This document is a Sources Sought announcement from the 21st Contracting Squadron at Peterson Space Force Base, Colorado. The announcement is seeking potential sources to provide Lightweight Modular/Mobile sensitive compartmented information facilities (SCIF) that meet permanent SCIF accreditation standards per ICD 705. The required command module must be a custom, lightweight 8 x 8 x 20' shelter that can be transported on a standard military cargo aircraft and weigh less than 6,000 lbs. This Sources Sought is for market research purposes only and does not constitute a commitment by the Government. Responses are voluntary, and the Government will not compensate respondents for any costs incurred. The related federal contract opportunity is a pre-solicitation for a Mobile SCIF requirement, for which interested parties should refer to the attached Sources Sought document.
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sources Sought
SAM
Lightweight Modular/Mobile SCIF
THIS IS A SOURCES SOUGHT ANNOUNCEMENT ONLY. The 21st Contracting Squadron is conducting market research to determine interest and capability of potential sources. This notice does not constitute a commitment by the Government. All information submitted in response to this announcement is voluntary, and the Government will not pay for information requested nor will it compensate any respondent for any cost incurred in developing information provided to the Government.
Peterson Space Force Base (PSFB), Colorado is seeking potential sources to provide Lightweight Modular/Mobile sensitive compartmented information facilities (SCIF), per the below specifications.
Specifications:
• Command Module A custom, lightweight 8 x 8 x 20' shelter that is built to meet permanent SCIF (not TSCIF) accreditation standards, per ICD 705. The final delivered module must not exceed the dimensions of three pallet positions on a standard military cargo aircraft (C-130/C-17) and shall weigh less than 6,000lbs.
o Physical Structure
Weight of the delivered command module should be (less than or equal to) </= 6,000lbs
Wall or panel thickness of 2.240”, +/- 0.06” Access Door Welded structural tube aluminum base Long term corrosion resistance using vinyl ester resin.
Custom Aluminum frame ASTM E-84 Class 1 construction.
Corner and base connection points for transport External tiedowns for secure transport Leveling Jacks W/Spreaders o Interior Two internal workstations for operators 8-Ton Heating and Cooling Capacity from ECU Four each, 42U component racks
• 36” depth
• 2 each PDU's per rack with individually addressable outlets o EMI Mitigating Tech Must attenuate EMI per ICD-705 standards, verified via test.
Must attenuate internal sound per ICD-705 standards, verified via test.
Faraday cage construction
• Must attenuate EMI per ICD-705 standards.
• Must attenuate internal sound per ICD-705 standards.
• Minimize and seal all boundaries such as waterfall panel, power inputs, panel joints, etc.
HVAC Input/Output Vents
• Internal HVAC ducting with visual inspection access ports o Exterior
EMCoat painted.
Internal Electrical/Signals cabling installed per TEMPEST standards.
o Electrical Primary 3-phase power connector, to receive power from the Service
Module Must support distribution of 120/208V 60Hz power distribution internally.
Electrical/Signals cabling installed per TEMPEST Standards Power EMI Filter, 200A 120/208V 3P at entrance Grounding Rod connected through 208V/200A Panel.
Customizable Signal entry Waterfall Panel:
• Various Ethernet, TFOCA, RF connections per govt direction 30kW 120/208V 3P 60hz Tower Uninterruptable Power Supply Control panel for Environmental Control System Power, unclassified and classified runs, for two workstations.
o Security External, 360deg. Lighting Security System
• XR550DEA-G Encrypted DMP Panel
• 322 DMP wire in transfer with metal enclosure
• 12V7A batteries to provide backup power.
• 7060-W DMP keypad with conduit backbox in container
• High security door status switch on the front door
• 70' ceiling mount PIR or similar at front and back of module
• Keypad o External Key lock override for emergency use o X-10 Lock with internal magnetic lock release and egress button.
• Intrusion Detection System meeting ICD-705 and Tempest requirements.
o DMP System Link software to be installed on Gov't
Provided laptop to allow remote alarm detection and system monitoring with 128bit AES encryption. (Possibly avoiding remote monitoring)
• Security system powered by isolated power run, separate from internal equipment rack power.
o Must be lightweight, and air transportable.
• Service Module
CONEX style experimental shelter to accept worldwide 3-phase shore power and allow control and emergency power generation. Shelter shall weigh less than 10000lbs, to include all associated hardware as identified below, and must not exceed the dimensions of three pallet positions on a standard military cargo aircraft (C-130/C-17).
o Physical Structure
Corner and base connection points for transport Doors on both ends for airflow.
Doors/Panels around generator for maintenance access.
Physical Storage for power plant, ECU, cables, and cable reels during shelter transport.
• Extra storage Cabinet for consumables
Full CARC Painted for protection.
Leveling Jacks W/Spreaders o Electrical System Power Requirements
• Must accept worldwide power from 190-520 VAC, 60KVA 3-phase, 45-440hz.
• Must transform worldwide 3-phase power to 120/208V @ 60Hz.
• Must provide 120/208V 60Hz, 200A to Command Module, via appropriately sized 25ft. umbilical cable.
Generator:
• 101kW Standby/91kW prime, 3-Phase 120/208V@ 60 Hz with 200-Gal Fuel tank
Shore Power Converter = 65KVa system converts 1{ 190V-260V/3P 170V-520V/Freq. 45Hz-440Hz to 120/208V @ 60Hz
Automatic Transfer Switch: 120/208, 3P 60 Hz to detect loss of Shore power and switch to generator.
8-Ton Environmental Control Unit (ECU)
The anticipated solicitation will be issued under North American Industry Classification Systems (NAICS) Code 332311 – Prefabricated Metal Building and Component Manufacturing. The size standard is 750 employees.
Please identify any relevant past performance to substantiate your capabilities statements.
Please accompany your submission with answers to the questions below:
Is your business categorized as a small business under the anticipated NAICS code of 332311 – Prefabricated Metal Building and Component Manufacturing?
Do you intend to provide a quote for this requirement? How many days would you need to draft a quote?
What is the average lead time for development/production of the required items?
What are the average lead times for this products delivery?
Can this be provided on a federal supply schedule? If so, what is the contract number?
In responding to this sources sought/RFI posting, we kindly request that contractors provide detailed insights into their execution plan or methodology for the project. Please outline how you would approach and perform the required tasks, including key milestones, resources allocation, and any unique strategies or capabilities you would bring to the table.
Provide any additional questions or comments.
This Sources Sought Announcement is solely for informational and planning purposes only and is not a solicitation or Request for Quote. Please send responses to: