9222 - Example BOM.xlsx
XLSX spreadsheet 23 KB Posted
- Solicitation number
- 127604259222
- Issued by
-
Department of Agriculture Forest Service
About this file
This is a Bill of Materials (BOM) for a communications shelter project at Fiddler Mountain for the Rogue River-Siskiyou National Forest. The document details requirements for an 8x8 walk-in enclosure with DC power layout to be installed at coordinates 42N 14' 24.94", 123W 48' 2.75" at 4,916 ft elevation. The shelter specifications include two 19" telecom equipment racks, battery trays, DC LED lighting, power entry provisions tied to a Faraday cage, passive ventilation, and a 50' integrated tower structure rated for TIA-222 Risk category II with capability to support five Command 150-5N antennas.
The scope includes manufacture, delivery to Cave Junction, OR, installation at the site location, and backhaul/disposal of an existing 8'x8'x8' shelter weighing approximately 3,000 lbs. Key requirements include solar mounting provisions, cable entry panels, antenna mounting brackets with 18-inch standoffs, and an OSHA-compliant fall restraint system. The contractor is responsible for project management activities and must repair any damage to adjacent facilities at their own expense. Site preparation and subsurface work are explicitly excluded from the scope.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 9222 -RFI for Comm Shelters.pdf | ||
| PWS_Shelter.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R6 Fiddler Mtn.
Bill of Materials
| Unit Name to Ship to: | Rogue River-Siskiyou NF | |
| Point of Contact (Local SAT): | TBD | |
| Phone (Local SAT): | TBD | |
| Street Address: | 26568 Redwood Highway | |
| City, State: | Cave Junction, OR | |
| Zip: | 97523 | |
| Additional Information needed for request. | ||
| Project Point of Contact (name and phone): | TBD | |
| Additional Technical Contact (name and phone), if applicable: | TBD | |
| WR# or Incident Number: | 20253800 | |
| Override/Job Code: | 2505/ITJVAA25 | |
| Q-Code | TBD | |
| IAS PMO | TBD | |
| UAI | TBD | |
| BOC | 3290 | |
| AAP# | RPSH | |
| POW Line Item # and Project Description | Fiddler Mtn. Shelter Replacement | |
| COR, if applicable: | TBD | |
| Comments: | Drive-in install: Lat 42N 14' 24.94", Long 123W 48' 2.75", Elevation: 4916ft. Door location: West, Tower: East |
| LINE | |||||
| ITEM | DESCRIPTION | Manufacturers Part Number | Unit of Issue | QTY | UNIT |
| PRICE | TOTAL |
PRICE
| 1 | SHELTER DESCRIPTION | ||||
| 2 | 8x8 Walk-in Enclosure w/ DC power layout | EA | 1 | $ - 0 | |
| 3 | INTERIOR LAYOUT | ||||
| 5 | 19" Telecom Equipment rack | EA | 2 | $ - 0 | |
| 6 | Battery Tray for 19" telecom rack | EA | 2 | $ - 0 | |
| 7 | Rack Mounted Busbar for 19" Telecom rack | EA | 1 | $ - 0 | |
| 9 | First Aid Kit | EA | 1 | $ - 0 | |
| 10 | Wall mounted light switch | EA | 1 | $ - 0 | |
| 11 | DC led lights with fixtures mounted to ceiling | EA | 2 | $ - 0 | |
| 12 | POWER ENTRY | ||||
| 13 | DC Power Entry | EA | 2 | $ - 0 | |
| 14 | 24-volt surge suppression device | EA | 2 | $ - 0 | |
| 15 | Note: Power entry provisions must be tied to Faraday Cage | ||||
| 16 | VENTILATION | ||||
| 17 | Passive ventilation | EA | 1 | $ - 0 | |
| 18 | TOWER | ||||
| 19 | 50' integrated tower structure | EA | 1 | $ - 0 | |
| 20 | Notes: Antennas used for loading calculations shall be (5) Command 150-5N antennas; (1) each at 50',45',40,35 & 30' marks. Tower rating shall follow TIA-222 Standards for a Risk category II structure. Site 3-second wind speed is 94mph, and radial ice loading is less than 1 inch. | ||||
| 21 | SOLAR | ||||
| 22 | Provisions for Roof and Wall mounted solar brackets | EA | 1 | $ - 0 | |
| 23 | Solar bracket | EA | 1 | ||
| 24 | CABLE ENTRY | ||||
| 25 | 6-port telecom entrance panel for coaxial cables | EA | 1 | ||
| 26 | 4-inch cable entry glands (Cable Type: LDF4, 1-Hole per entry gland) | EA | 3 | $ - 0 | |
| 27 | Cable Entry Covers | EA | 3 | $ - 0 | |
| 28 | Note: CAble entry provisions must be tied to Faraday Cage | ||||
| 29 | ANTENNA MOUNTING | ||||
| 30 | Mounting Brackets, hardware, and 18-inch standoffs suitable for attaching (3) Command 150-5N antennas onto tower structure | EA | 3 | $ - 0 | |
| 31 | Fall restraint: anchor point on roof of shelter that meets OSHA standard 29 CFR § 1926.502(d)(15) capable of sustaining 5,000lbs. (22.2KN) of force | EA | 1 | $ - 0 | |
| 32 | Site Specific Drawing | EA | 1 | $ - 0 | |
| 33 | Delivery & Offload at FS Staging Location: 26568 Redwood Highway Cave Junction, OR 97523 | EA | 1 | $ - 0 | |
| 34 | Drive-In Install: Transport shelter form staging location, transport, and install shelter at: Lat 42N 14' 24.94", Long 123W 48' 2.75", Elevation: 4916ft. Door location: North, Tower: East | EA | 1 | $ - 0 | |
| 35 | Backhaul: 8'x8'x8' shelter weighing approx. 3,000 lbs. and dispose at landfill. | EA | 1 | $ - 0 | |
| 36 | Mob & Demob | EA | 1 | $ - 0 | |
| 37 | Project Management: Requirements for PM activities outlines in Performance Work Statement | EA | TBD | ||
| 38 | NOTES: Items excluded from the BOM include any subsurface work and/or site preparation. The adjacent tower, guy wires, and radio equipment will be removed prior to shelter installation. Any damage to adjacent facility including the perimeter fence will be the responsibility of the contractor to repair a their own expense. | ||||
| 39 | GRAND TOTAL | $ - 0 |
File details come from the government source that posted it. Updated .