STATEMENT OF WORK
Bureau of Land Management
Nevada
Red Rock Canyon NCA Visitor Center
Septic System Pump Replacement Southern Nevada District, Las Vegas, Nevada
TABLE OF CONTENTS
1.0 INTRODUCTION
2.0 SCOPE OF WORK
3.0 PROJECT DETAILS
4.0 PROJECT ADMINISTRATION
Exhibits:
Exhibit 1 ........... Site Location Exhibit 2 .......... CSWS Location
Appendix A:
Red Rock Canyon Visitor Center Centralized Small Wastewater System – As-Built Plans
Appendix B:
Existing Pumps – Manufacturer Data
Appendix C:
ORENCO – Orignal Pump Programming Inputs
Appendix D:
ORENCO Biotube Pump Vault ORENCO Flow Inducer Towers
March 28, 2023 Red Rock Canyon NCA – Septic System Pump Replacement Page 1 of 5
1.0 INTRODUCTION
Red Rock Canyon National Conservation Area (RRCNCA) is located at 1000 Scenic Loop Drive, Las Vegas, Nevada 89161 (Exhibit 1).
RRCNCA hosts over 1.5 million visitors per year. Many of these visitors stop at the Visitor Center building to learn more about the NCA, shop at a gift store, hike local trails, or begin a tour.
The Visitor Center building (VC) and its parking lot are served by two restroom facilities; one is part of the building, and the other is a nearby stand-alone structure (Exhibit 2). These two facilities collectively have (2) janitor sinks, (6) standard sinks, (15) water closets, and (5) urinals all which account for the total flow discharged into a nearby centralized small wastewater system (CSWS) that processes the flow. The CSWS location is shown on Exhibit 2 and is located at – latitude: 36.13385° / longitude: -115.42685°.
System Components
The CSWS was built in 2012 and consists of following:
a) (2) 15,000 gal primary tanks;
b) (1) 10,000 gallon dosing tank;
c) (2) transfer pumps;
d) (6) dosing pumps; and
e) (6) chamber beds totaling 23,760 sq. ft.
In effect, the first primary tank acts as primary settling and the second primary performs both a secondary settling and flow equalization. The second primary tank contains (2) - ½ hp 50gpm pumps; the dosing tank contains (6) - ½ hp 50gpm pumps. Both primary tanks utilize effluent screens. The system design capacity is 10,000 per day. Current water meter readings suggest the absorption beds receive approximately 3,200 to 3,750 gallons per day.
The pumping systems uses both liquid floats and an Orenco TCOM timing control panel. Pump on/off operations are controlled by both the tank floats and pumping time presets within the control panel. Each dosing pump is dedicated to one of (6) chamber beds each composed of (6) chambers. System as-built plans are located in Appendix A.
Documentation shows the original pumps were submersible Orenco model PF500512-20 – a Franklin Electric pump (Appendix B).
All existing pumps are submersible Franklin Electric:
Model 2445059010 ½ hp; 60hz 5 amps at full load; 0.37 kw RPM 3450 SF Max Amp 6 Single Phase Code R SF 1.6 Continuous Duty E79319 2- Wire Submersible Motor
March 28, 2023 Red Rock Canyon NCA – Septic System Pump Replacement Page 2 of 5
System Operations and Maintenance
Pump malfunctions have dramatically increased in recent years due to age and lack of routine maintenance. Recent troubleshooting in January 2023 showed (4) of the (6) pumps to be inoperative and
(2) found to be drawing 5 amps.
Recent repair work includes the installation of new dosing tank float switches.
System Operations
Second primary tank pumps are in Orenco Biotube Pump vaults (Appendix D). Dosing tank pumps are placed in Orenco Flow Inducer Towers as shown on the as-built plans in Appendix D.
The two secondary tank pumps are transfer pumps and operate based on float settings and programmed timing. It is thought that they cycle together with a transfer rate of 100 gpm for two minutes, off for 12.4 minutes and then on again for 2 minutes until the time float switch lowers to the off position.
The dosing tanks utilizes of (3) pump sets each consisting of (2) pumps. Each pump set is programmed to run for (2) minutes followed by all pumps being off for (12) minutes, followed by a (2) minute run time for the next pump set. The three pumps sets continue this cycle until the time float switch is lowered to the off position. Each pump discharges to its own distribution valve with each being dedicated to its own chamber bed each which consists of (6) chamber rows. Pump timing inputs shown in Appendix D
2.0 SCOPE OF WORK
The scope of this project is to repair the CSWS so that the discharge pumping capacity is returned to the original design intent. This project calls the following actions to be taken:
1) Remove (8) pumps and replace with (8) new pumps.
2) Check all wiring to pumps – check for damage, electrical continuity. Repair damaged wire as needed.
3) Ensure proper operation of all system pumps, floats, and timers.
4) Check system programming to ensure pump cycling is in accordance with original design intent. Reprogram system if needed.
3.0 PROJECT DETAILS
3.1 Replace all existing pumps with new pumps.
3.2 All new pumps to be similar or equal in physical size, and have similar or equal hydraulic, electrical, and material characteristics as the existing pumps. New pumps shall be ½ hp – 60hz, 230 volt, 50 gpm, 2 wire submersible pumps;
3.3 Prior to ordering the pumps, submit pump specification and curve data to Government for review and approval.
March 28, 2023 Red Rock Canyon NCA – Septic System Pump Replacement Page 3 of 5
3.4 Prior to ordering pumps, provide Government with expected delivery lead time.
3.5 Notify Government a minimum of (5) working days prior to installing pumps.
3.6 Notify Government of any damaged wires between service panel and pumps prior to taking any repair action.
3.7 Any repairs to existing wiring shall be done in accordance with latest edition of the National Electrical Code.
3.8 Perform visual inspection of pumps. Confirm with Government the pumps are free of damage prior to installation.
3.9 Once electrical circuitry has been energized, start units to confirm proper rotation of motors and operations.
3.10 Complete pump installation and startup checks according to manufacturer’s written instructions.
3.11 Verify the automatic operation of the pumps by raising and lowering floats to simulate normal raising and lowering of the tank liquid level. Run pumps through several cycles to confirm timers are operating correctly. Contractor to verify these operations with Government present.
3.12 Pumps will be considered defective if they do not pass tests and inspections.
3.13 Provide Government with post installation report that details the following:
a) All repair actions taken.
b) Pump amperage draws.
c) Steps taken to verify proper pump operations.
d) Pump programming inputs.
3.14 Contractor shall repair any damage caused by their operations at their cost.
4.0 PROJECT ADMINISTRATION
4.1 Project Coordination
4.1.1 Contractor shall notify Government a minimum of 5 working days before initiating on-site work area work efforts.
4.1.2 Government shall provide the resources necessary to keep the work area free of Red Rock Canyon NCA visitors.
4.1.3 Government will provide water to Contractor at Contractors request to test pumps. Notice of need for water shall be provided by Contractor to Government (2) days prior to actual need.
4.1.4 Government personal shall be available by phone or email and may be present on-site to respond to Contractor questions. Contact information will be provided when Notice To Proceed is issued.
4.1.5 Government to provide Contract with system installation and operation and maintenance manual.
March 28, 2023 Red Rock Canyon NCA – Septic System Pump Replacement Page 4 of 5
4.1.6 Contractor personnel shall have a minimum of 5 years demonstrated experience programming Orenco pump timer/sequencing programs.
4.1.7 Contractor shall park their service vehicles in locations approved by Government to prevent damage to existing septic system components.
4.1.8 Contractor shall be responsible for disposing of existing pumps in accordance with all Federal, State, and local regulations.
4.1.9 Provide Government with all pump warranty information. Pumps shall be warranted for a minimum of (1) year to be free of defects in material and workmanship from date of installation.
4.1.10 Provide Government with pump documentation including any operations and maintenance instructions.
4.2 Period of Performance/Site Access/Work Hours/Protection
4.2.1 Period of Performance:
a. Pumps shall be purchased or backordered no later than 10 business days from the issuance of
Notice to Proceed.
b. Period of performance is 45 calendar days from Notice to Proceed.
c. The Contractor shall notify Government five working days in advance of initiating work at the site and obtain Government approval for that date.
4.2.2 Site Access:
a. The Contractor shall have full use of areas needed to perform the work. Contractor’s use of premises is limited only by Governments right to perform work. Schedule and sequence operations necessary to complete the work.
b. Government shall install as needed signs and protective barriers to prevent the public from entering the women’s restroom area during the project period of performance.
4.2.3 Work Hours:
a. Work shall be performed Monday through Friday, 7:00 a.m. to 5:00 p.m. except on legal holidays. Work at other times shall be prior approved by Government.
4.2.4 Protection:
a. Protect any areas adjacent to the project site from any debris. Comply with governing regulations pertaining to environmental protection. Ensure safety of persons in the work area.
Provide temporary barricades as required to protect personnel and public from injury.
4.3 BUREAU OF LAND MANAGEMENT SOUTHERN NEVADA POINTS OF CONTACT
NVSO Contracting Officer 1340 Financial Blvd Reno NV 89502 775-861-6402 Office 775-861-6634 Fax
March 28, 2023 Red Rock Canyon NCA – Septic System Pump Replacement Page 5 of 5
Contracting Officers Representative/Project Manager Paul Lohman, P.E.
4701 N. Torrey Pines Drive Las Vegas, NV 89130
(702) 515-5039
EXHIBITS
APPENDIX A
Red Rock Canyon Visitor Center Centralized Small Wastewater System
As-Built Plans kclick New Stamp
Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Text Box Depth of Bed = 8.5 ft kclick Text Box Depth of Bed = 8.0 ft kclick Text Box Depth of Bed = 8.5 ft kclick Text Box Depth of Bed = 8.0 ft kclick Text Box Depth of Bed = 7.5 ft kclick Text Box Depth of Bed = 7.0 ft kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Oval kclick Oval kclick Oval kclick Text Box Distribution Valves (7 ft from Tank) kclick Line kclick Line kclick Text Box 38 ft to Roadway kclick Line kclick Text Box 20 ft to Roadway kclick Rectangle kclick Typewritten Text
AS-BUILT EDITS
kclick Line kclick Typewritten Text
CLEANOUT
kclick Typewritten Text
VENT STACK
kclick Typewritten Text
REMOVED/MODIFIED
kclick Oval kclick Oval kclick Line kclick Line kclick Line kclick Oval kclick Oval kclick Oval kclick Callout 1.25" Blow-off Valves (See Sheet 00.06) kclick Line kclick Rectangle kclick Rectangle kclick Rectangle kclick Rectangle kclick Rectangle kclick Typewritten Text Edit Date: 06JUL12 kclick Line kclick Line
Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Typewritten Text kclick Typewritten Text kclick Line kclick Text Box Depth of Bed = 8.5 ft kclick Text Box Depth of Bed = 8.0 ft kclick Text Box Depth of Bed = 8.5 ft kclick Text Box Depth of Bed = 8.0 ft kclick Text Box Depth of Bed = 7.5 ft kclick Text Box Depth of Bed = 7.0 ft kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Oval kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Oval kclick Oval kclick Oval kclick Line kclick Text Box 20 ft to Roadway kclick Callout Pressurized Piping (No Cleanouts) kclick Line kclick Text Box 38 ft to Roadway kclick Rectangle kclick Rectangle kclick Rectangle kclick Callout 1.25" Blow-off Valves (See Sheet 00.06) kclick Line kclick Line kclick Line kclick Typewritten Text kclick Typewritten Text kclick Typewritten Text kclick Rectangle kclick Typewritten Text
AS-BUILT EDITS
kclick Typewritten Text kclick Typewritten Text
VENT STACK
kclick Typewritten Text
CLEANOUT
kclick Typewritten Text kclick Typewritten Text kclick Oval kclick Typewritten Text kclick Typewritten Text kclick Oval kclick Typewritten Text kclick Typewritten Text kclick Typewritten Text kclick Line kclick Line kclick Typewritten Text
REMOVED/MODIFIED
kclick Typewritten Text Edit Date: 06JUL12 kclick Callout Distribution Valves (7 ft from Tank) kclick Line
Rectangle kclick Typewritten Text
AS-BUILT EDITS
kclick Line kclick Typewritten Text Edit Date: 06JUL12 kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Line kclick Typewritten Text
REMOVED/MODIFIED
kclick Line kclick Oval kclick Oval kclick Oval kclick Oval kclick Callout 1.25" Blow-Off Valve at Terminus of Each Lateral kclick Line kclick Line kclick Line kclick Oval kclick Typewritten Text
1.25" BLOW-OFF VALVE
kclick Line
APPENDIX B
Existing Pumps – Manufacturer Data
Technical Data Sheet
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 8.0, © 09/19
PF Series Submersible Effluent Pumps:
1-Phase, 60-Hz, 4-inch (100-mm)
Applications Our PF Series 4-inch (100-mm) Submersible Effluent Pumps are designed to transport screened effluent (with low TSS counts) from septic tanks or dosing tanks.They are constructed of lightweight, corrosion-resistant stainless steel and engineered plastics; all are field-serviceable and repairable with common tools; PF Series pumps are CSA certified to the U.S. and Canadian safety standards for effluent pumps, meeting UL requirements.
PF Series pumps are used in a variety of applications, including pressur-ized drainfields, packed-bed filters, mounds, aerobic units, effluent irri-gation, liquid-only (effluent) sewers, wetlands, lagoons, and more. These pumps are designed to be used with a Biotube® pump vault or after a secondary treatment system.
Features/Specifications To specify this pump for your installation, require the following:
• Minimum 24-hour run-dry capability (liquid end) with no deterioration in pump life or performance*
• Patented 1⁄8-inch (3-mm) bypass orifice to ensure flow recirculation for motor cooling and to prevent air bind
• Liquid-end repair kits available for better long-term cost of ownership
• TRI-SEAL™ floating impeller design on 10, 20, and 30 gpm (0.6, 1.3, and 1.9 L/sec) models; floating stack design on 50 and 75 gpm (3.2 and 4.7 L/sec) models
• Franklin Electric Super Stainless motor, rated for continuous use and frequent cycling
• Type SOOW 600-V motor cable (model PF751512 uses 14 AWG, SJOOW, 300-V cord)
* Not applicable for 5-hp (3.73 kW) models
Standard Models See specifications chart, pages 2-3, for a list of standard pumps. For a complete list of available pumps, call Orenco.
Product Code Diagram
PF -
Nominal flow, gpm (L/sec):
10 = 10 (0.6) 20 = 20 (1.3) 30 = 30 (1.9) 50 = 50 (3.2) 75 = 75 (4.7)
Pump, PF Series
Frequency:
1 = single-phase 60 Hz
Voltage, nameplate:
1 = 115* 2 = 230
Horsepower (kW):
05 = ½ hp (0.37) 07 = ¾ hp (0.56) 10 = 1 hp (0.75) 15 = 1½ hp (1.11) 20 = 2 hp (1.50) 30 = 3 hp (2.24) 50 = 5 hp (3.73)
Cord length, ft (m):‡
Blank = 10 (3) 20 = 20 (6) 30 = 30 (9) 50 = 50 (15)
Check valve:
Blank = no internal check valve CV = internal check valve†
* ½-hp (0.37kW) only † Available for 10 gpm (0.6 L/sec), 1/2 hp (0.37 kW) ‡ Note: 20-ft cords are available only for pumps through 1½ hp
Franklin Super Stainless Motor
Franklin Liquid End
Discharge Connection
Bypass Orifice
Suction Connection
LR80980
LR2053896
Powered by
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 8.0, © 09/19
Technical Data Sheet
Specifications
Pump Model PF100511 10 (0.6) 0.50 (0.37) 1 115 120 12.7 12.7 6 1 ¼ in. GFP 23.0 (660) 16 (406) 26 (12) 300
PF100511CV 10 (0.6) 0.50 (0.37) 1 115 120 12.7 12.7 6 1 ¼ in. GFP 23.0 (660) 16 (406) 26 (12) 300
PF100512 10 (0.6) 0.50 (0.37) 1 230 240 6.3 6.3 6 1 ¼ in. GFP 23.0 (660) 16 (406) 26 (12) 300
PF100712 4, 5 10 (0.6) 0.75 (0.56) 1 230 240 8.3 8.3 8 1 ¼ in. GFP 25.9 (658) 17 (432) 30 (14) 300
PF101012 5, 6 10 (0.6) 1.00 (0.75) 1 230 240 9.6 9.6 9 1 ¼ in. GFP 27.9 (709) 18 (457) 33 (15) 100
PF102012 5, 6, 7, 8 10 (0.6) 2.00 (1.49) 1 230 240 12.1 12.1 18 1 ¼ in. SS 39.5 (1003) 22 (559) 48 (22) 100
PF200511 20 (1.3) 0.50 (0.37) 1 115 120 12.3 12.5 4 1 ¼ in. GFP 22.3 (566) 18 (457) 25 (11) 300
PF200512 20 (1.3) 0.50 (0.37) 1 230 240 6.4 6.5 4 1 ¼ in. GFP 22.5 (572) 18 (457) 26 (12) 300
PF201012 4, 5 20 (1.3) 1.00 (0.75) 1 230 240 10.5 10.5 7 1 ¼ in. GFP 28.4 (721) 20 (508) 33 (15) 100
PF201512 4, 5 20 (1.3) 1.50 (1.11) 1 230 240 12.4 12.6 9 1 ¼ in. GFP 34.0 (864) 24 (610) 41 (19) 100
PF300511 30 (1.9) 0.50 (0.37) 1 115 120 11.8 11.8 3 1 ¼ in. GFP 21.3 (541) 20 (508) 28 (13) 300
PF300512 30 (1.9) 0.50 (0.37) 1 230 240 6.2 6.2 3 1 ¼ in. GFP 21.3 (541) 20 (508) 25 (11) 300
PF300712 30 (1.9) 0.75 (0.56) 1 230 240 8.5 8.5 5 1 ¼ in. GFP 24.8 (630) 21 (533) 29 (13) 300
PF301012 4 30 (1.9) 1.00 (0.75) 1 230 240 10.4 10.4 6 1 ¼ in. GFP 27.0 (686) 22 (559) 32 (15) 100
PF301512 4, 5 30 (1.9) 1.50 (1.11) 1 230 240 12.6 12.6 8 1 ¼ in. GFP 32.8 (833) 24 (610) 40 (18) 100
PF302012 5, 6, 7 30 (1.9) 2.00 (1.49) 1 230 240 11.0 11.0 10 1 ¼ in. SS 35.5 (902) 26 (660) 44 (20) 100
PF303012 5, 6, 7, 8 30 (1.9) 3.00 (2.23) 1 230 240 16.8 16.8 14 1 ¼ in. SS 44.5 (1130) 33 (838) 54 (24) 100
PF305012 5, 6, 7, 8 30 (1.9) 5.00 (3.73) 1 230 240 25.6 25.8 23 1 ¼ in. SS 66.5 (1689) 53 (1346) 82 (37) 100
PF500511 50 (3.2) 0.50 (0.37) 1 115 120 12.1 12.1 2 2 in. SS 20.3 (516) 24 (610) 27 (12) 300
PF500512 50 (3.2) 0.50 (0.37) 1 230 240 6.2 6.2 2 2 in. SS 20.3 (516) 24 (610) 27 (12) 300
PF500712 50 (3.2) 0.75 (0.56) 1 230 240 8.5 8.5 3 2 in. SS 23.7 (602) 25 (635) 31 (14) 300
PF501012 50 (3.2) 1.00 (0.75) 1 230 240 10.1 10.1 4 2 in. SS 27.0 (686) 26 (660) 35 (16) 100
PF5015124 50 (3.2) 1.50 (1.11) 1 230 240 12.5 12.6 5 2 in. SS 32.5 (826) 30 (762) 41 (19) 100
PF503012 4, 5, 7, 8 50 (3.2) 3.00 (2.23) 1 230 240 17.7 17.7 8 2 in. SS 43.0 (1092) 37 (940) 55 (25) 100
PF505012 5,6,7,8 50 (3.2) 5.00 (3.73) 1 230 240 26.2 26.4 13 2 in. SS 65.4 (1661) 55 (1397) 64 (29) 100
PF751012 75 (4.7) 1.00 (0.75) 1 230 240 9.9 10.0 3 2 in. SS 27.0 (686) 27 (686) 34 (15) 100
PF751512 75 (4.7) 1.50 (1.11) 1 230 240 12.1 12.3 4 2 in. SS 33.4 (848) 30 (762) 44 (20) 100
1 GFP = glass-filled polypropylene; SS = stainless steel. The 1 ¼-in. NPT GFP discharge is 2 7⁄8 in. octagonal across flats; the 1 ¼-in. NPT SS discharge is 2 1⁄8 in. octagonal across flats; and the 2-in.
NPT SS discharge is 2 7⁄8 in. hexagonal across flats. Discharge is female NPT threaded, U.S. nominal size, to accommodate Orenco® discharge hose and valve assemblies. Consult your Orenco Distributor about fittings to connect hose and valve assemblies to metric-sized piping.
2 Minimum liquid level is for single pumps when installed in an Orenco Biotube® Pump Vault or Universal Flow Inducer. In other applications, minimum liquid level should be top of pump. Consult Orenco for more information.
3 Weight includes carton and 10-ft (3-m) cord.
4 High-pressure discharge assembly required.
5 Do not use cam-lock option (Q) on discharge assembly.
6 Custom discharge assembly required for these pumps. Contact Orenco.
7 Capacitor pack (sold separately or installed in a custom control panel) required for this pump. Contact Orenco.
8 Torque locks are available for all pumps, and are supplied with 3-hp and 5-hp pumps.
De si gn g pm
(L /s ec
Ho rs ep ow er
(k W
Ph as e
Na m ep la te vo lta ge
Ac tu al v ol ta ge
De si gn fl ow am ps
M ax a m ps
Im pe lle rs
Di sc ha rg e si ze an d m at er ia l 1
Le ng th , i n.
(m m
M in
. l iq ui d le ve l, in m m
W ei gh t, 3 l b
(k g)
Ra te d cy cl es
/d ay
X
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1
Technical Data Sheet
Materials of Construction Discharge Glass-filled polypropylene or stainless steel
Discharge bearing Engineered thermoplastic (PEEK)
Diffusers Glass-filled PPO (Noryl GFN3)
Impellers Celcon® acetal copolymer on 10-, 20, and 30-gpm models; 50-gpm impellers are Noryl GFN3
Intake screen Polypropylene
Suction connection Stainless steel
Drive shaft 7/16 inch hexagonal stainless steel, 300 series
Coupling Sintered stainless steel, 300 series
Shell Stainless steel, 300 series
Motor Franklin motor exterior constructed of stainless steel. Motor filled with deionized water and propylene glycol for constant lubrication. Hermetically sealed motor housing ensures moisture-free windings. All thrust absorbed by Kingsbury-type thrust bearing. Rated for continuous duty. Single-phase motors are equipped with surge arrestors for added security. Single-phase motors through 1.5 hp (1.11 kW) have built-in thermal over-load protection, which trips at 203-221˚ F (95-105˚ C).
Using a Pump Curve A pump curve helps you determine the best pump for your system. Pump curves show the relationship between flow and pressure (total dynamic head, or TDH), providing a graphical representation of a pump’s optimal performance range. Pumps perform best at their nominal flow rate. These graphs show optimal pump operation ranges with a solid line and show flow rates outside of these ranges with a dashed line. For the most accurate pump specification, use Orenco’s PumpSelect™ software.
Pump Curves
To ta l d yn am ic h ea d (T
D H
) i n fe et
Flow in gallons per minute (gpm) 2 4 8 10 12 14 1660
PF1005-FC
w/ ¼" flow controller
PF10 Series, 60 Hz, 0.5 - 2.0 hp
PF1007
PF1010
PF1020
PF1005
To ta l d yn am ic h ea d (T
D H
) i n fe et
Flow in gallons per minute (gpm) 5 10 20 25 30 35 40150
PF2005
PF2010
PF2015
PF20 Series, 60 Hz, 0.5 - 1.5 hp
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1
Technical Data Sheet
Pump Curves, cont.
To ta l d yn am ic h ea d (T
D H
) i n fe et
Flow in gallons per minute (gpm) 5 10 20 25 30 35 40 45150
PF3005
PF3007
PF3010
PF3015
PF3020
PF3030
PF3050 PF30 Series, 60 Hz, 0.5 - 5.0 hp
To ta l d yn am ic h ea d (T
D H
) i n fe et
Flow in gallons per minute (gpm)
10 0 20 40 50 60 70 80 9030
PF5050
PF5030
PF5015
PF5010
PF5007
PF5005
PF50 Series, 60 Hz, 0.5 - 5.0 hp
To ta l d yn am ic h ea d (T
D H
) i n fe et
Flow in gallons per minute (gpm) 10 20 40 50 60 70 80 90 100300
PF75 Series, 60 Hz, 1.0 - 1.5 hpPF7515
PF7510
X
APPENDIX C
ORENCO – Biotube Pump Vault
ORENCO – Flow Inducer Tower
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PVU-1 Rev. 3.0, © 08/18
Universal Biotube® Pump Vaults
Applications Orenco Biotube® Pump Vaults are used to filter effluent that is pumped from septic tanks or separate dosing tanks in STEP systems and onsite wastewater treatment systems. They remove two-thirds of suspended solids, on average. Pump vaults house a Biotube effluent filter and one or two Orenco high-head effluent pumps and can be used in single-compartment septic tanks with flows up to 40 gpm (2.5 L/sec). When flows are greater than 40 gpm (2.5 L/sec), a double-compartment sep-tic tank or separate dosing tank is recommended.
For use with Orenco® 4-inch (100-mm) Submersible Effluent Pumps
Tank Access and Riser Diameters Diameter, in. (mm) PVU with PVU with simplex pump duplex pumps
Tank access, minimum 19 (483) 19 (483)
Tank access, recommended 20 (508) 20 (508)
Riser, minimum 24 (600) 30 (750)
External flow inducer
Inlet holes
Side view
Support pipe
General The Orenco Biotube Pump Vault includes a molded polyethylene hous-ing with an internal Biotube filter cartridge constructed of polypropylene and PVC. Schedule 80 PVC support pipes are included to suspend the vault in a tank opening. “Earless” 68-inch (1727-mm) vaults, which rest on the bottom of the tank instead of on support pipes, are also available.
The filter cartridge can be removed without pulling the pump or the vault.
Effluent enters through inlet holes around the perimeter of the Biotube vault and flows through the Biotubes to the external flow inducer. The external flow inducer accommodates one or two pumps. Orenco Biotube Pump Vaults are covered by U.S. patents #4,439,323 and 5,492,635.
Standard Models
PVU48-1818, PVU57-1819, PVU68-2419, PVU84-2419, PVU95-3625
Product Code Diagram
Materials of Construction Support pipe Schedule 80 PVC
Biotube® vault Polyethylene
Biotube filter cartridge Polypropylene/PVC
Float stem Schedule 40 PVC
Drain valve ball Polypropylene
PVU - -
Vault height:* 48" (1219 mm) 57" (1448 mm) 68" (1727 mm) 72" (1829 mm) 84" (2134 mm) 95" (2413 mm) or custom specification
Universal Pump Vault
* Custom heights from 42" to 135" available
Inlet hole height, standard:
13" (330 mm) 18" (457 mm) 19" (482 mm) 25" (635 mm)
Support pipe length:
Blank = standard, for 24" (600 mm) riser L = long, for 30" (750 mm) riser NB = no support pipe bracket (earless)
Biotube® filter mesh:
Blank = 1/8" (3.2 mm) mesh P = 1/16" (1.6 mm) mesh
Cartridge height, standard:
18" (457 mm) 24" (610 mm) 36" (914 mm) x
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PVU-1 Rev. 3.0, © 08/18
Technical Data Sheet
DR
AW
N
BY
CD
O re nc o
Sy st em s
In co rp o ra te d
R Da te
6/ 1/
CU
ST
O M
D
RA
W
IN
G:
RE
VI
SI
O
N:
Installation Instruction
Instructions
Studies show that no individual will take the time to read this text. It is simply here to fulfill your imagination.
Installation Instruction
X-STYLE VAULT INSTRUCTIONS
PART# INSTR-X
1" SCH. 40 PVC
CUT LENGTH 48 3/4"
DO NOT GLUE JOINT
USE REINFORCED TOP
PV
UP
-1
9-
L
W O
RK
O
RD
ER
AP
PR
O
VE
D
BY
M
AS
TE
R:
Side view cutaway
C
D
Top view
Support pipes
H
F
2-inch (50-mm) min.
J
G
A
B
Dimensions A, in. (mm) 3 (76)
B, in. (mm) 4 (102)
C, in. (mm) 17.3 (439)
D, in. (mm) 16.6 (422)
E, in. (mm) 12 (305)
Drain valve ball
E
Specifications Model PVU48-1818 PVU57-1819 PVU68-2419 PVU84-2419 PVU95-3625
F, vault height, in. (mm) 48 (1219) 57 (1448) 68 (1727) 84 (1727) 95 (2413)
G, lowest float setting point, in. (mm) 21 (533) 29 (737) 35 (889) 51 (1295) 50 (1270)
H, inlet hole height, in. (mm)* 18 (457) 19 (483) 19 in. (483) 19 (482) 25 (635)
J, Biotube® cartridge height, in. (mm) 18 (457) 18 (457) 24 (610) 24 (610) 36 (914)
Biotube mesh opening, in. (mm) 0.125 (3) 0.125 (3) 0.125 (3) 0.125 (3) 0.125 (3)
Filter flow area, ft2 (m2) 4.4 (0.4) 4.4 (0.4) 5.9 (0.5) 5.9 (0.5) 9.0 (0.84)
Filter surface area, ft2 (m2) 14.5 (1.35) 14.5 (1.35) 19.7 (1.83) 19.7 (1.83) 30 (2.79)
Maximum flow rate, gpm (L/sec) 140 (8.8) 140 (8.8) 140 (8.8) 140 (8.8) 140 (8.8)
* May vary depending on the configuration of the tank.
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-FI-FIT-1 Rev. 3.0, © 06/19
Flow Inducer Towers Applications Orenco® flow inducer towers are designed for use in commercial/ municipal recirculation and final discharge tanks following secondary treatment, where filtration is not required. Flow inducer towers can be ordered to house from two to five of Orenco’s 4-in. submersible efflu-ent pumps.
General The base of the flow inducer tower rests on the bottom of the tank and the top of the flow inducer tower extends at least eight inches into the riser. For tanks with curved bottoms, an Orenco vault basin (VB1806-FRP) is necessary to create a flat surface on which the flow inducer tower can rest. The pumps sit on raised fiberglass platforms inside of the 5-inch (127-mm) diameter Class 125 flow inducer tubes.
A float bracket is attached to the tower to accommodate an Orenco float assembly.
Standard Models Recirculation Tank Models:
FITR-D102, FITR-T102, FITR-Q102, FITR-P102
FITR-D126, FITR-T126, FITR-Q126, FITR-P126
Discharge Tank Models:
FITD-D102, FITD-T102, FITD-Q102, FITD-P102
FITD-D126, FITD-T126, FITD-Q126, FITD-P126
Product Code Diagram
Height:
102 = 102" (2590 mm) 126 = 126" (3200 mm) Or specify custom size
Flow inducers:
D = duplex (houses two pumps) T = triplex (houses three pumps) Q = quad (houses four pumps) P = pentad (houses five pumps)
FIT -
Tank type:
R = recirculation tank D = discharge tank
Flow inducer tower
Discharge plumbing assembly (purchased separately)
Float assembly (purchased separately)
Float bracket
Support pipes
Flow inducer tubes
Structural plates
Inlet holes
Tower base
Orenco® flow inducer tower (Duplex model shown)
Materials of Construction Support pipes Schedule 80 PVC
Float bracket PVC
Flow inducer tubes PVC
Structural plates Fiberglass
Tower base Fiberglass
Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-FI-FIT-1 Rev. 3.0, © 06/19
Technical Data Sheet
Top view, Orenco flow inducer tower (Model FITR-D102 shown)
C B
A
GF
Close up, flow inducer tower for discharge tanks (Model FITD-D102 shown)
Close up, flow inducer tower for recirculation tanks (Model FITR-D102 shown)
Side view, Orenco flow inducer tower (Model FITR-D102 shown)
D E
F G
Specifications Recirculation Tank Examples
Dimensions, in. (mm) FITR-D102 FITR-T126 FITR-Q102 FITR-P126
Number of tubes 2 3 4 5
A - Tube diameter, nominal 5.00 (125) 5.00 (125) 5.00 (125) 5.00 (125)
B - Structural plate diameter 15.00 (381) 15.00 (381) 17.00 (432) 17.00 (432)
C - Support pipe length 24.00 (610) 24.00 (610) 24.00 (610) 24.00 (610)
D - Tower height 102.00 (2590) 126.00 (3200) 102.00 (2590) 126.00 (3200)
E - Support pipe height 94.75 (2407) 118.75 (3016) 94.75 (2407) 118.75 (3016)
F - Inlet hole height 19.25 (489) 19.25 (489) 19.25 (489) 19.25 (489)
G - Pump plate height 19.00 (483) 19.00 (483) 19.00 (483) 19.00 (483)
Inlet hole diameter 2.00 (50) 2.00 (50) 2.00 (50) 2.00 (50)
Inlet holes per tube 8 8 8 8
Discharge Tank Examples
Dimensions, in. (mm) FITD-D102 FITD-T126 FITD-Q102 FITD-P126
Number of tubes 2 3 4 5
A - Tube diameter, nominal 5.00 (125) 5.00 (125) 5.00 (125) 5.00 (125)
B - Structural plate diameter 15.00 (381) 15.00 (381) 17.00 (432) 17.00 (432)
C - Support pipe length 24.00 (610) 24.00 (610) 24.00 (610) 24.00 (610)
D - Tower height 102.00 (2590) 126.00 (3200) 102.00 (2590) 126.00 (3200)
E - Support pipe height 94.75 (2407) 118.75 (3016) 94.75 (2407) 118.75 (3016)
F - Inlet hole height 9.25 (235) 9.25 (235) 9.25 (235) 9.25 (235)
G - Pump plate height 9.00 (229) 9.00 (229) 9.00 (229) 9.00 (229)
Inlet hole diameter 2.00 (50) 2.00 (50) 2.00 (50) 2.00 (50)
Inlet holes per tube 8 8 8 8
APPENDIX D
ORENCO – Original Pump Programming Inputs
EIN-CP-SET-2729
Rev 1.0 © 05/16/12
Custom TCOM System Settings Orenco’s Custom TCOM Control Panels includes a number of user adjustable parameters that can be adjusted at the panel or remotely via modem connection. See document EIN-CP-TCOM-3 on how to access and change your adjustable parameters.
This TCOM program uses point numbers to identify the various program functions. The following point numbers (w/corresponding page letters) are adjustable by the system operator:
Adjustable Parameters Factory Default
Page d: Primary Tank Timer Settings 49 PT Man Off Time 12.4 Min 50 PT Man Ovr Off 5.2 Min 52 PT On Time 2.0 Min 53 PT OVR On Time 2.0 Min 55 PT HLA Delay 5.0 Sec 56 PTLagPumpEnable off 57 Min OVR Cycles 3.0 58 Pump 1 GPM 50.0 GPM 59 Pump 2 GPM 50.0 GPM 61 Pump1HighAmpLim 12.0 Amps 62 Pump1LowAmpLim 8.0 Amps 63 Pump2HighAmpLim 12.0 Amps 64 Pump2LowAmpLim 8.0 Amps
Page e: Dose Tank Timer Settings 65 DT Man Off Time 12.4 Min 66 DT Man Ovr Off 5.2 Min 68 DT On Time 2.0 Min 69 DT OVR On Time 2.0 Min 71 DT HLA Delay 5.0 Sec 73 DTLagPumpEnable on 74 Min OVR Cycles 3.0
Page f: Dose Tank Flow Settings 81 Pump 3 GPM 50.0 GPM 82 Pump 4 GPM 50.0 GPM 83 Pump 5 GPM 50.0 GPM 84 Pump 6 GPM 50.0 GPM 85 Pump 7 GPM 50.0 GPM 86 Pump 8 GPM 50.0 GPM
Page g: Dose Tank Current Settings
97 Pump3HighAmpLim 9.0 Amps 98 Pump3LowAmpLim 5.0 Amps 99 Pump4HighAmpLim 9.0 Amps 100 Pump4LowAmpLim 5.0 Amps 101 Pump5HighAmpLim 9.0 Amps 102 Pump5LowAmpLim 9.0 Amps 104 Pump6LowAmpLim 5.0 Amps 105 Pump7HighAmpLim 9.0 Amps 106 Pump7LowAmpLim 5.0 Amps 107 Pump8HighAmpLim 9.0 Amps 108 Pump8LowAmpLim 5.0 Amps
Page h: Alarm Settings 113 LocalAlarmDelay 120.0 Min 114 LocalReactDelay 480.0 Min 115 PageInterval 30.0 Min 116 Amp Alarm Delay 10.0 Secs
For instructions on how to override a numeric point value see page 14 of document EIN-
CP-TCOM-3.
USER LOG Summary
Normal Extended
1) Alarm Change 17) Pump1&2Totals
2) 18) Pump1Daily
3) 19) Pump2Daily
4) 20) DosePumpTotals
5) 21) Pump3Daily
6) 22) Pump4Daily
7) 23) Pump5Daily
8) 24) Pump6Daily
9) 25) Pump7Daily
10) 26) Pump8Daily
11) 27)
12) 28)
13) 29)
14) 30)
15) 31)
16) 32)
To access the User Logs: Go to 4)Expanded Reports Menu, then to 3)User Log Report
| SOW RR VC Septic System |
| Ex 1 |
| Ex 2 |
| APPENDIX A |
| RRCVC Septic - AS-BUILT DRAWINGS - A |
| 4-9SHT1 |
| 4-9SHT2 |
| 4-9SHT3 |
| 4-9SHT6 |
| 4-9SHT7 |
| 4-9SHT8 |
| 4-9SHT9 |
| 4-9SHT10 |
| 4-9SHT11 |
| 4-9SHT12 |
| 4-9SHT13 |
| 4-9SHT14 |
| 4-9SHT15 |
| 4-9SHT16 |
| 4-9SHT17 |
| 4-9SHT18 |
| 4-9SHT19 |
| 4-9SHT20 |
| APPENDIX B |
| Orenco Pump Data Sheet - B |
| APPENDIX C |
| Orenco Biotube - C |
| Orenco Flow Inducer Tower - C |
| APPENDIX D |
| Orenco Pump Timing Inputs - D |
File details come from the government source that posted it. Updated .