Scope of Work
Williams Creek National Fish Hatchery Apache County, Arizona
2021 Butler Building Rehabilitation
United States Fish and Wildlife Service Infrastructure Management Division 500 Gold Ave. S.W.
Albuquerque, New Mexico 87103
Approvals
Refuge/Hatchery Manager/Project Leader
Refuge/Hatchery Program Supervisor
Chief, Division of Infrastructure Mgmt.
Project Manager
Environmental Compliance
Cultural Resources
Energy Compliance
Emergency Manager
SPECIFICATIONS
TABLE OF CONTENTS
SECTION
010090
GENERAL INFORMATION AND REQUIREMENTS
081113 HOLLOW METAL DOORS AND FRAMES
087100 DOOR HARDWARE
099113 EXTERIOR PAINTING
08323 OVERHEAD COILING DOORS
00000 PHOTOGRAPHS
SECTION 01009 - GENERAL INFORMATION AND REQUIREMENTS
PART 1: GENERAL
1.1 SUMMARY:
A. Description of Work: The work shall consist of labor, equipment, supplies and materials to:
1. Remove rust, prime and paint the 2,072 S.F. (exterior) metal building with 14’ eave height. The color of paint will be selected by the hatchery manager. The existing topcoat paint is chalky and rubs off easily. Replace the skylight fasteners with stainless fasteners. The swab test for lead-based paint was inconclusive. See Appendix for photos of the building.
2. Replace five (5) coiling roll-up doors and one (1) personnel door.
Roll-Up doors: One—13’ wide x 13’ high and four—12’ wide x 11’ high. The existing doors are manually operated. The replacement doors will be motor-operated. Therefore, electrical wiring and circuit breakers must be installed from the existing load panel inside the building. Contractor shall submit a new power supply design for the overhead doors to the Contracting Officer’s Technical Representative (COTR) for approval. All electrical work will be performed by an electrician licensed in Arizona to meet the latest National Electrical Code.
The paint on the existing doors contain lead. The swab test for lead-based paint was positive. Therefore, the OSHA protocols will be followed for the removal of the doors. All federal and state regulations will be followed for the disposal of the doors.
The loose or peeling paint on the overhead door frames contain lead.
Completely remove the paint and dispose of the waste following all federal and state regulations.
Personnel door: The existing door rides the jamb. Replace the door, frame, threshold, and hardware including the lockset. The hardware and lockset will be commercial grade, BHMA Grade 1. Frame shall be hollow metal. The door will be insulated hollow metal and have no glazing. The lockset will be keyed to match the master key for the hatchery. Install one green LED exit sign, and permanent wiring, over the personnel door. It shall be equal to or better than “Lithonia” model
LQM EL N.
Colors of the overhead doors and personnel door must match the color of the building.
3. Install 10 – 6 inch pipe bollards, two for each overhead door, as shown below.
Prime and paint the bollards Safety Yellow, HEX #EED202.
4. Replace the damaged overhead door frame/trim and wall panel as shown in the photos to match the existing door frame/trim and wall panel. (Two locations)
B. Location: Work under this contract is located at the Williams Creek National Fish Hatchery in Apache County, Arizona.
C. The hatchery is located on the Fort Apache Indian Reservation. Therefore, Tribal Employment Rights Ordinance (TERO) will be applicable. Contractor shall coordinate with the TERO Office on labor and other tribal regulations.
D. Site Visit: Contractors are encouraged to visit the project site and inspect existing conditions prior to submitting quotes. See Federal Acquisition Regulation (FAR) clause 52.236-27 Site Visit. Contact Bradley Clarkson, Unit Leader, at 928-334-2346 or bradley_clarkson@fws.gov, to arrange a site visit.
1.2 REFERENCES:
Referenced Standards are listed in the applicable specification section.
1.3 DEFINITIONS:
Approvals: Approval of submittals is an indication that the Contractor's submittals have been reviewed and that there are no objections, except as noted. Approval of deviations shall apply only to those deviations or omissions from the requirements of the drawings and specifications brought to the COTR’s attention in writing.
1.4 SUBMITTALS:
A. Scope: Submittals include shop drawings, manufacturers' literature, as-built drawings, samples, work schedules and a schedule of values.
B. Requirements: Refer to specification sections for submittals required. Allow at least 7 working days for review. Submittals shall be sent to the COTR by e-mail at .
Submittals shall come directly from the Contractor with their stamp and signature of approval; submittals will not be accepted from sub-contractors or suppliers. Do not commence work which requires review of any submittals until receipt of returned submittals with an acceptable action. Do not allow submittals without an acceptable action marking to be used for the project.
C. Identification of Submittals: Completely identify each submittal by showing at least the following information:
1. Name and address of submitter (Contractor), plus name and telephone number of the individual to contact for further information.
2. Name of project as it appears in these specifications.
3. Contract number, submittal number, and specification section number to which the submittal applies.
4. Whether this is an original submittal or resubmittal.
5. Each item shall clearly note the manufacturer's name and address, trade name, product, lot, style, color, catalog designation or model number, and locations of use.
D. There will be no approval of submittals prior to bid opening and award. Submittals will be evaluated based on the requirements of the specifications and drawings, during the submittal process after contract award.
1.5 CONFORMANCE:
Submittals must show clearly that the product, sample or shop drawing conforms to the specifications.
1.6 QUALITY ASSURANCE:
A. Codes and Standards: The work shall comply with codes and standards applicable to each type of work and as listed in the individual sections of these specifications. This contract incorporates materials, applications, and tests by reference, with the same force and effect as if they were given in full text.
B. Conflict: Where a conflict occurs between reference documents, drawings, and project specifications, the most stringent requirement shall govern.
C. Product basis: Where specifications or drawings call out a specific product or manufacturer, it is understood that an equal or better product is acceptable, as approved in the submittal process.
1.7 DELIVERY, STORAGE, AND HANDLING:
A. Delivery: Protect products incorporated into the work from damage while in transit to the site. Products must be delivered in original unopened containers with manufacturer's name, brand designation, and contents legibly indicated. The containers shall bear the referenced specification number, type, and class as applicable.
B. Storage: Limited storage area is available at the project site. If additional storage area is needed, contractor shall provide temporary storage facilities for products. Storage shall comply with the manufacturer's instructions. The storage area shall permit access for inspection and handling.
C. Handling: Load and unload products protecting them from damage.
1.8 PROJECT/SITE CONDITIONS:
A. All damage caused by Contractor's activities shall be repaired by the Contractor at no additional cost to the Government.
B. Safety is paramount. Contractor is responsible for safety on the project site and shall take measures to maintain a safe area around the project site which is used by Government employees and the public. Applicable OSHA regulations shall be adhered to by the Contractor. Contractor shall submit a safety plan prior to starting work.
C. Landscape Protection: Protect all vegetation inside and outside work limits. All rutting caused by Contractor activities shall be filled and contoured to match adjacent areas.
Areas damaged by Contractor activities shall be repaired.
D. Unforeseen Conditions: Should unforeseen conditions be encountered that affect design or function of the project, investigate fully and submit an accurate, detailed, written report to the Contracting Officer and COTR. Follow procedures in contract FAR clauses 52.236-2, 52.236-3, and 52.243-5. While awaiting the Contracting Officer’s response, reschedule operations if necessary to avoid delay of overall project.
1.9 SEQUENCING AND SCHEDULING:
A bar chart type work schedule shall be submitted to the COTR within 5 days after the preconstruction conference. When requested, submit an updated schedule within 3 calendar days.
PART 2: TEMPORARY FACILITY
A. Contractor shall provide a portable toilet facility at the construction site.
B. Water is not available at the immediate site for the Contractor’s use. Contractor will be responsible for water used on-site for construction. Contact Hatchery Manager for other water sources at the Hatchery.
C. Electric power is available at the site for Contractor's use. Contractor will be allowed to use reasonable amount of electric power.
PART 3: EXECUTION
3.1 PROJECT MEETINGS:
A. Preconstruction Conference:
1. A preconstruction conference will be held prior to the start of work. The Contractor will be notified in advance of meeting time, date and place. The purpose of the meeting will be to review required work, project drawings and specifications, construction schedules, payroll, payments, and administrative provisions of the contract.
2. The Contractor, subcontractors and the persons responsible for coordination of the work shall be present at the meeting.
3. The Contractor shall submit a schedule of values within 5 days after the preconstruction conference, which may be used as a basis of payment as the work progresses.
B. Progress Meetings:
To be held at the project site as required.
C. Inspections:
1. Routine inspections will be performed by the government Construction Inspector
(CI). Inspection of work by the CI will not relieve the Contractor of the requirement to meet project specifications. The CI shall be informed 24 hours in advance of work requiring his observation. After being informed in advance the CI's non-attendance shall not prohibit the Contractor from proceeding with work in the CI's absence.
2. For final inspection, notify the COTR in writing at least 6 working days before the completion date so the Government can schedule final inspection. The superintendent shall be present during the final inspection.
3.2 DISPOSAL OF DEBRIS:
Demolition debris shall be removed from the project site and disposed of in a legal disposal site by the Contractor. Contractor shall pay all fees required for disposal.
3.3 WARRANTY:
A. All project construction shall be provided with a one-year warranty in accordance with
FAR 52.246-21.
B. With respect to warranties, expressed or implied, from manufacturers or suppliers for materials or equipment furnished under the contract, the Contractor shall:
1. Obtain the most favorable warranties that would be given by the Contractor in normal commercial practices, but in no case less than called for by the specifications.
2. Require warranties to be executed, in writing, for the benefit of the Government.
3. Submit warranties to the COTR prior to the final inspection.
END OF SECTION
SECTION 081113 - HOLLOW METAL DOORS AND FRAMES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes:
1. Exterior standard steel doors and frames.
1.3 SUBMITTALS
A. Product Data: For each type of product.
B. Sustainable Design Submittals:
C. Shop Drawings: Include the following:
1. Elevations of each door type.
2. Details of doors, including vertical- and horizontal-edge details and metal thicknesses.
3. Frame details for each frame type, including dimensioned profiles and metal thicknesses.
D. Product Schedule: For hollow-metal doors and frames, prepared by or under the supervision of supplier, using same reference numbers for details and openings as those on Drawings.
Coordinate with final door hardware schedule.
1.4 INFORMATIONAL SUBMITTALS
A. Product test reports.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Basis-of-Design Product: Subject to compliance with requirements, provide Steelcraft; an Allegion brand ; Steelcraft Hollow Metal Doors and Frames. or similar.
2.2 PERFORMANCE REQUIREMENTS
A. Thermally Rated Door Assemblies: Provide door assemblies with U-factor of not more than
0.38 deg Btu/F x h x sq. ft. when tested according to ASTM C 518.
2.3 EXTERIOR STANDARD STEEL DOORS AND FRAMES
A. Construct hollow-metal doors and frames to comply with standards indicated for materials, fabrication, hardware locations, hardware reinforcement, tolerances, and clearances, and as specified.
B. Heavy-Duty Doors and Frames: SDI A250.8, Level 2; SDI A250.4, Level B. At locations indicated in the Door and Frame Schedule.
1. Doors:
a. Type: HM1-Exterior
b. Thickness: 1-3/4 inches.
c. Face: Metallic-coated steel sheet, minimum thickness of 0.042 inch, with minimum A40coating.
d. Edge Construction: Model 1, Full Flush.
e. Edge Bevel: Provide manufacturer's standard beveled or square edges.
f. Top Edge Closures: Close top edges of doors with flush closures of same material as face sheets. Seal joints against water penetration.
g. Bottom Edges: Close bottom edges of doors where required for attachment of weather stripping with end closures or channels of same material as face sheets.
Provide weep-hole openings in bottoms of exterior doors to permit moisture to escape.
h. Core: Manufacturer's standard.
2. Frames:
a. Materials: Metallic-coated steel sheet, minimum thickness of 0.053 inch, with minimum A40coating.
b. Construction: Face welded.
2.4 FRAME ANCHORS
A. Jamb Anchors:
1. Type: Anchors of minimum size and type required by applicable door and frame standard, and suitable for performance level indicated.
2. Quantity: Minimum of three anchors per jamb, with one additional anchor for frames with no floor anchor. Provide one additional anchor for each 24 inches of frame height above 7 feet.
3. Post installed Expansion Anchor: Minimum 3/8-inch-diameter bolts with expansion shields or inserts, with manufacturer's standard pipe spacer.
B. Floor Anchors: Provide floor anchors for each jamb and mullion that extends to floor.
C. Material: ASTM A 879/A 879M, Commercial Steel (CS), 04Z coating designation; mill phosphatized.
1. For anchors built into exterior walls, steel sheet complying with ASTM A 1008/A 1008M or ASTM A 1011/A 1011M; hot-dip galvanized according to ASTM A 153/A 153M, Class B.
2.5 MATERIALS
A. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B; suitable for exposed applications.
B. Hot-Rolled Steel Sheet: ASTM A 1011/A 1011M, Commercial Steel (CS), Type B; free of scale, pitting, or surface defects; pickled and oiled.
C. Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS), Type B.
D. Inserts, Bolts, and Fasteners: Hot-dip galvanized according to ASTM A 153/A 153M.
E. Power-Actuated Fasteners in Concrete: Fastener system of type suitable for application indicated, fabricated from corrosion-resistant materials, with clips or other accessory devices for attaching hollow-metal frames of type indicated.
F. Mineral-Fiber Insulation: ASTM C 665, Type I (blankets without membrane facing); consisting of fibers manufactured from slag or rock wool; with maximum flame-spread and smoke-developed indexes of 25 and 50, respectively; passing ASTM E 136 for combustion characteristics.
G. Glazing: Comply with requirements in Section 088000 "Glazing."
2.6 FABRICATION
A. Hollow-Metal Frames: Fabricate in one piece except where handling and shipping limitations require multiple sections. Where frames are fabricated in sections, provide alignment plates or angles at each joint, fabricated of metal of same or greater thickness as frames.
1. Provide countersunk, flat- or oval-head exposed screws and bolts for exposed fasteners unless otherwise indicated.
2. Door Silencers: Not required in doors equipped with weatherstrip.
B. Hardware Preparation: Factory prepare hollow-metal doors and frames to receive templated mortised hardware, and electrical wiring; include cutouts, reinforcement, mortising, drilling, and tapping according to SDI A250.6, the Door Hardware Schedule, and templates.
1. Reinforce doors and frames to receive nontemplated, mortised, and surface-mounted door hardware.
2. Comply with BHMA A156.115 for preparing hollow-metal doors and frames for
2.7 STEEL FINISHES
A. Prime Finish: Clean, pretreat, and apply manufacturer's standard primer.
1. Shop Primer: Manufacturer's standard, fast-curing, lead- and chromate-free primer complying with SDI A250.10; recommended by primer manufacturer for substrate;
compatible with substrate and field-applied coatings despite prolonged exposure.
PART 3 - EXECUTION
3.1 PREPARATION
A. Remove welded-in shipping spreaders installed at factory. Restore exposed finish by grinding, filling, and dressing, as required to make repaired area smooth, flush, and invisible on exposed faces. Touch up factory-applied finishes where spreaders are removed.
B. Drill and tap doors and frames to receive nontemplated, mortised, and surface-mounted door
3.2 INSTALLATION
A. Hollow-Metal Frames: Comply with SDI A250.11.
1. Set frames accurately in position; plumbed, aligned, and braced securely until permanent anchors are set. After wall construction is complete, remove temporary braces without damage to completed Work.
a. Where frames are fabricated in sections, field splice at approved locations by welding face joint continuously; grind, fill, dress, and make splice smooth, flush, and invisible on exposed faces. Touch-up finishes.
b. Install frames with removable stops located on secure side of opening.
2. Floor Anchors: Secure with postinstalled expansion anchors.
a. Floor anchors may be set with power-actuated fasteners instead of postinstalled expansion anchors if so indicated and approved on Shop Drawings.
3. Solidly pack mineral-fiber insulation inside frames.
4. Installation Tolerances: Adjust hollow-metal frames to the following tolerances:
a. Squareness: Plus or minus 1/16 inch, measured at door rabbet on a line 90 degrees from jamb perpendicular to frame head.
b. Alignment: Plus or minus 1/16 inch, measured at jambs on a horizontal line parallel to plane of wall.
c. Twist: Plus or minus 1/16 inch, measured at opposite face corners of jambs on parallel lines, and perpendicular to plane of wall.
d. Plumbness: Plus or minus 1/16 inch, measured at jambs at floor.
B. Hollow-Metal Doors: Fit and adjust hollow-metal doors accurately in frames, within clearances specified below.
1. Non-Fire-Rated Steel Doors: Comply with SDI A250.8.
3.3 CLEANING AND TOUCHUP
A. Prime-Coat Touchup: Immediately after erection, sand smooth rusted or damaged areas of prime coat and apply touchup of compatible air-drying, rust-inhibitive primer.
B. Metallic-Coated Surface Touchup: Clean abraded areas and repair with galvanizing repair paint according to manufacturer's written instructions.
C. Touchup Painting: Cleaning and touchup painting of abraded areas of paint are specified in painting Sections.
END OF SECTION 081113
SECTION 08710 - DOOR HARDWARE
PART 1: GENERAL
1.1 SUMMARY
Provide labor, materials, equipment, and accessories as specified or reasonably implied for door finish hardware.
1.2 SUBMITTALS
A. Submit for approval a complete schedule of hardware. Identify each item by manufacturer's number, description, finish, and function.
B. Provide manufacturer's descriptive data.
1.3 QUALIFICATIONS
A. Hardware shall be furnished through one central supplier under direct supervision of a qualified contract hardware consultant.
B. Hardware shall comply with the standards of ANSI/BHMA A156 series.
1.4 KEYING
Locksets shall be keyed and master keyed to the existing grand master key system.
PART 2: PRODUCTS
2.1 MATERIALS
A. Furnish each item complete with screws, bolts, clips and other accessory parts, which are essential to the proper installation or operation of the item, finish matching adjacent metal parts of hardware.
B. Hardware shall conform to the Door Hardware Schedule at the end of this section and to the ANSI/BHMA A156 Grade 1 standards and ADA, and shall be Yale brand locks.
PART 3: EXECUTION
3.1 INSTALLATION
A. According to "Builder's Hardware Data Sheets" as published by Door and Hardware Institute, install accurately to template. Demonstrate hardware to be functioning properly and to be rigidly and permanently secured to supporting materials. Where more than minor adjustments are required or where improperly installed, correct or replace hardware as directed.
B. Weather Stripping: Weather strip at head, threshold, strike jamb rebate and on hinge jamb on surface containing butt leaf to be installed to form a continuous seal.
DOOR HARDWARE SCHEDULE
All finishes shall be Stainless Steel and as noted.
HARDWARE SET 1.0:
3 EA BUTTS A8111X(NRP)
1 STOPS/HOLDERS L01341
1 DOOR BOTTOM SWEEP PEMKO 315AR
1 DOOR SHOE PEMKO 211APK
WEATHER STRIP/
PERIMETER GASKETING PEMKO 303AS (Head & Jambs) THRESHOLD PEMKO 1715A (1/2" rise), ADA CLOSER x 1 C02021 (689) EXIT DEVICE TYPE 8, FUNCTION 04 - Push Pad
CONCEALED VERICAL ROD
CYLINDER YALE-COORDINATE W/ FACILITY
MASTER KEY SCHEDULE.
END OF SECTION
SECTION 099113 - EXTERIOR PAINTING
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes surface preparation and the application of paint systems on exterior substrates.
B. Related Requirements:
1. Section 051200 "Structural Steel Framing" for shop priming of metal substrates with primers specified in this Section.
2. Section 099123 "Interior Painting" for surface preparation and the application of paint systems on interior substrates.
1.3 DEFINITIONS
A. Gloss Level 1: Not more than 5 units at 60 degrees and 10 units at 85 degrees, according to ASTM D 523, a matte flat finish.
B. Gloss Level 2: Not more than 10 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523, a high-side sheen flat, velvet-like finish.
C. Gloss Level 3: 10 to 25 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523, an eggshell finish.
D. Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to
ASTM D 523, a satin-like finish.
E. Gloss Level 5: 35 to 70 units at 60 degrees, according to ASTM D 523, a semi-gloss finish.
F. Gloss Level 6: 70 to 85 units at 60 degrees, according to ASTM D 523, a gloss finish.
1.4 SUBMITTALS
A. Product Data: For each type of product. Include preparation requirements and application instructions.
B. Samples for Initial Selection: For each type of topcoat product.
C. Samples for Verification: For each type of paint system and each color and gloss of topcoat.
1. Submit Samples on rigid backing, 8 inches square.
2. Step coats on Samples to show each coat required for system.
3. Label each coat of each Sample.
4. Label each Sample for location and application area.
D. Product List: For each product indicated, include the following:
1. Cross-reference to paint system and locations of application areas. Use same designations indicated on Drawings and in schedules.
2. Printout of current "MPI Approved Products List" for each product category specified in
Part 2, with the proposed product highlighted.
3. VOC content.
1.5 CLOSEOUT SUBMITTALS
A. Coating Maintenance Manual: Provide coating maintenance manual including area summary with finish schedule, area detail designating location where each product/color/finish was used, product data pages, material safety data sheets, care and cleaning instructions, touch-up procedures, and color samples of each color and finish used.
1.6 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Paint: 5 percent, but not less than 1 gal. of each material and color applied.
1.7 QUALITY ASSURANCE
A. Mockups: Apply mockups of each paint system indicated and each color and finish selected to verify preliminary selections made under Sample submittals and to demonstrate aesthetic effects and set quality standards for materials and execution.
1. Architect will select one surface to represent surfaces and conditions for application of each paint system specified in Part 3.
a. Vertical and Horizontal Surfaces: Provide samples of at least 100 sq. ft..
b. Other Items: Architect will designate items or areas required.
2. Final approval of color selections will be based on mockups.
a. If preliminary color selections are not approved, apply additional mockups of additional colors selected by Architect at no added cost to Owner.
3. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing.
4. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Delivery and Handling: Deliver products to Project site in an undamaged condition in manufacturer's original sealed containers, complete with labels and instructions for handling, storing, unpacking, protecting, and installing. Packaging shall bear the manufacture’s label with the following information:
1. Product name and type (description).
2. Batch date.
3. Color number.
4. VOC content.
5. Environmental handling requirements.
6. Surface preparation requirements.
7. Application instructions.
B. Store materials not in use in tightly covered containers in well-ventilated areas with ambient temperatures continuously maintained at not less than 45 deg F.
1. Maintain containers in clean condition, free of foreign materials and residue.
2. Remove rags and waste from storage areas daily.
1.9 FIELD CONDITIONS
A. Apply paints only when temperature of surfaces to be painted and ambient air temperatures are between 50 and 95 deg F.
B. Do not apply paints in snow, rain, fog, or mist; when relative humidity exceeds 85 percent; at temperatures less than 5 deg F above the dew point; or to damp or wet surfaces.
C. Hazardous Materials: It is not expected that hazardous materials will be encountered in the Work.
1. If suspected hazardous materials are encountered, do not disturb; immediately notify
Architect and Owner.
D. Hazardous Materials: Hazardous materials including lead paint are present in buildings and structures to be painted. A report on the presence of known hazardous materials is on file for review and use. Examine report to become aware of locations where hazardous materials are present.
1. Do not disturb hazardous materials or items suspected of containing hazardous materials except under procedures specified.
2. Perform preparation for painting of substrates known to include lead paint in accordance with EPA Renovation, Repair and Painting Rule and additional requirements of authorities having jurisdiction.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Basis-of-Design Product: Subject to compliance with requirements, provide Sherwin-Williams Extreme Block Interior/Exterior Stain Blocking Alkyd Primer and Duration Exterior Acrylic Latex or comparable product.
B. Source Limitations: Obtain paint materials from single source from single listed manufacturer.
1. Manufacturer's designations listed on a separate color schedule are for color reference only and do not indicate prior approval.
2.2 PAINT, GENERAL
A. MPI Standards: Provide products that comply with MPI standards indicated and that are listed in its "MPI Approved Products List."
B. Material Compatibility:
1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience.
2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated.
C. VOC Content: Provide materials that comply with VOC limits of authorities having jurisdiction.
D. Colors: As selected by Hatchery Manager.
2.3 SOURCE QUALITY CONTROL
A. Testing of Paint Materials: Owner reserves the right to invoke the following procedure:
1. Owner will engage the services of a qualified testing agency to sample paint materials.
Contractor will be notified in advance and may be present when samples are taken. If paint materials have already been delivered to Project site, samples may be taken at Project site. Samples will be identified, sealed, and certified by testing agency.
2. Testing agency will perform tests for compliance with product requirements.
3. Owner may direct Contractor to stop applying paints if test results show materials being used do not comply with product requirements. Contractor shall remove noncomplying paint materials from Project site, pay for testing, and repaint surfaces painted with rejected materials. Contractor will be required to remove rejected materials from previously painted surfaces if, on repainting with complying materials, the two paints are incompatible.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers. Where acceptability of substrate conditions is in question, apply samples and perform in-situ testing to verify compatibility, adhesion, and film integrity of new paint application.
1. Report, in writing, conditions that may affect application, appearance, or performance of paint.
B. Proceed with coating application only after unsatisfactory conditions have been corrected;
application of coating indicates acceptance of surfaces and conditions.
3.2 PREPARATION
A. Comply with manufacturer's written instructions and recommendations in "MPI Manual" applicable to substrates and paint systems indicated.
B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting.
1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection.
C. Clean substrates of substances that could impair bond of paints, including dust, dirt, oil, grease, and incompatible paints and encapsulants.
1. Remove incompatible primers and reprime substrate with compatible primers or apply tie coat as required to produce paint systems indicated.
D. Steel Substrates: Remove rust, loose mill scale, and shop primer if any. Clean using methods recommended in writing by paint manufacturer.
E. Shop-Primed Steel Substrates: Clean field welds, bolted connections, and abraded areas of shop paint, and paint exposed areas with the same material as used for shop priming to comply with SSPC-PA 1 for touching up shop-primed surfaces.
F. Galvanized-Metal Substrates: Remove grease and oil residue from galvanized sheet metal by mechanical methods to produce clean, lightly etched surfaces that promote adhesion of subsequently applied paints.
G. Aluminum Substrates: Remove loose surface oxidation.
H. Plastic Trim Fabrication Substrates: Remove dust, dirt, and other foreign material that might impair bond of paints to substrates.
3.3 APPLICATION
A. Apply paints according to manufacturer's written instructions and recommendations in "MPI Manual."
1. Use applicators and techniques suited for paint and substrate indicated.
2. Paint surfaces behind movable items same as similar exposed surfaces. Before final installation, paint surfaces behind permanently fixed items with prime coat only.
3. Paint both sides and edges of exterior doors and entire exposed surface of exterior door frames.
4. Paint entire exposed surface of window frames and sashes.
5. Do not paint over labels of independent testing agencies or equipment name, identification, performance rating, or nomenclature plates.
6. Primers specified in painting schedules may be omitted on items that are factory primed or factory finished if acceptable to topcoat manufacturers.
B. Tint undercoats same color as topcoat, but tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of same material are to be applied. Provide sufficient difference in shade of undercoats to distinguish each separate coat.
C. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance.
D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.
3.4 FIELD QUALITY CONTROL
A. Dry Film Thickness Testing: Owner may engage the services of a qualified testing and inspecting agency to inspect and test paint for dry film thickness.
1. Contractor shall touch up and restore painted surfaces damaged by testing.
2. If test results show that dry film thickness of applied paint does not comply with paint manufacturer's written recommendations, Contractor shall pay for testing and apply additional coats as needed to provide dry film thickness that complies with paint manufacturer's written recommendations.
3.5 CLEANING AND PROTECTION
A. At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site.
B. After completing paint application, clean spattered surfaces. Remove spattered paints by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces.
C. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition.
D. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces.
3.6 EXTERIOR PAINTING SCHEDULE
A. Ferrous Metal, Galvanized-Metal, and Aluminum Substrates:
1. Water-Based Light Industrial Coating System:
a. Prime Coat: Primer, water-based, anti-corrosive for metal: S-W Pro Industrial Pro- Cryl Universal Primer, B66-310 Series, 5.0 to 10.0 mils wet, 2.0 to 4.0 mils dry.
b. Prime Coat: Shop primer specified in Section where substrate is specified.
c. Intermediate Coat: Light industrial coating, exterior, water based, matching topcoat.
d. Topcoat: Light industrial coating, exterior, water based, semi-gloss: S-W Pro
Industrial Acrylic Semi-Gloss Coating, B66-650 Series, at 2.5 to 4.0 mils dry, per coat.
END OF SECTION 099113
SECTION 08323 - OVERHEAD COILING DOORS
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Insulated service doors.
1.3 PERFORMANCE REQUIREMENTS
A. Delegated Design: Design overhead coiling doors, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
B. Structural Performance, Exterior Doors: Exterior overhead coiling doors shall withstand the wind loads, the effects of gravity loads, and loads and stresses within limits and under conditions indicated according to SEI/ASCE 7 and the following:
1. Wind Loads: Uniform pressure (velocity pressure) of 40 lbf/sq. ft., acting inward and outward.
2. Deflection Limits: Design overhead coiling doors to withstand design wind load without evidencing permanent deformation or disengagement of door components.
C. Operability under Wind Load: Design overhead coiling doors to remain operable under uniform pressure (velocity pressure) of 10 lbf/sq. ft. wind load, acting inward and outward.
D. Operation Cycles: Provide overhead coiling door components and operators capable of operating for not less than number of cycles indicated for each door. One operation cycle is complete when a door is opened from the closed position to the fully open position and returned to the closed position.
1.4 SUBMITTALS
A. Product Data: For each type and size of overhead coiling door and accessory. Include the following:
1. Construction details, material descriptions, dimensions of individual components, profiles for slats, and finishes.
B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data. Include plans, elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
C. Samples for Initial Selection: Manufacturer's finish charts showing full range of colors and textures available for units with factory-applied finishes, as selected by the CI.
D. Delegated-Design Submittal: For overhead coiling doors indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
E. Qualification Data: For qualified Installer.
F. Maintenance Data: For overhead coiling doors to include in maintenance manuals.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for both installation and maintenance of units required for this Project.
B. Source Limitations: Obtain overhead coiling doors from single source from single manufacturer.
C. Regulatory Requirements: Door and assembly shall be tested and approved by a testing agency acceptable to the IBC for a minimum 40 psf positive and negative pressure.
PART 2 - PRODUCTS
2.1 DOOR CURTAIN MATERIALS AND CONSTRUCTION
A. Door Curtains: Fabricate overhead coiling-door curtain of interlocking metal slats, designed to withstand wind loading indicated, in a continuous length for width of door without splices. Unless otherwise indicated, provide slats of thickness and mechanical properties recommended by door manufacturer for performance, size, and type of door indicated, and as follows:
1. Steel Door Curtain Slats: Zinc-coated (galvanized), cold-rolled structural steel sheet;
complying with ASTM A 653/A 653M, with G90 zinc coating; nominal sheet thickness (coated) of 0.028 inch and as required to meet requirements. First two subparagraphs below describe different interior facings for insulated slats; facing in first subparagraph is most common.
2. Insulation: Fill slats for insulated doors with manufacturer's standard thermal insulation complying with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, according to ASTM E 84. Enclose insulation completely within slat faces.
3. Metal Interior Curtain-Slat Facing: Match metal of exterior curtain-slat face.
B. Endlocks and Windlocks for Service Doors: Malleable-iron casings galvanized after fabrication, secured to curtain slats with galvanized rivets or high-strength nylon. Provide locks on not less than alternate curtain slats for curtain alignment and resistance against lateral movement.
C. Bottom Bar for Service Doors: Consisting of two angles, each not less than 1-1/2 by 1-1/2 by 1/8 inch thick; fabricated from manufacturer's standard hot-dip galvanized steel, stainless steel, or aluminum extrusions to match curtain slats and finish.
D. Astragal for Interior Doors: Equip each door bottom bar with a replaceable, adjustable, continuous, compressible gasket of flexible vinyl, rubber, or neoprene as a cushion bumper.
E. Curtain Jamb Guides: Manufacturer's standard angles or channels and angles of same material and finish as curtain slats unless otherwise indicated, with sufficient depth and strength to retain curtain, to allow curtain to operate smoothly, and to withstand loading. Slot bolt holes for guide adjustment. Provide removable stops on guides to prevent overtravel of curtain, and a continuous bar for holding windlocks.
2.2 HOOD
A. General: Form sheet metal hood to entirely enclose coiled curtain and operating mechanism at opening head. Contour to fit end brackets to which hood is attached. Roll and reinforce top and bottom edges for stiffness. Form closed ends for surface-mounted hoods and fascia for any portion of between-jamb mounting that projects beyond wall face. Equip hood with intermediate support brackets as required to prevent sagging.
1. Galvanized Steel: Nominal 0.028-inch- thick, hot-dip galvanized steel sheet with G90 zinc coating, complying with ASTM A 653/A 653M.
2. Stainless Steel: 0.025-inch- thick stainless-steel sheet, Type 304, complying with
ASTM A 666.
3. Aluminum: 0.040-inch- thick aluminum sheet complying with ASTM B 209, of alloy and temper recommended by manufacturer and finisher for type of use and finish indicated.
4. Include automatic drop baffle on fire-rated doors to guard against passage of smoke or flame.
5. Exterior-Mounted Doors: Fabricate hood to act as weather protection and with a perimeter sealant-joint-bead profile for applying joint sealant.
2.3 LOCKING DEVICES
A. Locking Device Assembly: Fabricate with cylinder lock, spring-loaded dead bolt, operating handle, cam plate, and adjustable locking bars to engage through slots in tracks.
1. Lock Cylinders: Provide cylinders standard with manufacturer and keyed to building keying system.
2. Keys: Provide two for each cylinder.
3. All keys shall be identical for each building.
2.4 CURTAIN ACCESSORIES
A. Weatherseals: Equip each exterior door with weather-stripping gaskets fitted to entire perimeter of door for a weathertight installation, unless otherwise indicated.
B. Push/Pull Handles: Equip each push-up-operated or emergency-operated door with lifting handles on each side of door, finished to match door.
1. Provide pull-down straps or pole hooks.
2.5 MANUAL DOOR OPERATORS
A. Equip door with manufacturer's recommended manual door operator unless another type of door operator is indicated.
B. Chain-Hoist Operator: Consisting of endless steel hand chain, chain-pocket wheel and guard, and gear-reduction unit with a maximum 25 lbf force for door operation. Provide alloy-steel hand chain with chain holder secured to operator guide.
2.6 DOOR ASSEMBLY
A. Service Door: Overhead coiling door formed with curtain of interlocking metal slats.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Best Rolling Doors, Inc.
b. Cornell Iron Works, Inc.
c. Overhead Door Corporation.
d. Raynor.
e. Or equal
B. Operation Cycles: Not less than 20,000 .
C. Curtain R-Value: 4.5 deg F x h x sq. ft./Btu.
D. Door Curtain Material: Galvanized steel.
E. Hood: Match curtain material and finish.
F. Locking Devices: Equip door with locking device assembly.
1. Locking Device Assembly: locking bars, operable from inside with thumb turn, outside with cylinder.
G. Manual Door Operator: Chain-hoist operator.
H. Door Finish:
1. Baked-Enamel or Powder-Coated Finish: Color as selected by the CI.
2. Interior Curtain-Slat Facing: Match finish of exterior curtain-slat face.
2.7 GENERAL FINISH REQUIREMENTS
A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.
B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
2.8 STEEL AND GALVANIZED-STEEL FINISHES
A. Baked-Enamel or Powder-Coat Finish: Manufacturer's standard baked-on finish consisting of prime coat and thermosetting topcoat. Comply with coating manufacturer's written instructions for cleaning, pretreatment, application, and minimum dry film thickness.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates areas and conditions, with Installer present, for compliance with requirements for substrate construction and other conditions affecting performance of the Work.
B. Examine locations of electrical connections.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install overhead coiling doors and operating equipment complete with necessary hardware, anchors, inserts, hangers, and equipment supports; according to manufacturer's written instructions and as specified.
B. Install overhead coiling doors, hoods, and operators at the locations indicated for each door.
C. Accessibility: Install overhead coiling doors, and controls along accessible routes in compliance with regulatory requirements for accessibility.
3.3 STARTUP SERVICE
A. Engage a factory-authorized service representative to perform startup service.
1. Perform installation and startup checks according to manufacturer's written instructions.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
3.4 ADJUSTING
A. Adjust hardware and moving parts to function smoothly so that doors operate easily, free of warp, twist, or distortion.
B. Lubricate bearings and sliding parts as recommended by manufacturer.
C. Adjust seals to provide weathertight fit around entire perimeter.
3.5 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain overhead coiling doors.
END OF SECTION 083323
APPENDIX
| United States Fish and Wildlife Service Infrastructure Management Division |
| SECTION 01009 - GENERAL INFORMATION AND REQUIREMENTS |
| 1.1 SUMMARY: |
| 1.2 REFERENCES: |
| 1.3 DEFINITIONS: |
| 1.4 SUBMITTALS: |
| 1.5 CONFORMANCE: |
| 1.6 QUALITY ASSURANCE: |
| 1.7 DELIVERY, STORAGE, AND HANDLING: |
| 1.8 PROJECT/SITE CONDITIONS: |
| 1.9 SEQUENCING AND SCHEDULING: |
| 3.1 PROJECT MEETINGS: |
| 3.2 DISPOSAL OF DEBRIS: |
| 3.3 WARRANTY: |
| END OF SECTION |
| 1.2 SUMMARY |
| 1.3 SUBMITTALS |
| 1.4 INFORMATIONAL SUBMITTALS |
| PART 2 - PRODUCTS |
| 2.2 PERFORMANCE REQUIREMENTS |
| 2.3 EXTERIOR STANDARD STEEL DOORS AND FRAMES |
| 2.4 FRAME ANCHORS |
| 2.5 MATERIALS |
| 2.6 FABRICATION |
| 2.7 STEEL FINISHES |
| PART 3 - EXECUTION |
| 3.2 INSTALLATION |
| 3.3 CLEANING AND TOUCHUP |
| END OF SECTION 081113 |
| SECTION 08710 - DOOR HARDWARE PART 1: GENERAL |
| 1.2 SUBMITTALS |
| 1.3 QUALIFICATIONS |
| 1.4 KEYING |
| 2.1 MATERIALS |
| 3.1 INSTALLATION |
| DOOR HARDWARE SCHEDULE |
| HARDWARE SET 1.0: |
| SECTION 099113 - EXTERIOR PAINTING PART 1 - GENERAL |
| 1.2 SUMMARY |
| 1.3 DEFINITIONS |
| 1.4 SUBMITTALS |
| 1.5 CLOSEOUT SUBMITTALS |
| 1.6 MAINTENANCE MATERIAL SUBMITTALS |
| 1.7 QUALITY ASSURANCE |
| 1.8 DELIVERY, STORAGE, AND HANDLING |
| 1.9 FIELD CONDITIONS |
| PART 2 - PRODUCTS |
| 2.2 PAINT, GENERAL |
| 2.3 SOURCE QUALITY CONTROL |
| PART 3 - EXECUTION |
| 3.2 PREPARATION |
| 3.3 APPLICATION |
| 3.4 FIELD QUALITY CONTROL |
| 3.5 CLEANING AND PROTECTION |
| 3.6 EXTERIOR PAINTING SCHEDULE |
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including Division 01 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. Section Includes: |
| 1. Insulated service doors. |
| 1.3 PERFORMANCE REQUIREMENTS |
| A. Delegated Design: Design overhead coiling doors, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated. |
| B. Structural Performance, Exterior Doors: Exterior overhead coiling doors shall withstand the wind loads, the effects of gravity loads, and loads and stresses within limits and under conditions indicated according to SEI/ASCE 7 and the following: |
| 1. Wind Loads: Uniform pressure (velocity pressure) of 40 lbf/sq. ft., acting inward and outward. |
| 2. Deflection Limits: Design overhead coiling doors to withstand design wind load without evidencing permanent deformation or disengagement of door components. |
| C. Operability under Wind Load: Design overhead coiling doors to remain operable under uniform pressure (velocity pressure) of 10 lbf/sq. ft. wind load, acting inward and outward. |
| D. Operation Cycles: Provide overhead coiling door components and operators capable of operating for not less than number of cycles indicated for each door. One operation cycle is complete when a door is opened from the closed position to the fully ... |
| 1.4 SUBMITTALS |
| A. Product Data: For each type and size of overhead coiling door and accessory. Include the following: |
| 1. Construction details, material descriptions, dimensions of individual components, profiles for slats, and finishes. |
| B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data. Include plans, elevations, sections, details, and attachments to other work. |
| 1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. |
| C. Samples for Initial Selection: Manufacturer's finish charts showing full range of colors and textures available for units with factory-applied finishes, as selected by the CI. |
| D. Delegated-Design Submittal: For overhead coiling doors indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation. |
| E. Qualification Data: For qualified Installer. |
| F. Maintenance Data: For overhead coiling doors to include in maintenance manuals. |
| 1.5 QUALITY ASSURANCE |
| A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for both installation and maintenance of units required for this Project. |
| B. Source Limitations: Obtain overhead coiling doors from single source from single manufacturer. |
| C. Regulatory Requirements: Door and assembly shall be tested and approved by a testing agency acceptable to the IBC for a minimum 40 psf positive and negative pressure. |
| PART 2 - PRODUCTS |
| 2.1 DOOR CURTAIN MATERIALS AND CONSTRUCTION |