Chiller Order:
Purpose: Provide cooling water for an IVI model 14 vacuum furnace, for sustained operation of furnace at high temperature.
Specifications:
- Stand-alone unit
- Provide minimum cooling capacity of:
o 80,000 BTUs/hr o Alternate units: 24,000 watts or 7 tons
- Operates on water or water-coolant solution
- Coolant flow pumping of at least 10 gpm controllable down to at least 18 psi to furnace input @ approximately 60 - 70 degrees F nominal.
- Coolant is end-user replenishable.
- 1-1/4” inlet/outlet NPT connections
- 208/460 V input power capable
- Limit monitoring that can be integrated into furnace control system.