This Statement of Work (SOW) outlines requirements for replacing two Folsom degassing pumps at Jones Hole National Fish Hatchery in Vernal, UT. The project involves delivering two Folsom 5 horsepower Simflo pumps (model OLS-PA7LX-1) that pump spring water through nitrogen degassing columns for fish health and safety.

The contractor must be a certified Folsom Pumps supplier and complete the work by April 1, 2025. The pumps must match specific requirements including: 20-degree colleted impellers, belled suction with standard basket strainer, 10" standard duty SPI flanged column, 1-1/4" line shaft, and Chesterton 155 mechanical seal. The motors must be 5 hp, VHS, TEFC, 1,770 rpm, with clockwise rotation. Performance specifications include 1,208 gpm x 6.08' @ 1,770 rpm bowl performance and 90-inch total pump length. The government will provide restrooms, electricity and water during installation. Quality control must meet industry standards, and final acceptance requires approval from U.S. Fish and Wildlife Service representatives.

View the file

Other files for this federal contract opportunity

Other files attached to UT-JONES HOLE NFH- DEGASSING PUMP REPLACEMENT, newest first.
File Type Posted
B03_Wage_Determination_Uintah_County__UT_2015-5497.pdf PDF
Sol_140FS225Q0064.pdf PDF
Photos_of_Pumps.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK

Service

Replacement of Two Folsom Degassing Pumps

PR Number: _______________

1. General:

1.1 Jones Hole National Fish Hatchery (NFH), 24495 East Jones Hole Hatchery Road, Vernal, UT

84078-2042. Replace two Folsom degassing pumps.

1.2 Purpose/End Application: This project is to replace two degassing pumps that pump spring water through nitrogen degassing colums for the health and safety of the fish.

1.3 Contractor Qualifications: The contractor must be a certified supplier of Folsom

Pumps.

1.4 Other: The contractor must follow all associated regulations and laws including: Federal, State, and County.

2. Place of Performance and Period of Performance

2.1 Work is to be performed at Jones Hole National Fish Hatchery, 24495 East Jones Hole

Hatchery Road, Vernal, UT 84078-2042.

2.2 This project needs to be completed prior to April 1, 2025.

2.3 Normal duty hours Monday thru Friday 8:00 a.m. - 4:30 p.m. In the event of emergencies, Contractor shall provide contact information.

3. Scope

3.1 The contractor shall deliver two (2) Folsom 5 horse power (hp), Simflo pumps – item number: OLS-PA7LX-1.

4. Deliverables and/or Delivery Schedule:

4.1 The contactor shall provide:

Estimate replacements for SN 118626 A & B

COS: 1,208 gpm x 6.08'@ 1,770 rpm (Bowl Performance)

Total Pump Length: 90 [in]

• Model: OLS-PA7LX-1 20 degree wl colleted Impellers

• Suction: Belled, Standard-Sized I Strainer: Standard Basket

• Column: 10" Standard Duty SPI Flanged, Sch.40), 5' Std. Section Length

• Line-Shaft: 1-114" - 10 TPI LH, 1 O" Stickup

• Head: SL R adius Fab. wl 8" 150# ANSI RF Slip-on Outlet for - VHS Driver wl

Packing Gland Seal Assembly, Standard Base I Foundation Plate: None

[Materials per Submittal Details]

• 5 hp, VHS, TEFC, 1,770 rpm, Sinewave Optimized, NRR, CLOCKWISE

ROTATION, 1" BX, 12" BD, Nidec US-Motors HT5P2BLE

Motor:

• 5 hp, VHS, TEFC, 1,770 rpm, Sinewave Optimized, NRR, CLOCKWISE

ROTATION, 1" BX, 12" BD, Nidec US-Motors HT5P2BLE

Seal

• Chesterton 155 Mechanical Seal

5. Data Management Plan (DMP) N/A

6. Government-Furnished Equipment (GFE) / Government-Furnished Information

(GFI)

6.1 Jones Hole NFH will provide restrooms, electricity, and water for the contractor to using while the contracted work is being completed.

6.2 Identify any limitations. N/A

7. Evaluation and Acceptance

7.1 The contractor will be evaluated as detailed herein. Government acceptance is contingent upon: designated U.S. Fish and Wildlife Service representative(s) determining the work to be acceptable and in good working order.

8. Quality Control/Quality Assurance:

8.1 For commercial supplies reference clauses for inspection and acceptance. Where appropriate, QC will be maintained according to industry standards and made available to the agency with the contractor’s proposal.

8.2 Identify and detail measures for assessing quality control and acceptance; each requirement is unique and a table format is visually friendly and may be desirable.

9. Technical Coordinator:

9.1 Primary individual responsible for the final product or service.

Travis Anderson

Hatchery Manager

24495 East Jones Hole Hatchery Road

Vernal, UT 84078-2042

Office: 435-789-4481 x12 travis_anderson@fws.gov

9.2 Secondary individual responsible for the final product or service.

Kristopher “Kris” Johnson

Facility Management Coordinator (FMC)

Asset Management Coordinator (AMC)

U.S. Fish and Wildlife Service

Fish and Aquatic Conservation (FAC)

1380 South 2350 West

Vernal, UT 84078

Cell: 435-299-5150

Office: 435-789-0351 ext. 16 kristopher_b_johnson@fws.gov mailto:travis_anderson@fws.gov mailto:kristopher_b_johnson@fws.gov