A Novel Water Heating System for Pathogen Control
David Yashar, PhD
Deputy Chief, Energy and Environment Division
The National Institute of Standards and Technology
This slide deck was presented at the Legionella Conference 2019 Building Water Systems: The Sustainability and Public Health Nexus Organized by the NSF International & National Environmental Health Association September 11-13, 2019 Westin Bonaventure Hotel & Suites, Los Angeles, CA
9/9/2020
Slide 2
• Background information
• Current treatment methods
• Basis for temperature control
• Analysis for basic system and system with mixing valve
• Proposed design and analysis
• Summary and next steps
Outline
Slide 3
• Legionella is present in all water sources
• Certain conditions promote growth of bacteria
• Temperature, biofilm/organic matter
• Infection through inhalation
• Susceptibility
• Legionnaires’ disease or Pontiac fever
• More than 6 000 cases per year reported in the US*
• Suspected underdiagnoses, likely 10x
• 10 % fatality rate
• The best control is to not allow it in building water systems in the first place
Background
*Source: Center for Disease Control - https://www.cdc.gov/legionella/fastfacts.html https://www.cdc.gov/legionella/fastfacts.html
Slide 4
• Chemical – typically chlorine
• Added at treatment facility
• Becomes less effective with time, little certainty of how long until POU
• Ionization, filtration, ultraviolet
• More complex approaches
• Thermal
Common Treatment Options
Temperature Range Notes
Dormant Range T < 20 °C (68 °F) Alive but inactive, does not multiply, much less likely to cause harm
Active Range 20 °C < T < 45 °C (68 °F < T < 113 °F)
Ideal range for growth
High Temp Range
T > 50 °C (122 °F) Bacteria has difficulty sustaining life
Slide 5
• Temperature control can be a very effective tool
• Focused on maintaining temperatures outside of active range
• Heat treatment effectiveness is related to temperature and the duration of exposure
Temperature Control
Decimal Reduction Rate – time to kill 90% of existing microorganisms
50 °C (122 °F) 2 h
60 °C (140 °F) 2 min
70 °C (158 °F) All microorganisms killed, almost instantly
Source: Legionella and the prevention of legionellosis, World Health Organization, 2007
Slide 6
• Requirements are set to protect against scalding
• Max temp typically in the range of 46 °C (115 °F) – 49 °C (120 °F)
• Exposure time that results in scalding is roughly 2 orders of magnitude faster than the decimal reduction rate
High Temperature Concern: Scalding
Exposure time to induce a burn injury
37 °C (100 °F) None
48 °C (120 °F) 5 min
52 °C (127 °F) 1 min
56 °C (133 °F) 15 s
60 °C (140 °F) 5 s
64 °C (148 °F) 2 s
68 °C (155 °F) 1 s
Source: Moritz and Henriques, Studies of Thermal Injuries, 1947
Slide 7
• Typical systems/setpoints invariably result in water within active range
• Heated to the lower end of the High Temp Range
• May be short duration
• Discharged into building piping network
• Heat rejection to building reduces temperature back into active range
• Can dwell or stagnate in piping network for a long time
Basic Water Heating System* Hot water to building 49 °C (120 °F)
Cold water supply ≈ 16 °C (60 °F)
Nutrient-rich sludge
Temperature variation within tank
49 °C (120 °F)
≈ 32 °C (90 °F)
* All temperatures are examples for illustrative purposes
Slide 8
Temperature Profile for Basic System
Time
Te m p er at u re
Active growth range
Bacteria killing range
Inside heating system
Enter building
Hot water distribution system
Slide 9
• Benefit
• Better temperature control
• Maintain higher temperature in tank
• Problem
• Dormant microorganisms may be reintroduced through mixing valve
• Hot water piping network - same situation as before, maybe with fewer organisms
• Option - Hot Water Return
• Easier to maintain high temperature in piping network
• Still introducing dormant microorganisms
Basic System with Mixing Valve*
> 49 °C (120 °F)
> 32 °C (90 °F)
49 °C (120 °F)
Slide 10
Temperature Profile System with Mixing Valve
Time
Te m p er at u re
Hot water return
Bacteria killing range
Inside heating system
Enter building
Hot water distribution system
Slide 11
• Raise tank temperature much higher
• > 71 °C (160 °F) should kill all live organisms
• Water-to-water heat exchanger
• Thermal energy taken from water leaving tank, reduce supply to safe temperature
• Energy recovered to preheat water entering tank, minimizes energy impact on system
• Unmixed streams prevent dormant microorganisms from entering piping network
• Fixed volume tank will not allow flow without heat removal
• Minimizes possibility of occupant exposure to ultra-hot water
Proposed System* Hot water to building 49 °C (120 °F)
Cold water supply ≈ 16 °C (60 °F)
> 71 °C (160 °F)
> 54 °C (130 °F)
≈ 38 °C (100 °F)
Slide 12
Temperature Profile for Proposed System
Time
Te m p er at u re
Bacteria killing range
Inside heating system
Enter building
Hot water distribution system
Heat exchanger heat absorption
Heat exchanger heat rejection
Slide 13
• Water-to-water heat exchanger between tank inlet and outlet
• Eliminate living microorganisms to protect against exposure to waterborne pathogens
• Recovers energy from ultra-hot water to protect against scalding
• Rejected energy from ultra-hot water is reused to preheat incoming water to conserve energy
• Need experimental data to investigate
• Effectiveness for legionella control
• Sensitivity to water flow rate and inlet temperature
• Other factors
• For practical application
• Additional equipment ($)
• Thicker insulation to reduce impact of higher storage temperature
• Training and education needs
Summary and next steps