SF Gross 2
106 CORRIDOR GROUP-B 278.82 SF 150.00 SF Gross 2
107 IT/PRINTER GROUP-B 103.01 SF 150.00 SF Gross 1
108 SHOP GROUP-B 111.94 SF 150.00 SF Gross 1
109 EMPLOYEE RR GROUP-B 66.97 SF 150.00 SF Gross 1
111 SPARE PRIVATE OFFICE GROUP-B 90.25 SF 150.00 SF Gross 1
112 MECH. GROUP-B 88.66 SF 150.00 SF Gross 1
113 PUBLIC RR GROUP-B 55.32 SF 150.00 SF Gross 1
114 SPARE PRIVATE OFFICE GROUP-B 108.90 SF 150.00 SF Gross 1
116 CLO. GROUP-B 13.69 SF 150.00 SF Gross 1
GROUP-B 2038.72 SF 20
LEVEL 1 3537.63 SF 20
Grand total 3537.63 SF 20
5/ 2/
5/ 2/
S SS
R E
F
EGRESS PATH & DIRECTION
CALCULATED OCCUPANCY
EGRESS CAPACITY (MAX)
EGRESS DISTANCE
EGRESS START
### OCC
### OCC
FIRE SEPARATION WALL
AUTOMATIC EXTERNAL DEFIBRILLATORAED
FEC FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHERFE
EXIT LIGHT
EXIT LIGHT WITH ARROW
EXIT LIGHT (DOUBLE SIDED)
EMERGENCY LIGHT (WALL MOUNTED)
EMERGENCY LIGHT (CEILING MOUNTED)
EXIT LIGHT (WALL MOUNTED)
1 HOUR FIRE WALL
SMOKE PARTITION
LIFE SAFETY LEGEND
SYMBOL DESCRIPTION
OPEN PERIMETER
O
C C
34'-06"
O
C C
60'-00"
FE
FE
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C e rt ifi c a te o f A u th o ri za tio n N u m b e r:
P
E F
E xp ir a tio n
/3
/2
P e a ch tr e e D u n w o o d y R o a d
B u ild in g C
S u ite n ta
.3
.1 yw ils o n .c o m
E m p lo ye e -O w n e d
/2
/2
:3 :0
P
M fs h \U se rP ro fil e
\n e s se r\ D o cu m e n ts \2
R
C
A rc h
B o n
S e co u r_ n e ss e r4
C N
F R
.r vt
LIFE SAFETY - FIRST
FLOOR PLAN
F
IS
H
W
IL
D L
IF
E
S E
R V
IC
E
S B
O N
S E
C O
U R
N A
T
IO
N A
L W
IL
D
L
IF
E R
E F
U G
E
B O
N S
E C
O U
R V
IS
IT
O R
C E
N T
E R
A
D M
IN
IS
T R
A T
IO
N
SAT
NXE
05/02/2024
230182
GL101
NXE
S
T R
O N
G R
D
G U
L F
S H
O R
E S
A
L
IS
SU
ED
F
O R
C O
N
STR
U C
TIO
N
1 PROVIDE SEMI-RECESSED FIRE EXTINGUISHER CABINETS. PROVIDE
FIRE EXTINGUISHER AT ALL FIRE EXTINGUISHER CABINETS.
2 SURFACE MOUNTED FIRE EXTINGUISHER CABINETS ARE REQUIRED IN
MECHANICAL AND ELECTRICAL SPACES ONLY.
3 ALL ROOM OCCUPANT LOADS ARE BASED ON NFPA 101
CALCULATIONS.
4 PROVIDE APPLICABLE SIGNAGE FOR AED AND FIRE EXTINGUISHERS AS
REQUIRED. SEE SIGNAGE SHEETS FOR ADDITIONAL INFORMATION.
5 SEE WALL TYPES FOR WALL CONSTRUCTION AND ADDITIONAL
INFORMATION AND RATINGS.
6 SEE DOOR SCHEDULE FOR DOOR/FRAME RATINGS.
7 REFER TO CIVIL DRAWINGS FOR THE LOCATION OF THE ADJACENT
BUILDINGS.
8 REFER TO CIVIL DRAWINGS FOR FIRE DEPARTMENT VEHICLE ACCESS.
9 SEE SHEET GL001 FOR ADDITIONAL CODE AND LIFE SAFETY
INFORMATION.
10 PERMANENTLY IDENTIFY WITH SIGNS OR STENCILING THAT ARE NOT
LESS THAN 3 INCHES IN HEIGHT , MIN 3/8 INCH STROKE IN
CONTRACTING COLOR AND LOCATED WITHIN 15 FEET OF EACH END
WALL AND AT INTERVALS NOT EXCEEDING 30 FEET MEASURED
HORIZONTALLY FOR FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
PROTECTED OPENINGS OR PENETRATIONS.
Code_BLDG ANALYSIS - EGRESS
E X
IT
N
U M
B E
R
DOOR (0.20 INCHES PER OCCUPANT)
STAIR (0.3 INCHES PER
OCCUPANT)
MOST
STRINGENT
OCCUPANT LOADSIZE
EGRESS
WIDTH
OCCUPANT
LOAD
EGRESS
WIDTH
OCCUPANT
LOAD
101A 6'-0" 68 340 --- --- 340
101B 3'-0" 32 160 --- --- 160
106 3'-0" 32 160 --- --- 160
112 6'-0" 68 340 --- --- 340
TOTAL: 4
0 2' 4' 8'
PLAN
NORTH
SCALE: 1/4" = 1'-0"
LIFE SAFETY PLAN
M R
K D
A T
E R
E V
I S
IO
N D
E S
C R
IP
T
IO
N
GENERAL SHEET NOTES
5/ 2/
5/ 2/
1. ALL WORK MUST BE PERFORMED IN STRICT COMPLIANCE WITH THE MOST CURRENT
APPLICABLE FEDERAL, STATE , AND LOCAL LAWS AND REGULATIONS, INCLUDING BUT NOT
LIMITED TO, ENVIRONMENTAL PROTECTION AGENCY (EPA), OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION (OSHA), NATIONAL EMISSIONS STANDARDS FOR HAZARDOUS AIR
POLLUTANTS (NESHAPS), AND NATIONAL INSTITUTE OF OCCUPATIONAL SAFETY AND HEALTH
(NIOSH).
2. WHEN DURING THE COURSE OF CONSTRUCTION, ANY OBJECT OF AN UNUSUAL NATURE IS
ENCOUNTERED, CEASE WORK IN THAT AREA AND IMMEDIATELY NOTIFY THE CONTRACTING
OFFICER.
3. GRADING, EXCAVATING, AND CONSTRUCTION OF THE PROJECT MUST NOT COMMENCE UNTIL
THE APPROPRIATE EROSION AND SEDIMENT CONTROL MEASURES ARE IN PLACE AS SPECIFIED
ON THIS PLAN.
4. PROVIDE POSITIVE DRAINAGE AWAY FROM STRUCTURES IN ALL GRADED AREAS.
5. IF PORTABLE TOLIETS ARE NECESSARY FOR THE CONSTRUCTION OF THE PROJECT, LOCATE A
MINIMUM OF 25 FEET AWAY FROM THE NEAREST STORMWATER FEATURE (INLET, SWALE,
POND, ETC.).
6. A SMOOTH GRADE MUST BE MAINTAINED FROM EDGE OF EXISTING PAVEMENT TO CURB AND
GUTTER AND/OR PAVEMENT TO PRECLUDE THE FORMING OF FALSE GUTTERS AND/OR THE
PONDING OF ANY WATER ON THE PAVEMENT. REMOVE AND RECONSTRUCT EXISTING
PAVEMENT AND/OR CURB AS DICTATED BY FIELD CONDITIONS TO PROVIDE POSITIVE
DRAINAGE AT TIE-IN-POINTS.
7. ALL SOLID WASTE, HAZARDOUS WASTE, AND HAZARDOUS MATERIALS MUST BE MANAGED IN
ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL ENVIRONMENTAL
REGULATIONS.
8. ALL EXISTING UTILITIES MAY OR MAY NOT BE SHOWN IN THEIR EXACT LOCATION. CONTRACTOR
TO VERIFY LOCATIONS OF EXISTING UTILITIES PRIOR TO START OF CONSTRUCTION.
9. REPAIR ANY ACTIVE UTILITIES DAMAGED DURING CONSTRUCTION AND NOTIFY THE
CONTRACTING OFFICER OF THE DAMAGE.
10. LENGTHS OF LINES INDICATED ON THE DRAWINGS FOR UTILITY SYSTEMS ARE APPROXIMATE
ONLY. DETERMINE THE EXACT AMOUNT OF PIPING REQUIRED TO FURNISH A COMPLETE
WORKING SYSTEM IN ACCORDANCE WITH THE INTENT OF THE DRAWINGS.
11. SUBMIT A UTILITY OUTAGE REQUEST A MINIMUM OF SEVEN (7) DAYS IN ADVANCE OF ANY
UTILITY OUTAGE.
12. PHASE CONSTRUCTION IN ORDER TO MINIMIZE DISRUPTION TO UTILITIES DURING
INSTALLATION, DEMOLITION, AND REMOVAL.
13. GEOTECHNICAL INFORMATION IS CONTAINED IN A REPORT PREPARED BY ECS SOUTHEAST,
LLC, REPORT NUMBER 30:2596, DATED FEBRUARY 14, 2024. BORING LOGS AND LABORATORY
TEST RESULTS ARE INCLUDED FOR REFERENCE IN THE PROJECT MANUAL.
14. THE CONTRACTOR MUST PROCURE AND MAINTAIN AN ECS GEOTECHNICAL RESPRESENTATIVE
ON-SITE FULL TIME DURING EARTHWORK AND FOUNDATION CONSTRUCTION ACTIVITIES. THE
GEOTECHNICAL REPRESENTATIVE MUST VERIFY COMPLIANCE WITH THE PROJECT'S
GEOTECHNICAL REPORT AND PROVIDE REMEDIAL ACTIONS, AS REQUIRED.
15. LOW CONSISTENCY AND MOISTURE SENSITIVE SOILS, THAT MUST BE UNDERCUT, REMOVED, AND REPLACED, ARE EXPECTED TO BE ENCOUNTERED ON SITE. THE CONTRACTOR MUST
COMPLY WITH THE RECOMMENDATIONS CONTAINED IN THE GEOTECHNICAL REPORT AND THE
PROJECT SPECIFICATIONS WHEN PERFORMING EXCAVATIONS AND PREPARING THE
SUBGRADE UNDER SIDEWALKS AND PAVEMENTS.
16. TOTAL LIMITS OF DISTURBANCE = 0.60 ACRES
GENERAL CIVIL NOTES
THE PURPOSE OF THE EROSION CONTROL MEASURES SHOWN ON THESE PLANS IS TO PRECLUDE THE TRANSPORT OF ALL WATERBORNE SEDIMENTS RESULTING FROM CONSTRUCTION ACTIVITIES FROM ENTERING ONTO ADJACENT PROPERTIES OR STATE WATERS. IF FIELD INSPECTION REVEALS THE INADEQUACY OF THE PLAN TO CONFINE SEDIMENT TO THE PROJECT SITE, APPROPRIATE MODIFICATIONS WILL BE MADE TO CORRECT ANY PLAN
DEFICIENCIES.
1. THE CONTRACTOR MUST BE THOROUGHLY FAMILIAR WITH ALL APPROVED PROCEDURES, WHICH MAY BE PERTINENT TO THE PROJECT. MAINTENANCE WILL INCLUDE THE REPAIR OF MEASURES DAMAGED BY ANY
SUBCONTRACTOR INCLUDING THOSE OF THE PUBLIC UTILITY COMPANIES.
2. SEDIMENT CONTROL DEVICES NOT LOCATED IN PROPOSED FILL OR EXCAVATION AREAS MUST BE
CONSTRUCTED PRIOR TO ALL OTHER LAND DISTURBANCE.
3. SURFACE FLOWS OVER CUT AND FILL SLOPES MUST BE CONTROLLED BY REDIRECTING FLOWS FROM
TRAVERSING THE SLOPES.
4. SEDIMENT CONTROL MEASURES MAY REQUIRE MINOR FIELD ADJUSTMENTS AT THE TIME OF CONSTRUCTION TO ENSURE THEIR INTENDED PURPOSE IS ACCOMPLISHED. CONTRACTING OFFICER APPROVAL WILL BE
REQUIRED FOR OTHER DEVIATION FROM THE APPROVED PLANS.
5. TEMPORARY STOCKPILES OF SOIL / TOPSOIL EXCAVATED DURING SITE CONSTRUCTION MUST BE KEPT ONSITE
AT A TEMPORARY LOCATION IN ACCORDANCE WITH STATE AND FEDERAL LAW.
6. TEMPORARY VEGETATIVE COVER MUST BE PROVIDED IN ALL AREAS WHICH ARE NOT DESIGNATED FOR PAVING, UNDERGROUND UTILITIES, OR STRUCTURAL USES. SUCH AREAS MUST NOT BE EXPOSED FOR PERIODS EXCEEDING 14 DAYS. TEMPORARY VEGETATIVE COVER MAY BE ELIMINATED IN FAVOR OF FINAL
VEGETATIVE COVER IF CONSTRUCTION AND SEASONAL CONDITIONS PERMIT.
7. ALL AREAS DESIGNATED FOR PAVING, UNDERGROUND UTILITIES, AND STRUCTURAL USE MUST BE COMPACTED, SEEDED, AND MULCHED AS SOON AS POSSIBLE BUT NOT EXCEEDING 14 DAYS FOLLOWING
INSTALLATION. NO MORE THAN 500' OF UTILITY TRENCHES ARE TO BE OPEN AT ONE TIME.
8. THE TERM SEEDING, FINAL VEGETATIVE COVER OR STABILIZATION, ON THIS PLAN MUST MEAN THE SUCCESSFUL GERMINATION AND ESTABLISHMENT OF A STABLE GRASS COVER FROM A PROPERLY PREPARED SEEDBED CONTAINING THE SPECIFIED AMOUNTS OF SEED, LIME, AND FERTILIZER. IRRIGATION MUST BE
REQUIRED AS NECESSARY TO ENSURE ESTABLISHMENT OF GRASS COVER.
9. INLET PROTECTION MUST BE PROVIDED FOR ALL CULVERTS AS SOON AS PRACTICAL.
10. BASE COURSE MATERIAL MUST BE PLACED IN ALL PAVED AREAS WITHIN 30 DAYS OF FINAL GRADING.
11. TEMPORARY EROSION CONTROL MEASURES ARE NOT TO BE REMOVED UNTIL ALL DISTURBED AREAS ARE STABILIZED. AFTER STABILIZATION IS COMPLETE, ALL MEASURES MUST BE REMOVED WITHIN 30 DAYS.
TRAPPED SEDIMENT MUST BE SPREAD AND SEEDED.
12. SEED AND MULCH AND PROVIDE TOPSOIL TO ALL DISTURBED AREAS THAT WILL NOT BE COVERED WITH
PAVEMENT.
GENERAL EROSION AND SEDIMENT CONTROL NOTES ABBREVIATIONS
EDGE OF VEGETATION
MAJOR CONTOURS
MINOR CONTOURS
CHAIN LINK FENCE
WATER LINE
SANITARY SEWER FORCEMAIN
OVERHEAD ELECTRIC
BURIED FIBER
LIMITS OF CONSTRUCTION
TREELINE
BUILDING OVERHANG
EDGE OF PAVEMENT
DEMOLISH UTILITY
BENCHMARK
CABLE TV JUNCTION BOX
CLOSED CIRCUIT SECURITY CAMERA
COMMUNICATIONS JUNCTION PEDESTAL
FIRE HYDRANT
IRON PIPE
SANITARY SEWER DOSING TANK
SANITARY SEWER MANHOLE
SIGN
UTILITY POLE
WATER METER /VALVE
DESIGN EXISTING
CONCRETE
BUILDING
DEMOLITION
PAVEMENT
GRAVEL
FM
W
OHE
LOD
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
1:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -0
.d w g
05/02/2024
230182
MKA
GKT
SMS
C-001
CIVIL NOTES
COMMUNICATION COMM
CONCRETE CC
EASTING E
ELEVATION EL
FINISHED FLOOR ELEVATION FFE
FORCEMAIN FM
LIMITS OF DISTURBANCE LOD
NORTHING N
OVERHEAD POWER OHP
SANITARY SEWER SS
WATER W
1. A MINIMUM COVER OF THREE (3) FEET IS REQUIRED OVER PROPOSED LINES UNLESS SHOWN OTHERWISE IN
DESIGN PROFILE.
2. ALL EXISTING UTILITIES MAY OR MAY NOT BE SHOWN IN THEIR EXACT LOCATION.
3. VERIFY ALL UTILITY LOCATIONS PRIOR TO EXCAVATION.
4. REPAIR ANY ACTIVE UTILITIES DAMAGED DURING CONSTRUCTION AND NOTIFY THE COR OF THE DAMAGE AT NO
COST TO THE GOVERNMENT.
5. LENGTHS OF LINES INDICATED ON THE DRAWINGS FOR UTILITY SYSTEMS ARE APPROXIMATE ONLY. DETERMINE THE EXACT AMOUNT OF PIPING REQUIRED TO FURNISH A COMPLETE WORKING SYSTEM IN ACCORDANCE WITH
THE INTENT OF THE DRAWINGS.
6. PHASE CONSTRUCTION IN ORDER TO MINIMIZE DISRUPTION TO UTILITIES DURING INSTALLATION, DEMOLITION, AND REMOVAL. COORDINATE ALL UTILITY DISCONNECTION AND DEMOLITION. ALL TRANSITION AND RECONNECTION OF UTILITIES MUST BE COORDINATED WITH OWNER. COORDINATE FINAL TRANSITION AND
RECONNECTION PLAN AFTER CONTRACT AWARD.
7. CONSTRUCTION OF WATER AND SEWER LINES MUST BE IN ACCORDANCE WITH DECATUR UTILITIES
CONSTRUCTION REQUIREMENTS.
GENERAL UTILITY NOTES
I I I I I I
HORIZONTAL CONTROL: ALABAMA STATE PLANE COORDINATE SYSTEM (WEST ZONE)
GPS EQUIPMENT: TOPCON HIPER VR
ROBOTIC TOTAL STATION: TOPCON
DATUM: NAD 1983(CONUS)
GEOID MODEL: G2018U7
CONVERGENCE: -0.15799444
COMBINED SCALE FACTOR: 0.99994834
*ALL COORDINATES REPORTED AND DRAWING PROVIDED IN ASP
SURVEY NOTES
SEE SPECIFICATION SECTION 01 10 00 SUMMARY OF WORK.
1. DEMOLITION OF EXISTING OFFICE TRAILER TO BE COMPLETED BY OTHERS PRIOR TO THIS PROJECT.
2. PROVIDE TEMPORARY POWER TO EXISTING PARKING CANOPY EAST OF THE REMOVED OFFICE TRAILER.
3. DEMOLISH OVERHEAD POWER AND UTILITY POLE.
4. CLEAR STUMPS AND GRUB THE SITE (TREES WILL HAVE BEEN REMOVED PRIOR TO THIS PROJECT)
5. COMPLETE OTHER DEMOLITION AND SITEWORK. CONSTRUCT NEW BUILDING. MAINTAIN VISITOR PARKING
ACCESS TO THE EXISTING OFFICE BUILDING THROUGHOUT CONSTRUCTION.
6. PROVIDE 1 MONTH NOTICE PRIOR TO DEMOLITION OF THE EXISTING OFFICE BUILDING BY OTHERS.
7. DISCONNECT UTILITIES FROM EXISTING OFFICE BUILDING.
8. DEMOLISH EXISTING OFFICE BUILDING.
9. FINISH GRADING AND PARKING LOT CONSTRUCTION.
GENERAL CONSTRUCTION SEQUENCE
05/02/2024
O H
P O
H P
O H
P
TV
SIGN
SIGN
line height 42.48' heavily wooded heavily wooded
C line height 39.39'
BM
St ro ng R oa d
(n o de ed ed ri gh t o f w ay fo un d)
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P
WOOD FRAME OFFICE BUILDING
heavily wooded
05/02/2024
230182
MKA
GKT
SMS
C-101
EXISTING CONDITIONS AND
DEMOLITION PLAN
DEMOLITION NOTES
1 CLEAR STUMPS AND GRUB THIS AREA. AREA TO BE CLEARED OF
TREES AND STRUCTURES BY OTHERS PRIOR TO CONSTRUCTION
2 DEMOLISH AND REMOVE FENCE. STOP DEMOLITION AT THE NEXT
EXISTING FENCE POST
3 REMOVE OVERHEAD ELECTRIC
4 TREE TO BE REMOVED BY OTHERS PRIOR TO CONSTRUCTION
5 DEMOLISH AND REMOVE POWER POLE; COORDINATE WITH LOCAL
UTILITY
6 REMOVE LANDSCAPING
7 REMOVE GATE
8 REMOVE UNDERGROUND COMMUNICATION
9 DEMOLISH AND REMOVE SIGN
10 DEMOLISH AND REMOVE PAVEMENT. REPLACE WITH GRAVEL TO
MAINTAIN PARKING LOT FOR EXISTING BUILDING
11 DEMOLISH AND REMOVE CONCRETE
12 REMOVE EQUIPMENT AND CONCRETE PAD
13 BUILDING TO BE DEMOLISHED BY OTHERS
14 DEMOLISH AND REMOVE SANITARY MANHOLE AND PUMP
15 OFFICE TRAILER TO BE DEMOLISHED BY OTHERS
16 SAWCUT PAVEMENT
17 REMOVE FLAG POLE
GENERAL PLAN NOTES
1. SEE SHEET C-001 FOR CIVIL NOTES, LEGENDS, AND ABBREVIATIONS
2. KEEP EXISTING BUILDING OPERATIONAL UNTIL NEW BUILDING IS
COMPLETE
0 10' 20'
SCALE: 1" = 10'
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
2:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -1
.d w g
TV
SIGN
SIGN
line height 42.48' heavily wooded heavily wooded
C line height 39.39'
BM
St ro ng R oa d
(n o de ed ed ri gh t o f w ay fo un d)
WOOD FRAME OFFICE BUILDING
LO
D
LO
D
LO
D
LO
D
LO
D
LODLODLODLOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D LO
D
LO
D LOD LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
II
I
II
I
II
I
II
I
I I I
I I I
I I I I I I
I I I
III
III I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
II
I
II
I
I I I
II
I
II
I
II
I
III
II
I
II
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
III
III
IIIIII
III
III
II
I
II
I
II
I
III
III
III
III
III
III
III
III
III
III
II
I
8R20'
R5' R5'
R5'R5'
R20'
11 12
N90°00'00"E
7.83'
5.02' 23.64'
8.21'
34.63'
2.58'
2.59'
13.43'
2.64'0.79'
4.21'
COORDINATE POINTS
POINT #
NORTHING
92,010.85
91,988.37
91,988.37
91,983.37
91,983.37
91,988.37
91,996.67
91,983.90
91,965.37
91,965.37
91,970.37
91,970.37
91,965.37
91,941.37
91,936.37
91,923.37
91,923.37
91,936.37
91,941.37
91,941.37
91,921.37
91,915.78
91,988.37
EASTING
1,869,526.64
1,869,560.85
1,869,509.35
1,869,509.35
1,869,599.35
1,869,599.35
1,869,482.09
1,869,483.03
1,869,502.98
1,869,504.35
1,869,509.35
1,869,599.35
1,869,604.35
1,869,604.35
1,869,599.35
1,869,599.35
1,869,509.32
1,869,509.32
1,869,504.32
1,869,497.94
1,869,477.94
1,869,477.94
1,869,566.86
DESCRIPTION
BUILDING CORNER
SIDEWALK CORNER
SIDEWALK CORNER
SIDEWALK CORNER
SIDEWALK CORNER
SIDEWALK CORNER
PAVEMENT END
PAVEMENT POINT OF CURVATURE
PAVEMENT POINT OF TANGENCY
PAVEMENT POINT OF CURVATURE
PAVEMENT POINT OF TANGENCY
PAVEMENT POINT OF CURVATURE
PAVEMENT CORNER
PAVEMENT POINT OF CURVATURE
PAVEMENT POINT OF TANGENCY
PAVEMENT CORNER
PAVEMENT CORNER
PAVEMENT POINT OF CURVATURE
PAVEMENT POINT OF TANGENCY
PAVEMENT POINT OF CURVATURE
PAVEMENT POINT OF TANGENCY
PAVEMENT END
SIDEWALK CORNER
05/02/2024
230182
MKA
GKT
SMS
C-102
SITE PLAN
WORK NOTES
DETAIL
1 INSTALL NEW FENCE LINE AND CONNECT TO
BUILDING. CONNECT TO EXISTING FENCE POST.
FENCE TO MATCH EXISTING
1/C-501
2 VEHICLE GATE 2/C-501
3 CONCRETE SIDEWALK 6,12/C-501
4 EQUIPMENT PAD 11/C-501
5 PAVEMENT 5/C-501
6 ACCESSIBLE PARKING SPACES 7,8,9/C-501
7 PAVEMENT TRENCH 3/C-502
8 PRECAST CONCRETE WHEEL STOP 4/C-501
0 10' 20'
SCALE: 1" = 10'
GENERAL PLAN NOTES
1. SEE SHEET C-001 FOR SITE NOTES, LEGENDS, AND ABBREVIATIONS
2. 19 TOTAL PARKING SPACES PROVIDED, INCLUDING 2 VAN
ACCESSIBLE SPACES
X
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
2:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -1
.d w
P O
H P
O H
P
TV
SIGN
SIGN
line height 42.48' heavily wooded heavily wooded
C line height 39.39'
BM
St ro ng R oa d
(n o de ed ed ri gh t o f w ay fo un d)
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P
WOOD FRAME OFFICE BUILDING
UG
E
UG
E
UGE UGE
LO
D
LO
D
LO
D
LO
D
LO
D
LODLODLODLOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D LO
D
LO
D LOD LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
II
I
II
I
II
I
W W
W W
W
W
W
W W
UGE UGE
II
I
I I I
I I I
I I I I I I
I I I
III
III I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
II
I
II
I
I I I
II
I
II
I
II
I
III
II
I
II
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
III
III
IIIIII
III
III
II
I
II
I
II
I
III
III
III
III
III
III
III
III
III
III
II
I
10.68'
EXISTING
20.00'
ELECTRIC
EASEMENT
05/02/2024
230182
MKA
GKT
SMS
C-103
UTILITY PLAN
WORK NOTES
DETAIL
1 1.25" PVC SANITARY SEWER FORCEMAIN
2 SANITARY SEWER PUMP STATION 2/C-502
3 2.5" PVC WATER LINE
4 2.5" PVC WATER LINE 90° BEND
5 2.5" PVC WATER LINE 45° BEND
6 2.5" PVC WATER LINE 22.5° BEND
7 CONNECT TO EXISTING GULF SHORES UTILITIES
WATER LINE ON THE NORTH SIDE OF FORT
MORGAN ROAD (TOTAL WATER LINE LENGTH
APPROXIMATELY 520 FEET).
8 CONNECT TO EXISTING GULF SHORES UTILITIES
SANITARY SEWER ON THE NORTH SIDE OF FORT
MORGAN ROAD (TOTAL FORCE MAIN LENGTH
APPROXIMATELY 400 FEET).
0 10' 20'
SCALE: 1" = 10'
GENERAL PLAN NOTES
1. SEE SHEET C-001 FOR CIVIL NOTES, LEGENDS, AND ABBREVIATIONS
X
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
3:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -1
.d w
P O
H P
O H
P
TV
SIGN
SIGN
line height 42.48' heavily wooded heavily wooded
C line height 39.39'
BM
St ro ng R oa d
(n o de ed ed ri gh t o f w ay fo un d)
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P
WOOD FRAME OFFICE BUILDING
UG
E
UG
E
UGE UGE
LO
D
LO
D
LO
D
LO
D
LO
D
LODLODLODLOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D LO
D
LO
D LOD LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
II
I
II
I
II
I
UGE UGE
II
I
I I I
I I I
I I I I I I
I I I
III
III I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
II
I
II
I
I I I
II
I
II
I
II
I
III
II
I
II
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
III
III
IIIIII
III
III
II
I
II
I
II
I
III
III
III
III
III
III
III
III
III
III
II
I
FFE = 11.75
10.90
10.95
11.01
11.07
11.24
11.21
11.31 11.43
11.32
11.30
11.30
11.84
11.89
11.49
11.31
11.23
10.60
11.10
10.76
11.10
11.04
10.95
10.90
10.90 10.90
11.60
11.60
11.70
11.70
11.6011.60
11.25 11.25
11.25
11.25 11.25
11.25 11.24
11.24 10.77
10.66
05/02/2024
230182
MKA
GKT
SMS
C-104
GRADING PLAN
0 10' 20'
SCALE: 1" = 10'
GENERAL PLAN NOTES
1. SEE SHEET C-001 FOR CIVIL NOTES, LEGENDS, AND ABBREVIATIONS
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
3:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -1
.d w
FFE = 11.75
O H
P O
H P
O H
P
TV
SIGN
SIGN
line height 42.48' heavily wooded heavily wooded
C line height 39.39'
BM
St ro ng R oa d
(n o de ed ed ri gh t o f w ay fo un d)
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P O
H P
O H
P
WOOD FRAME OFFICE BUILDING
UG
E
UG
E
UGE UGE
LO
D
LO
D
LO
D
LO
D
LO
D
LODLODLODLOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D LO
D
LO
D LOD LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
II
I
II
I
II
I
W W
W W
W
W
W
W W
UGE UGE
II
I
I I I
I I I
I I I I I I
I I I
III
III I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
II
I
II
I
I I I
II
I
II
I
II
I
III
II
I
II
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
III
III
IIIIII
III
III
II
I
II
I
II
I
III
III
III
III
III
III
III
III
III
III
II
I
X
X
X
X
X
X
X X X X X X X X X X X
X X
X X
X X
X X
TS PS
MU
SF
SF
SF
05/02/2024
230182
MKA
GKT
SMS
C-105
EROSION AND SEDIMENT
CONTROL PLAN
SILT FENCE
MULCHING, TEMPORARY
X XX
EROSION AND SEDIMENT
CONTROL LEGEND
SF
TS PS
MU
0 10' 20'
SCALE: 1" = 10'
GENERAL PLAN NOTES
1. SEE SHEET C-001 FOR CIVIL NOTES, LEGENDS, AND ABBREVIATIONS
2. USE NATIVE TEMPORARY AND PERMANENT SEEDING PER
APPROPRIATE GOVERNING BODY. FOLLOW MANUFACTURER'S OR
GOVERNING BODY GUIDELINES FOR ALL SEEDING SCHEDULES,
RATES, AND MIXTURES.
SEEDING, PERMANENT SEEDING
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
3:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -1
.d w
NOTE: MIN 28-DAY CONCRETE COMPRESSIVE STRENGTH
SHALL BE 2500 PSI
TOP RAIL
3 STRANDS OF BARBED WIRE
LINE POST
TOP OF
FENCE
2" MESH 9 GAGE WIRE
CHAIN LINK
3/8" Ø TRUSS ROD
CONCRETE BASE MIN
DIA 6"
COMPRESSIVE BRACE
xx x x xx x x x x xxxx x x x x x x x xxxx x x x x xxxx
3 STRANDS OF
BARBED WIRE
PROVIDE GATE STOP & LATCH SUITABLE
FOR PADLOCK
2" MESH 9 GAGE WIRE CHAIN
LINK
CONCRETE
FOOTING
3/8" MIN ROUND ROD
AT GATE
RAIL
GATE
POST
IIIIIIIIIIII
EDGE OF PAVEMENT
3/4" Ø X 2' DOWELS
TO ANCHOR BLOCKS
TO PAVEMENT
CLASS A3
CONCRETE
1" DIA.
18'-0"
9'-0" 9'-0"
PARKING
BLOCK
(TYP)
4" WHITE
STRIPING
(TYP)
CHAIN LINK FENCE
NOT TO SCALE1 DOUBLE SWING GATE
NOT TO SCALE2 PIPE TRENCH
NOT TO SCALE3
PRECAST CONCRETE PARKING BLOCK
NOT TO SCALE4
ASPHALT PAVEMENT
NOT TO SCALE5 CONCRETE SIDEWALK
NOT TO SCALE6
PARKING SPACE
NOT TO SCALE10
RESERVED
PARKING
VAN
ACCESSIBLE
NOTES:
1. HANGING ORDER OF THE VAN ACCESSIBLE SPACE AND PENALTY
SIGN DOES NOT MATER.
2. THE VAN ACCESSIBLE SIGN IN NOT REQUIREDED BY CODE AND
SHALL ONLY BE HUNG WHEN INDICATED ON THE PLAN.
PENATLY $100-500
FINE TOW AWAY
ZONE
1'
3'
4' MIN
7.5"
1'-6"
7' MAX
3'-6" 6"
18"
12" X 18" 0.80 GA.
RETRO-REFLECTORIZED
ALUMINUM SIGN
INTERNATIONAL SYMBOL OF
ACCESSIBILITY. BORDER AND
LETTERING IN WHITE ON
BLUE BACKGROUND
ADDITIONAL SIGN STATING
"VAN ACCESSIBLE SPACE"
WHERE INDICATED ON PLAN
PENALTY SIGN AS
REQUIREDED BY
IBC 1103.1.1
RADIUS 1 12" (TYP)
2" SQUARE GALVaANIZED
SIGN POST SET IN
6" PIPE BOLLARD,
PAINT YELLOW, FILL
WITH GROUT
12" EXPANSION JOINT
4' DEEP X 18" DIA.
CONCRETE FOOTING
ACCESSIBLE PARKING SIGN
NOT TO SCALE8
9'-0"
PRECAST
CONCRETE
WHEEL
STOP (TYP)
4" WHITE
STRIPING
(TYP)
20'-0"
9'-0" 9'-0"
ACCESSIBLE PARKING SPACES
NOT TO SCALE7
ACCESSIBLE PARKING SIGN
34"
39"
4"
48"
40.75"
SYMBOL COLOR:
WHITE
SQUARE
COLOR:
BLUE
ACCESSIBLE PARKING MARKER
NOT TO SCALE9
SEE PLAN FOR WIDTH
2" ASPHALT BASE COURSE, 25 MM
8" AGGREGATE BASE COURSE
COMPACTED SUBGRADE
2" ASPHALT SURFACE COURSE, 9.5MM
NOTE:
CONCRETE MATERIAL OF ALDOT STANDARD AND TO BE INSTALLED AS PER
ALDOT SPECIFICATIONS
SEE PLAN FOR WIDTH
4" AGGREGATE BASE COURSE
COMPACTED SUBGRADE
4" CONCRETE WWF (6x6-W1.4x1.4)
12" PIPE
SIZE 12"
12"
*4" MIN
NOTE:
*6" MIN IF TRENCH BOTTOM IS ROCK
COMPACTED EARTH
CLEAN EARTH COMPACTED
BY HAND IN 6" LAYERS
CLEAN COURSE AGGREGATE
SPRING LINE
OF PIPE
UNDISTURBED SOIL
#5's @ 12" O.C., E.W.
ANCHOR BOLTS AS REQ'D, COORDINATE W/
EQUIP MANUF.
#5's @ 12" O.C., E.W.
4" BASE AGGREGATE
EDGE OF EQUIPMENT
GRADE VARIES
1'-6" MIN
6" MIN
6"
MIN
8"
EXTERIOR CONCRETE EQUIPMENT PAD
NOT TO SCALE11
COMPACTED EARTH
SEE PLANS
5' TYP.
EXPANSION JOINT WHERE
WALK ABUTS CURB,
PAVEMENT, OR STEPS
TRANSVERSE
CONTRACTION JOINT
TRANSVERSE EXPANSION
JOINT
LONGITUDINAL
CONTRACTION JOINT
40' OR MATCH JOINTS OF CURB WHEN ADJACENT
WALK WIDTHS
< 5' 11"
6' 0" - 7' 11" 8' 0" - 12' 0"
LONGITUDINAL CONTRACTION JOINT
NONE
ONE ALONG WALK AT CENTERLINE
TWO ALONG WALK AT THIRD POINTS
CONCRETE SIDEWALK JOINT LAYOUT
NOT TO SCALE12
NOTE: SEE STRUCTURAL GENERAL NOTES ON
S-001 FOR FOUNDATION AND SUBGRADE
PREPARATION REQUIREMENTS.
05/02/2024
230182
MKA
GKT
SMS
C-501
CIVIL DETAILS
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
3:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -5
.d w
SILT FENCE
NOT TO SCALE1
NOTES:
1. CONCRETE BALLAST MUST BE PROVIDED TO COUNTERACT BUOYANCY.
CONCRETE BALLAST DELEGATED DESIGN TO PUMP STATION
MANUFACTURER.
2. GRINDER PACKAGE LIFT STATION MUST BE PROVIDED WITH A BUCK BOOST
TRANSFORMER FOR CONVERSION OF 208V TO 240V POWER AS PART OF
THE LIFT STATION PACKAGE PROVIDED BY THE MANUFACTURER.
3. CONTRACTOR MUST PROVIDE APPURTENANCES AS REQUIRED FOR
CONNECTION OF 1" HDPE FORCEMAIN TO LIFT STATION. COORDINATE
CONNECTION WITH ENGINEER.
4. GRINDER PUMPS MUST ALTERNATE START/STOP SEQUENCE BETWEEN
PUMPS AT EACH PUMP START.
5. PACKAGE GRINDER LIFT STATION MUST BE INSTALLED PER THE
MANUFACTURER'S REQUIREMENTS.
SEE NOTE 3
NOTES:
1. CONCRETE BALLAST MUST BE PROVIDED TO COUNTERACT
BUOYANCY. CONCRETE BALLAST DELEGATED DESIGN TO PUMP
STATION MANUFACTURER.
2. GRINDER PACKAGE LIFT STATION MUST BE PROVIDED WITH A BUCK
BOOST TRANSFORMER FOR CONVERSION OF 208V TO 240V POWER
AS PART OF THE LIFT STATION PACKAGE PROVIDED BY THE
MANUFACTURER.
3. CONTRACTOR MUST PROVIDE APPURTENANCES AS REQUIRED FOR
CONNECTION OF 1" HDPE FORCEMAIN TO LIFT STATION. COORDINATE
CONNECTION WITH ENGINEER.
4. GRINDER PUMPS MUST ALTERNATE START/STOP SEQUENCE
BETWEEN PUMPS AT EACH PUMP START.
5. PACKAGE GRINDER LIFT STATION MUST BE INSTALLED PER THE
MANUFACTURER'S REQUIREMENTS.
(SEE NOTE 3)
GRINDER LIFT STATION
NOT TO SCALE2
18"
OUTSIDE Ø OF PIPE
18"
2" MIN ASPHALT SURFACE COURSE
MATCH EXISTING DEPTH OF
ASPHALT BASE COURSE.
CREATE A 6" BENCH (EACH SIDE)
TACK JOINTS
BACKFILL WITH NO 21B STONE OR OTHER
APPROVED CRUSHED STONE IN COMPACTED
LIFTS.
PROPOSED STORM SEWER OR
UTILITIES
4" OF NO. 57 STONE BEDDING
PAVEMENT PATCH FOR UTILITY TRENCH
NOT TO SCALE3
EXISTING ASPHALTEXISTING ASPHALT
SAWCUT JOINTS FULL DEPTH
OF ASPHALT COURSES.
SIDE VIEW
METHOD I
STOP GEOTEXTILE HERE
TRENCH (APPROX 6"X 6")
BACKFILL ON TOP OF
GEOTEXTILE WITH SOIL
ANCHOR STAKE
GROUND
LINE
FLOW
POST
6"
6"
TIEBACK TO BE USED AS NEEDED
FOR ADDITIONAL STRENGTH TO
PREVENT OVERTURNING (TYP)
LOOP GEOTEXTILE
OVER T-POST
ELEVATION VIEW
4' -0
" M
IN
P O
ST
S
M
IN
2' -0
ANCHOR AT EACH END
OF FENCE AS REQUIRED
GROUND
LINE
10'-0" (TYP)
RING FASTENERS
(TOP ONLY)
@ APPROXIMATELY
1'-0" O C
STUDDED METAL
"T" POST
ANCHOR AT EACH END
OF FENCE AS REQUIRED
GROUND LINE
2' -0
05/02/2024
230182
MKA
GKT
SMS
C-502
CIVIL DETAILS
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
C er tif ic at e of A ut ho riz at io n
N um be r:
PE
F0
Ex pi ra tio n:
6/
/2
P ea ch tre e D un w oo dy
R oa d, B ui ld in g
C
Su ite
At la nt a, G A
8.
0.
w ile yw ils on .c om
0%
E m pl oy ee -O w ne d
FI
SH
W
IL
D
LI
FE
S
ER
VI
C
ES
BO
N S
EC
O
U R
N
AT
IO
N
AL
W
IL
D
LI
FE
R
EF
U G
E
BO
N
S
EC
O U
R V
IS
IT
O R
C
EN
TE
R
A
D M
IN
IS
TR
AT
IO
N
ST
R O
N G
R D
G
U
LF
S H
O R
ES
, A
L
M R
K D
AT
E
R
EV
IS
IO
N D
ES
C
R
IP
TI
O
N
5/ 2/
:3
4:
P M
X:
\2
3\
F
W S
Bo n
Se co ur O ffi ce
\7
D ra w in gs \7
C iv il\
Sh ee ts \2
2A
_C -5
.d w
A. GENERAL
1. STRUCTURAL GENERAL NOTES ARE INTENDED TO HIGHLIGHT OR IN SOME CASES SUPPLEMENT PROJECT SPECIFICATIONS. REFER TO THE
PROJECT SPECIFICATIONS FOR COMPLETE WORK COVERAGE.
2. THE DESIGN OF THE STRUCTURE COMPLIES WITH THE INTERNATIONAL BUILDING CODE 2021 AS ADOPTED BY THE 2021 ALABAMA BUILDING
CODE.
3. GRAVITY DESIGN LOADS ARE AS FOLLOWS:
a. SUPERIMPOSED DEAD LOADS:
FINISHES ACTUAL
MECHANICAL AND CEILING 5 PSF
ROOFING – MECHANICALLY FASTENED SINGLE PLY 1 PSF
SPRINKLER SYSTEMS AS REQ’D (3 PSF MIN)
b. LIVE LOADS:
MECHANICAL SPACE 150 PSF
STORAGE – LIGHT 125 PSF
ASSEMBLY AREAS – MOVEABLE SEATS 100 PSF
LOBBIES 100 PSF
LATRINES, HEADS, TOILETS 70 PSF
OFFICE SPACE 50 PSF
ROOF – MINIMUM 20 PSF
4. HANDRAILS AND GUARDS RAILS MUST BE DESIGNED FOR A LINEAR LOAD OF 50 POUNDS PER FOOT OR CONCENTRATED LOAD OF 200 POUNDS, EACH APPLIED NON-CONCURRENTLY TO THE TOP OF THE HANDRAIL, IN ANY DIRECTION TO CREATE THE WORST LOAD EFFECT.
BALUSTERS, PANEL FILLERS, AND GUARDRAIL INFILL COMPONENTS, INCLUDING ALL RAILS EXCEPT THE HANDRAIL AND TOP RAIL, MUST BE DESIGNED FOR A HORIZONTAL LOAD OF 50 POUNDS OVER A 12 INCH BY 12 INCH AREA LOCATED TO CREATE THE WORST LOAD EFFECT.
5. IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE’S SECTION 1607.4, THE FLOOR SYSTEM IS DESIGNED TO WITHSTAND CONCENTRATED LOADS ASSUMED ACTING UNIFORMLY ON A 2-1/2 FEET SQUARE AREA AND LOCATED TO PRODUCE THE MAXIMUM EFFECT
IN STRUCTURAL MEMBERS.
6. THE DESIGN OF THE STRUCTURE TO RESIST SNOW LOADS IS IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE’S SECTION 1608
AND ASCE 7, CHAPTER 7
GROUND SNOW LOAD Pg = 0.0 PSF FLAT ROOF SNOW LOAD Pf = 0.0 PSF EXPOSURE FACTOR Ce = 1.0
IMPORTANCE FACTOR IS = 1.0
ROOF THERMAL FACTOR Ct = 1.0 ROOF SLOPE FACTOR Cs = 1.0
7. THE DESIGN OF THE STRUCTURE TO RESIST WIND PRESSURES IS IN ACCORDANCE WITH INTERNATIONAL BUILDING CODE’S SECTION 1609.0, WHICH IS BASED ON ASCE 7, CHAPTER 26. DESIGN INFORMATION IS AS FOLLOWS:
DESIGN WIND SPEED (ULTIMATE) V = 160 MPH
DESIGN WIND SPEED (SERVICE) VASD = 124 MPH
RISK CATEGORY II
WIND EXPOSURE CATEGORY FOR MWFRS D
INTERNAL PRESSURE COEFFICIENT GCPI = ± 0.18
COMPONENTS AND CLADDING PRESSURE SEE PLANS
8. THE DESIGN OF THE STRUCTURE TO RESIST RAIN LOADS IS IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE’S SECTION 1611, AND…