This document is a specifications sheet for four TransData transducer units required as of October 20, 2026.
The solicitation specifies procurement of four distinct transducer items with detailed technical requirements. Item 1 is a Current Transducer with 45 electrical elements, operating range of -20°C to 70°C, 0-95% humidity tolerance, 100-130V 60 Hz power supply, 50-70 Hz frequency range, 5 Amps full scale input, 4-20mA DC output, response time under 400ms, 5000V peak surge withstand capability, and ±0.2% accuracy at 25°C ±5°C. Item 2 is a Voltage Transducer with identical specifications to Item 1 except featuring 30 electrical elements instead of 45. Item 3 is a Wattage 2-Element Transducer with 10 wiring terminals, three-phase operation (versus single-phase for Items 1-2), 120V 60 Hz power supply, 0-99% non-condensing humidity tolerance, tighter accuracy of ±0.1% at 25°C ±2°C, and no zero adjustment requirement. Item 4 is a Wattage 2.5-Element Transducer with 5 wiring terminals featuring identical specifications to Item 3, including three-phase operation and ±0.1% accuracy. All four items require utility-specified steel enclosures, standardized mounting footprints, ±10% calibration adjustment capability, and 5 Amps full scale input with 4-20mA DC output.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SATPC0043132 Tab 07 Capability Statement.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10x10 TransData units 10/20/2026
1.0 Current Transducer Specifications (Item 1):
1.1.1 Number of Electrical Elements: 45
1.1.2 Temperature Range: -20 degrees C to 70 degrees C
1.1.3 Operating Humidity: 0-95%
1.1.4 Power Supply: 100-130V, 60 Hz
1.1.5 Frequency Range: 50-70 Hz
1.1.6 Full Scale Input: 5 Amps
1.1.7 4-20mA DC output
1.1.8 Response Time to 99%: <400 MS
1.1.9 Surge Withstand Capability: 5000V Peak
1.1.10 Accuracy @ 25 degrees C +/- 5 degrees C: +/-0.2% of rated output
1.1.11 Single phase
1.1.12 Calibration Adjustment: +/-10%
1.1.13 Zero (offset) Adjustment: +/- 5%
1.1.14 Utility specified steel enclosure
1.1.15 Standardized mounting footprint
2.0 Voltage Transducer Specifications (Item 2):
2.1.1 Number of electrical elements: 30
2.1.2 Temperature Range: -20 degrees C to 70 degrees C
2.1.3 Operating Humidity: 0-95%
2.1.4 Power Supply: 100-130V, 60 Hz
2.1.5 Frequency Range: 50-70 Hz
2.1.6 Full Scale Input: 5 Amps
2.1.7 4-20mA DC output
2.1.8 Response Time to 99%: <400 MS
2.1.9 Surge Withstand Capability: 5000V Peak
2.1.10 Accuracy @ 25 degrees C +/- 5 degrees C: +/-0.2% of rated output
2.1.11 Single phase
2.1.12 Calibration Adjustment: +/-10%
2.1.13 Zero (offset) Adjustment: +/- 5%
2.1.14 Utility specified steel enclosure
2.1.15 Standardized mounting footprint
3.0 Wattage 2-Element Transducer Specifications (Item 3):
3.1.1 Number of wiring terminals: 10
3.1.2 Temperature Range: -20 deg C to 70 deg C
3.1.3 Operating Humidity: 0-99% non-condensing
3.1.4 Power Supply: 120V, 60 Hz
3.1.5 Frequency Range: 50-70 Hz
3.1.6 Full Scale Input: 5 Amps
3.1.7 4-20mA DC output
3.1.8 Response Time to 99%: <400 MS
3.1.9 Surge Withstand Capability: 5000V Peak
3.1.10 Accuracy @ 25 degrees C +/- 2 deg C: +/-0.1% of rated output
3.1.11 Three phase
3.1.12 Calibration Adjustment: +/-10%
3.1.13 Zero Adjustment: none required
3.1.14 Utility specified steel enclosure
3.1.15 Standardized mounting footprint
4.0 Wattage 2.5-Element Transducer Specifications (Item 4):
4.1.1 Number of wiring terminals: 5
4.1.2 Temperature Range: -20 deg C to 70 deg C
4.1.3 Operating Humidity: 0-99% non-condensing
4.1.4 Power Supply: 120V, 60 Hz
4.1.5 Frequency Range: 50-70 Hz
4.1.6 Full Scale Input: 5 Amps
4.1.7 4-20mA DC output
4.1.8 Response Time to 99%: <400 MS
4.1.9 Surge Withstand Capability: 5000V Peak
4.1.10 Accuracy @ 25 degrees C +/- 2 deg C: +/-0.1% of rated output
4.1.11 Three phase
4.1.12 Calibration Adjustment: +/-10%
4.1.13 Zero Adjustment: none required
4.1.14 Utility specified steel enclosure
4.1.15 Standardized mounting footprint