This solicitation package includes drawings and specifications for the restoration of historic walls at Fort Rosecrans National Cemetery in San Diego County, California. The project scope involves the complete design and rehabilitation of the cemetery's boundary walls, including concrete repair, coating application, drainage improvements, and accessibility upgrades. The period of performance is 270 calendar days with an estimated value between $1-5 million. The solicitation is issued as a competitive set-aside for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification System code listed is 237990 for retaining walls. The U.S. Army Corps of Engineers Engineering District in Los Angeles is the contracting agency.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS:
CLR CLEAR
CONC CONCRETE
DIA DIAMETER
EXIST EXISTING
EQ EQUAL
EW EACH WAY
HORIZ HORIZONTAL
LF LINEAL FEET
MAX MAXIMUM
MILS ONE THOUSANDTH OF AN INCH
MIN MINIMUM
NEW NEW
NTS NOT TO SCALE
OC ON CENTER
SF SQUARE FEET
S.S. STAINLESS STEEL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
W/ WITH
VERT VERTICAL
VIF VERIFY IN FIELD
INDEX TO DRAWINGS:
A-001 GENERAL NOTES
AS100 SITE PLAN
A-101 HISTORIC WEST BOUNDARY WALL 1 AND 2
A-102 HISTORIC EAST BOUNDARY WALL
A-103 ACCESS STAIRS
A-104 WEST MAIN ENTRANCE GATES
A-105 EAST MAIN ENTRANCE GATES
A-106 ROSTRUM
A-501 CONCRETE DETAILS AT ROSTRUM AND ENTRY GATES
A-502 CONCRETE AND COATING DETAILS
A-503 CONCRETE DETAILS AT EAST BOUNDARY WALL
ARCHITECTURAL HISTORIC MATERIALS PRESERVATION SCOPE OF WORK
1. HISTORIC WEST BOUNDARY WALL 1:
1.A. REPLACE WALL DUE TO STRUCTURAL FAILURE.
1.B. REPLACEMENT WALL TO MATCH ORIGINAL IN GEOMETRY, COLOR, AND OVERALL AESTHETIC.
1.C. REPLICATE AND REPLACE MISSING FINIALS AND CAPITALS.
1.D. INSTALL SEPARATION BETWEEN PLANTER/SOIL AND CONCRETE FOOTING AND WALL.
1.E. REDIRECT SPRINKLERS AND IRRIGATION AWAY FROM THE WALL. REFER TO LANDSCAPE DRAWINGS.
2. HISTORIC WEST BOUNDARY WALL 2:
2.A. REPLACE WALL DUE TO EXTENSIVE DISTRESS AND FAILURE.
2.B. REPLACEMENT WALL TO MATCH ORIGINAL IN GEOMETRY, COLOR, AND OVERALL AESTHETIC.
2.C. REPLICATE AND REPLACE MISSING FINIALS AND CAPITALS.
2.D. REDIRECT SPRINKLERS AND IRRIGATION AWAY FROM WALLS.
3. HISTORIC EAST BOUNDARY WALL:
3.A. REPLICATE AND REPLACE MISSING FINIALS.
3.B. REPAIR CORROSION RELATED DISTRESS AND DETERIORATION AT WALL. CONTRACTOR TO IDENTIFY REPAIR LOCATIONS AND
CONFIRM WITH ARCHITECT/ENGINEER PRIOR TO REMOVAL. ASSUME 500 SF FOR BIDDING.
3.C. REMOVE LOOSE AND DELAMINATED CONCRETE AT AREAS OF SCALING; SOUND SUBSTRATE TO REMAIN.
3.D. REDIRECT SPRINKLERS AND IRRIGATION AWAY FROM WALLS.
3.E. CLEAN ORGANIC GROWTH FROM WALL.
4. 3 SETS OF ACCESS STAIRS (SECTION E AND OFFICER SECTION A):
4.A. REMOVE AND REPLACE STAIRS.
4.B. MATCH TOP OR BOTTOM ELEVATION OF EXISTING STAIRS WHERE INDICATED.
4.C. ADD SLOPE TO TREADS TO FACILITATE DRAINAGE.
4.D. REPLACE HANDRAIL.
5. WEST MAIN ENTRANCE GATES:
5.A. REMOVE 100% OF EXISTING COATING FROM CONCRETE AND STEEL GATE COMPONENTS TO REMAIN.
5.B. OBSERVE EXPOSED CONCRETE FOR DISTRESS OR DAMAGE.
5.C. REPAIR CONCRETE AS NEEDED. CONTRACTOR TO IDENTIFY REPAIR LOCATIONS AND CONFIRM WITH ARCHITECT/ENGINEER
PRIOR TO REMOVAL. ASSUME 25 SF FOR BIDDING.
5.D. PATCH EXISTING FASTENER HOLES. ASSUME 10 LOCATIONS FOR BIDDING.
5.E. INSTALL NEW COATING AT CONCRETE AND STEEL GATE COMPONENTS TO REMAIN.
6. EAST MAIN ENTRANCE GATES:
6.A. REMOVE 100% OF EXISTING COATING FROM CONCRETE AND STEEL GATE COMPONENTS TO REMAIN.
6.B. OBSERVE EXPOSED CONCRETE FOR DISTRESS OR DAMAGE.
6.C. REPAIR CONCRETE AS NEEDED. CONTRACTOR TO IDENTIFY REPAIR LOCATIONS AND CONFIRM WITH ARCHITECT/ENGINEER
PRIOR TO REMOVAL. ASSUME 50 SF FOR BIDDING.
6.D. REPLACE PREVIOUS REPAIRS THAT ARE UNSOUND OR DO NOT MATCH TEXTURE OR ORIGINAL CONCRETE.
6.E. PATCH EXISTING FASTENER HOLES. ASSUME 10 LOCATIONS FOR BIDDING.
6.F. INSTALL NEW COATING AT CONCRETE AND STEEL GATE COMPONENTS TO REMAIN.
7. ROSTRUM:
7.A. REMOVE 100% OF EXISTING COATING TO EXPOSE CONCRETE AND STUCCO.
7.B. REMOVE EXISTING TRAFFIC MEMBRANE FROM CONCRETE SLAB ON GROUND WHERE INDICATED.
7.C. OBSERVE EXPOSED CONCRETE AND STUCCO FOR DISTRESS OR DAMAGE.
7.D. REPAIR CONCRETE AS NEEDED. CONTRACTOR TO IDENTIFY REPAIR LOCATIONS AND CONFIRM WITH ARCHITECT/ENGINEER
PRIOR TO REMOVAL. ASSUME 25 SF FOR BIDDING.
7.E. REPAIR STUCCO AS NEEDED. CONTRACTOR TO IDENTIFY REPAIR LOCATIONS AND CONFIRM WITH ARCHITECT/ENGINEER
PRIOR TO REMOVAL. ASSUME 20 SF FOR BIDDING.
7.F. INSTALL NEW COATING.
7.G. INSTALL NEW TRAFFIC MEMBRANE.
GENERAL NOTES
1. DO NOT DAMAGE EXISTING ROADWAYS, BUILDINGS, CURBS, FENCES, GATES AND OTHER FACILITIES ADJOINING OR NEAR
THE SITE. REPAIR OR REPLACE IN KIND AND QUALITY ANY DAMAGE CAUSED BY THE CONTRACTOR'S OPERATIONS TO ANY
EXISTING PROPERTY AT NO COST TO THE OWNER AND TO THE SATISFACTION OF ARCHITECT/ENGINEER AND THE OWNER.
2. KEEP THE OWNER AND THE ARCHITECT/ENGINEER INFORMED AND APPRISED OF PROGRESS SO THAT THE OWNER'S
REPRESENTATIVES AND CONSULTANTS MAY MAKE APPROPRIATE JOB SITE REVIEWS.
3. STRUCTURAL OBSERVATIONS AND OTHER JOBSITE REVIEWS MADE BY THE ENGINEER OR ARCHITECT ARE ONLY INTENDED
TO VERIFY THAT THE VISIBLE PORTIONS OF THE WORK IN THE AREAS BEING OBSERVED APPEAR TO BE IN GENERAL
CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS AND THE DESIGN INTENT. STRUCTURAL OBSERVATION AND OTHER
JOBSITE REVIEWS ARE NOT INTENDED TO SERVE AS OR REPLACE INSPECTIONS BY THE BUILDING DEPARTMENT OR SPECIAL
INSPECTIONS REQUIRED BY THESE DRAWINGS OR THE BUILDING CODE.
4. THE CONTRACTOR MUST VERIFY EXISTING CONDITIONS AND DIMENSIONS BEFORE STARTING WORK. SINCE THESE ARE
EXISTING BUILDINGS/STRUCTURES, VERIFICATION OF EXISTING DIMENSIONS AND MATERIALS IS CRITICAL. NOTIFY
ARCHITECT/ENGINEER IMMEDIATELY OF ANY DISCREPANCIES, AND DO NOT PROCEED WITH AFFECTED WORK UNTIL THE
DISCREPANCIES ARE RESOLVED.
5. DO NOT SCALE DRAWINGS.
6. DETAILS NOT SHOWN, INCLUDED ON DRAWINGS, OR CALLED FOR IN THESE NOTES MUST BE CONSTRUCTED TO SAME SIZE
AND CHARACTER AS FOR SIMILAR CONDITIONS THAT ARE SHOWN, DETAILED, OR SPECIFIED, SUBJECT TO THE APPROVAL OF
ARCHITECT/ENGINEER.
7. BEFORE COMMENCING CONSTRUCTION, PROTECT ALL EXISTING BUILDING/STRUCTURE SURFACES TO REMAIN. ANY DAMAGE
CAUSED BY THE CONTRACTOR'S OPERATIONS TO BUILDING/STRUCTURE ELEMENTS TO REMAIN MUST BE REPAIRED IN KIND
BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER AND TO THE SATISFACTION OF THE OWNER AND
ARCHITECT/ENGINEER.
8. PROVIDE ACCESS FOR THE ARCHITECT/ENGINEER TO REVIEW EXISTING CONDITIONS PRIOR TO INSTALLATION OF NEW WORK
FOR CONFORMANCE WITH PROJECT DOCUMENTS. ANY DEFECTIVE WORK WILL BE REPAIRED AT NO COST TO THE OWNER.
9. THESE DRAWINGS AND SPECIFICATIONS APPLY TO THE PROJECT IDENTIFIED IN THE TITLE BLOCK ONLY AND MUST NOT BE
USED FOR ANY OTHER PURPOSE WITHOUT THE EXPRESSED WRITTEN CONSENT OF WJE.
1.0 GENERAL
A. GENERAL CONDITIONS
1. CONTRACTOR RESPONSIBLE FOR MEANS AND METHODS OF REPAIR WORK.
B. EXISTING CONDITIONS
1. AREAS OF REPAIR TO BE IDENTIFIED BY CONTRACTOR AND VERIFIED BY ARCHITECT/ENGINEER AND OWNER.
C. PROTECTION
1. TAKE PRECAUTIONS TO ENSURE SAFETY OF PEOPLE, INCLUDING TENANTS AND WORKMEN, AND PROTECTION OF PROPERTY
INCLUDING ADJACENT BUILDING ELEMENTS. LIMIT ACCESS TO WORK AREAS. ASSUME RESPONSIBILITY FOR INJURY TO
PERSONS OR DAMAGE TO PROPERTY DUE TO WORK AND REMEDY AT NO COST TO OWNER.
2. REMOVE AND DISPOSE OF IN A PROPER MANNER (OFF-SITE) ALL EXISTING MATERIAL REMOVED FROM THE
BUILDINGS/STRUCTURES DURING THE COURSE OF THE WORK ON A DAILY BASIS. REMOVAL AND DISPOSAL MUST BE
SATISFACTORY TO THE ARCHITECT/ENGINEER AND OWNER.
3. CONTRACTOR MUST BE RESPONSIBLE FOR MAINTAINING THE WATER TIGHTNESS OF THE AREAS OF THE STRUCTURE BEING
WORKED ON DURING THE COURSE OF THE WORK. PROVIDE TEMPORARY PROTECTION OF THE EXISTING CONSTRUCTION
FROM THE WEATHER UNTIL REMOVED PORTIONS ARE COMPLETELY REPLACED WITH NEW CONSTRUCTION. THE COST OF
DAMAGE TO REPAIRS MUST BE MADE AT NO COST TO THE OWNER.
D. CONTRACTOR MUST SUBMIT DEMOLITION AND CONSTRUCTION SCHEDULES TO THE OWNER AND ARCHITECT/ENGINEER FOR
APPROVAL PRIOR TO BEGINNING DEMOLITION.
E. DELIVER, STORE, AND HANDLE MATERIALS ACCORDING TO MANUFACTURER'S RECOMMENDATIONS AND TO PREVENT DAMAGE TO
MATERIALS AND STRUCTURE. LIMIT STORED MATERIALS ON STRUCTURE TO SAFE LOADING CAPACITY OF STRUCTURE. REMOVE
AND REPLACE MATERIALS THAT CANNOT BE APPLIED WITHIN STATED SHELF LIFE.
F. ELECTRICITY WILL NOT BE MADE AVAILABLE FROM BUILDING OR SITE FOR CONSTRUCTION PURPOSES. WATER WILL BE AVAILABLE
FROM AREAS IDENTIFIED ACCEPTABLE BY THE OWNER.
G. WARRANTY
1. CONTRACTOR TO OBTAIN WRITTEN WARRANTY FROM MANUFACTURER AND INSTALLER FOR PERIOD OF 5 YEARS FROM DATE
OF SUBSTANTIAL COMPLETION.
HISTORIC NOTES
1. ALL WORK TO BE COMPLETED IN ACCORDANCE WITH SECRETARY OF THE INTERIOR'S STANDARDS FOR REHABILITATION.
DESIGN CRITERIA
1. DEPARTMENT OF DEFENSE UNIFIED FACILITIES CRITERIA (UFC).
2. 2018 INTERNATIONAL BUILDING CODE (IBC).
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C T
N
O
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
P S
F
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I L E
A M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
G
U
N T
Y
C
A L I F
O R
N I A
F O
R
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R I
W
L L
R
E H
A B
I L I T
A T
I O
N
A
D
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i r s
H
L M
H
A H
L M
H
A H
G E
N E
R A
L
N
O T
E S
A-001
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
No. C80977
Exp.03/31/21
W P
L R
A d w g
10-15-2020
HISTORIC WEST BOUNDARY WALL 1
SEE A-101. REFER TO CD101, CS101, AND S-501
FOR ADDITIONAL INFORMATION.
HISTORIC WEST BOUNDARY WALL 2
SEE A-101. REFER TO CD101, CS101, AND S-501
FOR ADDITIONAL INFORMATION.
HISTORIC EAST BOUNDARY WALL
SEE A-102. REFER TO CD104 AND CS104 FOR ADDITIONAL INFORMATION.
3 SETS OF ACCESS STAIRS (SECTION E
AND OFFICER SECTION A)
SEE A-103. REFER TO CD102 AND
CS102 FOR ADDITIONAL INFORMATION
ROSTRUM
SEE A-106. REFER TO CS102 FOR
ADDITIONAL INFORMATION.
EAST MAIN ENTRANCE GATES
SEE A-105. REFER TO CD103 AND
CS103 FOR ADDITIONAL INFORMATION.
WEST MAIN ENTRANCE GATES
SEE A-104. REFER TO CD103 AND
CS103 FOR ADDITIONAL INFORMATION.
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
S I T
E
P
L A
N
AS100
SCALE: NTS
SITE PLAN
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
W P
L R
A
S d w
1'-0"
10"
8"
VARIES. REFER TO CIVIL DRAWINGS
1.5"
CONC WALL BELOW
A-101
A-101
TOP OF CONC WALL
CONC COLUMN AND
FINIAL
HISTORIC WEST BOUNDARY WALL 1 SCOPE OF WORK:
1. REPLACE WALL DUE TO STRUCTURAL FAILURE.
2. REPLACEMENT WALL TO MATCH ORIGINAL IN GEOMETRY, COLOR, AND OVERALL AESTHETIC.
3. REPLICATE AND REPLACE MISSING FINIALS AND CAPITALS.
4. INSTALL SEPARATION BETWEEN PLANTER/SOIL AND CONCRETE FOOTING AND WALL.
5. REDIRECT SPRINKLERS AND IRRIGATION AWAY FROM THE WALL.
6. REFER TO STRUCTURAL, CIVIL, AND LANDSCAPING DRAWINGS FOR ADDITIONAL INFORMATION.
HISTORIC WEST BOUNDARY WALL 2 SCOPE OF WORK:
1. REPLACE WALL DUE TO EXTENSIVE DISTRESS AND FAILURE.
2. REPLACEMENT WALL TO MATCH ORIGINAL IN GEOMETRY, COLOR, AND OVERALL AESTHETIC.
3. REPLICATE AND REPLACE MISSING FINIALS AND CAPITALS.
4. REDIRECT SPRINKLERS AND IRRIGATION AWAY FROM WALLS.
5. REFER TO STRUCTURAL, CIVIL, AND LANDSCAPING DRAWINGS FOR ADDITIONAL INFORMATION.
A-101
10"
1'-0"
1"
8"
REFER TO CIVIL AND STRUCTURAL DRAWINGS FOR
FOOTING, GRADING, AND MOW CURB INFORMATION
CONC WALL. MATCH
COLOR, FINISH AND
TEXTURE AS
EXISTING
TOP OF CONC
WALL
V A
R I E
S
R
E F
C
I V
I L
A
R
U C
T U
R A
L
D
R A
W I N
G S
REFER TO STRUCTURAL
DRAWINGS FOR WALL
REINFORCING
V A
R I E
S
CONC FINIAL AT
TOP OF COLUMN
CONC WALL EITHER SIDE
OF COLUMN, LOCATION
VARIES. SEE STRUCTURAL
AND CIVIL DRAWINGS
CONC COLUMN. MATCH
COLOR, FINISH AND
TEXTURE AS EXISTING
V A
R I E
S
R
E F
C
I V
I L
A
R
U C
T U
R A
L
D
R A
W I N
G S
REFER TO CIVIL AND STRUCTURAL DRAWINGS FOR
FOOTING, GRADING, AND MOW CURB INFORMATION
REFER TO STRUCTURAL
DRAWINGS FOR COLUMN
REINFORCING
REFER TO CIVIL AND STRUCTURAL
DRAWINGS FOR FOOTING, GRADING,
AND MOW CURB INFORMATION
VARIES. REFER TO CIVIL DRAWINGS
V A
R I E
S
V A
R I E
S
V A
R I E
S
R
E F
C
I V
I L
A
R
U C
T U
R A
L
D
R A
W I N
G S
CONC COLUMN
TOP OF CONC
WALL
CONC FINIAL
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
H I S
T O
R
S
T
B
O U
N D
A R
Y
W
A L L
A
A-101
SCALE: 1 1/2" = 1'-0"
PLAN DETAIL OF REBUILT WEST BOUNDARY WALLS 1 AND 2
SCALE: 1 1/2" = 1'-0"
SECTION AT WALL
SCALE: 1 1/2" = 1'-0"
SECTION AT COLUMN
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
SCALE: 1 1/2" = 1'-0"
ELEVATION AT WALL
W P
L R
A d w
SCOPE OF WORK
1. REPLICATE AND REPLACE MISSING FINIALS.
2. REPAIR CORROSION RELATED DISTRESS AND DETERIORATION AT WALL. SEE DETAILS 1, 2, 3, 4, AND 5 ON A-503. CONTRACTOR TO IDENTIFY REPAIR LOCATIONS AND CONFIRM WITH
ARCHITECT/ENGINEER PRIOR TO REMOVAL.
3. REMOVE LOOSE AND DELAMINATED CONCRETE AT AREAS OF SCALING; SOUND SUBSTRATE TO REMAIN.
4. REDIRECT SPRINKLERS AND IRRIGATION AWAY FROM WALLS.
5. CLEAN ORGANIC GROWTH FROM WALL.
6. REFER TO CS104 FOR ADDITIONAL INFORMATION.
REPAIR CORROSION RELATED DISTRESS AND DETERIORATION AT WALL. SEE DETAILS 1, 2, 3, 4, AND 5 ON A-503. CONTRACTOR TO IDENTIFY REPAIR LOCATIONS AND CONFIRM WITH
REMOVE LOOSE AND DELAMINATED CONCRETE AT AREAS OF SCALING; SOUND SUBSTRATE TO REMAIN.
STAINING AND
ORGANIC GROWTH.
CLEAN PER A-503
SPALLED CONCRETE
AND EXPOSED
REINFORCEMENT.
REPAIR PER A-503
CONCRETE SURFACE
SCALING. REMOVE LOOSE
AND DELAMINATED
CONCRETE; SOUND
SUBSTRATE TO REMAIN.
SEE CIVIL DRAWINGS
FOR SWALE REPAIRS ORGANIC GROWTH.
DELAMINATED AND CRACKED
CONCRETE. REPAIR PER A-503
CONCRETE SURFACE SCALING.
REMOVE LOOSE AND
DELAMINATED CONCRETE;
SOUND SUBSTRATE TO REMAIN.
PREVIOUS
REPAIRS/REPLACEMENT
SPALLED CONCRETE AND EXPOSED
REINFORCEMENT AT CAP EDGE.
REPAIR PER 5/A-503
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
H I S
T O
R
S
T
B
O U
N D
A R
Y
W
A L L
A-102
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
NTS
EAST BOUNDARY WALL PARTIAL WEST ELEVATION
SCALE: NTS
EAST BOUNDARY WALL PARTIAL EAST ELEVATION
SCALE: NTS
EAST BOUNDARY WALL TYPICAL CONDITIONS
SCALE: NTS
EAST BOUNDARY WALL TYPICAL
CONCRETE CONDITIONS
SCALE: NTS
EAST BOUNDARY WALL TYPICAL PREVIOUS
REPAIR CONDITION
SCALE: NTS
EAST BOUNDARY WALL CAP EDGE CONDITION
W P
L R
A d w
REMOVE AND REPLACE ACCESS STAIR AND RAILING.
SALVAGE EXIST RAILING FOR HISTORIC RECORDS. SEE
3/A-103
REMOVE AND REPLACE ACCESS STAIR AND RAILING.
SALVAGE EXIST RAILING FOR HISTORIC RECORDS. SEE
4/A-103
REMOVE AND REPLACE ACCESS STAIR AND RAILING.
SALVAGE EXIST RAILING FOR HISTORIC RECORDS. SEE
6/A-103
1'-2", TYP
T Y
P
1'-8
1'-9"
EXIST CURB TO
REMAIN
EXIST ROAD TO
REMAIN
8"
SET TOP OF STAIR
FLUSH WITH EXIST
CURB
" WIDE
EXPANSION JOINT.
SEE 8/A-103
V I F
#3 NOSING BAR,
TYP. 1" COVER
NEW CONC STAIR
ON GRADE WITH
SLIP RESISTANT
CONC FINISH
RADIUS
" MAX
2% TYP
#4 AT 12" OC, EW
BOTTOM AND END OF
CHEEK WALL (BEYOND)
NEW COATED 1-1/2" DIA (OUTSIDE)
PIPE RAILING (BEYOND). MATCH
EXIST AESTHETICS. BEND PIPE AT
JOINTS TO MATCH EXIST
1'-2" MIN
EQEQ
WEEP HOLE AT
POST BASE, TYP
8"
T
Y
P
ANTI-SLIP GROOVED
NOSE, TYP. SEE 9/A-103
A-103
INSTALL ADDITIONAL POST
HALFWAY BETWEEN TOP AND
BOTTOM POSTS
90 DEGREE ELBOW PIPE FITTING AT TOP OF
STAIR, ONE LOCATION PER RAILING
12" MIN
7"
DO NOT EXTEND
RAILING INTO ROAD
RE-GRADE FLUSH
WITH NEW STAIR
NEW CONCRETE
CHEEK WALL (BEYOND)
EXIST GRADE
ELEVATION
NOTE: DO NOT DISTURB ADJACENT BURIAL
SITES. CONFIRM LAYOUT AND EXTENT OF
ADJACENT BURIAL SITES PRIOR TO EXCAVATION.
7"
EXIST ROAD TO
REMAIN.
REPAIR AS
NECESSARY
TO INSTALL
DETAIL
1'-1
" VIF
1'-0", TYP
T Y
P
1'-0"
NEW COATED 1-1/2" DIA (OUTSIDE) PIPE RAILING (BEYOND). MATCH
EXIST AESTHETICS. BEND PIPE AT JOINTS TO MATCH EXIST
NEW
CONCRETE
CHEEK WALL
(BEYOND)
SET FLUSH WITH
EXIST ROAD
FACE OF EXIST STONE
WALL (BEYOND). ALIGN
NEW CHEEK WALL WITH
WALL TO MATCH EXIST
" WIDE EXPANSION
JOINT. SEE 8/A-103
#3 NOSING
BAR, TYP.
1" COVER
NEW CONC STAIR ON
GRADE WITH SLIP
RESISTANT CONC FINISH
RADIUS
" MAX
BOTTOM AND END OF
CHEEK WALL (BEYOND)
2% TYP
8"
V
I F
8"
RE-GRADE
FLUSH WITH
NEW STAIR
EXIST GRADE
ELEVATION
#4 AT 12" OC, EW
6"
WEEP HOLE AT
POST BASE, TYP
T
Y
P
ANTI-SLIP GROOVED
NOSE, TYP. SEE 9/A-103
A-103
90 DEGREE ELBOW PIPE
FITTING AT TOP OF STAIR, ONE
LOCATION PER RAILING
12" MIN
7"
NOTE: DO NOT DISTURB ADJACENT BURIAL
SITES. CONFIRM LAYOUT AND EXTENT OF
ADJACENT BURIAL SITES PRIOR TO EXCAVATION.
SHIFT ENTIRE STAIR 12" FROM EXIST LOCATION,
LENGTHENING BOTTOM LANDING. NOTIFY
ARCHITECT/ ENGINEER IF SHIFTED STAIR WILL
DISTURB ADJACENT BURIAL SITES.
1'-0"
ALIGN EDGE OF RAILING
WITH EDGE OF CHEEK WALL
BELOW. DO NOT EXTEND
RAILING INTO ROAD
7"
1'-3
1'-2", TYP
T Y
P
1'-2"
EXIST CURB TO
REMAIN
EXIST ROAD TO
REMAIN
#3 NOSING BAR,
TYP. 1" COVER
NEW CONC STAIR ON
GRADE WITH SLIP
RESISTANT CONC FINISH
INSTALL TWO ADDITIONAL POSTS
AT THIRD POINTS BETWEEN TOP
AND BOTTOM POSTS
NEW CONCRETE
CHEEK WALL (BEYOND)
EXIST GRADE ELEVATION
SET TOP OF STAIR
FLUSH WITH EXIST
CURB
" WIDE
EXPANSION JOINT.
SEE 8/A-103
RADIUS
" MAX
8"
2% TYP
8"
V I F
BOTTOM AND END OF
CHEEK WALL (BEYOND)
#4 AT 12" OC, EW
7'-8"
RE-GRADE FLUSH WITH
NEW STAIR
7" 7"
EQEQ
NEW COATED 1-1/2" DIA (OUTSIDE) PIPE
RAILING. MATCH EXIST AESTHETICS
#4 AT 12"
OC, EW
V A
R I E
S
TOP OF STAIR TREAD
BENT #4 DOWEL AT 12" OC,
WITH PLASTIC SLEEVE IN
STAIR SLAB, 12" EMBED
" WIDE EXPANSION JOINT,
BOTH SIDES. SEE 8/A-103
CONC CHEEK WALL
BENT #4 DOWEL INTO BOTTOM
STAIR FOOTING, WITH PLASTIC
SLEEVE IN FOOTING, 12" EMBED
(BEYOND) (SIM AT TOP FOOTING)
BOTTOM STAIR
FOOTING (BEYOND)
COMPACTED AGGREGATE BASE.
REFER TO SPECIFICATION FOR
MORE INFORMATION
COMPACTED FILL. REFER TO
SPECIFICATIONS FOR MORE
INFORMATION
SEALANT
BACKER ROD
EXPANSIVE
MATERIAL
1'-2" MIN
EQ EQ
WEEP HOLE AT
POST BASE, TYP
MATCH EXIST GRADE
ELEVATION, BOTH SIDES
T
Y
P
NEW COATED 1-1/2" DIA (OUTSIDE)
PIPE RAILING (BEYOND). MATCH EXIST
AESTHETICS. BEND PIPE AT JOINTS TO
MATCH EXIST
ANTI-SLIP
GROOVED
NOSE, TYP.
SEE 9/A-103
A-103
(4) TROWELLED-IN TACTILE
V-SHAPED GROOVES,
DEEP, SPACED AT
" ON
CENTER. EXTEND FULL
WIDTH OF EACH STAIR
CONCRETE STAIR
NOSING BAR
COAT EDGE OF STAIR
AT GROOVES, COLOR
TO BE SELECTED BY
OWNER
6" DEEP PREFORMED OR CORE
DRILLED POST HOLE. SET POST
IN NON-SHRINK GROUT.
90 DEGREE ELBOW PIPE FITTING AT TOP OF
STAIR, ONE LOCATION PER RAILING
12" MIN
7"
ALIGN EDGE OF RAILING WITH EDGE OF STAIR
BELOW. DO NOT EXTEND RAILING INTO ROAD
NOTE: DO NOT DISTURB ADJACENT BURIAL
SITES. CONFIRM LAYOUT AND EXTENT OF
ADJACENT BURIAL SITES PRIOR TO EXCAVATION.
7"
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
A C
C E
A
I R
S
A-103
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
SCALE: 1" = 1'-0"
NORTHWEST ACCESS STAIR EXISTING CONDITION
SCALE: 1" = 1'-0"
SOUTH ACCESS STAIR EXISTING CONDITION
SCALE: 1" = 1'-0"
NORTHEAST ACCESS STAIR EXISTING CONDITION
SCALE: 3/4" = 1'-0"
SECTION AT NEW SOUTH ACCESS STAIR
SCALE: 3/4" = 1'-0"
SECTION AT NEW NORTHWEST ACCESS STAIR
SCALE: 3/4" = 1'-0"
SECTION AT NEW NORTHEAST ACCESS STAIR
SCALE: NTS
TYPICAL EXPANSION JOINT
SCALE: 3/4" = 1'-0"
TYPICAL STAIR SECTION
SCALE: NTS
TYPICAL ANTI-SLIP
GROOVED NOSE
W P
L R
A d w
EAST ELEVATION OF WEST ENTRANCE GATE NORTHERN PORTION OF WEST ENTRANCE GATE (WEST ELEVATION)SOUTHERN PORTION OF WEST ENTRANCE GATE (SOUTH ELEVATION)
SCOPE OF WORK (SEE DASHED LINES FOR EXTENT OF WORK):
1. REMOVE 100% OF EXIST COATING FROM ALL CONC GATE COMPONENTS, INCLUDING ALL SIDES OF COLUMNS AND WALLS. SEE 1/A-502. REMOVE 100% OF EXIST COATING FROM
STEEL GATE COMPONENTS TO REMAIN.
2. SURVEY EXPOSED CONC FOR DISTRESS OR DAMAGE (VISUAL AND HAMMER SOUNDING). REPAIR AS NEEDED. SEE DETAILS 1, 2, 3, 4, AND 8 ON A-501.
3. REPLACE PREVIOUS CONC REPAIRS THAT ARE UNSOUND OR DO NOT MATCH TEXTURE OF ORIGINAL CONC. SEE DETAILS 1, 2, 3, 4, AND 8 ON A-501.
4. PATCH ALL EXIST FASTENER HOLES. SEE 5/A-502.
5. INSTALL NEW COATING AT CONC; COLOR TO BE SELECTED BY OWNER. SEE DETAILS 1, 2, 3, AND 4 ON A-502. INSTALL NEW COATING AT STEEL GATE COMPONENTS TO REMAIN.
TYP BLISTERING AND
PEELING OF COATING
TYP PEELING COATING
AT WALL COPING
PATCH ALL EXIST
FASTENER HOLES. SEE
5/A-502
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
W E
M
T
R A
N C
E
G
A T
E S
A-104
SCALE: NTS
WEST MAIN ENTRANCE GATE ELEVATION
SCALE: NTS
TYPICAL COATING CONDITION
SCALE: NTS
TYPICAL COATING CONDITION AT WALL COPING
SCALE: NTS
TYPICAL CONDITION AT EXISTING FASTENER HOLES
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
W P
L R
A d w
SCOPE OF WORK (SEE DASHED LINES FOR EXTENT OF WORK):
1. REMOVE 100% OF EXIST COATING FROM ALL CONC GATE COMPONENTS, INCLUDING ALL SIDES OF COLUMNS AND WALLS. SEE 1/A-502. REMOVE 100% OF EXIST
COATING FROM STEEL GATE COMPONENTS TO REMAIN.
2. SURVEY EXPOSED CONC FOR DISTRESS OR DAMAGE (VISUAL AND HAMMER SOUNDING). REPAIR AS NEEDED. SEE DETAILS 1, 2, 3, 4, AND 8 ON A-501.
3. REPLACE PREVIOUS CONC REPAIRS THAT ARE UNSOUND OR DO NOT MATCH TEXTURE OF ORIGINAL CONC. SEE DETAILS 1, 2, 3, 4, AND 8 ON A-501.
4. PATCH ALL EXIST FASTENER HOLES. SEE 5/A-502.
5. INSTALL NEW COATING; COLOR TO BE SELECTED BY OWNER. SEE DETAILS 1, 2, 3, AND 4 ON A-502. INSTALL NEW COATING AT STEEL GATE COMPONENTS TO REMAIN.
WEST ELEVATION OF EAST ENTRANCE GATE SOUTHERN PORTION OF EAST ENTRANCE GATE (WEST ELEVATION)NORTHERN PORTION OF EAST ENTRANCE GATE (WEST ELEVATION)
TYP SCALING AND
BLISTERING OF COATING
TYP SCALING AND
BLISTERING OF COATING
TYP BLISTERING OF COATING
PATCH ALL EXIST FASTENER HOLES.
SEE 5/A-502
REPLACE PREVIOUS REPAIRS (PERFORMED
BY OTHERS) THAT ARE UNSOUND OR DO NOT
MATCH TEXTURE OF ORIGINAL CONC (TYP).
SEE DETAILS 1, 2, 3, 4, AND 8 ON A-501.
TYP CRACKING AND
DELAM OF CONC
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
E A
T
R A
N C
E
G
A T
E S
A-105
SCALE: NTS
EAST MAIN ENTRANCE GATE ELEVATION
SCALE: NTS
TYPICAL COATING BLISTERING AND SCALING 2
SCALE: NTS
TYPICAL COATING BLISTERING AND SCALING
SCALE: NTS
TYPICAL COATING BLISTERING
SCALE: NTS
TYPICAL EXISTING FASTENER HOLES
SCALE: NTS
TYPICAL PREVIOUS CONCRETE REPAIR
SCALE: NTS
TYPICAL CRACKING AND DELAMINATION OF CONC
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
W P
L R
A d w
REMOVE 100% OF EXIST COATING FROM ALL STUCCO
COMPONENTS, INCLUDING BACKSIDE OF WALLS AND BENCH,
TO EXPOSE EXIST STUCCO AND CONCRETE, SEE 1/A-502.
SURVEY EXPOSED STUCCO AND CONC FOR DISTRESS OR
DAMAGE AND REPAIR AS NEEDED, SEE DETAILS 1, 9, 10, AND
11 ON A-501. INSTALL NEW COATING; COLOR TO BE
SELECTED BY OWNER, SEE DETAILS 1, 2, 3, AND 4 ON A-502.
REMOVE EXIST MEMBRANE AT
HORIZONTAL SURFACES, INCLUDING AT
STEPS AND MAIN SLAB AREA. SURVEY
EXPOSED CONC FOR DISTRESS OR
DAMAGE AND REPAIR AS NEEDED PER
6/A-502. INSTALL NEW MEMBRANE; COLOR
TO BE SELECTED BY OWNER. SEE 7/A-502,
8/A-502, AND 9/A-502.
A-106
A-106
A-502
TYP.
BASE OF WALL
A-502
TYP.
SEE CS102 FOR
LOCATIONS AND
DETAILS OF NEW DRAIN
PIPES THROUGH WALLS
STUCCO DISTRESS AND CRACKING AT EXIST
BENCH, TYP
TYP CRACKING AT EXIST BENCH
TYP AREA OF STUCCO DELAMINATIONTYP STUCCO CRACKING
TYPICAL CONC SLAB DISTRESS
UNDER EXIST MEMBRANE
TYPICAL MEMBRANE CRACKINGTYPICAL STUCCO
DISTRESS/CRACKING
EXIST STUCCO-CLAD BENCH
BRACKETS, 4 INCH WIDE
EXIST COATED CONC BENCH
EXIST STUCCO-CLAD WALL
EXIST CONC SLAB
EXIST PLANTER
REPAIR STUCCO AND CONC
DISTRESS PER 11/A-501
EXIST COATED
CONC BENCH
EXIST CONC SLAB
EXIST STUCCO-CLAD
WALL
EXIST STUCCO-CLAD
BENCH BRACKET.
REPAIR STUCCO AND
CONC DISTRESS
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
R O
S T
R U
M
A-106
SCALE: NTS
ROSTRUM ELEVATION
SCALE: NTS
TYPICAL STUCCO DISTRESS UNDER BENCH
SCALE: NTS
TYPICAL CRACKING AT BENCH
SCALE: NTS
TYPICAL STUCCO DELAMINATION
SCALE: NTS
TYPICAL STUCCO CRACKING
SCALE: NTS
TYPICAL MEMBRANE DISTRESS
SCALE: NTS
TYPICAL STUCCO DISTRESS
AND MEMBRANE CRACKING
SCALE: 1" = 1'-0"
ROSTRUM BENCH AND BACK WALL SECTION
SCALE: 1" = 1'-0"
ROSTRUM BENCH AND BACK WALL ELEVATION
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
W P
L R
A d w
" MIN
REPAIR FLUSH WITH EXISTING CONCRETE UNLESS
OTHERWISE DIRECTED BY ARCHITECT/ENGINEER.
SUPPLEMENTAL
INCH S.S. THREADED ROD SET IN
EPOXY ADHESIVE WITH MIN 3 INCH EMBED (TYP),
SEE 5/A-501. ARCHITECT/ENGINEER TO CONFIRM
LOCATION OF SUPPLEMENTAL RODS. ASSUMED 2
RODS PER REPAIR AREA.
EXISTING REINFORCING BARS. IF EXPOSED, ABRASIVELY
CLEAN AND COAT WITH CORROSION INHIBITING COATING.
CUT ENDS OF STRAIGHT BARS TO PROVIDE MIN. 1
INCH
OF CLEAR COVER. DO NOT CUT HOOKED BARS.
NEW COATING
INCH DEEP SAW CUT AROUND PERIMETER OF
REPAIR AREA
4" MIN
REPAIR FLUSH WITH EXISTING
CONCRETE UNLESS
OTHERWISE DIRECTED BY
ARCHITECT/ENGINEER.
EXISTING REINFORCING BARS.
(ABRASIVELY CLEAN AND COAT
WITH CORROSION INHIBITING
COATING WHERE EXPOSED).
CUT ENDS OF STRAIGHT BARS
TO PROVIDE MIN 1
INCH OF
CLEAR COVER. DO NOT CUT
HOOKED BARS.
REMOVE CONCRETE TO A MIN
DEPTH OF
INCH CLEAR BEHIND
EXISTING REINFORCING BARS
OR 4 INCH MIN TOTAL DEPTH,
WHICHEVER IS GREATER.
INCH DEEP SAW CUT
AROUND PERIMETER OF
REPAIR AREA.
SUPPLEMENTAL L-SHAPED
INCH S.S. THREADED RODS
SET IN EPOXY ADHESIVE
WITH MIN 3 INCH EMBED AT
8-INCH OC (TYP), SEE 5/A-501.
" MIN COVER.
NEW COATING
8" +/- VIF
NEW COATING
REMOVE UNSOUND AND SOUND CONC FROM
REPAIR AREA. RESTORE ORIGINAL
CROSS-SECTION USING FORMED REPAIR CONC
REPAIR CONCRETE FLUSH WITH EXISTING
CONCRETE UNLESS OTHERWISE DIRECTED BY
ARCHITECT/ENGINEER.
ABRASIVE BLAST AND AIRBLAST EXPOSED
CONCRETE SURFACES WITHIN PATCH AREA
INCLUDING SAW CUT EDGES
EXIST REINFORCING BARS. (ABRASIVE BLAST
CLEAN AND PAINT WITH CORROSION
INHIBITING COATING WHERE EXPOSED)
SUPPLEMENTAL #3 EPOXY COATED
REINFORCING BAR SET IN EPOXY ADHESIVE
WITH MIN 4 INCH EMBED, SEE 5/A-501. ASSUME
12-INCH OC BOTH DIRECTIONS (TYP)
INCH DEEP SAW CUT AROUND PERIMETER OF
REPAIR AREA.
REMOVE CONCRETE TO A MIN DEPTH OF
INCH
CLEAR BEHIND EXISTING REINFORCING BARS OR 4
INCH MIN TOTAL DEPTH, WHICHEVER IS GREATER
4" MIN
MIN
INCH ON CONCRETE, STUCCO, OR MASONRY
MIN
INCH ON METAL OR GLASS
MIN
INCH TO
INCH FOR SILICONE SEALANTS
MIN
INCH TO
INCH FOR URETHANE SEALANTS
PROVIDE AN "HOURGLASS" PROFILE WHERE POSSIBLE (B>T)
PROVIDE MIN 2:1 LENGTH TO THICKNESS RATIO (H:T)
"B" BOND LINE
"T" SEALANT THICKNESS
SEALANT BEAD PROFILE
SEALANT CHART
W D
INCH
TO
INCH
TO 1 INCH
GREATER THAN 1 INCH
INCH
INCH
W/2
W/2
D
W
DRILL HOLE PER ADHESIVE MANUFACTURER'S
RECOMMENDATIONS AND REQUIREMENTS. CLEAN
HOLE THOROUGHLY WITH CLEAN COMPRESSED AIR
AND STIFF WIRE BRUSH TO REMOVE ALL DUST AND
DEBRIS PRIOR TO DOWEL INSTALLATION PER
MANUFACTURER'S REQUIREMENTS.
#3 EPOXY COATED STEEL REINFORCING BAR OR
1/4-INCH DIA STAINLESS STEEL DOWEL. SET USING
EPOXY ADHESIVE INTO EXISTING CONCRETE.
4" MIN
(UON)
NOTES:
1. CLEAN ALL MACHINING OIL, RESIDUE, OR OTHER
SURFACE CONTAMINANTS FROM DOWEL THAT
MAY INHIBIT BOND WITH EPOXY ADHESIVE.
2. INSTALL AT LOCATIONS DESIGNATED BY
ARCHITECT/ENGINEER.
4" MIN
REPAIR FLUSH WITH EXISTING
CONCRETE UNLESS
OTHERWISE DIRECTED BY
ARCHITECT/ENGINEER.
EXISTING REINFORCING BARS.
(ABRASIVELY CLEAN AND COAT
WITH CORROSION INHIBITING
COATING WHERE EXPOSED).
CUT ENDS OF STRAIGHT BARS
TO PROVIDE MIN 1
INCH OF
CLEAR COVER. DO NOT CUT
HOOKED BARS.
REMOVE CONCRETE TO A MIN
DEPTH OF
INCH CLEAR BEHIND
EXISTING REINFORCING BARS OR
4 INCH MIN TOTAL DEPTH,
WHICHEVER IS GREATER.
INCH DEEP SAW CUT
AROUND PERIMETER OF
REPAIR AREA.
SUPPLEMENTAL L-SHAPED
INCH S.S. THREADED
RODS SET IN EPOXY
ADHESIVE WITH MIN 3 INCH
EMBED AT 8-INCH OC (TYP),
SEE 5/A-501
NEW COATING
EXIST ONE-COAT STUCCO TO
REMAIN
EXIST ONE-COAT STUCCO
TO REMAIN
NEW DIRECT-APPLIED ONE-COAT
STUCCO. TEXTURED FINISH TO
MATCH EXIST
" MIN
REPAIR FLUSH WITH EXISTING CONCRETE UNLESS
OTHERWISE DIRECTED BY ARCHITECT/ENGINEER.
SUPPLEMENTAL
INCH S.S. THREADED ROD SET IN
EPOXY ADHESIVE WITH MIN 3 INCH EMBED (TYP),
SEE 5/A-501. ARCHITECT/ENGINEER TO CONFIRM
LOCATION OF SUPPLEMENTAL RODS. ASSUMED 2
RODS PER REPAIR AREA.
EXISTING REINFORCING BARS. IF EXPOSED, ABRASIVELY
CLEAN AND COAT WITH CORROSION INHIBITING COATING.
CUT ENDS OF STRAIGHT BARS TO PROVIDE MIN. 1 1/2" OF
CLEAR COVER. DO NOT CUT HOOKED BARS.
NEW COATING
INCH DEEP SAW CUT AROUND PERIMETER OF
REPAIR AREA
EXIST ONE-COAT STUCCO TO REMAIN
NEW DIRECT-APPLIED ONE-COAT STUCCO.
TEXTURED FINISH TO MATCH EXIST
REMOVE CONCRETE TO A MIN DEPTH OF
INCH
CLEAR BEHIND EXISTING REINFORCING BARS OR 4
INCH MIN TOTAL DEPTH, WHICHEVER IS GREATER
4" MIN
NEW COATING
REPAIR CONCRETE FLUSH WITH EXISTING
CONCRETE UNLESS OTHERWISE DIRECTED BY
ARCHITECT/ENGINEER.
ABRASIVE BLAST AND AIRBLAST EXPOSED
CONCRETE SURFACES WITHIN PATCH AREA
INCLUDING SAW CUT EDGES
EXIST REINFORCING BARS. (ABRASIVE BLAST
CLEAN AND PAINT WITH CORROSION
INHIBITING COATING WHERE EXPOSED)
SUPPLEMENTAL #3 EPOXY COATED REINFORCING
BAR SET IN EPOXY ADHESIVE WITH MIN 4" EMBED,
SEE 5/A-501. ASSUME 12-INCH OC BOTH
DIRECTIONS (TYP)
INCH DEEP SAW CUT AROUND PERIMETER OF
REPAIR AREA.
NEW DIRECT-APPLIED ONE-COAT STUCCO.
TEXTURED FINISH TO MATCH EXIST
EXIST ONE-COAT STUCCO TO REMAIN
REMOVE UNSOUND AND SOUND CONC FROM
REPAIR AREA. RESTORE ORIGINAL
CROSS-SECTION USING FORMED REPAIR CONC
ROUT CRACK USING V-SHAPED GRINDER.
CLEAN AND PRIME CONCRETE.
EXISTING CRACK GREATER THAN 15 MILS OR PER
COATING MANUFACTURERS REQUIREMENTS
M
A X
NEW COATING
SECOND LIFT OF SEALANT. TOOL FLUSH WITH CONCRETE.
CLEAN EXCESS SEALANT FROM SIDES OF CONCRETE.
FIRST LIFT OF SEALANT. TOOL SEALANT CONCAVE.
CONCRETE REPAIR NOTES:
1. CONTRACTOR TO HAMMER SOUND ALL CONCRETE SURFACES IN WORK AREA AND MARK DELAMINATED AREAS. ARCHITECT/ENGINEER TO CONFIRM AREAS BEFORE REMOVAL. ASSUME 100 SF OF
PARTIAL DEPTH CONCRETE REPAIRS FOR BIDDING.
2. INSTALL SHORING AS REQUIRED.
3. REMOVE ALL LOOSE CONCRETE FROM THE DETERIORATED AREA.
4. MAKE A SAW CUT AROUND THE ENTIRE PERIMETER OF EACH AFFECTED AREA. THE SAW CUT SHALL BE MADE NO CLOSER THAN 2 INCHES TO THE PERIMETER OF THE AREA OF DETERIORATION.
THE CUT SHALL BE MADE TO A DEPTH OF 3/4 INCH, IF POSSIBLE. REMOVAL AREAS SHOULD BE RECTANGULAR IN SHAPE AND MADE WITH STRAIGHT LINES. IF THERE ARE AREAS AROUND THE
PERIMETER OF THE DETERIORATED AREAS WHERE STEEL REINFORCING IS CLOSER TO THE SURFACE THAN 3/4 INCH, THEN NO SAW CUT SHALL BE MADE IN THOSE AREAS. INSTEAD OF A SAW CUT, THE PERIMETER OF THE AREA SHALL BE CAREFULLY CHIPPED AWAY WITH A LIGHT DUTY CHIPPING HAMMER TO ACHIEVE AS CLOSE TO A SMOOTH UNIFORM EDGE AS POSSIBLE (I.E., SIMULATE A
SAW CUT PERIMETER).
5. CHIP AND REMOVE ALL LOOSE AND UNSOUND CONCRETE IN THE AREA BOUNDED BY THE SAW CUTS AND CHIPPING USING A CHIPPING HAMMER OF NOMINAL 15-LB CLASS OR LESS. CONTINUE TO
CHIP INTO THE UNDERLYING SOUND CONCRETE AND REMOVE IT TO A DEPTH OF AT LEAST 3/4 INCH BEHIND THE EXPOSED REINFORCING STEEL. TAKE CARE NOT TO EXCESSIVELY VIBRATE THE
EXPOSED REINFORCING WITH THE CHIPPING HAMMER, IN ORDER TO AVOID FRACTURING ANY OF THE CONCRETE THAT IS BONDED TO THE REINFORCEMENT OUTSIDE THE PERIMETER OF THE
PATCH.
6. ABRASIVELY BLAST AND CLEAN THE EXPOSED CONCRETE SURFACES WITHIN THE AREA OF THE PATCH. BE SURE TO ABRASIVELY BLAST AND CLEAN THE SAW CUT EDGES AROUND THE PERIMETER
OF THE PATCH.
7. CLEAN THE EXPOSED REINFORCING STEEL BY ABRASIVE BLAST AND CLEAN. REMOVE ALL RUST SCALE FROM THE PERIMETER OF ALL STEEL REINFORCING BARS. THE STEEL REINFORCING
SHOULD BE CLEANED DOWN TO GRAY METAL.
8. CAREFULLY INSPECT THE EXPOSED STEEL REINFORCING BARS FOR LOSS OF SECTION DUE TO CORROSION. THE INSPECTION SHOULD TAKE PLACE AFTER CLEANING OF THE STEEL REINFORCING.
ANY STEEL REINFORCING WITH MORE THAN 20 PERCENT LOSS OF SECTION SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER FOR POSSIBLE FURTHER REMEDIAL ACTION.
9. INSTALL SUPPLEMENTAL REINFORCING BARS AS REQUIRED BY REPAIR DETAILS OR AS OTHERWISE DIRECTED BY THE ARCHITECT/ENGINEER WITH 1
INCH MINIMUM CLEAR COVER.
10. IMMEDIATELY CLEAN THE ENTIRE AREA OF THE PATCH WITH HIGH PRESSURE, OIL FREE COMPRESSED AIR.
11. IMMEDIATELY COAT ALL EXPOSED STEEL REINFORCING WITH TWO COATS OF CORROSION INHIBITING COATING. TAKE CARE NOT TO GET ANY OF THE COATING ON THE SURROUNDING CONCRETE
SURFACES AS THIS WILL INTERFERE WITH CONCRETE BOND.
12. AS SOON AS THE COATING HAS CURED (AS RECOMMENDED BY MANUFACTURER), FORM AND PLACE THE REPAIR CONCRETE TO RESTORE THE PROFILE OF THE EXISTING SECTION WITHIN THE AREA
OF THE PATCH. IF DIRECTED BY THE ARCHITECT/ENGINEER, BUILD-OUT THE FORM WORK TO ACHIEVE AT LEAST 1 INCH OF COVER OVER THE EXPOSED STEEL REINFORCING.
13. INTERNALLY AND EXTERNALLY VIBRATE THE CONCRETE AS IT IS PLACED TO ACHIEVE PROPER CONSOLIDATION. VIBRATE PRE-BAGGED MATERIAL PER MANUFACTURERS REQUIREMENTS.
14. WET CURE CONCRETE FOR SEVEN DAYS AND PER PRE-BAGGED MANUFACTURERS REQUIREMENTS.
15. REMOVE THE FORMS AFTER CONCRETE HAS REACHED 75% OF SPECIFIED STRENGTH AND PER MANUFACTURERS REQUIREMENTS. CAREFULLY INSPECT THE PATCH FOR IMPROPER
CONSOLIDATION, CRACKING AROUND THE PERIMETER, OR DEBONDING OF THE NEW CONCRETE. IF THESE CONDITIONS EXIST, NOTIFY THE ARCHITECT/ENGINEER FOR POSSIBLE REMEDIAL ACTION
OR REPLACEMENT OF THE PATCH.
16. SOUND REPAIR AREAS TO CONFIRM INTEGRITY OF PATCH. UNSOUND AREAS MUST BE REMOVED AND REPAIRED.
17. PERFORM CRACK REPAIR AS NEEDED.
18. REMOVE EXISTING COATING FROM ENTIRE WALL SURFACE IN WORK AREA BY SCRAPING. DO NOT DAMAGE EXISTING CONCRETE. CLEAN EXISTING WALL SURFACE BY WARM, HIGH-PRESSURE
WATER RINSE, FOLLOWED BY HIGH PRESSURE AIR BLAST. PREPARE SURFACE AS PER COATING MANUFACTURERS RECOMMENDATIONS.
19. INSTALL TWO COATS OF NEW COATING ON WALL SURFACE IN WORK AREA PER MANUFACTURERS INSTRUCTIONS AND REQUIREMENTS.
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
C O
N C
R E
T
A I
R
O S
T R
U
T
Y
T
E S
A-501
SCALE: NTS
SHALLOW VERTICAL CONCRETE REPAIR DETAIL
SCALE: NTS
VERTICAL CORNER CONCRETE REPAIR DETAIL
SCALE: NTS
VERTICAL CONCRETE REPAIR DETAIL
SCALE: NTS
SEALANT PROFILES
SCALE: NTS
SEALANT CHART
SCALE: NTS
EPOXY ADHESIVE DOWEL DETAIL
SCALE: NTS
VERTICAL CORNER CONCRETE REPAIR
DETAIL WITH STUCCO CLADDING
SCALE: NTS
SHALLOW VERTICAL CONCRETE REPAIR
DETAIL WITH STUCCO CLADDING
SCALE: NTS
VERTICAL CONCRETE REPAIR
DETAIL WITH STUCCO CLADDING
SCALE: NTS
CONCRETE CRACK REPAIR DETAIL
SCALE: NTS
CONCRETE REPAIR NOTES AT ROSTRUM AND ENTRY GATES
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
W P
L R
A d w
TYPICAL COATING DETAILS NOTES:
1. GENERAL INSTALLATION EXTENTS OF THE COATING SYSTEM ARE AS SHOWN ON THE
ELEVATIONS.
2. COATING TERMINATIONS AND DETAILS AT JOINTS, CRACKS AND SIMILAR SHALL CONFORM THE
DETAILS HEREIN, OR MANUFACTURER DETAILS FOR ITEMS NOT SHOWN.
3. REFERENCE SPECIFIC MATERIALS, DRY MIL THICKNESS, AND SURFACE PREPARATION IN
SPECIFICATION.
4. COATING SYSTEM SHOWN WITH SINGLE LINES IN SUBSEQUENT DETAILS FOR CLARITY AND IS
NOT INTENDED TO ILLUSTRATE THICKNESS OR FINISH PROFILE.
TYPICAL COATING NOTES:
THESE NOTES SHALL APPLY TO ALL COATING WORK UNLESS OTHERWISE NOTED ON A SPECIFIC
DETAIL. THESE NOTES SERVE TO SUPPLEMENT THE SPECIFICATIONS. REFERENCE THE
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1. COATING TERMINATIONS AND DETAILS AT JOINTS, CRACKS AND SIMILAR SHALL CONFORM TO
THE DETAILS HEREIN, OR MANUFACTURER DETAILS FOR ITEMS NOT SHOWN. CONFIRM
REQUIREMENTS OF DETAILS/REQUIREMENTS HEREIN WITH COATING MANUFACTURER PRIOR
TO SUBMITTING BID. NOTIFY ENGINEER OF DISCREPANCIES BETWEEN THESE DRAWINGS AND
MANUFACTURER TYPICAL DETAILS OR WRITTEN INSTRUCTIONS. ENGINEER SHALL DETERMINE
WHICH REQUIREMENT(S) DO NOT PROCEED WITH WORK UNTIL RECEIVING DIRECTION FROM
ENGINEER.
2. REMOVE EXISTING POORLY-ADHERED COATING FROM CONCRETE ELEMENTS. EXTENTS OF
EXIST COATING REMOVAL TO BE DETERMINED DURING MOCKUPS.
3. CONFIRM CONCRETE OR CONCRETE REPAIRS HAVE APPROPRIATELY CURED AND ARE AT
MOISTURE LEVELS BELOW THE COATING MANUFACTURER'S REQUIREMENTS PRIOR TO
COATING.
4. PREPARE SURFACE TO PROFILE OF CSP 2 OR 3 FOR EXPOSED CONCRETE SURFACES.
5. PREPARE EXIST COATED SURFACES IN ACCORDANCE WITH SELECTED SURFACE
PREPARATION METHOD BASED ON MOCKUP RESULTS.
6. REMOVE LOOSE MATERIAL AND CLEAN SURFACES PER ASTM D4258.
7. REMOVE AND REPLACE, OR INSTALL JOINT SEALANTS PER 6/A-501 AND 7/A-501. ROUT AND
SEAL CRACKS AS SPECIFIED.
8. INSTALL COATING SYSTEM.
PREPARE EXIST AND NEW SURFACE AS DETERMINED BY MANUFACTURER
EXIST CONCRETE SUBSTRATE TO REMAIN OR NEW CONC REPAIR AREA
PRIMER COAT (AT LOCATIONS AS RECOMMENDED BY
MANUFACTURER AND CONFIRMED IN MOCKUP)
FIRST COAT
SECOND COAT
ROUT AND SEAL CRACK. SEE 8/A-501
DETAIL BASE COAT PRIOR TO FIRST COAT
CRACKS LESS THAN 15 MILS
NEW COATING SYSTEM
EXIST CONSTRUCTION JOINTS AND
CRACKS GREATER THAN 15 MILS
1 INCH EACH SIDE OF JOINT/CRACK, TYP
DETAIL BASE COAT PRIOR TO FIRST COAT
PATCH ALL EXIST FASTENER HOLES PER 5/A-502
NEW COATING SYSTEM
TRAFFIC COATING SYSTEM WITH BROADCAST
SAND AT HORIZ SURFACES AND STAIRS
REMOVE EXIST SURFACE COATING. PREPARE
CONC SUBSTRATE AND PRIME AS REQUIRED BY
MANUFACTURER
CONC SUBSTRATE
NEW 1 INCH URETHANE SEALANT CANT AT
TRANSITIONS BETWEEN VERT AND HORIZ
SURFACES
TROWEL-APPLIED TRAFFIC COATING. EXTEND 4
INCH MIN ON VERT SURFACES. TOP COAT COLOR
TO MATCH EXIST COATING AT WALLS.
MANUFACTURER'S
INCH TERMINATION/COVE
STRIP
CONTINUOUS PAINTABLE URETHANE SEALANT
BEAD ALONG TOP EDGE OF TRAFFIC COATING
NEW SURFACE COATING AT EXIST PERIMETER
WALL. EXTEND OVER PAINTABLE URETHANE
SEALANT
EXIST PERIMETER WALL. REMOVE LOOSE AND
DEBONDED SURFACE COATING AND PERFORM
STUCCO REPAIR WORK, AS NECESSARY
1"
M
I N
TRAFFIC COATING SYSTEM WITH BROADCAST
SAND AT HORIZ SURFACES AND STAIRS
REMOVE EXIST SURFACE COATING. PREPARE
CONC SUBSTRATE AND PRIME AS REQUIRED BY
MANUFACTURER
CONC SUBSTRATE
NEW 1 INCH URETHANE SEALANT WITH BOND
BREAKER TAPE AT TRANSITIONS BETWEEN VERT
AND HORIZ SURFACES
1"
NEW TRAFFIC COATING
REMOVE ALL UNSOUND CONC AND
REPLACE WITH REPAIR MATERIAL.
RESTORE ORIGINAL CONC THICKNESS.
ABRASIVE BLAST AND AIRBLAST EXPOSED
CONCRETE SURFACES WITHIN PATCH AREA
INCLUDING SAW CUT EDGES
EXIST REINFORCING BARS.
ABRASIVE BLAST CLEAN AND
PAINT WITH CORROSION
INHIBITING COATING WHERE
EXPOSED. ADD SUPPLEMENTAL
REINFORCING AS DIRECTED BY
CONTRACTING OFFICER.
INCH DEEP SAW CUT AROUND
PERIMETER OF REPAIR AREA.
SAWCUT OR CHIP SQUARE THE
REMAINING EDGES OF THE
REMOVAL AREA TO NECESSARY
DEPTH. DO NOT DAMAGE EXIST
REINFORCING.
REMOVE CONCRETE TO A MIN
DEPTH OF
INCH CLEAR BELOW
EXIST REINFORCING BARS
EXPOSED DURING CHIPPING
REPAIR NOTES:
1. REMOVE ABANDONED MATERIAL FROM HOLE.
2. FLUSH OUT LOOSE MATERIAL WITH COMPRESSED AIR.
3. INSTALL TROWEL-APPLIED REPAIR MATERIAL IN 1/4" LIFTS UNTIL HOLE IS FILLED.
TOOL EACH LIFT WHEN IT IS "THUMBPRINT HARD". TOOL FINAL LIFT TO A SMOOTH,
CONCAVE FINISH. INSTALL A MINIMUM OF THREE LIFTS WITH EACH LIFT BEING NO
MORE THAN 1/4" DEEP.
4. IF HOLE IS LARGER THAN 2 INCHES IN DIAMETER OR WIDTH, REPAIR PER 3/A-501
ABANDONED ANCHOR HOLE.
VERIFY SIZE AND DEPTH IN FIELD
FILL EXIST ABANDONED ANCHOR
HOLE WITH CEMENTITIOUS
TROWEL-APPLIED REPAIR
MATERIAL IN
-INCH DEEP LIFTS
H O
L E
1"
TRAFFIC COATING SYSTEM WITH
BROADCAST SAND AT STAIR
CONC SUBSTRATE
NEW 1 INCH URETHANE SEALANT WITH BOND
BREAKER TAPE AT TRANSITIONS BETWEEN
VERT AND HORIZ SURFACES
EXIST MEMBRANE TO REMAIN
RETAIN 2" MIN OF EXIST MEMBRANE ON
VERTICAL FACE OF STAIR. CLEAN
MEMBRANE OF ALL DIRT AND DEBRIS, AND
PREPARE SUBSTRATE AS RECOMMENDED
BY TRAFFIC COATING MANUFACTURER. LAP
NEW MEMBRANE OVER THE EXIST
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
C O
N C
R E
A
T I N
G
D
E T
A I L S
A-502
SCALE: NTS
TYPICAL COATING NOTES
SCALE: NTS
TYPICAL COATING SYSTEM
SCALE: NTS
TYPICAL COATING DETAIL AT CRACKS
SCALE: NTS
TYPICAL COATING DETAIL AT
EXIST FASTENER HOLES
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
SCALE: NTS
TYPICAL TRAFFIC MEMBRANE VERT TO HORIZ
JOINT DETAIL
SCALE: NTS
TYPICAL TRAFFIC MEMBRANE CORNER BEAD DETAIL
SCALE: NTS
TYPICAL HORIZONTAL CONCRETE REPAIR DETAIL
SCALE: NTS
TYPICAL DETAIL AT EXISTING FASTENER HOLES
SCALE: NTS
TYPICAL TRAFFIC MEMBRANE TIE-IN DETAIL
W P
L R
A d w
CONCRETE REPAIR NOTES:
1. CONTRACTOR TO HAMMER SOUND ALL CONCRETE SURFACES IN WORK AREA AND MARK DELAMINATED AREAS. ARCHITECT/ENGINEER TO CONFIRM AREAS BEFORE REMOVAL. ASSUME 500 SF OF
PARTIAL DEPTH CONCRETE REPAIRS FOR BIDDING.
2. INSTALL SHORING AS REQUIRED.
3. REMOVE ALL LOOSE CONCRETE FROM THE DETERIORATED AREA.
4. MAKE A SAW CUT AROUND THE ENTIRE PERIMETER OF EACH AFFECTED AREA. THE SAW CUT SHALL BE MADE NO CLOSER THAN 2 INCHES TO THE PERIMETER OF THE AREA OF DETERIORATION.
THE CUT SHALL BE MADE TO A DEPTH OF 3/4 INCH, IF POSSIBLE. REMOVAL AREAS SHOULD BE RECTANGULAR IN SHAPE AND MADE WITH STRAIGHT LINES. IF THERE ARE AREAS AROUND THE
PERIMETER OF THE DETERIORATED AREAS WHERE STEEL REINFORCING IS CLOSER TO THE SURFACE THAN 3/4 INCH, THEN NO SAW CUT SHALL BE MADE IN THOSE AREAS. INSTEAD OF A SAW CUT, THE PERIMETER OF THE AREA SHALL BE CAREFULLY CHIPPED AWAY WITH A LIGHT DUTY CHIPPING HAMMER TO ACHIEVE AS CLOSE TO A SMOOTH UNIFORM EDGE AS POSSIBLE (I.E., SIMULATE A
SAW CUT PERIMETER).
5. CHIP AND REMOVE ALL LOOSE AND UNSOUND CONCRETE IN THE AREA BOUNDED BY THE SAW CUTS AND CHIPPING USING A CHIPPING HAMMER OF NOMINAL 15-LB CLASS OR LESS. CONTINUE TO
CHIP INTO THE UNDERLYING SOUND CONCRETE AND REMOVE IT TO A DEPTH OF AT LEAST 3/4 INCH BEHIND THE EXPOSED REINFORCING STEEL. TAKE CARE NOT TO EXCESSIVELY VIBRATE THE
EXPOSED REINFORCING WITH THE CHIPPING HAMMER, IN ORDER TO AVOID FRACTURING ANY OF THE CONCRETE THAT IS BONDED TO THE REINFORCEMENT OUTSIDE THE PERIMETER OF THE
PATCH.
6. ABRASIVELY BLAST AND CLEAN THE EXPOSED CONCRETE SURFACES WITHIN THE AREA OF THE PATCH. BE SURE TO ABRASIVELY BLAST AND CLEAN THE SAW CUT EDGES AROUND THE PERIMETER
OF THE PATCH.
7. CLEAN THE EXPOSED REINFORCING STEEL BY ABRASIVE BLAST AND CLEAN. REMOVE ALL RUST SCALE FROM THE PERIMETER OF ALL STEEL REINFORCING BARS. THE STEEL REINFORCING
SHOULD BE CLEANED DOWN TO GRAY METAL.
8. CAREFULLY INSPECT THE EXPOSED STEEL REINFORCING BARS FOR LOSS OF SECTION DUE TO CORROSION. THE INSPECTION SHOULD TAKE PLACE AFTER CLEANING OF THE STEEL REINFORCING.
ANY STEEL REINFORCING WITH MORE THAN 20 PERCENT LOSS OF SECTION SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER FOR POSSIBLE FURTHER REMEDIAL ACTION.
9. INSTALL SUPPLEMENTAL REINFORCING BARS AS REQUIRED BY REPAIR DETAILS OR AS OTHERWISE DIRECTED BY THE ARCHITECT/ENGINEER WITH 1
INCH MINIMUM CLEAR COVER.
10. IMMEDIATELY CLEAN THE ENTIRE AREA OF THE PATCH WITH HIGH PRESSURE, OIL FREE COMPRESSED AIR.
11. IMMEDIATELY COAT ALL EXPOSED STEEL REINFORCING WITH TWO COATS OF CORROSION INHIBITING COATING. TAKE CARE NOT TO GET ANY OF THE COATING ON THE SURROUNDING CONCRETE
SURFACES AS THIS WILL INTERFERE WITH CONCRETE BOND.
12. AS SOON AS THE COATING HAS CURED (AS RECOMMENDED BY MANUFACTURER), FORM AND PLACE THE REPAIR CONCRETE TO RESTORE THE PROFILE OF THE EXISTING SECTION WITHIN THE AREA
OF THE PATCH. IF DIRECTED BY THE ARCHITECT/ENGINEER, BUILD-OUT THE FORM WORK TO ACHIEVE AT LEAST 1 INCH OF COVER OVER THE EXPOSED STEEL REINFORCING.
13. INTERNALLY AND EXTERNALLY VIBRATE THE CONCRETE AS IT IS PLACED TO ACHIEVE PROPER CONSOLIDATION. VIBRATE PRE-BAGGED MATERIAL PER MANUFACTURERS REQUIREMENTS.
14. WET CURE CONCRETE FOR SEVEN DAYS AND PER PRE-BAGGED MANUFACTURERS REQUIREMENTS.
15. REMOVE THE FORMS AFTER CONCRETE HAS REACHED 75% OF SPECIFIED STRENGTH AND PER MANUFACTURERS REQUIREMENTS. CAREFULLY INSPECT THE PATCH FOR IMPROPER
CONSOLIDATION, CRACKING AROUND THE PERIMETER, OR DEBONDING OF THE NEW CONCRETE. IF THESE CONDITIONS EXIST, NOTIFY THE ARCHITECT/ENGINEER FOR POSSIBLE REMEDIAL ACTION
OR REPLACEMENT OF THE PATCH.
16. SOUND REPAIR AREAS TO CONFIRM INTEGRITY OF PATCH. UNSOUND AREAS MUST BE REMOVED AND REPAIRED.
17. PERFORM CRACK REPAIR AS NEEDED.
18. CLEAN STAINING AND ORGANIC GROWTH FROM CONCRETE SURFACE.
8" +/-
REMOVE UNSOUND AND SOUND CONC FROM
REPAIR AREA. RESTORE ORIGINAL
CROSS-SECTION USING FORMED REPAIR CONC
REPAIR CONCRETE FLUSH WITH EXISTING
CONCRETE UNLESS OTHERWISE DIRECTED BY
ARCHITECT/ENGINEER.
ABRASIVE BLAST AND AIRBLAST EXPOSED
CONCRETE SURFACES WITHIN PATCH AREA
INCLUDING SAW CUT EDGES
EXIST REINFORCING BARS. (ABRASIVE BLAST
CLEAN AND PAINT WITH CORROSION
INHIBITING COATING WHERE EXPOSED)
SUPPLEMENTAL #3 EPOXY COATED
REINFORCING BAR SET IN EPOXY ADHESIVE
WITH MIN 4 INCH EMBED, SEE 5/A-501. ASSUME
12-INCH OC BOTH DIRECTIONS (TYP)
INCH DEEP SAW CUT AROUND PERIMETER OF
REPAIR AREA.
REMOVE CONCRETE TO A MIN DEPTH OF
INCH
CLEAR BEHIND EXISTING REINFORCING BARS OR 4
INCH MIN TOTAL DEPTH, WHICHEVER IS GREATER
4" MIN
NOTE: CONC REPAIR TO MATCH ADJACENT
CONC COLOR, FINISH, AND TEXTURE
" MIN
REPAIR FLUSH WITH EXISTING CONCRETE UNLESS
OTHERWISE DIRECTED BY ARCHITECT/ENGINEER.
SUPPLEMENTAL
INCH S.S. THREADED ROD SET IN
EPOXY ADHESIVE WITH MIN 3 INCH EMBED (TYP),
SEE 5/A-501. ARCHITECT/ENGINEER TO CONFIRM
LOCATION OF SUPPLEMENTAL RODS. ASSUMED 2
RODS PER REPAIR AREA.
EXISTING REINFORCING BARS. IF EXPOSED, ABRASIVELY
CLEAN AND COAT WITH CORROSION INHIBITING COATING.
CUT ENDS OF STRAIGHT BARS TO PROVIDE MIN. 1
INCH
OF CLEAR COVER. DO NOT CUT HOOKED BARS.
INCH DEEP SAW CUT AROUND PERIMETER OF
REPAIR AREA
NOTE: CONC REPAIR TO MATCH ADJACENT
CONC COLOR, FINISH, AND TEXTURE
4" MIN
REPAIR FLUSH WITH EXISTING
CONCRETE UNLESS
OTHERWISE DIRECTED BY
ARCHITECT/ENGINEER.
EXISTING REINFORCING BARS.
ABRASIVELY CLEAN AND COAT
WITH CORROSION INHIBITING
COATING WHERE EXPOSED.
CUT ENDS OF STRAIGHT BARS
TO PROVIDE MIN 1
INCH OF
CLEAR COVER. DO NOT CUT
HOOKED BARS.
REMOVE CONCRETE TO A MIN
DEPTH OF
INCH CLEAR BEHIND
EXISTING REINFORCING BARS
OR 4 INCH MIN TOTAL DEPTH,
WHICHEVER IS GREATER.
INCH DEEP SAW CUT
AROUND PERIMETER OF
REPAIR AREA.
SUPPLEMENTAL L-SHAPED
INCH S.S. THREADED RODS
SET IN EPOXY ADHESIVE
WITH MIN 3 INCH EMBED AT
8-INCH OC (TYP), SEE 5/A-501.
" MIN COVER.
NOTE: CONC REPAIR TO MATCH ADJACENT
CONC COLOR, FINISH, AND TEXTURE
NOTE: CONC REPAIR TO MATCH ADJACENT
CONC COLOR, FINISH, AND TEXTURE
INCH DEEP SAW CUT
AROUND PERIMETER OF
REPAIR AREA.
REMOVE CONCRETE TO A MIN
DEPTH OF
INCH CLEAR BEHIND
EXISTING REINFORCING BARS OR
4 INCH MIN TOTAL DEPTH,
WHICHEVER IS GREATER.
SUPPLEMENTAL
INCH S.S.
THREADED ROD SET IN EPOXY
ADHESIVE WITH MIN 3 INCH EMBED
AT 8-INCH OC (TYP), SEE 5/A-501.
EXISTING REINFORCING BARS.
ABRASIVELY CLEAN AND COAT WITH
CORROSION INHIBITING COATING
WHERE EXPOSED. CUT ENDS OF
STRAIGHT BARS TO PROVIDE MIN 1
INCH OF CLEAR COVER. DO NOT CUT
HOOKED BARS.
REMOVE UNSOUND AND SOUND
CONC FROM REPAIR AREA. MATCH
EXIST GEOMETRY AND REPAIR
FLUSH WITH EXIST CONCRETE
UNLESS OTHERWISE DIRECTED BY
ARCHITECT/ENGINEER.
ABRASIVE BLAST AND AIRBLAST EXPOSED
CONCRETE SURFACES WITHIN PATCH AREA
INCLUDING SAW CUT EDGES
EXISTING NOSING REINFORCING
BARS (VIF). ABRASIVELY CLEAN AND
COAT WITH CORROSION INHIBITING
COATING WHERE EXPOSED.
SUPPLEMENT IF SECTION LOSS
EXCEEDS 15% OR AT DIRECTION OF
ARCHITECT/ENGINEER.
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
L O
S
A
N G
E L E
S
D
I S
T R
I C
T
L O
S
A
N G
E L E
S
C
A L I F
O R
N I A
F I
M
E
C A
D
F
I L E
A N
S I
D
S A
N
D
I E
U
N T
Y
C
A L I F
O R
N I A
F O
S
E C
R A
T
I O
N A
L
C
E M
E T
E R
Y
H I S
T O
R
L L
R
E H
A B
I L I T
A T
I O
N
A
T
E
I M
P R
O V
E M
E N
T S
U S
D e p a r t m e n t o f
V e t e r a n s
A f f a i
L M
H
A H
L M
H
A H
C O
N C
R E
T
A I
E
A S
T
B
O U
N D
A R
Y
W
A L L
A-503
SCALE: NTS
CONCRETE REPAIR NOTES AT EAST BOUNDARY WALL
SCALE: NTS
VERTICAL CONCRETE REPAIR
DETAIL AT EAST BOUNDARY WALL
SCALE: NTS
SHALLOW VERTICAL CONCRETE REPAIR
DETAIL AT EAST BOUNDARY WALL
SCALE: NTS
VERTICAL CORNER CONC REPAIR
DETAIL AT EAST BOUNDARY WALL
S
T
A
CA
L
I
F
O
R
N
I
A
R E G
I S
T
E
R
O
F
ESS
I O
N
G
I
N
E E R
C
I
V
R
R
SCALE: NTS
CAP EDGE CONCRETE REPAIR DETAIL AT
EAST BOUNDARY WALL
W P
L R
A d w
| Sheets and Views |
| A-001 GENERAL NOTES |
| NOTES |
| AS100 SITE PLAN |
| SITE PLAN |
| A-101 HISTORIC WEST BOUNDARY WALL 1 AND 2 |
| PLAN DETAIL OF REBUILT WALL |
| SECTION AT WALL |
| SECTION AT COLUMN |
| ELEVATION AT WALL |
| A-102 HISTORIC EAST BOUNDARY WALL |
| EAST BOUNDARY WALL PARTIAL WEST ELEVATION |
| EAST BOUNDARY WALL PARTIAL EAST ELEVATION |
| EAST BOUNDARY WALL TYPICAL CONDITIONS |
| EAST BOUNDARY WALL TYPICAL CONCRETE CONDITIONS |
| EAST BOUNDARY WALL TYPICAL PREVIOUS REPAIR CONDITION |
| EAST BOUNDARY WALL CAP EDGE CONDITION |
| A-103 ACCESS STAIRS |
| NORTHWEST ACCESS STAIR EXISTING CONDITION |
| SOUTH ACCESS STAIR EXISTING CONDITION |
| NORTHEAST ACCESS STAIR EXISTING CONDITION |
| SECTION AT NEW SOUTH ACCESS STAIR |
| SECTION AT NEW NORTHWEST ACCESS STAIR |
| SECTION AT NEW NORTHEAST ACCESS STAIR |
| A-104 WEST MAIN ENTRANCE GATES |
| WEST MAIN ENTRANCE GATE ELEVATION |
| TYPICAL COATING CONDITION |
| TYPICAL COATING CONDITION AT WALL COPING |
| TYPICAL CONDITION AT EXISTING FASTENER HOLES |
| A-105 EAST MAIN ENTRANCE GATES |
| EAST MAIN ENTRANCE GATE ELEVATION |
| TYPICAL COATING BLISTERING AND SCALING 2 |
| TYPICAL COATING BLISTERING AND SCALING |
| TYPICAL COATING BLISTERING |
| TYPICAL EXISTING FASTENER HOLES |
| TYPICAL PREVIOUS CONCRETE REPAIR |
| TYPICAL CRACKING AND DELAMINATION OF CONC |
| A-106 ROSTRUM |
| ROSTRUM ELEVATION |
| TYPICAL STUCCO DISTRESS UNDER BENCH |
| TYPICAL CRACKING AT BENCH |
| TYPICAL STUCCO DELAMINATION |
| TYPICAL STUCCO CRACKING |
| TYPICAL MEMBRANE DISTRESS |
| TYPICAL STUCCO DISTRESS AND MEMBRANE CRACKING |
| ROSTRUM BENCH AND BACK WALL SECTION |
| ROSTRUM BENCH AND BACK WALL ELEVATION |
| A-501 CONCRETE DETAILS AT ROSTRUM AND ENTRY GATES |
| SHALLOW VERTICAL CONCRETE REPAIR DETAIL |
| VERTICAL CORNER CONCRETE REPAIR DETAIL |
| VERTICAL CONCRETE REPAIR DETAIL |
| SEALANT PROFILES |
| SEALANT CHART |
| EPOXY ADHESIVE DOWEL DETAIL |