SOW Generator Fuel Polishing.pdf
PDF 320 KB Posted
- Attached to
- WRSU Generator Day Tank Polishing
- Solicitation number
- 75H71224R00018
About this file
This statement of work outlines requirements for generator day tank fuel polishing services. The Whiteriver Indian Health Service Hospital through the Department of Health and Human Services Indian Health Service is seeking these services. The attached statement of work provides details on the diesel generator day tanks that require polishing. Interested parties should review the statement of work for information on the scope of work, specifications, delivery schedule and other requirements to provide fuel polishing services for the generator day tanks at the Whiteriver Indian Health Service Hospital.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCOPE OF WORK
GENERATOR FUEL POLISHING
WHITERIVER SERVICE UNIT
December 2023
A. BACKGROUND
The Whiteriver Indian Health Service Hospital requires a contracting action for the procurement of diesel generator day tank fuel polishing services.
B. DELIVERABLES
1. The contractor shall provide one (1) micron day tank fuel polishing services for the following diesel generators.
a. Power Plant Building: Caterpillar; 1000kVA; Model #3412; Day Tank Size 1,283 Gallons
b. Garrett Building/Annex: Kohler, 100kW, Model #100REOZJF, Day Tank Size 375 Gallons
c. Specialty Services Building: Kohler, 500 kW, Model #500REOZJB, Day Tank Size 600 Gallons
2. Power Plant generator is located indoors and 115’ from nearest accessible door.
3. The contractor shall demonstrate successful polishing performance by pulling samples from the bottom of generator day tanks as witnessed by the COR and showing samples from each generator upon completion of polishing work.
4. The Whiteriver Service Unit is located at 200 West Hospital Drive, Whiteriver, AZ 85941. See Attachment A for map of generator locations on the Whiteriver Service unit campus.
C. PERIOD OF PERFORMANCE
1. The period of performance is 90 days.
2. Facility day time hours of operation are 7:00 AM – 5:00 PM, Monday through Friday (excluding
Federal holidays). Work outside of these hours must be requested in writing to the Contracting Officers Representative (COR).
D. CONTRACT POINTS OF CONTACT
1. Contracting Officer Representative (COR): Dwayne Melton
2. Technical Point of Contact: Lance Matthews dmelton Text Box
ATTACHMENT A
Whiteriver Service Unit Generator Location Map dmelton Rectangle dmelton Rectangle dmelton Rectangle dmelton Arrow dmelton Arrow dmelton Arrow dmelton Text Box
POWER PLANT
Caterpillar 1,000 kVA 1,283 Gallon Day Tank dmelton Text Box
GARRETT BUILDING/ANNEX
Kohler 100kW 375 Gallon Day Tank dmelton Text Box SPECIALITY SERVICES BUILDING Kohler 500kW 600 Gallon Day Tank
| 200 - SOW, Generator Fuel Polishing |
| SCOPE OF WORK |
ATTACHMENT A - WRSU Generator Location Map
File details come from the government source that posted it. Updated .