PRELEASE

FIRE PROTECTION AND LIFE SAFETY EVALUATION FOR AN OFFICE BUILDING

GENERAL SERVICES ADMINISTRATION PAGE 1 of 6 GSA FORM 12000 (May 2015)

The prelease form contains two parts that must be completed depending on which floor the proposed offered space is located within a building. Part A must be completed when an offered space is located below the 6th floor of a building.

Part A shall be completed by the Offeror or their authorized representative. Part B must be completed when an offered space is located on or above the 6th floor of a building. Part B shall be completed by a professional engineer. The Fundamental Code Requirements apply to Part A and Part B.

Fundamental Code Requirements

a. The offered building shall be evaluated for compliance with the most recent edition of the building and fire code adopted by the jurisdiction in which the building is located; with the exception that the technical egress requirements of the building shall be evaluated based on the egress requirements of the most recent edition of the National Fire Protection Association (NFPA) 101, Life Safety Code. (Note: a building with a Certificate of Occupancy indicating that a building fully complies with the International Building Code shall be deemed to comply with this requirement.) All areas that do not meet the above stated criteria shall be identified as to the extent that they do comply.

b. A fire escape located on the floor(s) where the offered space is located shall not be counted as an approved exit stair.

c. An interlocking or scissor stair located on the floor(s) where the offered space is located shall only count as one exit stair.

d. The number of floors used to determine when Part A or Part B is applicable is based on counting the number of floors starting from the street floor.

Exhibit H

GENERAL SERVICES ADMINISTRATION PAGE 2 of 6 GSA FORM 12000 (May 2015)

PART A

The Offeror or their representative shall complete Part A. Part A consists of a series of short answer and yes/no/not applicable questions related to general building information and fire protection and life safety systems. Upon completion of Part A, the Offeror must sign and date the “Offeror’s Statement”. Part A is applicable to offered space located below the 6th floor of the building.

I. BUILDING ADDRESS

Building Name:

Building Address:

City:

State:

9-Digit Zip Code:

II. GENERAL BUILDING INFORMATION

a. Identify each floor on which space is offered and the square footage of space on each floor offered to Government:

Floor

Sq. Ft. Per Floor

b. Identify the total number of floors in the building starting at the street floor:

c. Identify the total number of floors in the building below the street floor:

d. Identify which floor(s) in the building permit reentry from the exit stair enclosure to the interior of the building:

III. OTHER USES IN BUILDING (Check All That Apply)

Restaurants Laboratories Storage Retail Parking Garage

Other (list)

IV. AUTOMATIC FIRE SPRINKLER SYSTEM

Please Check YES, NO, or N/A to the following questions: YES NO N/A

a. a. Is an automatic fire sprinkler system installed throughout the building?

b. b. If automatic fire sprinklers are installed within the building, is the automatic fire sprinkler system maintained in accordance with the applicable local codes or NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems?

V. FIRE ALARM SYSTEM

Please Check YES, NO, N/A to the following questions: YES NO N/A

a. a. Is a fire alarm system installed in the building?

b. b. Is an emergency voice/alarm communication system installed in the building?

c. c. If a fire alarm system is installed in the building, are audible devices (e.g., horns, bells, speakers, etc.)

installed on the floor in which the offered space is located in the building?

d. d. If a fire alarm system is installed in the building, are strobe devices installed on the floor in which the offered space is located in the building?

e. e. If a fire alarm system is installed in the building, is the fire alarm system over 25 years old?

f. f. If a fire alarm system is installed in the building, does the operation of the fire alarm system automatically notify the local fire department via any of the following means: directly to the local fire department, to the (911) public communications center, to a central station, to a remote supervising station, or to a proprietary supervising station?

g. If a fire alarm system is installed in the building, is the fire alarm system maintained in accordance with the applicable local codes or NFPA 72, National Fire Alarm and Signaling Code?

GENERAL SERVICES ADMINISTRATION PAGE 3 of 6 GSA FORM 12000 (May 2015)

VI. EXIT SIGNS & EMERGENCY LIGHTING

a. a. Are exit signs installed in the paths of egress travel to the exit stairs or exits?

a. b. Is emergency lighting installed in the paths of egress travel to the exit stairs or exits?

b. c. If an emergency lighting system is installed in the building, is the emergency lighting system arranged to provide illumination automatically in the event of any interruption of the building’s normal lighting system?

VII. ELEVATORS

Are elevators installed in the building?

If elevators are installed in the building, are the elevator cars equipped with a telephone or another two-way communication system?

If elevators are installed in the building, are the elevators recalled by smoke detectors located in the elevator lobbies and elevator machine rooms?

VIII. ADDITONAL INFORMATION

OFFEROR’S STATEMENT

I hereby attest that the above information is complete and accurate to the best of my knowledge.

Signature: Date:

Printed Name:

Title:

Name of Firm:

GENERAL SERVICES ADMINISTRATION PAGE 4 of 6 GSA FORM 12000 (May 2015)

PART B

The Offeror’s professional engineer shall complete Part B when an offered space is located on the 6th floor or higher of a building. Part B consists of a detailed narrative report based on an evaluation of the entire building that also includes a walk-through of the building and the review of the preventive maintenance records of the building’s fire alarm system and automatic fire sprinkler system. The fire protection engineer shall prepare a detailed narrative report. The detailed narrative report shall address at a minimum the items noted below as they apply to the offered space in the building, with specific attention to fire safety conditions that affect the floor(s) where the offered space to the Government is located, including those floors located below the offered space. In addition, the detailed narrative report shall include all deficiencies that do not meet the specified criteria (see Fundamental Code Requirements), the associated code reference(s), as well as any recommended corrective action(s).

NOTES:

a. The professional engineer must be licensed as a fire protection engineer in the same State in which the subject building is located unless the subject State does not formally recognize fire protection engineering. In such cases, GSA will accept the services of any professional engineer in the subject State provided the professional engineer is also recognized as a fire protection engineer in any other U.S. State or Territory.

b. Upon completion of Part B, the Offeror’s fire protection engineer must sign and date the “Fire Protection Engineer Statement.”

c. Upon completion of Part B, the Offeror must sign and date the “Offeror’s “Statement of Correction.”

d. The accepted GSA Form 12000, Part B is valid for a time period of 5 years from the noted date on the completed and accepted Part B.

This acceptance is conditional in that no major modifications or construction has occurred associated with the building.

The detailed narrative report shall address at a minimum the items noted below as they apply to the offered space in the building.

1. General Information.

a. Identify all current citations or violations noted by the local jurisdiction regarding the building.

b. Provide digital pictures of the building. Include exterior views showing the front of the building and all sides of the building.

c. Identify the number of floors in the building (above and below grade).

d. Identify the approximate gross square footage per floor in the building.

e. Identify the gross square footage and associated floor of offered space proposed to the Government to occupy.

f. Identify by location and describe hazardous/significant fuel load areas (greater than normal for the type of occupancy).

g. Identify and describe potential fire ignition sources in hazardous/significant fuel load areas in the building.

2. Occupancy Classifications.

a. Identify all the different types of occupancies and particular uses on each floor of the subject building. For example, include retail, restaurants, mechanical equipment areas, storage areas, inside parking areas, etc.

3. Building Construction.

a. Identify the building construction type.

4. Vertical Openings.

a. Identify by location and describe the enclosure of vertical openings through floors, such as stairways, atriums, hoistways for elevators, escalators, and shafts.

b. Identify any deficiencies in the rated vertical enclosures that affect the integrity of the enclosure.

5. Means of Egress.

a. Identify the number of enclosed exit stairs on each floor of the building.

b. For each exit stair, describe:

i. The clear width of each stair tread and location of measurement.

ii. The egress capacity of each exit stair.

iii. The location of where each exit stair discharges.

iv. Identify and describe the operation and application of the exit stair re-entry provisions to the interior of the building, if provided.

GENERAL SERVICES ADMINISTRATION PAGE 5 of 6 GSA FORM 12000 (May 2015)

v. Any penetrations into and openings through each exit stair enclosure assembly.

vi. Any headroom obstruction within each exit stair enclosure.

vii. If any exit stair has been compromised in such a way to have the potential to interfere with its use as an exit; and

viii. The exit stair remoteness arrangement.

ix. Identify and describe if all exit stair doors are self-closing and self-latching.

c. Identify and describe all exit doors that do not swing in the direction of exit travel.

d. Identify and describe if all fire doors are in proper working order. Provide location of noted fire door and purpose.

e. Identify by floor and describe any concerns regarding the exit access system (i.e., corridor or open plan office concept), as it applies to the proposed offered space.

f. Identify by location and describe any concern regarding the exit signage within the building.

g. Describe the building’s emergency lighting system.

h. Identify and describe if emergency power is provided within the building.

i. If emergency power for life safety systems is provided by generator(s) or UPS systems describe if they are tested and maintained in accordance with NFPA 110, Standard for Emergency and Standby Power Systems or NFPA 111, Standard on Stored Electrical Energy

Emergency and Standby Power Systems as applicable. If not complying with the applicable NFPA Standards; identify and evaluate the procedures being used.

6. Automatic Fire Suppression Systems.

a. Identify and describe if the building is protected or not protected throughout by an automatic fire sprinkler system. If the building is not protected throughout by an automatic fire sprinkler system, identify those areas of the building where partial fire sprinkler protection is provided.

b. Identify and describe the different types of automatic fire sprinkler systems (e.g., dry, wet, pre-action, etc.) that are installed within the building and their respective locations.

c. Identify and describe any other fire suppression systems installed within the building.

d. Identify and describe the types of standpipes installed in the building.

e. If automatic fire sprinkler systems are installed in the building, describe if they are tested and maintained in accordance with the applicable local codes or NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. If not complying with the applicable NFPA Standards; identify and evaluate the procedures being used. If not complying with the applicable NFPA

Standard; identify and evaluate the procedures being used.

7. Fire Alarm System.

a. Identify and describe the fire alarm system, as a minimum, the date of installation, type, manufacturer and model, and components such as manual pull stations, etc.

b. Describe if the fire alarm system automatically notifies the local fire department via any of the following means: directly to the local fire department, to the (911) public communications center, to a central station, to a remote supervising station, or to a proprietary supervising station.

c. Describe in detail the operation of the fire alarm system, including if it has emergency voice/alarm communication capabilities.

d. Describe if the fire alarm system is tested and maintained in accordance with NFPA 72, National Fire Alarm and Signaling Code. If not complying with the applicable NFPA Standard; identify and evaluate the procedures being used.

8. Elevators.

a. Verify the elevators have a current certificate (date of inspection) of elevator inspection from the local jurisdiction.

b. Identify and describe the emergency recall operation features of the elevators. Describe all differences with the requirements of

ASME/A17.1, Safety Code for Elevators and Escalators, Phase I Emergency Recall Operation requirements.

c. Identify and describe the emergency in car operation features of the elevators. Describe all differences with the requirements of

ASME/A17.1, Safety Code for Elevators and Escalators, Phase II Emergency In-Car Operation requirements.

d. Identify and describe if the elevators are equipped with telephones or other two-way emergency signaling systems connected to an emergency communication location staffed 24 hours per day, 7 days per week.

GENERAL SERVICES ADMINISTRATION PAGE 6 of 6 GSA FORM 12000 (May 2015)

STATEMENT OF FIRE PROTECTION ENGINEER

I hereby attest that I have performed a full assessment of the subject premises; and that the above information is complete and accurate to the best of my knowledge. I have initialed at the bottom of each page. My official seal, professional license information, and signature are affixed below.

I have included findings, recommended corrective action(s), and made specific references to the applicable code sections as an attachment to this report. Such findings specifically identify instances where the building does not comply with the specified criteria, and recommendations have been made in order to rectify the situation and assure substantial compliance of the building to all applicable criteria.

(If no deficiencies were identified, during the evaluation, please explicitly state so in the findings and recommendations portion of the report.)

Name of Firm: Phone #: ( ) -

License Number:

Stamp Here:

OFFEROR’S STATEMENT OF CORRECTION

In the event any of the offered space does not meet the above criteria, the Offeror shall attest below that all work required to bring the offered space into full compliance with all applicable criteria will be completed at the Offeror's sole cost and expense prior to the Government's acceptance of the offered space under the terms of any prospective lease agreement.

NOTE: REPORTS SUBMITTED WITHOUT THE FPE’S FINDINGS, RECOMMENDED CORRECTIVE ACTIONS

AND CODE REFERENCES WILL BE RETURNED WITHOUT REVIEW BY THE GSA REGIONAL FIRE

PROTECTION ENGINEERING OFFICE.

Title:

Name of Firm:

Representation Regarding Certain Telecommunications and Video Surveillance Services or Equipment

See instructions within the representation regarding whether or not completion of this form is required If required, complete appropriate boxes, sign the form, and return form, along with any other required disclosure information, to LCO or his/her designee.

NOTE: The "Offeror," as used on this form, is the owner of the property offered, not an individual or agent representing the owner.

52.204-24 Representation Regarding Certain Telecommunications and Video Surveillance Services or Equipment (NOV 2021)

The Offeror shall not complete the representation at paragraph (d)(1) of this provision if the Offeror has represented that it "does not provide covered telecommunications equipment or services as a part of its offered products or services to the Government in the performance of any contract, subcontract, or other contractual instrument" in paragraph (c)(1) in the provision at 52.204-26, Covered Telecommunications Equipment or Services—Representation, or in paragraph (v)(2)(i) of the provision at 52.212-3, Offeror Representations and Certifications- Commercial Products or Commercial Services. The Offeror shall not complete the representation in paragraph (d)(2) of this provision if the Offeror has represented that it "does not use covered telecommunications equipment or services, or any equipment, system, or service that uses covered telecommunications equipment or services" in paragraph (c)(2) of the provision at 52.204-26, or in paragraph (v)(2)(ii) of the provision at 52.212-3.

(a) Definitions. As used in this provision—

Backhaul, covered telecommunications equipment or services, critical technology, interconnection arrangements, reasonable inquiry, roaming, and substantial or essential component have the meanings provided in the clause 52.204-25, Prohibition on Contracting for Certain Telecommunications and Video Surveillance Services or Equipment.

(b) Prohibition.

(1) Section 889(a)(1)(A) of the John S. McCain National Defense Authorization Act for Fiscal Year 2019 (Pub. L. 115-232) prohibits the head of an executive agency on or after August 13, 2019, from procuring or obtaining, or extending or renewing a contract to procure or obtain, any equipment, system, or service that uses covered telecommunications equipment or services as a substantial or essential component of any system, or as critical technology as part of any system. Nothing in the prohibition shall be construed to—

(i) Prohibit the head of an executive agency from procuring with an entity to provide a service that connects to the facilities of a third-party, such as backhaul, roaming, or interconnection arrangements; or

(ii) Cover telecommunications equipment that cannot route or redirect user data traffic or cannot permit visibility into any user data or packets that such equipment transmits or otherwise handles.

Representation Regarding Certain Telecommunications and Video

Surveillance Services or Equipment

REV (11/21)

Exhibit I https://www.acquisition.gov/far/part-52#FAR_52_204_26 https://www.acquisition.gov/far/part-52#FAR_52_212_3 https://www.acquisition.gov/far/part-52#FAR_52_204_26 https://www.acquisition.gov/far/part-52#FAR_52_212_3 https://www.acquisition.gov/far/part-52#FAR_52_204_25

(2) Section 889(a)(1)(B) of the John S. McCain National Defense Authorization Act for Fiscal Year 2019 (Pub. L. 115-232) prohibits the head of an executive agency on or after August 13, 2020, from entering into a contract or extending or renewing a contract with an entity that uses any equipment, system, or service that uses covered telecommunications equipment or services as a substantial or essential component of any system, or as critical technology as part of any system. This prohibition applies to the use of covered telecommunications equipment or services, regardless of whether that use is in performance of work under a Federal contract.

Nothing in the prohibition shall be construed to—

(i) Prohibit the head of an executive agency from procuring with an entity to provide a service that connects to the facilities of a third-party, such as backhaul, roaming, or interconnection arrangements; or

(ii) Cover telecommunications equipment that cannot route or redirect user data traffic or cannot permit visibility into any user data or packets that such equipment transmits or otherwise handles.

(c) Procedures. The Offeror shall review the list of excluded parties in the System for Award Management (SAM) ( https://www.sam.gov) for entities excluded from receiving federal awards for "covered telecommunications equipment or services".

(d) Representation. The Offeror represents that—

(1) It □ will, □ will not provide covered telecommunications equipment or services to the Government in the performance of any contract, subcontract or other contractual instrument resulting from this solicitation. The Offeror shall provide the additional disclosure information required at paragraph (e)(1) of this section if the Offeror responds "will" in paragraph (d)(1) of this section; and

(2) After conducting a reasonable inquiry, for purposes of this representation, the Offeror represents that—

It □ does, □ does not use covered telecommunications equipment or services, or use any equipment, system, or service that uses covered telecommunications equipment or services.

The Offeror shall provide the additional disclosure information required at paragraph (e)(2) of this section if the Offeror responds "does" in paragraph (d)(2) of this section.

(e) Disclosures.

(1) Disclosure for the representation in paragraph (d)(1) of this provision. If the Offeror has responded "will" in the representation in paragraph (d)(1) of this provision, the Offeror shall provide the following information as part of the offer:

(i) For covered equipment—

(A) The entity that produced the covered telecommunications equipment (include entity name, unique entity identifier, CAGE code, and whether the entity was the original equipment manufacturer (OEM) or a distributor, if known);

https://www.sam.gov

(B) A description of all covered telecommunications equipment offered (include brand; model number, such as OEM number, manufacturer part number, or wholesaler number;

and item description, as applicable); and

(C) Explanation of the proposed use of covered telecommunications equipment and any factors relevant to determining if such use would be permissible under the prohibition in paragraph (b)(1) of this provision.

(ii) For covered services—

(A) If the service is related to item maintenance: A description of all covered telecommunications services offered (include on the item being maintained: Brand; model number, such as OEM number, manufacturer part number, or wholesaler number; and item description, as applicable); or

(B) If not associated with maintenance, the Product Service Code (PSC) of the service being provided; and explanation of the proposed use of covered telecommunications services and any factors relevant to determining if such use would be permissible under the prohibition in paragraph (b)(1) of this provision.

(2) Disclosure for the representation in paragraph (d)(2) of this provision. If the Offeror has responded "does" in the representation in paragraph (d)(2) of this provision, the Offeror shall provide the following information as part of the offer:

(i) For covered equipment—

(A) The entity that produced the covered telecommunications equipment (include entity name, unique entity identifier, CAGE code, and whether the entity was the OEM or a distributor, if known);

(B) A description of all covered telecommunications equipment offered (include brand; model number, such as OEM number, manufacturer part number, or wholesaler number;

and item description, as applicable); and

(C) Explanation of the proposed use of covered telecommunications equipment and any factors relevant to determining if such use would be permissible under the prohibition in paragraph (b)(2) of this provision.

(ii) For covered services—

(A) If the service is related to item maintenance: A description of all covered telecommunications services offered (include on the item being maintained: Brand; model number, such as OEM number, manufacturer part number, or wholesaler number; and item description, as applicable); or

(B) If not associated with maintenance, the PSC of the service being provided; and explanation of the proposed use of covered telecommunications services and any factors relevant to determining if such use would be permissible under the prohibition in paragraph (b)(2) of this provision.

(End of provision)

OFFEROR OR

LEGALLY

AUTHORIZED

REPRESENTATIVE

NAME, ADDRESS (INCLUDING ZIP CODE) TELEPHONE NUMBER

Signature

Date

RLP OFFER ATTACHMENT - SEISMIC OFFER FORMS

Instructions for Offeror:

Forms A through D are pre-award submittals. Depending upon the form, either the Offeror or the Offeror’s engineer shall complete and sign the form to confirm seismic compliance with RP 8. When the engineer fills out a form, he or she is also required to stamp it. The Offeror’s engineer shall represent whether the Building meets RP 8 standards, using Form A for Benchmark Buildings or Form B for other existing buildings.

If the engineer’s certification indicates that the Building does not meet RP 8 standards, the Offeror shall agree to retrofit the building to meet the standards, using Form C, Part

1. Offerors providing new construction shall commit to a design code, using Form C, Part

2. Offerors may represent that their building meets an exemption criteria, using Form D.

Forms E and F are post-award submittals. They only apply when the Offeror has agreed to either retrofit an existing building (use Form E) or is constructing a new building (use Form F). Prior to the Government accepting leased space, the Lessor’s engineer shall complete, stamp, and sign the appropriate representation.

The forms must include the supporting documentation stated in the RLP and Lease.

Below is a detailed explanation of each of the forms.

SEISMIC FORM A - CERTIFICATE OF SEISMIC COMPLIANCE BENCHMARK BUILDING

A benchmark building is one that was designed and built or retrofitted in accordance with structural provisions that are considered to provide acceptable life-safety protection. RP 8, Section 1.3, Table 1-1 shows the construction codes that qualify a building as a Benchmark Building. If a building qualifies, no additional hazards need be considered. If the seismicity of a region has changed since the benchmark dates listed in the table, the building must be evaluated in accordance with the now current or greater seismicity of the region to be compliant with the RP 8 Standards.

SEISMIC FORM B - CERTIFICATE OF SEISMIC COMPLIANCE EXISTING BUILDING

The engineer shall evaluate the building to determine compliance with the Life Safety Performance Level. He or she shall use RP 8 Chapter 3 and ASCE/SEI 31 to determine compliance. The evaluation must include the appropriate Structural, Nonstructural, and Geologic Site Hazard and Foundation Checklists with backup calculations.

SEISMIC FORM C – BUILDING RETROFIT OR NEW CONSTRUCTION PRE-AWARD

COMMITMENT

Part 1 only applies to planned retrofit of an existing building. The Offeror shall identify the engineer in charge of the seismic retrofit and commit that the retrofit’s design and construction will conform to the requirements of ASCE/SEI 41, Basic Safety Objective.

The commitment must also include a Tier 1 report with supporting documentation, a narrative, scope, and schedule of the proposed renovations.

Part 2 only applies to new construction. The Offeror shall identify the engineer in charge of the design of the building and specify which building code he or she is using to design and construct.

Exhibit J

SEISMIC FORM D – OFFEROR’S REPRESENTATION OF EXEMPTION FROM SEISMIC

STANDARDS

The Offeror may claim an exemption from seismic compliance if representing that the offered building meets either of the following exemptions:

• In an area of moderate seismicity, the total space leased in the building by the Federal government, including the offered space, will be less than 10,000 ABOA SF upon commencement of the lease term.

• In an area of high to very high seismicity, the offered building is a one-story building of steel light frame or wood construction with less than 280 m2 (3,000

ABOA SF).

SEISMIC FORM E - CERTIFICATE OF SEISMIC COMPLIANCE RETROFITTED BUILDING

The engineer in charge of the building’s structural retrofit of the leased building shall certify that the design standard was the Basic Safety Objective as set forth in ASCE/SEI 41, Seismic Rehabilitation of Existing Buildings, and that the building was retrofitted to that standard.

SEISMIC FORM F - CERTIFICATE OF SEISMIC COMPLIANCE NEW BUILDING

The engineer shall certify that the design and construction of new buildings or additions to existing buildings conforms to the seismic provisions of the latest edition of the applicable State or local government codes under which it was built.

DEFINITIONS - The following definitions apply to the completion of the above-referenced forms:

1. Engineer means a professional engineer who is licensed in Civil or Structural Engineering and qualified in the structural design of buildings. They must be licensed in the state where the property is located.

2. ASCE/SEI 31 means the American Society of Civil Engineers standard, Seismic

Evaluation of Existing Buildings.” ASCE/SEI 31 can be purchased from ASCE at

(800) 548-2723, or by visiting http://www.pubs.asce.org.

3. ASCE/SEI 41 means American Society of Civil Engineers standard, Seismic

Rehabilitation of Existing Buildings.” ASCE/SEI 41 can be purchased from ASCE at (800) 548-2723, or by visiting http://www.pubs.asce.org.

4. Seismic Certificate means a certificate executed and stamped by an Engineer on the appropriate Certificate of Seismic Compliance form included with this solicitation together with any required attachments.

5. RP 8 means “Standards of Seismic Safety for Existing Federally Owned and Leased Buildings ICSSC Recommended Practice 8 (RP 8),” issued by the Interagency Committee on Seismic Safety in Construction as ICSSC RP 8 and the National Institute of Standards and Technology as NIST GCR 11-917-12.

You can obtain RP 8 from the Building and Fire Research Laboratory, National Institute of Standards and Technology, Gaithersburg, MD 20899, or download copy athttp://www.wbdg.org/ccb/NIST/nist_gcr11_917_12.pdf.

http://www.pubs.asce.org/ http://www.pubs.asce.org/

SEISMIC FORM A

CERTIFICATE OF SEISMIC COMPLIANCE

BENCHMARK BUILDING

Date: __________

This affirms that ________________________ served as engineer in charge of the seismic evaluation of the building located at ______________________________________________.

The building has the following characteristics:

ASCE Building Type: No. of Stories: Approx. Area:

Building Design Code: Year of Design Code: Year of Construction:

On the basis of the building characteristics and to the extent permitted by this level of evaluation, it is my opinion that the subject Building qualifies as a Benchmark Building as indicated in ASCE/SEI 31, Table 1-1.

Affix Stamp and Sign Here

Engineer’s Name:

Firm:

Address:

Telephone:

License No.:

License State:

Expiration Date:

SEISMIC FORM B

EXISTING BUILDING

This affirms that ________________________ served as engineer in charge of the seismic evaluation of the building located at ______________________________________________.

I have evaluated this building at the Life Safety Performance Level as set forth in the ICSSC RP 8, Standards of Seismic Safety for Existing Federally Owned and Leased Buildings, using ASCE/SEI 31 methodology:

___Tier 1 Evaluation

___Tier 2 Evaluation

___Tier 3 Evaluation

___Other (please explain below)

Documentation of this evaluation must be attached to this Certificate.

On the basis of the building characteristics and to the extent permitted by this level of evaluation it is my opinion that subject Building (check one) does / does not meet the Life Safety Performance Level of ICSSC RP 8.

Address:

Telephone:

License No.:

License State:

Comments:

Attach: ASCE/SEI 31 Checklist(s) Structural, Nonstructural, and Geologic Site Hazards and Foundation.

SEISMIC FORM C

BUILDING RETROFIT OR NEW CONSTRUCTION

PREAWARD COMMITMENT

PART 1

PREAWARD COMMITMENT TO RETROFIT BUILDING:

This affirms that _________________________ shall serve as the engineer in charge of the seismic retrofit of the building located at ________________________. The retrofit must be designed to meet the Basic Safety Objective, as set forth in ASCE/SEI 41 Seismic Rehabilitation of Existing Buildings.

In accordance with the requirements of this Standard and the seismic paragraph in the Request for Lease Proposals (RLP), our offer includes a commitment to retrofit the building to satisfy all of the Basic Safety Objective requirements of ASCE/SEI 41. The offer includes a Tier 1 report with all supporting documents, a narrative explaining the process, scope of renovations, and a schedule for the seismic retrofit.

Documentation shall be provided before award that demonstrates the seismic retrofit will meet the seismic standards and be completed within the time frame required.

PART 2

PREAWARD COMMITMENT TO CONSTRUCT A NEW BUILDING:

This affirms that _________________________ will serve as the engineer in charge of the structural design of the building located at ________________________. The criteria for design must be the ______ edition of the _____________________ building code.

In accordance with the requirements of this code, we prepared a quality assurance plan that included requirements for testing and inspecting critical elements of the structure and also periodic observation by our staff. We reviewed special inspection and testing reports prepared by the inspection agency and contractor submittals. On the basis of this, and to the extent permitted by this level of construction surveillance, it is my opinion that the Building was designed and constructed in conformance with the requirements of the above code.

Building Type: Building Height: Approx. Area:

OFFEROR

SIGNATURE NAME OF SIGNER

SEISMIC FORM D

OFFEROR’S REPRESENTATION OF EXEMPTION FROM SEISMIC STANDARDS

I represent that my building is exempt from the requirements of RP 8 because:

The Building is located in an area of medium seismicity and the Building will have less than 10,000 ABOA SF of space leased to the Federal Government upon commencement of the lease term.

The Building is located in an area of high to very high seismicity, and it is a one-story building with a steel light frame or wood construction with less than 3,000 ABOA SF of space in the building.

OFFEROR

SIGNATURE NAME OF SIGNER

SEISMIC FORM E

RETROFITTED BUILDING

PRE-OCCUPANCY CERTIFICATE:

This affirms that _________________________ served as the engineer in charge of the structural retrofit of the building located at ________________________. The standard for design was the Basic Safety Objective as set forth in ASCE/SEI 41 Seismic Rehabilitation of Existing Buildings.

In accordance with this Standard, we prepared a quality assurance plan, which requires staff to observe, test, and inspect the seismic retrofit work. We have also reviewed special inspection and testing reports prepared by the inspection agency and contractor submittals. On the basis of this, and to the extent permitted by this level of construction surveillance, it is my opinion that building was designed and constructed to conform with the requirements of the Standard listed above.

Retrofit Design Standard: Year of Retrofit Standard: Year of Retrofit:

Documentation of this retrofit must be available to GSA.

On the basis of the above, it is my opinion that subject Building ___ does, ___ does not meet the Basic Safety Objective - Performance Level as set forth in ASCE/SEI 41, Seismic Rehabilitation of Existing Buildings.

Address:

Telephone:

License No.:

SEISMIC FORM F

NEW BUILDING

PRE-OCCUPANCY CERTIFICATE:

This affirms that _________________________ served as the engineer in charge of the structural design of the building located at ________________________. The criteria for design were the ______ edition of the _____________________ code.

In accordance with the requirements, we prepared a quality assurance plan, which requires staff to observe, test, and inspect the structure’s critical elements. We have also reviewed special inspection and testing reports prepared by the inspection agency and contractor submittals. On the basis of this, and to the extent permitted by this level of construction surveillance, it is my opinion that the building was designed and constructed to conform with the requirements of the code listed above.

Building Type: Bldg. Height: Approx. Area:

Affix stamp and sign here

Address:

Telephone:

License No.:

Comments:

RLP Procurement Summary GSA Public Buildings Service

U.S. GOVERNMENT

General Services Administration (GSA) seeks to lease the following space:

State: MOAB

City: UTAH

Delineated Area: N: HIGHWAY 191, COLORADO RIVER PASSING

E: S SPANISH VALLEY DR

S: OLD AIRPORT RD AND HIGHWAY 191

W 500 W AND RIMROCK LANE

Minimum Sq. Ft. (ABOA): 2,000 SQ FT

Maximum Sq. Ft. (ABOA): 2,909 SQ FT

General Purpose Space 844 SQ FT

Special-Use Space 415 SQ FT

Industrial Space 1,250 SQ FT

Ware Yard 5,900 SQ FT

Space Type: Mixed Use

Parking Spaces (Total): 8

Parking Spaces (Surface): 8

Parking Spaces (Structured): 0

Parking Spaces (Reserved): 8

Full Term: 144 MONTHS

Firm Term: 120 MONTHS

Option Term: N/A

Additional Requirements: SEE ATTACHED ASR (Exhibit B)

Offered space must meet Government requirements for fire safety, accessibility, seismic, and sustainability standards per the terms of the Lease. A fully serviced lease is required. Offered space shall not be in the 100-year flood plain.

Entities are advised to familiarize themselves with the telecommunications prohibitions outlined under Section 889 of the FY19 National Defense Authorization Act (NDAA), as implemented by the Federal Acquisition Regulation (FAR). ). For more information, visit: https://acquisition.gov/FAR- Case-2019-009/889_Part_B.

Offers Due: 05/17/2023

Occupancy (Estimated): 03/04/2024 https://acquisition.gov/FAR-Case-2019-009/889_Part_B https://acquisition.gov/FAR-Case-2019-009/889_Part_B

09/2020

Send Offers to:

Electronic Offer Submission:

Offers must be submitted electronically through the Requirement Specific Acquisition Platform (RSAP), located at https://lop.gsa.gov/rsap/.

Interested parties must go to the RSAP website, select the “Registration” link and follow the instructions to register. Instructional guides and video tutorials are offered on the RSAP homepage and in the “HELP” tab on the RSAP website.

Solicitation Number:

Solicitation (RLP) Number 9UT2187

Government Contact Information (Not for Offer Submission)

Role Phone Email

Lease Contracting Officer 720-903-5728 JOHN.TINER@GSA.GOV

Leasing Specialist 720-654-2112 SADAT.DARDOVSKI@GSA.GOV

Note: Entities not currently registered in the System for Award Management (SAM) are advised to start the registration process as soon as possible.

https://lop.gsa.gov/rsap/

GSA TEMPLATE R100A (10/22)

GSA REQUEST

FOR LEASE

PROPOSALS

NO. 9UT2187

MOAB, UTAH

Offers due by 05/17/2023

In order to be considered for award, offers conforming to the requirements of the RLP shall be received no later than 4:00 PM MST on the date above. See “Receipt of Lease Proposals” herein for additional information.

This Request for Lease Proposals ("RLP") sets forth instructions and requirements for proposals for a Lease described in the RLP documents. Proposals conforming to the RLP requirements will be evaluated in accordance with the Method of Award set forth herein to select an Offeror for award. The Government will award the Lease to the selected Offeror, subject to the conditions herein.

The information collection requirements contained in this Solicitation/Contract, that are not required by regulation, have been approved by the Office of Management and Budget pursuant to the Paperwork Reduction Act and assigned the OMB Control No.

3090-0163.

SLAT RLP

TABLE OF CONTENTS

SLAT RLP

SECTION 1 STATEMENT OF REQUIREMENTS

1.01 GENERAL INFORMATION (SLAT) (OCT 2020)

1.02 AMOUNT AND TYPE OF SPACE AND LEASE TERM (SLAT) (OCT 2020)

1.03 NEIGHBORHOOD AND PARKING (SLAT) (OCT 2021)

1.04 LIST OF RLP DOCUMENTS (SLAT) (OCT 2022)

1.05 LEASE DESCRIPTION (SLAT) (OCT 2021)

1.06 AUTHORIZED REPRESENTATIVES (OCT 2020)

1.07 BROKER COMMISSION AND COMMISSION CREDIT (OCT 2020)

1.08 PRICING OF SECURITY REQUIREMENTS (OCT 2022)

1.09 NORTH AMERICAN INDUSTRY CLASSIFICATION SYSTEM (NAICS) CODE AND SMALL BUSINESS SIZE

STANDARD (OCT 2020)

1.10 UNIQUE ENTITY IDENTIFIER (OCT 2021)

SECTION 2 ELIGIBILITY AND PREFERENCES FOR AWARD

2.01 EFFICIENCY OF LAYOUT (SLAT) (OCT 2020)

2.02 FLOOD PLAINS (OCT 2022)

2.03 SEISMIC SAFETY – MODERATE SEISMICITY (OCT 2022)

2.04 SEISMIC SAFETY – HIGH SEISMICITY (OCT 2022)

2.05 HISTORIC PREFERENCE (SMALL) (SEP 2015)

2.06 ENERGY INDEPENDENCE AND SECURITY ACT (OCT 2022)

2.07 DUE DILIGENCE AND NATIONAL ENVIRONMENTAL POLICY ACT REQUIREMENTS - RLP (SEP 2014)

2.08 NATIONAL HISTORIC PRESERVATION ACT REQUIREMENTS - RLP (SMALL) (OCT 2020)

SECTION 3 HOW TO OFFER

3.01 GENERAL INSTRUCTIONS (SLAT) (OCT 2020)

3.02 RECEIPT OF LEASE PROPOSALS (SLAT) (OCT 2022)

3.03 STEP 1: OFFER SUBMITTAL (SLAT) (OCT 2022)

3.04 STEP 2: DUE DILIGENCE - ADDITIONAL SUBMITTALS (SLAT) (OCT 2022)

3.05 BUILDING TOUR (SLAT) (OCT 2020)

3.06 TENANT IMPROVEMENTS INCLUDED IN OFFER (SLAT) (OCT 2020)

3.07 OPERATING COSTS REQUIREMENTS INCLUDED IN OFFER (JUN 2012)

3.08 UTILITIES SEPARATE FROM RENTAL / BUILDING OPERATING PLAN (JUN 2012)

3.09 SECURITY IMPROVEMENTS INCLUDED IN OFFER (OCT 2022)

SECTION 4 METHOD OF AWARD

4.01 NEGOTIATIONS (SLAT) (OCT 2020)

GSA FORM R100A (10/22)

4.02 HUBZONE SMALL BUSINESS CONCERN ADDITIONAL PERFORMANCE REQUIREMENTS (SMALL) (SEP 2015)

4.03 AWARD BASED ON PRICE (JUN 2012)

4.04 PRESENT VALUE PRICE EVALUATION (OCT 2022)

4.05 AWARD (SLAT) (OCT 2020)

SECTION 5 ADDITIONAL TERMS AND CONDITIONS

5.01 MODIFIED RLP PARAGRAPHS (OCT 2016)

5.02 SWING SPACE - RLP (OCT 2022)

RLP NO. 9UT2187, PAGE 1 GSA TEMPLATE R100A (10/22)

REQUEST FOR LEASE

PROPOSALS NO. 9UT2187

10/24/2022 SLAT RLP GSA TEMPLATE R100A (October 2022)

SECTION 1 STATEMENT OF REQUIREMENTS

1.01 GENERAL INFORMATION (SLAT) (OCT 2020)

A. This Request for Lease Proposals (RLP) sets forth instructions and requirements for proposals for a Lease described in the RLP documents. The Government will evaluate proposals conforming to the RLP requirements in accordance with the Method of Award set forth below to select an Offeror for award. The Government will award the Lease to the selected Offeror, subject to the conditions below.

B. Included in the RLP documents is a lease template setting forth the lease term and other terms and conditions of the Lease contemplated by this RLP and a GSA Proposal to Lease Space (GSA Form 1364) on which Offeror shall submit its offered rent and other price data, together with required information and submissions. The Lease paragraph titled “Definitions and General Terms” shall apply to the terms of this RLP.

C. Do not attempt to complete the lease template. GSA will transcribe the successful Offeror’s final offered rent and other price data included on the GSA Form 1364 into the lease and transmit the completed Lease, including any appropriate attachments, to the successful Offeror for execution. Neither the RLP nor any other part of an Offeror’s proposal shall be part of the Lease except to the extent expressly incorporated therein. The Offeror should review the completed Lease for accuracy and consistency with his or her proposal, sign and date the first page, initial each subsequent page of the Lease, and return it to the Lease Contracting Officer (LCO).

D. The Offeror's executed Lease shall constitute a firm offer. No Lease shall be formed until the LCO executes the Lease and delivers a signed copy to the Offeror.

1.02 AMOUNT AND TYPE OF SPACE AND LEASE TERM (SLAT) (OCT 2020)

A. The Space shall be located in a modern quality Building of sound and substantial construction with a facade of stone, marble, brick, stainless steel, aluminum or other permanent materials in good condition and acceptable to the LCO. If not a new Building, the Space offered shall be in a Building that has undergone, or will complete by occupancy, modernization or adaptive reuse for the Space with modern conveniences. Buildings with Property boundary(ies) on the boundary streets are deemed to be within the delineated Area of Consideration.

CITY, STATE MOAB, UTAH

AREA OF CONSIDERATION N: HIGHWAY 191, COLORADO RIVER PASSING

E: S SPANISH VALLEY DR

S: OLD AIRPORT RD AND HIGHWAY 191

W 500 W AND RIMROCK LANE

SPACE TYPE(S) MIXED USE

MINIMUM SQ. FT. (ABOA) 2,000 SQFT

MAXIMUM SQ. FT. (ABOA) 2,909 SQFT

OFFICE SPACE 844 SQFT

SPECIALIZED USE SPACE 415 SQFT

INDUSTRIAL SPACE 1,250 SQFT

WARE YARD SQ. FT. 5,900 SQFT

RESERVED PARKING SPACES (TOTAL) 8

RESERVED PARKING SPACES (SURFACE) 8

RESERVED PARKING SPACES (STRUCTURE) 0

INITIAL FULL TERM 144 MONTHS

INITIAL FIRM TERM 120 MONTHS

TERMINATION RIGHTS 120 DAYS

OPTION TERM N/A

ADDITIONAL REQUIREMENTS SEE ATTACHED ASR (EXHIBIT B)

1.03 NEIGHBORHOOD AND PARKING (SLAT) (OCT 2021) INTENTIONALLY DELETED

1.04 LIST OF RLP DOCUMENTS (SLAT) (OCT 2022)

A. The following documents are attached to and included as part of this RLP package:

RLP NO. 9UT2187, PAGE 2 GSA TEMPLATE R100A (10/22)

DOCUMENT NAME

NO. OF PAGES

EXHIBIT

Lease No. GS-XXP- LUT00574 (Template L100A) 37 A

Agency’s Requirements 16 B

Security Requirements for Level I 5 C

GSA Form 3516A, Solicitation Provisions 6 D

GSA Form 3517A, General Clauses 9 E

Proposal to Lease Space (GSA Form 1364) 4 F

GSA Form 1217, Lessor's Annual Cost Statement 3 G

GSA Form 12000 for Prelease Fire Protection and Life Safety Evaluation for an Office Building (Part A or Part B) (See Section 3 for applicable requirements)

8 H

FAR 52.204-24, Representation Regarding Certain Telecommunications and Video

4 I

Seismic Reporting Package (Forms A-F) 8 J

1.05 LEASE DESCRIPTION (SLAT) (OCT 2021)

A. Offeror shall examine the Lease template included in the RLP documents to understand the Government's and the Lessor's respective rights and responsibilities under the contemplated Lease.

B. The Lease contemplated by this RLP includes:

1. The term of the Lease, and renewal option, if any.

2. Terms and Conditions of the Lease, including Definitions, Standards, and Formulas applicable to the Lease and this

RLP.

3. Building Shell standards and requirements.

4. Information concerning the tenant agency's buildout requirements, to be supplemented after award.

5. Security Requirements.

6. A description of all services to be provided by the Lessor.

C. Should the Offeror be awarded the Lease, the terms of the Lease shall be binding upon the Lessor without regard to any statements contained in this RLP.

D. The Lease contemplated by this RLP is a fully serviced Lease. Rent shall be based upon a proposed rental rate per Rentable Square Foot (RSF), limited by the offered rate and the maximum ABOA SF solicited under this RLP. Although certain Tenant Improvement (TI) requirements information is provided with this RLP and will be incorporated into the Lease, the TIs to be delivered by the Lessor will be based on the final design to be developed after award of the Lease, which reflects the Agency’s full requirements.

The Lessor shall design and build the TIs and will be compensated for TI costs, together with design and project management fees to be set under the Lease. Although the TI requirements will not be developed fully until after award, Offerors shall provide the allowance stated in the Tenant Improvement Allowance paragraph of the Lease.

Unless the Government prepares Design Intent Drawings (DIDs), after award the Lessor must prepare DIDs for the leased Space conforming to the lease requirements and other Government-supplied information related to the client agency’s interior build-out requirements. The Government will have the opportunity to review the Lessor's DIDs to determine that the Lessor's design meets the requirements of the Lease. Only after the Government approves the DIDs and a final price for TIs is negotiated will the Lessor be released to proceed with buildout. The Lease also provides that the Government may modify the TI requirements, subject to the Lessor's right to receive compensation for such changes.

E. The security pricing process is described in a separate paragraph.

F. Upon completion and acceptance of the leased Space, the Space will be measured for establishing the actual annual rent, and the lease term shall commence. In instances involving an incumbent Lessor where the Government commences the lease term pending completion of TI and/or BSAC alterations, the Government shall withhold TI and/or BSAC rent pursuant to Section 1 of the Lease until such time as the TI and/or BSAC is completed and accepted by the Government. During the term of the Lease, rent will be adjusted for changes to the Lessor's operating costs and real estate taxes, pursuant to paragraphs set forth in the Lease.

G. Offerors are advised that doing business with the Government carries special responsibilities with respect to sustainability, fire protection and life safety, and security, as well as other requirements not typically found in private commercial leases. These are set forth both in the lease template and in the GSA Form 3517A and will be made part of the Lease.

RLP NO. 9UT2187, PAGE 3 GSA TEMPLATE R100A (10/22)

1.06 AUTHORIZED REPRESENTATIVES (OCT 2020)

With respect to all matters relating to this RLP, only the Government's LCO designated below shall have the authority to amend the RLP and award a Lease. The Government shall have the right to substitute its LCO by notice, without an express delegation by the prior LCO.

Lease LCO:

John Tiner Office: 720-903-5728

JOHN.TINER@GSA.GOV

As to all other matters, Offerors may contact the Alternate Government Contact designated below.

Alternate Government Contact:

Sadat Dardovski Office: 720-654-2112

SADAT.DARDOVSKI@GSA.GOV

1.07 BROKER COMMISSION AND COMMISSION CREDIT (OCT 2020) INTENTIONALLY DELETED

1.08 PRICING OF SECURITY REQUIREMENTS (OCT 2022)

A. The proposed Lease contains an attachment with the security requirements and obligations for the Building, which are based on the facility security level (FSL). The Federal Government determines the facility’s FSL rating, which ranges from FSL I to FSL IV.