A04_-_Attachment_-_Corrective_Action_Reports.pdf
PDF 12 MB Posted
- Attached to
- AK-MCGRATH ADMIN SITE-UST EVALUATION Federal contract opportunity
- Solicitation number
- 140FS126Q0059
About this file
This is a Corrective Action Report documenting the removal of contaminated soils at the Wollard House in McGrath, Alaska, a United States Fish and Wildlife Service (USFWS) property. The report details activities performed August 22-24, 2018, by Tikigaq Construction LLC and Agviq Environmental Services LLC in response to a home heating oil (HHO) spill from a decommissioned 500-gallon underground storage tank. The remediation involved excavating 16 cubic yards of contaminated soil to a depth of 6.5 feet and conducting post-excavation sampling and analysis. Field screening using photoionization detection (PID) identified contamination levels ranging from 44 to 382 ppm, with seven soil samples submitted to SGS Laboratories for laboratory analysis of diesel range organics (DRO), gasoline range organics (GRO), residual range organics (RRO), BTEX compounds, and polycyclic aromatic hydrocarbons (PAH).
Laboratory results indicated DRO contamination exceeding Alaska Department of Environmental Conservation (ADEC) cleanup levels of 250 mg/kg at two locations: 1,170 mg/kg at sample PE-2-6.5 and 1,280 mg/kg at PE-3-6.5, both collected from the west wall at 6.5 feet below ground surface. Additional DRO exceedances were identified in floor samples PEF-3 (422 mg/kg) and PEF-5 (229 mg/kg). All other analytes were either non-detected or below ADEC Method Two cleanup criteria. The report concluded that DRO contamination extends beyond the excavated area and recommends further characterization through soil borings and groundwater monitoring wells or direct sensing technologies to delineate the vertical extent of contamination. Indoor air quality assessment using PID readings of 0 to 0.1 ppm indicated no hazard to human health at the facility. The Alaska Department of Environmental Conservation approved the final corrective action report on March 27, 2019, under ADEC File Number 2612.38.009 and contract numbers F15PC00080/F17PD01978.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140FS126Q0059_Amd_0001.pdf | ||
| B08_-_140FS126Q0059.pdf | ||
| Sol_140FS126Q0059.pdf | ||
| A06_-_Bid_Schedule.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DDepartmentt off Environmentall Conservationn
SPILL PREVENTION & RESPONSE
Contaminated Sites Program
610 University Avenue Fairbanks, Alaska 99709
Main: 907.451.2143 Fax: 907.451.2155 www.dec.alaska.gov
File No: 2612.38.009
March 27, 2019
Electronic Delivery Only Charles D. Grant Regional Environmental Compliance Coordinator USFWS Region 1, 7, 8 Division of Engineering 1011 East Tudor Road Anchorage, Alaska 99503
Subject: DEC Approval of Final Wollard House Soil Removal Corrective Action Report, United States Fish & Wildlife Service, McGrath, Alaska
Dear Mr. Grant, The Alaska Department of Environmental Conservation (DEC) has received and reviewed the final Wollard House Soil Removal Corrective Action Report for McGrath, Alaska. The report details the activities performed during the removal of contaminated soils at the Wollard House in McGrath, Alaska. DEC provided comments on a previous version of this report on February 28, 2019 and received the most recent response on March 27, 2019. All of DEC’s comments have been satisfactorily addressed and the report is approved.
If you have any questions, please contact me at (907) 451-5175 or via email at jamie.mckellar@alaska.gov.
Sincerely, Jamie McKellar Environmental Program Specialist
Enclosure: Comment Table for Wollard House CA Report, McGrath cc: Dumitru Radu, Tikigaq/AGVIQ Dean Camery, Tikigaq/AGVIQ David Leadenham, Tikigaq/AGVIQ Anthony Kuntz, USFWS Eric Breitenberger, DEC
Digitally signed by Jamie McKellar Date: 2019.03.27 10:06:41 -08'00'
A
LA
SK
A
D
EP
A R
TM
EN
T O
F
EN
V
IR
O N
M
EN
TA
L
C O
N
SE
R V
A
TI
O N
C
N
TA
M
IN
A
TE
D
S
IT
ES
P
R O
G R
M
Pa ge o f 2
D oc um en t:
Fi na l W ol la rd H ou se
S oi l R em ov al
, M cG ra th
, A K
, C or re ct iv e
A ct io n
Pl an
G
V
IQ
E nv iro nm en ta l S er vi ce s, M ar ch
6, D
EC
R ev ie w er
Ja m ie
M cK el la r C om m en t o.
/S ec tio n D
EC
C om m en t/R ec om m en da tio n
Fe br ua ry
8, U
SF
W
S R es po ns e
3/ 1/
1.
Se c.
.2 ea se in cl ud e th e ap pr ox im at e di m en si on s o f t he ex ca va n.
In se rte d te xt
3/
/2
9:
D
EC
a cc ep ta nc e co nt in ge nt u po n re vi ew o f f in al iz ed d oc um en t.
/2
9:
D
EC
A cc ep ts
2.
Ta bl e se in cl ud e th e de pt h of e ac h sa m pl e.
se in cl ud e un its in th e A
D
EC
C le an up
L ev el s co lu m
Th
A D
EC
C le an up L ev el li st ed fo r c hr ys en e is ot ac cu ra te
It is u nc le ar w hy o nl y th re e
PA
H s ( ch ry se ne flu or an th en e, a nd p yr en
e) a re in cl ud ed in
T ab le
Sa pl e de pt hs a dd ed
U ni ts a dd t t he ti m e of w rit in g th e re po rt, th e cu rr en t C hr ys en e C le an up le ve l w as m g/ K g.
T he n ew C le an up le ve l a s o f t he ct ob er
7, A A
C ve rs io no w in th e ta bl ta bl e is fo r d et ec ta bl e re su lts th er ef or e, n on -d et ec te d an al yt es w er e no t in cl ud
/2
9:
D
EC
a cc ep ta nc e co nt in ge nt u po n re vi ew o f f in al iz ed d oc um en t.
3/
/2
9:
D
EC
A cc
LA
SK
A
D
EP
A R
TM
EN
T O
F
EN
V
IR
O N
M
EN
TA
L
C O
N
SE
R V
A
TI
N
TA
M
IN
A
TE
D
S
IT
ES
P
R O
G R o f 2 om m en t o.
/S ec tio n
D
EC
C om m en t/R ec om m en da
Fe br ua ry
8, U
SF
W S
R es po ns e 3/
1/
3.
on ce pt ua l S ite od el
“u pd at ed
C
SM
in di ca te s t ha t c on ta m in at ed su rf ac e so il
(0 to fe et ) i s s til l p re se nt a fte r t he e xc av at io n.
Is th co rr ec t?
Y es
Th e ar ea g en er al ly n or th ea st a nd e as t o f th e or ig in al e xc av at io n w as n ot d is tu rb du rin g th is fi el d ef fo rt.
T he re fo re , i t i s un kn ow n if co nt am in at io n ex is ts w ith in th e
0-ft in te rv al
/2
9:
D
EC
a cc ep ts
3/
/2
9:
D
EC
A cc
4.
Re ad in gs w er e 1, m g/ kg a nd
,2 p pm fo r P
E- 2-
6.
an d
PE
-3
-6 .5 re sp ec tiv el y, b ot h at th e ba se o f t he w es t w al l.
W er e th es e re ad in gs o r a na ly tic al re su lts
B as ed o n
Ta bl e 3, th e
Fi el d sc re en in g
R ea di ng s w er e a nd
1.
se in cl ud e th e de pt h of e ac h ex ce ed an ce in th e Se ct io n 4.
te
Te c ha ng ed to
A na ly tic al re su lts
Te a dd ed in se co nd p ar ag ra ph to in di ca te th at a ll la b sa m pl es w er e co lle ct ed fr om a d ep th o f 6 .5 ft . b gs
3/
/2
9:
D
EC
a cc ep ta nc e co nt in ge nt u po n re vi ew o f f in al iz ed d oc um en t.
3/
/2
9:
D
EC
A cc
5.
es e re su lts a re in di ca tiv e of so il ga s w ith in th e sc re en in g sa m pl es . T he re fo re
, t he se lo ca tio ns m ay b in cl os e pr ox im ity to th e co nt am in an t p lu
W hi ch p lu m e do es th is st at em en t r ef er to
D R
O p lu m e/ co nt am in at io n.
C ha ng ed te
“D R
O c on ta m in an t p lu m e”
3/
/2
9:
D
EC
a cc ep ta nc e co nt in ge nt u po n re vi ew o f f in al iz ed d oc um en t.
3/
/2
9:
D
EC
A cc
6.
D
EC
a gr ee s t ha t f ur th er in ve st ig at io n is n ee de d de lin ea te th e ve rti ca l e xt en t o f c on ta m in at io
7.
se n ot e th at th e m os t r ec en t v er si on o f 1
A
A C w as pr om ul ga te d on
O ct ob er
7, 8.
ot ed
3/
/2
9:
D
EC
A cc ep ts
3/
/2
9:
D
EC
A cc
WOLLARD HOUSE SOIL REMOVAL
McGRATH, ALASKA
CORRECTIVE ACTION REPORT
FINAL
March 26, 2019
Prepared for:
United States Fish & Wildlife Services
Innoko Wildlife Refuge
Prepared by:
Signature of Qualified Environmental
Professional Responsible for Preparing the Report:
Dumitru Radu
Date: March 26, 2019
Contract No. F15PC00080/F17PD01978
ADEC File Number – 2612.38.009
Tikigaq Construction LLC, and Agviq Environmental Services, LLC
701 S. Knik Goose Bay Road
Wasilla, AK. 99654
PAGE INTENTIONALLY BLANK
Wollard House Contaminated Soils Removal, McGrath, AK Work Plan United States Fish & Wildlife Services
CES-AGVIQ of Alaska i 3/26/2019
TABLE OF CONTENTS
ACRONYMS AND ABBREVIATIONS ..................................................................................... ii
Executive summary
1. Introduction
1.1. Project Objectives
1.2. Summary of Field Activities
2. Field Work
2.1. Soils Removal
2.2. Indoor Air Quality Initial Assessment
3. Field methodology
3.1. Field Screening
3.2. Sample Handling
4. Results and findings
4.1. Field Screening
4.2. Analytical Results
4.3. Indoor Air Quality Assessment
4.4. Quality Control and Quality Assurance
4.5. Conceptual Site Model
5. Conclusions and Recommendations
6. REFERENCES
TABLES IN TEXT
1: Cleanup Levels
2: Field Screening Results
3: Tabulated Detectable Results
FIGURES
1: Site Location Map
2: Site Vicinity
3: Site Detail
4: Excavation and Sampling Locations
APPENDICES
A: Figures
B: Photographic Log
C: SGS Laboratory Report
D: ADEC Laboratory Data Review Checklist
E: Updated Conceptual Site Model
F: Field Log Book
G: Transportation and Disposal
CES-AGVIQ of Alaska ii 3/26/2019
ACRONYMS AND ABBREVIATIONS
AAC ................ Alaska Administrative Code
ADEC .............. Alaska Department of Environmental Conservation
AES…………...Agviq Environmental Services, LLC
AK ................... Alaska Method bgs ................... below ground surface
BTEX............... benzene, toluene, ethylbenzene, and xylenes
COC ................. contaminants-of-concern
CSM ................ Conceptual Site Model
DQO ................ data quality objectives
DRO ................ diesel range organics
GRO ................ gasoline range organics
HHO………….Home Heating Oil
IDW ................. investigation-derived waste
LCS/LCSD ...... laboratory control sample/ laboratory control sample duplicate mg/kg ............... milligrams per kilogram
MS/MSD ......... matrix spike/ matrix spike duplicate
PAH ................. polynuclear aromatic hydrocarbon
PID .................. photoionization detector
PPE .................. personal protective equipment
QA/QC............. quality assurance/quality control
RCRA .............. Resource Conservation and Recovery Act
RRO ................. residual range organics
SGS .................. SGS Environmental Services, Inc.
TCON…………Tikigaq Construction, LLC.
USFWS……….United States Fish and Wildlife Services
UST ................. underground storage tank
VOC ................ volatile organic compound yd3…………….cubic yards
AES of Alaska 3 3/26/2019
EXECUTIVE SUMMARY
On behalf of the U.S. Fish and Wildlife Service, Innoko Wildlife Refuge (USFWS), Tikigaq
Construction (TCON) and Agviq Environmental Services (AES) performed additional corrective action at the Wollard House in McGrath, Alaska on August 22 to August 24, 2018. This action is in response to the decommissioning of a 500-gallon underground storage tank (UST) that was found to have spilled/leaked an unknown quantity of Home Heating Oil (HHO). The removal of the tank was performed by Silver Mountain Construction with environmental support from North
Wind Site Services as a subcontractor.
Sixteen cubic yards (yd3) of HHO contaminated soils were excavated around the area of the former UST. Post excavation samples show that Diesel Range Organics (DRO) contamination remains above the Alaska Department of Environmental Conservation cleanup levels (ADEC, 2017a) at a depth below 6.5 ft to the north and east of the former excavation. A total of six samples and one duplicate were submitted to SGS Laboratories in Anchorage for analysis. Of these, three are above cleanup levels, one below, and two had non-detectable results for DRO.
Two post-excavation wall samples taken from the northern wall indicate that a clean edge to a depth of 6.5 feet was established. Excavated soils were placed in one cubic yard super sacks and transported to Alaska Soil Recycling in Anchorage for final disposal. A reinforced 10-mil polyethylene liner was placed in the excavation prior to backfilling to existing grade.
AES of Alaska 4 3/26/2019
1. INTRODUCTION
This Corrective Action Report, developed by Agviq Environmental Services (AES) and Tikigaq
Construction, LLC of Alaska for the US Fish and Wildlife Services (USFWS), details the activities performed during the removal of contaminated soils at the Wollard House in McGrath, Alaska. The tasks performed are associated with Alaska Department of Environmental
Conservation (ADEC) Contaminated Sites Database file number 2612.38.009, under Prime
Contract Number F15PC00080/F17PD01978 for the US Fish and Wildlife Services.
McGrath is a remote village along the Kuskokwim River, accessible by commercial aircraft. The
Wollard House is a property of the US Fish and Wildlife Service, located at the corner of Chinana
Ave. and E Street. In 2016, a 500-gallon non-regulated UST was decommissioned by Silver
Mountain Construction, with environmental support from North Wind Site Services.
Contaminated soils are the result of the overfilling of the tank. This effort was conducted to further remediate contaminated soils that remained from the initial tank removal.
Site Location and Description
The Site is located at 101 Chinana Avenue, McGrath, Alaska, approximately 220 miles northwest of Anchorage, Alaska (Figures 1-3) with map coordinates of 62.9514 latitude and -155.5918 longitude. McGrath is located along the south bank of the Kuskokwim River, just south of the
Kuskokwim Mountain range and approximately 60 miles from the Alaska Range in western
Alaska. According to the United States Census Bureau, the village has total of area of 54.6 square miles, of which, 48.9 miles of it is land and 5.7 square miles of it is water. The area is considered to have a continental subarctic climate (Koppen Dfc). Temperatures range from an average low of -18o Fahrenheit (oF) to an average high of 70oF over the course of a yearly cycle.
McGrath receives an average of 18 inches of precipitation annually.
The Wollard House is a log sided building on a concrete slab foundation, used as an office space and temporary living quarters for USFWS personnel. The facility is used on a part time basis, typically having one employee there for a few days per week. The UST was located along the north side of the facility. The area consists of poorly to well sorted, poorly to moderately well-stratified deposits of alluvial, colluvial, lacustrine, eolian, and swamp deposits. Groundwater is believed to be between 15 to 20 feet below ground surface.
AES of Alaska 5 3/26/2019
Site History
Previous site activities were conducted in June of 2016 by Silver Mountain Construction, LLC with North Wind Site Services to remove and decommission a 500-gallon underground storage tank, located at the north corner of the facility. A tank closure report was submitted to ADEC in
September 2016.
1.1. Project Objectives
The objectives of this field effort were to delineate the horizontal and vertical extent of contamination and protection of human health and the environment by the removal of fuel impacted media caused by the incidental release of home heating oil to a 500-gallon underground storage tank. Results for diesel range organics (DRO), gasoline range organics (GRO), residual range organics (RRO), benzene, toluene, ethylbenzene and xylenes (BTEX), and polynuclear aromatic hydrocarbons (PAH) were compared against applicable ADEC criteria set forth in 18
AAC 75 Oil and Other Hazardous Substances Pollution Control (ADEC. 2017a, Tables B1 and
B2) and presented in tabular form below in Table 1. These levels are the most stringent under
Method Two, Under 40 Inch Zone, human health exposure or the Migration to Groundwater pathways. Samples were collected according to the approved Sampling and Analysis Plan, generally following ADEC Field Sampling Guidance (ADEC 2017b).
AES of Alaska 6 3/26/2019
Table 1: Cleanup Levels
Contaminants of Concern mg/kg
Petroleum Fractions
DRO 250
GRO 300
RRO 10000
VOCs
Benzene 0.022
Toluene 6.7
Ethylbenzene 0.13
Xylenes 1.5
PAHs
1-methylnaphthalene 0.41
2-methylnaphthalene 1.3
Acenaphthene 37
Acenaphthylene 18
Anthracene 390
Benzo(a)anthracene 0.28
Benzo(a)pyrene 0.27
Benzo(b)fluoranthene 2.7
Benzo(g,h,i)perylene 2300
Benzo(k)fluoranthene 20
Chrysene 82
Dibenzo(a,h)anthracene 0.2
Fluoranthene 590
Fluorene 36
Indeno(1,2,3-cd)pyrene 2
Naphthalene 0.038
Phenanthrene 39
Pyrene 87
Notes: Based on the Alaska Department of Environmental Conservation Method Two, Under 40-Inch Zone, most stringent exposure pathway cleanup level as stated in 18 AAC 75.341.
mg/kg = milligrams per kilogram
1.2. Summary of Field Activities
Excavation commenced on August 22, 2018 after utility locations were marked out, ensuring no conflicts with the area of concern. Upon determining the location of the former excavation, work began on the western side to find the lateral and vertical extent of contamination. Excavation continued generally north, guided by Photoionization Detector (PID) readings. Contaminated soils were placed directly into super sacks and staged on site until transported to the airport for final disposal in Anchorage at Alaska Soil Recycling. A total of 16 super sacks were generated during field activities, consisting of 16 yd3 of soils. Excavation limits for this field effort reached a depth of 6.5 ft, an overall length of 14.5 ft, and 7 ft wide (see Figure 4 of Appendix A). Post
AES of Alaska 7 3/26/2019 excavation sampling was conducted, collecting a total of 25 screening samples and seven confirmation samples (six samples plus one duplicate), which were sent to SGS North America
Laboratory in Anchorage, Alaska for off-site analysis. After sampling activities were concluded, a liner was placed in the excavation and backfilled to existing grade.
In addition to soil removal activities, an initial assessment of indoor air quality was done by using a PID to measure areas of the facility that would typically be inhabited by members of the
USFWS, as well as conduct an interview with an employee that most frequents the Wollard
House.
The following data quality objectives were met:
• Collect accurate, precise and representative data
• Meeting 95% data completeness and usability goals
• Generate reproducible data
• Produce results that are comparable (use same sampling techniques, follow same procedures)
• Achieve sensitivity necessary to support action levels
• Meeting regulatory and guidance requirements
AES of Alaska 8 3/26/2019
2. FIELD WORK
On August 22, 2018 Mr. Dumitru Radu, a Qualified Environmental Professional with AES and
Mr. David Thomas of TCON mobilized to McGrath to perform site work. Mr. Tom Parker of the
City of McGrath Utility Service marked out all utilities that were within or near the work area prior to commencement of excavation activities. Upon determining the location of the former
UST, work commenced along the western edge. Soils were screened using a PID and the heated headspace method, as per ADEC Field Sampling Guidance, 2017a. Soils that screened above the
20 parts per million (ppm) action level were placed in one cubic yard super sacks for disposal.
Excavation continued in a generally north direction until PID readings indicated a clean edge had been achieved. An initial indoor air quality survey was conducted as well during this mobilization.
2.1. Soils Removal
Excavation did not start within the former excavation as this is a known area of contamination.
Instead, excavation work started along the western side of the former excavation in order to determine the horizontal extent of contamination. Historical results indicate that the southern end of the former UST excavation were below cleanup levels, contamination extended under the building to the east, therefore work proceeded generally north towards greater concentrations of contamination. Soils were field screened with a PID, analyzing every other bucket, as well as using olfactory senses. Soils that had results above the 20 ppm action level were placed directly into super sacks. Super sacks were filled close to the excavation, within the swing radius of the equipment. A 10’x12’ heavy duty tarp was used as a liner to prevent cross contamination from soils spilled during filling of the sacks. After a sack was filled, soils on the tarp were funneled back into the excavation.
After the first three sacks were filled, it was noted that approximately two less-than-level buckets and one-half bucket filled one super sack, therefore screening was adjusted to a rate equaling one screening per super sack. PID readings for the first day ranged from 76 ppm to 382 ppm for the six filled super sacks.
Excavation continued the next day, generally extending northward from the former UST area.
PID readings ranged from 44 ppm to 187 ppm, filling an additional 10 super sacks for a total of
16 sacks. Post excavation sampling was performed in accordance with the approved Sampling
Plan and the ADEC Field Sampling Guidance, 2017a. PID readings of the post excavation
AES of Alaska 9 3/26/2019 samples ranged from a low of 0 ppm to a high of 173 ppm. Table 2, in Section 4.1 below lists all excavation walls and floor PID results. A total of six confirmation samples (one for each sidewall plus two excavation floor) and one duplicate were collected for GRO, DRO, RRO, BTEX, and PAHs analysis. Samples were packaged and delivered to SGS Laboratories under appropriate chain-of-custody procedures. After sample collection, 10 mil polyethylene sheeting was placed in the excavation as a liner and backfilled.
All sixteen super sacks were transported to Northern Air Cargo at the McGrath airport for delivery to Anchorage and subsequently to Alaska Soil Recyclers (ASR) for final disposal.
Delivery tickets, ASR acceptance letter, and ADEC approval of waste disposal are in
Appendix G.
2.2. Indoor Air Quality Initial Assessment
The Wollard House is constructed of log siding on a concrete slab foundation. Chinking between log courses appears to be in good condition, providing an air tight seal along the walls. Due to the close proximity of the former UST to the building and the levels of contamination found in surface soils, an indoor air quality survey was conducted to assess the potential exposure to human health by inhalation from volatile petroleum vapors. A PID was used to measure ambient air in the northern end of the facility and the main area. The northern end of the building near the work area consists of two rooms, an empty office space currently being used for electronic devices, such as printers and routers, and a bedroom/living quarters for USFWS personnel. The building also consists of a second office area, a bathroom, utility room, and a multi-purpose main open area where there is a kitchen, dining/meeting/sitting area, and a merchandise/library area. A
USFWS employee, Mr. Ken Chase, was present during field work and interviewed as part of the air quality assessment. A detailed discussion of indoor air quality can be found in Section 4.3 of this report.
AES of Alaska 10 3/26/2019
3. FIELD METHODOLOGY
On August 22, 2018, TCON and AES mobilized to McGrath to perform site activities. Upon arrival, and after picking up the shipped supplies from Northern Air Cargo, the field crew meet with Utility Location of McGrath representatives were on site to mark out all utility that may be impacted by site activities. United Utilities Inc. of Alaska had previously indicated that they have no conflicts. A water line enters the Wollard House from the west, entering the building near the entryway on the west side of the building. A sewer line is on the south side of the building, extending to E Street. Neither of these are within the anticipated area of excavation.
3.1. Field Screening
The heated headspace field screening method with the use of a MiniRAELite PID was the primary method used during this removal, however, others include visual and olfactory senses to assist with determining if soils were contaminated. Field screening was conducted in accordance with the approved Sampling and Analysis Plan and the ADEC Field Sampling Guidance (ADEC, 2017). The PID was calibrated at the beginning of each day, prior to field activities. During excavation, screening of soils was done by taking a reading from the center of the equipment bucket. Overburden soils were determined by scraping an area with bucket, digging down at least six inches into the exposed soils and inserting the PID probe into the hole. Scraping continued in six to eight-inch cuts until PID readings indicated contaminates soils were reached. Excavation wall and floor samples were collected and screened utilizing the heated headspace method.
Screening results of greater than 20 ppm was considered contaminated and placed in super sacks.
Headspace samples were collected by filling a new sealable plastic bag one-third to one-half full of freshly uncovered soil. The bag was shaken for about 30 seconds and vapors allowed to develop for at least 10 minutes, but no longer than one hour. The bag was again agitated for about 15 seconds. The bag was partially opened to allow the PID probe to be inserted into the headspace of the bag, and re-sealed around the probe. The highest reading was recorded in the field log book.
3.2. Sample Handling
AES collected each soil sample for field screening or laboratory analysis utilizing clean stainless steel spoons and/or clean nitrile gloves. Laboratory samples were placed in clean glassware, preservative added if applicable, and placed in a cooler with gel ice to maintain sample temperatures between 00 and 60 Celsius. Sample, including one trip blank, were packaged and delivered to the laboratory under standard chain-of-custody procedures.
AES of Alaska 11 3/26/2019
4. RESULTS AND FINDINGS
As PID readings decreased from the screening of equipment bucket soils, screening of sidewalls and the floor were taken to determine if limits were reached. Sidewall samples were taken from the west, north, and east wall. The south wall consists of the former excavation, with historical screening and laboratory results showing contamination, therefore this wall was not sampled. A total of 25 screening samples were collect and screened. Results indicate that horizontal extent at a 6.5-foot depth were reached on the north and west walls. Clean soils were also screened at locations near the northeast corner. Measurements of excavation are 14.5 feet at its longest along the west side, 7 feet wide along the north wall, and 8 feet along the east wall. Excavation limits with sample locations are shown in Figure 4 of Appendix A.
4.1. Field Screening
Field Screening samples collected during soils segregation were taken from the center of the equipment bucket. Readings from soils determined to be contaminated (>20 ppm PID) ranged from a low of 44 ppm to a high of 382 ppm. Overburden was removed by scraping along the surface, taking PID readings by digging into exposed soils at least six inches, inserting the PID nozzle into the hole and covering the hole. All readings from soils considered overburden ranged from 0 to 1.5 ppm.
As readings for contaminated soils decreased, the excavation was assessed to determine if clean boundaries were achieved. A total of 25 field screening samples were collected and analyzed via the headspace method. Results from the sidewalls on the northwest and north walls indicate clean limits have been reached to a depth of 6.5 feet. Based on approximately 77 square feet of excavation floor, five floor samples were collected for field screening, with readings between 32 and 127 ppm.
PID readings from the east wall show contamination near the former excavation, with other readings toward the northeast corner indicating clean soils, with 0 ppm results from each of the four various depths (2, 4, 5.5, and 6.5 ft bgs). PID results with sample locations are shown in
Figure 4 of Appendix A.
AES of Alaska 12 3/26/2019
TABLE 2 - Field Screening PID Results
Excavated Soils Post-Excavation Sampling
Sample ID
PID
(ppm) Sample ID PID (ppm) Sample ID PID (ppm)
S1 138 PE-1-2 173 PE-5-2 0.8
S2 178 PE-1-4 155 PE-5-4 3.6
S3 254 PE-1-6.5 80 PE-5-6.5 14.8
S4 307 PE-2-2 0.0 PE-5-3 0.9
S5 382 PE-2-4 71.1 PE-5-5 10.1
S6 187 PE-2-6.5 81 PE-6-2 0.0
S7 234 PE-3-2 1.0 PE-6-4 0.0
S8 193 PE-3-4 1.4 PE-6-6.5 0.0
S9 149 PE-3-6.5 141 PEF-1 113
S10 93 PE-4-2 0.4 PEF-2 32
S11 105 PE-4-4 3.0 PEF-3 127
S12 113 PE-4-6.5 48 PEF-4 92
S13 126 PEF-5 111
S14 94 S15 58 S16 76 S17 75 S18 87 S19 44
4.2. Analytical Results
AES collected a total of seven soil samples (one from each side sidewall, two from the floor, and one duplicate) for analysis of GRO, DRO, RRO, BTEX, and PAHs at SGS Laboratories, an
ADEC approved laboratory. A summary of detectable results is found in Table 3 below, with the full laboratory report in Appendix C. In consideration of screening results, sidewall confirmation samples were collected at the 6.5 foot bgs depth to evaluate contaminant concentrations that may still be present. Of the four sidewall samples, two samples with highest PID readings were collected from the west wall, one sample from the north wall that had a PID reading of 14.8 ppm, and one from the east side wall with a PID reading of 0 ppm were submitted for analysis. The two floor samples were chosen to show concentrations remaining along the west wall and possibly clean soils in the northeast corner.
AES of Alaska 13 3/26/2019
TABLE 3 - Detectable Results
PE-2-6.5 PE-3-6.5 PE-5-6.5 PE-6-6.5 PE-6-6.5D PEF-3 PEF-5
Sample Depth (ft bgs)
6.5 6.5 6.5 6.5 6.5 6.5 6.5
Field Screening Reading (ppm) 81 141 14.8 0.0 --- 127 111
Analyte ADEC Cleanup Level (mg/Kg)
Petroleum Fractions mg/Kg mg/Kg mg/Kg mg/Kg mg/Kg mg/Kg mg/Kg
Diesel Range Organics 250 1170 1280 13.3 U 13.4 U 12.7 J 422 229
Residual Range Organics 10,000 10.8 U 43.0 30.7 42.1 42.8 32.2 28.1
Gasoline Range Organics 300 8.52 15.4 2.20 U 2.39 U 2.40 U 17.2 7.73
Volatiles (BTEX) µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg
Benzene 22 6.85 U 7.70 U 11.0 U 11.9 U 12.0 U 9.25 U 12.9 U
Ethylbenzene 130 23.0 J 21.8 J 22.0 U 23.9 U 24.0 U 15.9 J 25.8 U
P & M -Xylene 111 102 44.0 U 47.9 U 48.0 U 79.9 35.1 J o-Xylene 39.2 346 22.0 U 23.9 U 24.0 U 447 184
Xylenes (total) 1,500 150 448 66.0 U 71.5 U 72.0 U 527 219
Toluene 6,700 22.7 J 10.8 J 22.0 U 23.9 U 24.0 U 19.6 J 25.8 U
PAHs µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg µg/Kg
Chrysene 600,000 26.6 17.4 J 16.6 U 16.7 U 16.4 U 14.5 U 10.2 J
Fluoranthene 590,000 112 38.6 16.6 U 16.7 U 16.4 U 10.3 J 19.6 J
Pyrene 87,000 51.0 34.4 16.6 U 16.7 U 16.4 U 11.4 J 17.0 J
Key: BOLD indicat results exceed ADEC Method Two, Under 40-inch Zone Cleanup Levels mg/Kg= milligrams per kilogram µg/Kg= micrograms per kilogram ppm= parts per million PAH= polycyclic aromatic hydrocarbons
Flag Definition: J= quantitation is an estimate U= analyte not detected at the detection limit listed
DRO was the only analyte reported with concentrations in exceedance of ADEC cleanup criteria, based on the Method Two, Under 40 Inch Zone limit of 250 mg/kg. Analytical results were 1,170 mg/kg and 1,280 ppm for PE-2-6.5 and PE-3-6.5 respectively, both at the base of the west wall.
PEF-3, a floor sample has a result of 422 mg/kg, above ADEC cleanup criteria, while PEF-5 had a result of 229 mg/kg. All other results are either Non-Detected or well below Method Two cleanup criteria. PE-5-6.5 had a PID reading of 14.5 ppm but laboratory DRO results were below detection limits. PEF-5 had an analytical result of 229 mg/kg, below cleanup levels, but a PID reading of 111 ppm. All samples submitted for laboratory analysis had a depth of 6.5 ft bgs.
These results are indicative of soil gas within the screening samples. Therefore, these locations may be in close proximity to the DRO contaminant plume.
Although GRO concentrations range from Non-Detect to 15.4 mg/kg, all detectable results are correlated to samples with concentrations of DRO. DRO has constituents that are within the
GRO range (C6-C10), therefore, the middle distillate (DRO) is contributing to the GRO results.
This would be consistent with reports of heating oil spilled/leaked to the ground, not gasoline.
AES of Alaska 14 3/26/2019
4.3. Indoor Air Quality Assessment
Indoor air quality was assessed due the close proximity of contaminated soils to the Wollard
House. The conceptual site model completed prior to field work indicated that the inhalation of indoor air pathway is complete and further assessment is required. A PID was used to as an initial assessment of air quality, with other considerations given to building design, room locations and occupation frequency, and interviewing an employee of the USFWS that was at the
Wollard House but is not there on a fulltime basis. PID readings ranged from 0 to 0.1 ppm. The
0.1 ppm reading was located in the north unoccupied office next to the work area, but the room also had other electronics such as a printer/copier. All other results were 0 ppm.
The Wollard House is log sided structure with the chinking in good condition, on a concreate slab foundation. Upon entering the building, no noticeable petroleum odors were noted, nor was it present in any area of the building. Mr. Ken Chase of the USFWS was interviewed for further information. Mr. Chase has work for the USFWS for several years and travels to the Wollard
House as part of his rotation, with stays as long as two weeks. During his stays at the site, he has never noted any petroleum odors within the building, even during the timeframe of the UST removal.
4.4. Quality Control and Quality Assurance
The Analytical data was reviewed for quality including completeness, compliance with method procedures, correctness, and quality control field duplicate sample was collected and submitted blind to the laboratory for analysis of each analyte. Laboratory Data was reviewed utilizing the
ADEC Laboratory Data Review Checklist, found in Appendix D. Sample PE-6-6.5 was used as a duplicate. Though this sample had low results, it was chosen to confirm the low readings from field screening.
Based on the LDRC, all analytical data is considered usable for the purpose of evaluating the presence or absence of petroleum contamination. The precision, accuracy, comparability, completeness, sensitivity, and representativeness were evaluated as part of the LDRC.
4.5. Conceptual Site Model
An ADEC Conceptual site model (CSM) scoping forms have been completed and is included as
Appendix E. Though changes to site conditions occurred from the removal event and new laboratory data is available, the CSM indicates the same exposure pathways of incidental soil ingestion, dermal absorption, ingestion of groundwater, and the inhalation of outdoor and indoor air. However, indoor air quality was assessed during this field effort and does not currently
AES of Alaska 15 3/26/2019 affect inhabitants of the Wollard House. In addition, prior to commencement of work and after the excavation was backfilled, no petroleum odors were noted.
AES of Alaska 16 3/26/2019
5. CONCLUSIONS AND RECOMMENDATIONS
On August 22nd and 23rd, AES provided environmental support to TCON during the removal of contaminated soils located at the Wollard House in McGrath, Alaska. A total of 25 post excavation field screening samples and seven confirmation samples were collected during site activities. Laboratory results indicate DRO contamination extends beyond 6.5 feet bgs in the area that was excavated. PID field screening and laboratory results indicate that clean sidewalls were accomplished on the northern end of the excavation, including the northern portion of the east wall, down to a depth of 6.5 feet.
As contamination is still present at depth, AES recommends further characterization of the site to delineate the vertical extent of contamination. Considering the silty sands present in the area and the passage of time since the UST was removed, migration of contaminants may extend down to groundwater. Delineation of soils can be accomplished via soil borings that extend into the groundwater table, followed by installation of groundwater monitoring wells. Monitoring would then consist of multiple sampling events over the course of several months, requiring multiple mobilizations.
An alternative to this would be the utilization of Direct Sensing technologies such as a Membrane
Interface Probe or an Ultra Violet Optical Screening Tool. Both require the use of direct push technology. When used to their full potential, these technologies are capable of delineating both soil and groundwater contaminant plumes within one mobilization. Though these technologies are usually costlier on a first mobilization basis, historically, the cost of direct sensing versus traditional methods of characterization are found to be approximately equal.
Based on PID results and the interview with Mr. Chase, indoor air quality does not appear to be a hazard to human health at the Wollard House. AES recommends no further action along this pathway.
AES of Alaska 17 3/26/2019
6. REFERENCES
Alaska Department of Environmental Conservation (ADEC). 2017a. 18 AAC 75, Oil and Other
Hazardous Substances Pollution Control. As amended through October 27, 2018.
ADEC. 2017b. Field Sampling Guidance for Contaminated Sites and Leaking Underground
Storage Tank Sites. August 2017.
ADEC. 2017c. Site Characterization Work Plan and Reporting Guidance for Investigation of
Contaminated Sites. March 2017.
ADEC. 2017e. Underground Storage Tanks Procedures Manual. March 2017.
ADEC. 2017g. Guidance on Developing Conceptual Site Models January 2017.
ADEC. 2017h. Technical Memorandum. Data Quality Objectives, Checklists, Quality Assurance
Requirements for Laboratory Data, and Sample Handling. March 2017.
ADEC. 2016. Transitioning to the New Cleanup Levels Memorandum. October 11, 2016.
North Wind 2016 UST Removal Report. Wollard House U.S. Fish and Wildlife Service, McGrath, Alaska. September 2016.
PAGE INTENTIONALLY BLANK
APPENDIX A:
FIGURES
APPENDIX B:
PHOTOGRAPHIC LOG
Wollard House, McGrath Photographic Log US Fish & Wildlife Service
AES, LLC 1 9/7/18
Photo 1: View looking east of start of excavation activities with a cut west of former UST excavation.
Photo 2: View of liner from former UST removal.
AES, LLC 2 9/7/18
Photo 3: View looking west of excavation. Super sacks were hold open with the forks of the all-terrain forklift.
Photo 4: View looking north of the temporary staging area of the filled super sacks.
AES, LLC 3 9/7/18
Photo 5: View looking west of secured excavation after first day of activities.
Photo 6: View of excavation looking generally southwest. The liner of the former UST excavation can be seen in the upper left of photo.
AES, LLC 4 9/7/18
Photo 7: View looking generally southwest of excavation as liner was being placed prior to backfilling.
Photo 8: View looking generally north at the backfilled excavation before final grading.
Rainy conditions delayed final grading.
APPENDIX C:
SGS LABORATORY REPORT
Report Number: 1184766
Client Project: USFWS McGrath Job 5010
Laboratory Report of Analysis
Dear Dumitru Radu, Enclosed are the results of the analytical services performed under the referenced project for the received samples and associated QC as applicable. The samples are certified to meet the requirements of the National
Environmental Laboratory Accreditation Conference Standards. Copies of this report and supporting data will be retained in our files for a period of ten years in the event they are required for future reference. All results are intended to be used in their entirety and SGS is not responsible for use of less than the complete report. Any samples submitted to our laboratory will be retained for a maximum of fourteen (14) days from the date of this report unless other archiving requirements were included in the quote.
If there are any questions about the report or services performed during this project, please call Chuck at (907)
562-2343. We will be happy to answer any questions or concerns which you may have.
Thank you for using SGS North America Inc. for your analytical services. We look forward to working with you again on any additional analytical needs.
Sincerely, SGS North America Inc.
Chuck Homestead Date
Project Manager Charles.Homestead@sgs.com
To: AGVIQ Environmental Services (AES)
701 S. Knik Goodse Bay Rd., B
Wasilla, AK 99654
(907)980-9936
Print Date: 08/30/2018 4:19:02PM
Member of SGS Group
SGS North America Inc. 200 West Potter Drive, Anchorage, AK 99518 t 907.562.2343 f 907.561.5301 www.us.sgs.com
Results via Engage
Case Narrative
SGS Client: AGVIQ Environmental Services (AES)
SGS Project: 1184766
Project Name/Site: USFWS McGrath Job 5010
Project Contact: Dumitru Radu
Refer to sample receipt form for information on sample condition.
*QC comments may be associated with the field samples found in this report. When applicable, comments will be applied to associated field samples.
Print Date: 08/30/2018 4:19:03PM
Member of SGS Group
SGS North America Inc.
200 West Potter Drive, Anchorage, AK 99518
Laboratory ID Client Sample ID Analytical Batch Analyte Reason
Report of Manual Integrations
8270D SIM (PAH)
PE-3-6.5 XMS11026 Phenanthrene BLC1184766002
PEF-5 XMS11026 Phenanthrene BLC1184766007
Manual Integration Reason Code Descriptions
Code Description
O Original Chromatogram
M Modified Chromatogram
SS Skimmed surrogate
BLG Closed baseline gap
RP Reassign peak name
PIR Pattern integration required
IT Included tail
SP Split peak
RSP Removed split peak
FPS Forced peak start/stop
BLC Baseline correction
PNF Peak not found by software
All DRO/RRO analysis are integrated per SOP.
Print Date: 08/30/2018 4:19:04PM
Member of SGS Group
SGS North America Inc.
Laboratory Qualifiers
Enclosed are the analytical results associated with the above work order. All results are intended to be used in their entirety and SGS is not responsible for use of less than the complete report. This document is issued by the Company under its General Conditions of Service accessible at <http://www.sgs.com/en/Terms-and-Conditions.aspx>.
Attention is drawn to the limitation of liability, indenmification and jurisdiction issues defined therein.
Any holder of this document is advised that information contained hereon reflects the Company's findings at the time of its intervention only and within the limits of Client's instructions, if any. The Company's sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the context or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law.
SGS maintains a formal Quality Assurance/Quality Control (QA/QC) program. A copy of our Quality Assurance Plan
(QAP), which outlines this program, is available at your request. The laboratory certification numbers are AK00971
(DW Chemistry & Microbiology) & 17-021 (CS) for ADEC and 2944.01 for DOD ELAP/ISO17025 (RCRA methods:
1020B, 1311, 3010A, 3050B, 3520C, 3550C, 5030B, 5035A, 6020A, 7470A, 7471B, 8015C, 8021B, 8082A, 8260C, 8270D, 8270D-SIM, 9040C, 9045D, 9056A, 9060A, AK101 and AK102/103). Except as specifically noted, all statements and data in this report are in conformance to the provisions set forth by the SGS QAP and, when applicable, other regulatory authorities.
The following descriptors or qualifiers may be found in your report:
* The analyte has exceeded allowable regulatory or control limits.
! Surrogate out of control limits.
B Indicates the analyte is found in a blank associated with the sample.
CCV/CVA/CVB Continuing Calibration Verification
CCCV/CVC/CVCA/CVCB Closing Continuing Calibration Verification
CL Control Limit
DF Analytical Dilution Factor
DL Detection Limit (i.e., maximum method detection limit)
E The analyte result is above the calibrated range.
GT Greater Than
IB Instrument Blank
ICV Initial Calibration Verification
J The quantitation is an estimation.
LCS(D) Laboratory Control Spike (Duplicate)
LLQC/LLIQC Low Level Quantitation Check
LOD Limit of Detection (i.e., 1/2 of the LOQ)
LOQ Limit of Quantitation (i.e., reporting or practical quantitation limit)
LT Less Than
MB Method Blank
MS(D) Matrix Spike (Duplicate)
ND Indicates the analyte is not detected.
RPD Relative Percent Difference
U Indicates the analyte was analyzed for but not detected.
Note: Sample summaries which include a result for "Total Solids" have already been adjusted for moisture content.
All DRO/RRO analyses are integrated per SOP.
Print Date: 08/30/2018 4:19:05PM
Member of SGS Group
SGS North America Inc. 200 West Potter Drive, Anchorage, AK 99518 t 907.562.2343 f 907.561.5301 www.us.sgs.com http://www.sgs.com/terms_and_conditions.htm http://www.sgs.com/terms_and_conditions.htm
Sample Summary
Client Sample ID Lab Sample ID Collected Received Matrix
PE-2-6.5 1184766001 08/23/2018 08/27/2018 Soil/Solid (dry weight)
PE-3-6.5 1184766002 08/23/2018 08/27/2018 Soil/Solid (dry weight)
PE-5-6.5 1184766003 08/23/2018 08/27/2018 Soil/Solid (dry weight)
PE-6-6.5 1184766004 08/23/2018 08/27/2018 Soil/Solid (dry weight)
PE-6-6.5D 1184766005 08/23/2018 08/27/2018 Soil/Solid (dry weight)
PEF-3 1184766006 08/23/2018 08/27/2018 Soil/Solid (dry weight)
PEF-5 1184766007 08/23/2018 08/27/2018 Soil/Solid (dry weight)
TRIP BLANK 1184766008 08/23/2018 08/27/2018 Soil/Solid (dry weight)
Method DescriptionMethod
8270 PAH SIM Semi-Volatiles GC/MS8270D SIM (PAH)
AK101/8021 Combo. (S)AK101
AK101/8021 Combo. (S)SW8021B
Diesel/Residual Range OrganicsAK102
Diesel/Residual Range OrganicsAK103
Percent Solids SM2540GSM21 2540G
Print Date: 08/30/2018 4:19:05PM
Member of SGS Group
SGS North America Inc.
Detectable Results Summary
Client Sample ID: PE-2-6.5
Lab Sample ID: 1184766001 UnitsParameter Result
Benzo[b]Fluoranthene ug/Kg19.3JPolynuclear Aromatics GC/MS
Chrysene ug/Kg26.6
Fluoranthene ug/Kg112
Phenanthrene ug/Kg20.0J
Pyrene ug/Kg51.0
Diesel Range Organics mg/Kg1170Semivolatile Organic Fuels
Ethylbenzene ug/Kg23.0JVolatile Fuels
Gasoline Range Organics mg/Kg8.52 o-Xylene ug/Kg39.2
P & M -Xylene ug/Kg111
Toluene ug/Kg22.7J
Xylenes (total) ug/Kg150
Client Sample ID: PE-3-6.5
Lab Sample ID: 1184766002 UnitsParameter Result
Benzo[b]Fluoranthene ug/Kg19.3JPolynuclear Aromatics GC/MS
Benzo[g,h,i]perylene ug/Kg9.99J
Chrysene ug/Kg17.4J
Fluoranthene ug/Kg38.6
Indeno[1,2,3-c,d] pyrene ug/Kg9.77J
Phenanthrene ug/Kg16.8J
Pyrene ug/Kg34.4
Diesel Range Organics mg/Kg1280Semivolatile Organic Fuels
Residual Range Organics mg/Kg43.0
Ethylbenzene ug/Kg21.8JVolatile Fuels
Gasoline Range Organics mg/Kg15.4 o-Xylene ug/Kg346
P & M -Xylene ug/Kg102
Toluene ug/Kg10.8J
Xylenes (total) ug/Kg448
Client Sample ID: PE-5-6.5
Lab Sample ID: 1184766003 UnitsParameter Result
Residual Range Organics mg/Kg30.7Semivolatile Organic Fuels
Client Sample ID: PE-6-6.5
Lab Sample ID: 1184766004 UnitsParameter Result
Residual Range Organics mg/Kg42.1Semivolatile Organic Fuels
Client Sample ID: PE-6-6.5D
Lab Sample ID: 1184766005 UnitsParameter Result
Diesel Range Organics mg/Kg12.7JSemivolatile Organic Fuels
Residual Range Organics mg/Kg42.8
Print Date: 08/30/2018 4:19:06PM
Member of SGS Group
SGS North America Inc.
Detectable Results Summary
Client Sample ID: PEF-3
Lab Sample ID: 1184766006 UnitsParameter Result
Fluoranthene ug/Kg10.3JPolynuclear Aromatics GC/MS
Pyrene ug/Kg11.4J
Diesel Range Organics mg/Kg422Semivolatile Organic Fuels
Residual Range Organics mg/Kg32.2
Ethylbenzene ug/Kg15.9JVolatile Fuels
Gasoline Range Organics mg/Kg17.2 o-Xylene ug/Kg447
P & M -Xylene ug/Kg79.9
Toluene ug/Kg19.6J
Xylenes (total) ug/Kg527
Client Sample ID: PEF-5
Lab Sample ID: 1184766007 UnitsParameter Result
Benzo[b]Fluoranthene ug/Kg12.3JPolynuclear Aromatics GC/MS
Chrysene ug/Kg10.2J
Fluoranthene ug/Kg19.6J
Phenanthrene ug/Kg9.28J
Pyrene ug/Kg17.0J
Diesel Range Organics mg/Kg229Semivolatile Organic Fuels
Residual Range Organics mg/Kg28.1
Gasoline Range Organics mg/Kg7.73Volatile Fuels o-Xylene ug/Kg184
P & M -Xylene ug/Kg35.1J
Xylenes (total) ug/Kg219
Print Date: 08/30/2018 4:19:06PM
Member of SGS Group
SGS North America Inc.
Client Project ID: USFWS McGrath Job 5010
Lab Sample ID: 1184766001
Lab Project ID: 1184766
Collection Date: 08/23/18 11:50
Received Date: 08/27/18 08:08
Matrix: Soil/Solid (dry weight)
Solids (%):92.1
Results by Polynuclear Aromatics GC/MS
Results of PE-2-6.5
Location:
Date AnalyzedParameter DFUnitsResult LOQ/CL DL Allowable
LimitsQual
1-Methylnaphthalene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
2-Methylnaphthalene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Acenaphthene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Acenaphthylene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Anthracene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Benzo(a)Anthracene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Benzo[a]pyrene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Benzo[b]Fluoranthene 19.3 ug/Kg 126.6 6.65 08/28/18 15:27J
Benzo[g,h,i]perylene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Benzo[k]fluoranthene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Chrysene 26.6 ug/Kg 126.6 6.65 08/28/18 15:27
Dibenzo[a,h]anthracene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Fluoranthene 112 ug/Kg 126.6 6.65 08/28/18 15:27
Fluorene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Indeno[1,2,3-c,d] pyrene 13.3 ug/Kg 126.6 6.65 08/28/18 15:27U
Naphthalene 10.7 ug/Kg 121.3 5.32 08/28/18 15:27U
Phenanthrene 20.0 ug/Kg 126.6 6.65 08/28/18 15:27J
Pyrene 51.0 ug/Kg 126.6 6.65 08/28/18 15:27
Surrogates
2-Methylnaphthalene-d10 (surr) 83.1 % 158-103 08/28/18 15:27
Fluoranthene-d10 (surr) 75.2 % 154-113 08/28/18 15:27
Batch Information
Prep Batch: XXX40314
Prep Method: SW3550C
Prep Date/Time: 08/28/18 08:51
Prep Initial Wt./Vol.: 22.966 g
Prep Extract Vol: 5 mL
Analytical Batch: XMS11026
Analytical Method: 8270D SIM (PAH)
Analyst: BMZ
Analytical Date/Time: 08/28/18 15:27
Container ID: 1184766001-A
Print Date: 08/30/2018 4:19:07PM
Member of SGS Group
SGS North America Inc.
200 West Potter Drive Anchorage, AK 95518
J flagging is activated
Lab Sample ID: 1184766001
Lab Project ID: 1184766
Collection Date: 08/23/18 11:50
Received Date: 08/27/18 08:08
Matrix: Soil/Solid (dry weight)
Solids (%):92.1
Results by Semivolatile Organic Fuels
Results of PE-2-6.5
Location:
Date AnalyzedParameter DFUnitsResult LOQ/CL DL Allowable
LimitsQual
Diesel Range Organics 1170 mg/Kg 121.5 6.66 08/28/18 13:03
Surrogates
5a Androstane (surr) 95.5 % 150-150 08/28/18 13:03
Batch Information
Prep Batch: XXX40311
Prep Method: SW3550C
Prep Date/Time: 08/28/18 07:18
Prep Initial Wt./Vol.: 30.344 g
Prep Extract Vol: 5 mL
Analytical Batch: XFC14546
Analytical Method: AK102
Analyst: VDL
Analytical Date/Time: 08/28/18 13:03
Container ID: 1184766001-A
Date AnalyzedParameter DFUnitsResult LOQ/CL DL Allowable
LimitsQual
Residual Range Organics 10.8 mg/Kg 121.5 6.66 08/28/18 13:03U
Surrogates n-Triacontane-d62 (surr) 84.8 % 150-150 08/28/18 13:03
Batch Information
Prep Batch: XXX40311
Prep Method: SW3550C
Prep Date/Time: 08/28/18 07:18
Prep Initial Wt./Vol.: 30.344 g
Prep Extract Vol: 5 mL
Analytical Batch: XFC14546
Analytical Method: AK103
Analyst: VDL
Analytical Date/Time: 08/28/18 13:03
Container ID: 1184766001-A
Print Date: 08/30/2018 4:19:07PM
Member of SGS Group
SGS North America Inc.
200 West Potter Drive Anchorage, AK 95518
Lab Sample ID: 1184766001
Lab Project ID: 1184766
Collection Date: 08/23/18 11:50
Received Date: 08/27/18 08:08
Matrix: Soil/Solid (dry weight)
Solids (%):92.1
Results by Volatile Fuels
Results of PE-2-6.5
Location:
Date AnalyzedParameter DFUnitsResult LOQ/CL DL Allowable
LimitsQual
Gasoline Range Organics 8.52 mg/Kg 12.74 0.822 08/28/18 15:49
Surrogates
4-Bromofluorobenzene (surr) 97.5 % 150-150 08/28/18 15:49
Batch Information
Prep Batch: VXX33001
Prep Method: SW5035A
Prep Date/Time: 08/23/18 11:50
Prep Initial Wt./Vol.: 58.779 g
Prep Extract Vol: 29.6597 mL
Analytical Batch: VFC14382
Analytical Method: AK101
Analyst: ST
Analytical Date/Time: 08/28/18 15:49
Container ID: 1184766001-B
Date AnalyzedParameter DFUnitsResult LOQ/CL DL Allowable
LimitsQual
Benzene 6.85 ug/Kg 113.7 4.38 08/28/18 15:49U
Ethylbenzene 23.0 ug/Kg 127.4 8.55 08/28/18 15:49J o-Xylene 39.2 ug/Kg 127.4 8.55 08/28/18 15:49
P & M -Xylene 111 ug/Kg 154.8 16.4 08/28/18 15:49
Toluene 22.7 ug/Kg 127.4 8.55 08/28/18 15:49J
Xylenes (total) 150 ug/Kg 182.2 25.0 08/28/18 15:49
Surrogates
1,4-Difluorobenzene (surr) 98.1 % 172-119 08/28/18 15:49
Batch Information
Prep Batch: VXX33001
Prep Method: SW5035A
Prep Date/Time: 08/23/18 11:50
Prep Initial Wt./Vol.: 58.779 g
Prep Extract Vol: 29.6597 mL
Analytical Batch: VFC14382
Analytical Method: SW8021B
Analyst: ST
Analytical Date/Time: 08/28/18 15:49
Container ID: 1184766001-B
Print Date: 08/30/2018 4:19:07PM
Member of SGS Group
SGS North America Inc.
200 West Potter Drive Anchorage, AK 95518
Client Sample ID: PE-3-6.5
Lab Sample ID: 1184766002
Lab Project ID: 1184766
Collection Date: 08/23/18 11:56
Received Date: 08/27/18 08:08
Matrix: Soil/Solid (dry weight)
Solids (%):85.2
Results by Polynuclear Aromatics GC/MS
Results of PE-3-6.5
Location:
Date AnalyzedParameter DFUnitsResult LOQ/CL DL Allowable
LimitsQual
1-Methylnaphthalene 14.4 ug/Kg 128.9 7.22 08/28/18 15:47U
2-Methylnaphthalene 14.4 ug/Kg 128.9 7.22 08/28/18 15:47U
Acenaphthene 14.4 ug/Kg 128.9 7.22 08/28/18 15:47U
Acenaphthylene…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .